MANUAL
Control Panel
SETRONIK1
MSTK11-GB
Rev.01
30/12/05
SEA SYSTEMS
MSTK11-GB
Rev.01
30/12/05
INTRODUCTION
Our compliments for choosing the SETRONIK1 controller as the controller for your lift.
Please carefully read this booklet so that you will be able to understand all the qualities of
this device and its potential.
Warning
Since our products are in constant evolution, all information contained in this manual can
be modified by SEA SYSTEMS without notice.
In the case of special lifts, any accessory documentation relating to additional or modified
functions is provided.
SETRONIK1
Pagina 2 di 56
SEA SYSTEMS
MSTK11-GB
Rev.01
30/12/05
TABLE OF CONTENTS
1.
2.
INSTALLATION..................................................................................... 6
3.
PROGRAMMING................................................................................. 27
3.1
3.2.
3.3.
3.4.
3.5.
3.6.
4.
4.1.
4.2.
4.3.
4.4.
4.5.
4.6.
DIAGNOSIS......................................................................................... 42
LIFT STATUS DISPLAY ................................................................................................42
DISPLAY AND CANCELLATION OF FAILURES / MALFUNCTIONS.........................................43
COUNT OF RUNS AND RE-LEVELLINGS PERFORMED. .....................................................44
COMMANDS FOR LIFT OPERATION IN THE MACHINE ROOM: .............................................45
LED SIGNALLING LEGEND OF CARDS STK1-B, STK1-E AND AL01................................46
ERROR CODE LEGEND ...............................................................................................49
SETRONIK1
Pagina 3 di 56
SEA SYSTEMS
5.
5.1.
5.2.
5.3.
5.4.
6.
MSTK11-GB
Rev.01
30/12/05
MAINTENANCE ................................................................................ 52
BATTERY REPLACEMENT.............................................................................................52
SHAFT SENSORS ........................................................................................................52
STK1-B BASIC ELECTRONIC BOARD REPLACEMENT .....................................................53
CS1 SAFETY CIRCUIT REPLACEMENT ..........................................................................54
7.
SETRONIK1
Pagina 4 di 56
SEA SYSTEMS
MSTK11-GB
Rev.01
30/12/05
1.FUNCTIONAL CHARACTERISTICS
LIFT TYPES
OPERATIONS
NUMBER OF STOPS
DOOR CONTROL
VARIOUS CONTROLS
SHAFT
EMERGENCY
SETRONIK1
Pagina 5 di 56
SEA SYSTEMS
MSTK11-GB
Rev.01
30/12/05
2.INSTALLATION
2.1.GENERAL NOTES
NOTE
Carefully read any warning information in the present operating instructions as
holding important safety, operating and service instructions.
Should the machine be sold or transferred to a different owner, check that the present
operating instructions are always available, as to be duly used by the new owner or
operator.
The installation manager must store any enclosed documents in a safe place, within
reach, thus providing for a correct lift set-up and service. Operating instructions are an
integral part to the installation and therefore they are not allowed to be damaged. Avoid
tearing pages and when consulted, it is necessary to avoid damaging to provide for any
possible future correct reference.
Guarantee terms are on the product transportation document back. SEA SYSTEMS
will support its products through the guarantee, in case of defects with a specified time
period. Should the product not be correctly operated or its performance anyhow modified,
differently from factory original specifications, the guarantee no longer applies.
When necessary, get in touch with the company Service Department always
providing for the installation serial number.
The serial number is specified:
on the adhesive label on the outside of the control board unit;
On the first page of the board electric wiring;
On the Control board programming paper
On the Board Declaration of Conformity
SETRONIK1
Pagina 6 di 56
SEA SYSTEMS
MSTK11-GB
Rev.01
30/12/05
2.2.SAFETY RULES
The unit can only be installed by qualified and authorised personnel, who is liable for the
specific compliance to standards according to the technical best practice available.
Before any cleaning or serve, cut the unit from the power supply by means of the
installation cut-out switch.
Always wear the demanded personal protections (fig. 2.1),and more precisely:
-
Cask.
Gloves.
Protective shoes.
Safety belts.
Headphones.
Fig. 2.1 Safety signalling
Never wear loose objects and/or clothing (necklaces, watches, ties), avoid long hair.
Never store cutting or pointed objects (screwdriver, scissors ) in the shirt pocket.
Never tamper, wear or hide warning signs or labels. When wore and demanded,
immediately replace the.
In order to lift heavy loads, always used suitable tools, thus avoiding any damage to the
spine cord depending on the unit manual handling.
2.3.GLOSSARY
NOTE
It provides personnel with specific and valuable information.
WARNING
It provides personnel with information which, when not complied with, can lead to
light people or installation damages
CAUTION
It provides personnel with information on a specific operation, which, if not taken
into account in compliance with safety regulations in force, can lead to possible
severe physical damages.
SETRONIK1
Pagina 7 di 56
SEA SYSTEMS
MSTK11-GB
Rev.01
30/12/05
2.4.PRELIMINARY OPERATIONS
Before starting the installation, check what follows:
A)INSTALLATION PLACE SET UP
A storage area next to the unit is to be available, easily accessible to operators and
protected from any adverse weather condition.
Check any cable tray and passing holes suitable for electric cabling, always to be
easily inspected and well-refined.
Check the Control Panel specifications (Control Panel type, Contactors, Starting,)
must comply with demanded specifications on the order confirmation.
Check the availability of any suitable material to be used during assembly, referring
to the checklist accompanying the board documents.
Check any unit and material condition when delivery to the site, to check possible
damages which arrived during transportation. Immediately prevent SEA SYSTEMS
Srl in the case of missing units or damages
Store electric and electronic unit in a dry and cold room, in the original packaging.
C)SCAFFOLDING
When setting the unit up, use standard scaffolding, exhibiting operating floors at any stop,
at about 0.5 meter lower than the stop.
CAUTION
Scaffolding completely or partially in metal, to be connected to a suitable
grounding, in compliance with safety regulations in force.
SETRONIK1
Pagina 8 di 56
SEA SYSTEMS
MSTK11-GB
Rev.01
30/12/05
SETRONIK1
Pagina 9 di 56
SEA SYSTEMS
MSTK11-GB
Rev.01
30/12/05
A TYPE
B TYPE
C TYPE
KIT BRAKET
KIT BRAKET
KIT BRAKET
CFR
CFR
G-CFR
CVR
SR, DR, DS
SR, DR, DS
MFR
MFR
G-MFR
MVR-SR
No Bracket
G-MVR-SR
MVR-DR
No Bracket
G-MVR-DR
MVR-DS
No Bracket
G-MVR-DS
See diagram
See diagram
CVIA
CVIC
HIGHLIGHT
We recommend that you choose A System or C System for the installation of
magnets. The system ensures tighter fastening of the magnets, a better magnetic
field, less exposure to various bodies (grease, iron fillings.)
With the B System, the magnets without bracket have to be fixed directly on the
guide.
SETRONIK1
Pagina 10 di 56
SEA SYSTEMS
CVIA
MSTK11-GB
Rev.01
30/12/05
SHAFT SENSORS PLACING FOR HYDRAULIC LIFT WITH A OR B SHAFT SENSOR KIT
HIGHLIGHT
With the B System, the magnets without bracket have to be fixed directly on the
guide.
SHAFT FRONTAL VIEW
SLOWING DISTANCE K
SPEED
0.2 m/s
0.4 m/s
0.6 m/s
0.8 m/s
SETRONIK1
K
20cm
40 cm
60 cm
80 cm
Pagina 11 di 56
SEA SYSTEMS
CVIC
MSTK11-GB
Rev.01
30/12/05
SHAFT SENSORS PLACING FOR HYDRAULIC LIFT WITH C SHAFT SENSOR KIT
SHAFT FRONTAL VIEW
SLOWING DISTANCE K
SPEED
0.2 m/s
0.4 m/s
0.6 m/s
0.8 m/s
SETRONIK1
K
20cm
40 cm
60 cm
80 cm
Pagina 12 di 56
SEA SYSTEMS
MSTK11-GB
Rev.01
30/12/05
SETRONIK1
Pagina 13 di 56
SEA SYSTEMS
MSTK11-GB
Rev.01
30/12/05
SETRONIK1
Pagina 14 di 56
SEA SYSTEMS
MSTK11-GB
Rev.01
30/12/05
A TYPE
B TYPE
KIT BRAKET
KIT BRAKET
Sensors IS, ID
CVF
IS, ID
Sensors SR, DR
CRF
SR, DR
MVF
No Bracket
MVR-IS
No Bracket
MVR-ID
No Bracket
MVR-SR
No Bracket
MVR-DR
No Bracket
See diagram
See diagram
CVFA
CVFA
HIGHLIGHT
We recommend that you choose A System for the installation of magnets. The
system ensures tighter fastening of the magnets, a better magnetic field, less
exposure to various bodies (grease, iron fillings.)
With the B System, the magnets without bracket have to be fixed directly on the
guide.
SETRONIK1
Pagina 15 di 56
SEA SYSTEMS
MSTK11-GB
Rev.01
30/12/05
CVFA SHAFT SENSORS PLACING FOR ELECTRIC LIFT WITH A SHAFT SENSOR KIT
HIGHLIGHT
With the B System, the magnets without bracket have to be fixed directly on the
guide.
SLOWING DISTANCE K
SPEED
0.6 m/s
0.8 m/s
1 m/s
1.2 m/s
Zf
Zp
h
SETRONIK1
K
60cm
80 cm
120 cm
140 cm
Stop Zone (5 cm apart)
Door opening Zone
5 cm apart
Pagina 16 di 56
SEA SYSTEMS
MSTK11-GB
Rev.01
30/12/05
SETRONIK1
the sensor and its corresponding magnet are kept 11.5 cm apart
Pagina 17 di 56
SEA SYSTEMS
MSTK11-GB
Rev.01
30/12/05
2.8.INSTALLATION DIAGRAMS
S01CONNECTIONS BETWEEN PANEL AND USERS IN THE MACHINE ROOM: WIRING DIAGRAM
SETRONIK1
Pagina 18 di 56
SEA SYSTEMS
MSTK11-GB
Rev.01
30/12/05
SETRONIK1
Pagina 19 di 56
SEA SYSTEMS
MSTK11-GB
Rev.01
30/12/05
SETRONIK1
Pagina 20 di 56
SEA SYSTEMS
MSTK11-GB
Rev.01
30/12/05
SETRONIK1
Pagina 21 di 56
SEA SYSTEMS
MSTK11-GB
Rev.01
30/12/05
S04CALLING PUSH BUTTONS AND BOOKING SIGNALINGS IN THE CAR AND AT THE FLOORS IN UP
AND DOWN COLLECTIVE WITH 1 ACCESS: WIRING DIAGRAM (*).
DOWN FLOOR
UP FLOOR
CAR
NOTE (*)
refer to Paragraph 2.5
SETRONIK1
Pagina 22 di 56
SEA SYSTEMS
MSTK11-GB
Rev.01
30/12/05
DESCRIPTION
ACC
AF
Pit stop
BA; BA1
1st operator door opening push-button being serviced; 2nd operator door
opening push-button being serviced
BC
BD; BS
BKC
C; D
CE
Overload contact
CM; FT
CM1; FT1
DS
ED1,ED2,(*)
ELE
ELF; ELM
Up calling keys
EX
FCA; FCC
1st operator opening limit switch; 1st operator closing limit switch
FCA1; FCC1
2nd operator opening limit switch; 2nd operator closing limit switch
FG
FM
HAA
HAG
Gong
HD1,HD2, (*)
HDS
Position display
HF1,HF2,
HFS-HFD
Direction signal
HLS; HAS
HO1,HO2,
Engaged signal
HS1,HS2, (*)
Up calling signal
IP
SETRONIK1
Pagina 23 di 56
SEA SYSTEMS
MSTK11-GB
Rev.01
30/12/05
CODE
DESCRIPTION
IS, ID
LV
Overspeed governor
MA
Maintenance stop
MB
MC
Exchange motor
MG
MN
Maintenance switch
MP
MP1
MPR
MR
PA
Alarm push-button
PAP1
PC
PC1
PCP, PAP
PT
QF
Light switch
QM
Master switch
RT
Drive thermistor
SP; SP1
SR, DR
STO
XS1
Pit plug
XS2
Car plug
YBR
Brake
YCT
YVD
YVL
YVP
HIGHLIGHT (*)
For further information on how to connect ringing keys and calling signals, refer to
Paragraph 2.5.
SETRONIK1
Pagina 24 di 56
SEA SYSTEMS
MSTK11-GB
Rev.01
30/12/05
2.9.INSULATION TEST
Before carrying out the flash tests reported in the following table, perform the following
operations:
1
Pull out and insulate the ground cables that reach the panel;
FROM
Master
Switch,
Motors
R,S,T,
U,V,W,
U1,V1,W1
U2,V2,W2
Safety dev.,
Brake,
Retractable
Sliding
block
Three-phase Car
Motor, Doors Lighting
MP,MP,MP,
L1,L,N
MP1,MP1,MP1
+,-,30,32,
MP,MP
PS1,PS2
1..10, F+,F-,
PR+,PR-
GROUND
_____
___
_
Master Switch,
Motors
R,S,T, U,V,W,
U1,V1,W1
U2,V2,W2
Safety
dev.,
Brake,
Retractable
Sliding block
1..10, F+,F-,
PR+,PR-
Alarm
AL+, AL-, AL
Car Lighting
L1,L,N
Signals
OCC,FD,FS,PS1
Safety Circuit
DI,XC2,CI,XC1
U U U U
NO
U U U U
NO
U U
U
U
U
U
NO
U U NO U
U NO U U
U U U NO
U U NO U
U
U
NO
NO
Pagina 25 di 56
SEA SYSTEMS
MSTK11-GB
Rev.01
30/12/05
2.10.SYSTEM COMMISSIONING
1. Make sure that the maintenance push-button panel switch placed on the car roof is set
to NORMAL;
2. Turn ON the control panel and ascertain that the following leds are switched ON:
1, 2, 8, 10, CM, 01, +5 (in case of Hydraulic lift also TC and PST);
3. Should any problems arise (ex: alarmed card: ALL leds ON), refer to Paragraph 6:
Basic Troubleshooting Procedures.
SETRONIK1
Pagina 26 di 56
SEA SYSTEMS
MSTK11-GB
Rev.01
30/12/05
3.PROGRAMMING
3.1PROGRAMMER CONNECTION (STK2-PM)
1. Check that the ON\OFF switch of the Keyboard is in the OFF position.
2. Insert the connection cable in connector FC3 on the STK1-B board.
3. Bring the ON\OFF switch in the ON position.
4. All the 7 displays show the number 8 for about 2: this function is used to check that
all displays are working correctly.
5. After the 2, the displays show 0.00.XXXX (X indicates any number), or 0.00.0000
with the last four digits flashing. In this second case it means that an access code
has been stored and that it is therefore necessary to enter the digits of the access
code in the last 4 displays (DG3..DG6) and then to press
.
ab
d ef
g c
a= Displays indicating the Parameter Code, marked as DG0, DG1 and DG2.
b= Displays indicating the Parameter Value, marked DG3, DG4, DG5, DG6.
c= DIN guide release
d= ON\OFF switch.
e= Connection cable to connector FC3 on the STK1-B board.
f= Pushbutton
to select the display from DG0 to DG6, scrolling from left to right
whenever it is pressed. The selected display flashes.
g= Pushbuttons
SETRONIK1
Pagina 27 di 56
SEA SYSTEMS
MSTK11-GB
Rev.01
30/12/05
DG1
DG2
DG3
DG4
DG5
DG6
DG0 flashes
1.2. Set 4 on DG0 using pushbuttons
DG0
DG1
DG2
DG3
DG4
DG5
DG6
DG0 flashes
DG1
DG2
DG3
DG4
DG5
pushbutton once
DG6
DG1
DG2
DG3
DG4
DG5
DG6
4 0 2
DG1
DG2
DG3
DG4
DG5
pushbutton once
DG6
DG3..DG6 flash
4 0 2
DG1
DG2
DG3
DG4
DG5
DG6
4 0 2 0 0 8 0
DG3..DG6 flash
NOTA
SETRONIK1
Pagina 28 di 56
SEA SYSTEMS
MSTK11-GB
Rev.01
30/12/05
DG1
DG2
DG3
DG4
DG5
DG6
0 1 0
ACCESS CODE
The old access code stored is displayed. If no code has been entered, value 0000 is
displayed.
Enter the new access code on displays DG3..DG6.
(Value 0000 removes the access code)
2. Set Parameter Code 0.11 on displays DG0, DG1, DG2.
DG0
DG1
DG2
DG3
DG4
DG5
DG6
0 1 1
ACCESS CODE
Enter the same access code entered in point 2 on displays DG3..DG6. If the code is
different, the same is not accepted, therefore the old code previously stored, if any, is
valid.
(Value 0000 removes the access code)
3. Perform the storing. (Please refer to the Par.3.4_Parameters Storing).
SETRONIK1
Pagina 29 di 56
SEA SYSTEMS
MSTK11-GB
Rev.01
30/12/05
3.4.PARAMETERS STORING.
This parameter execute the command for the permanent storing of the parameters
modified. If this operation is not performed, any modifications made remain valid until the
power supply to the STK1_B boards is cut off.
1. Set Parameter Code 0.12 on displays DG0, DG1, DG2.
DG0
DG1
DG2
DG3
DG4
DG5
DG6
0 1 2 0 0 0 0
2. Press
DG0
:
DG1
DG3..DG6 flash.
DG2
DG3
DG4
DG5
DG6
0 1 2 0 0 0 0
3. Press
for one second, then displays DG3..DG6 indicate the following result of the
operation:
DG0
DG1
DG2
DG3
DG4
DG5
DG6
0 1 2 0 0 0 2
Or
DG0
DG1
DG2
DG3
DG4
DG5
DG6
0 1 2 0 0 0 3
SETRONIK1
STORING INCORRECT.
Repeat the command or replace the board.
Pagina 30 di 56
SEA SYSTEMS
MSTK11-GB
Rev.01
30/12/05
DG1
DG2
DG3
DG4
DG5
DG6
1 0 0
MASTER / SLAVE
0= Single Lift
1= Master control panel for Duplo with two signalings
Coming
2= Master control panel for Duplo with one signaling
Coming
3= Slave control panel for Duplo
4= Not used
SELECTOR TYPE
0= APB
1= Not enabled
2= Down collective
3= Up and down Collective
4= Pick-Up
LIFT TYPE
DG1
DG2
DG3
DG4
DG5
DG6
1 0 1
NUMBER OF SERVICES
NUMBER OF STOPS
SETRONIK1
Pagina 31 di 56
SEA SYSTEMS
MSTK11-GB
Rev.01
30/12/05
DG1
DG2
DG3
DG4
DG5
DG6
1 0 2
- PARKING FLOOR (TIMER 4.08)
- PREFERENTIAL OPERATION FLOOR
MAIN FLOOR
DG0
DG1
DG2
DG3
DG4
DG5
DG6
1 0 3
FIREMAN FLOOR #2
(Input Function 9)
FIREMAN FLOOR #1
DG0
DG1
DG2
DG3
DG4
DG5
DG6
1 0 4
NUMBER OF DUPLO VERTICAL RISE FLOORS
NOTA
Floors numbering starts from number 1 corresponding to the lower external floor
SETRONIK1
Pagina 32 di 56
SEA SYSTEMS
MSTK11-GB
Rev.01
30/12/05
DG1
DG2
DG3
DG4
DG5
DG6
1 0 5
OPERATOR B
See Operator A
OPERATOR A:
00
01
02
03
04
05
09
10
11
12
13
Floor Doors
No Available
Manual
Manual
Manual
Manual
Manual
Automatic
Automatic
Automatic
Automatic
Automatic
Car Doors
No Available
Manual
safety photocell
Automatic
Automatic
Automatic
Automatic
Automatic
Automatic
Automatic
Automatic
Limit switches
No Available
Nothing
Nothing
Closing and Opening
Opening
Nothing
Closing and Opening
Closing and Opening
Opening
Nothing
Nothing
Notes
(1)
(1)
(2)
(1), (4)
(1)
(1)
(2)
(2), (3)
(1)
= Set the timer 4.04 (for Operator A) end/or the timer 4.05 (for operator B) twice the
door closing time;
(Limit switches are controlled: see error codes from 76 to 79)
(2)
Set the timer 4.04 (for Operator A) end/or the timer 4.05 (for operator B) equal to the
door closing time;
(3)
= The door opening/closing signal is turned off when the set with the timer 4.04
end/or 4.05 is over;
(4)
= Set the timer 4.06 (for both operators A and B) to delay the door ri-opening after
the photocell activation (with 4.06.0000 = immediate ri-opening)
Operators with Motor power supplied during the run with closing limit switch:
In case of operators that need to be power supplied during le lift run, it is necessary to use
the input programmable functions 30 and 31 (see par. 3.14)
SETRONIK1
Pagina 33 di 56
SEA SYSTEMS
MSTK11-GB
Rev.01
30/12/05
DG1
DG2
DG3
DG4
DG5
DG6
1 0 6
TYPE OF POSITION INDICATIONS
Once the lift has reached the value set, the lift goes
out of service (Only for hydraulic lifts)
If set on 00, this function is not considered.
SETRONIK1
Pagina 34 di 56
SEA SYSTEMS
MSTK11-GB
Rev.01
30/12/05
DG1
DG2
DG3
DG4
DG5
DG6
1 0 7
GONG ACTIVATION
0= No function enabled
1= Advance door opening enabled during run, safety
circuit required (CS1)
2= Floor levelling enabled, safety circuit required
(CS1)
3= Advance doors opening and floor levelling, safety
circuit required (CS1).
MOVABLE PLATFORM (*)
SETRONIK1
Pagina 35 di 56
SEA SYSTEMS
MSTK11-GB
Rev.01
30/12/05
DG1
DG2
DG3
DG4
DG5
DG6
1 0 8
OVERLOAD CONTACT (INPUT CE)
0=Contact NO;
1=Contact NC
SETRONIK1
Pagina 36 di 56
SEA SYSTEMS
MSTK11-GB
Rev.01
30/12/05
3.11.PROGRAMMING OF SERVICES.
In order to modify the parameters values, it is necessary to disconnect the FA automatic
valve while, to only display the same, this is not necessary.
DG0
DG1
DG2
DG3
DG4
DG5
DG6
2
TYPE OF OPENING AND
DOOR STATUS IN PARKING FOR B ACCESS:
0= There is no service
1= Simplex Access (*)
2= Duplo Access (*)
STOP
01= Stop1
02= Stop2
03= Stop3
04= Stop4
.
.
.
12= Stop12
(*) Simplex / Duplo Access= The Access has to be programmed Simplex if the relative
stop is served by only one lift (in this case the Simplex access has to be
programmed on this lift);
The access has to be programmed Duplo if the relative stop is served by both the
lifts (in this case the Duplo Access has to be programmed on both the lifts).
SETRONIK1
Pagina 37 di 56
SEA SYSTEMS
MSTK11-GB
Rev.01
30/12/05
3.12.SHAFT PROGRAMMING:
In order to modify the parameters values, it is necessary to disconnect the FA automatic
valve while, to only display the same, this is not necessary.
DG0
DG1
DG2
DG3
DG4
DG5
DG6
0 0
INTER-FLOOR TYPE (*)
SETRONIK1
Pagina 38 di 56
SEA SYSTEMS
MSTK11-GB
Rev.01
30/12/05
3.13.PROGRAMMING OF TIMERS:
DG0
DG1
DG2
DG3
DG4
DG5
DG6
4
TIME
SETRONIK1
Pagina 39 di 56
SEA SYSTEMS
MSTK11-GB
Rev.01
30/12/05
3.14.INPUT PROGRAMMING:
DG0
DG1
DG2
DG3
DG4
DG5
DG6
0 0
INPUTS:
Led
Term.
00
01
02 (*)
03 (*)
04 (*)
05 (*)
06
07 (*)
08
09
10
11
12
13
14
X1
X2
X3
X4
X5
X6
X7
X8
X9
X10
X11
FG
MR
TC
X1
X2
X3
X4
X5
J8.4
J9.4
J2.4
J2.5
J2.6
J2.7
FG
MR
TC
15
16
PST
MP
PST
MP
INPUT FUNCTION
00 None
01 - Safety photocells (With operators in 02 type);
- Door opening extralimit switch of the 1 and 2 operator (with
operator different from 02 type) (NC contact)
02 Oil thermal sensor (NC contact)
03 Low point pressure switch (NC contact)
04 Peak point pressure switch (NC contact)
05 Landing operation stop control (for ACVV or 3VF with old interface)
06 Operator A sticking contactor control
07 Operator B sticking contactor control
08 Fire-fighting operation with despatch to the fire-fighting floor #1
09 Fire-fighting operation with despatch to the fire-fighting floor #2
10 Preferential operation
11 Safety circuit control (err 19, 20)
12 Very close landings control (with Additional ID switch)
13 Very close landings control (with Additional IS switch)
14 High/low speed Maintenance
16 Full load
17 Alarm with 0094 error, Out-of-service on landing
18 Additional extralimit switch in the top_Contact monitoring and 0095
error signalling
19 Alarm with 0096 error, immediate out-of-service
20 Alarm with 0097 error, Failed start (3VF)
21 Reserved operation
22 Hong Kong Firemen operation
23 Photocell of the operator A independent of the opening push button
(used with selective opening)
24 Photocell of the operator B independent of the opening push button
(used with selective opening)
25 Out-of-service with despatch to the programmed parking floor with
signalling of error 098
26 BA1 input (NA) for panels without board STK1-E
28 Emergency operation (not with board B12E)
29 CM1 input (NC) for panels without board STK1-E
30 Doors closing limit switch for operator A (NC contact for lifts with
motors powered during the run)
31 Doors closing limit switch for operator B (NC contact for lifts with
motors powered during the run)
32 Low and peak point pressure switch (PST) (NC contact; it can be
used only on inputs X6, X9, FG, PST)
SETRONIK1
Pagina 40 di 56
SEA SYSTEMS
MSTK11-GB
Rev.01
30/12/05
3.15.OUTPUT PROGRAMMING:
DG0
DG1
17
18
19 (*)
20 (*)
21
22
Led
01
02
03
04
05
06
DG2
DG3
DG4
DG5
DG6
0 0
Term.
32 / J8.2
30 / J8.3
42 / J9.2
40 / J9.3
J7.1 / J7.2
J7.1 / J7.3
OUTPUT FUNCTION
00 None
01 Door opening command for operator A (NO)
02 Door opening command for operator B (NO)
03 Door closing command for operator A (NO)
04 Door closing command for operator B (NO)
05 Fixed occupied command, car light
06 Retiring cam command
07 Stop command at stop: for ACVV e 3VF with old interface
08 Soft Starter command
09 Soft Stop command during upward run
10 Delta contactor command
12 Soft Stop command during upward and downward run
13 Brake command with 3VF starting
14 Resistors or impedance exclusion command (SCC) at
start
15 Resistors exclusion command upon speed change
16 CS1 enabling (obsolete)
17 Intermediate speed command between short floors with
3VF (obsolete)
18 Intermediate speed command between close floors with
3VF (obsolete)
19 Relevelling command
20 Relay KV1 command for 3VF
21 Relay KV2 command for 3VF
22 Door closing command for both the operators
23 Door opening command for operator A (NC)
24 Door opening command for operator B (NC)
25 VMP command with Soft Stop and valve 2CH
26 Alarm filtering command
Timer
4.04
4.05
4.04
4.05
4.10
4.11
4.10
4.11
4.11
4.10
4.04
4.05
4.11
NOTE: Functions 0016, 0017, 0018 are obsolete with diagrams based on Eprom 4.00 or
later types.
SETRONIK1
Pagina 41 di 56
SEA SYSTEMS
MSTK11-GB
Rev.01
30/12/05
4.DIAGNOSIS
4.1.LIFT STATUS DISPLAY
The parameter value (DG3..DG6) is constantly updated in relation to the current status of
the lift.
If the Car Position is 00 (DG5, DG6), this means that the resetting operation has not been
performed.
DG0
DG1
DG2
DG3
DG4
DG5
DG6
0 0 0
CAR POSITION
0= Floor parking
1= Doors closing for start
2= High speed motion
3= Low speed motion
4= Doors opening
5= Car still off landing
LIFT STATUS
0= Normal operation
1= Firemen operation on
2= Fire-fighting operation on
3= Preferential operation on
4= Reserved operation on
5= Safety photocell action
6= Not used
7= Out-of-service for failures at floor
8= Out-of-service for permanent failures
9= Maintenance operation on
SETRONIK1
Pagina 42 di 56
SEA SYSTEMS
MSTK11-GB
Rev.01
30/12/05
DG1
DG2
DG3
DG4
DG5
DG6
0 0 1
FAILURE CODE
NUMBER OF TIMES THE BOARD DETECTED THE FAILURE
(MAX 9)
If the parameter value (DG3..DG6) is 0000, this means that no failure or malfunction has
occurred.
B).DISPLAY OF THE LAST 16 FAILURES:
Set Parameter Code 0.02 on displays DG0, DG1, DG2 and press :
DG0
DG1
DG2
DG3
DG4
DG5
DG6
0 0 2
FAILURE CODE
NUMBER OF TIMES THE BOARD HAS DETECTED THE
FAILURE (MAX 9)
By pressing pushbutton
By pressing pushbutton
If the parameter value (DG3..DG6) is 0000, this means that no failure/malfunction has
occurred or the end of the failure codes list has been reached.
C).FAILURES CANCELLATION:
1. Set Parameter Code 0.03 on displays DG0, DG1, DG2 and press :
DG0
DG1
DG2
DG3
DG4
DG5
DG6
0 0 3 0 0 0 0
DG3..DG6 FLASH
2. Press . The parameter value (DG3..DG6) shows 0001 to indicate that failures have
been deleted:
DG0
DG1
DG2
DG3
DG4
DG5
DG6
0 0 3 0 0 0 1
SETRONIK1
FAILURES DELETED
Pagina 43 di 56
SEA SYSTEMS
MSTK11-GB
Rev.01
30/12/05
DG1
DG2
DG3
DG4
DG5
DG6
0 0
NUMBER OF TENS OF RUNS
DG1
DG2
DG3
DG4
DG5
DG6
0 0 6 0 0
RUNS NUMBER
DG1
DG2
DG3
DG4
DG5
DG6
0 0
NUMBER OF RELEVELLINGS
SETRONIK1
Pagina 44 di 56
SEA SYSTEMS
MSTK11-GB
Rev.01
30/12/05
DG1
DG2
DG3
DG4
DG5
DG6
0 0 9
B OPERATOR CLOSING\OPENING OPERATION:
SETRONIK1
Pagina 45 di 56
SEA SYSTEMS
MSTK11-GB
Rev.01
30/12/05
CARD
PORT
TYPE
STATUS
DESCRIPTION
STK1-B
IN_NP
ON
STK1-B
IN_NP
ON
ON
OFF
Normal operation
STK1-B
IN_NP
STK1-B
IN_NP
ON
10
STK1-B
IN_NP
ON
+5
STK1-B
ON
AD
STK1-B
OUT_NP
ON
ALL
STK1-B
OUT_NP
AS
STK1-B
OUT_NP
ON
Upward command
AV
STK1-B
OUT_NP
ON
BA
STK1-B
IN_NP
ON
BA1
STK1-E
IN_NP
ON
BD
STK1-B
IN_NP
ON
BKC
STK1-B
IN_NP
ON
BS
STK1-B
IN_NP
ON
CE
STK1-B
IN_NP
ON
CM
STK1-B
IN_NP
ON
CM1
STK1-E
IN_NP
ON
D-E
STK1-B
IN_NP
ON
DR
STK1-B
IN_NP
ON
DS
STK1-B
IN_NP
ON
ED1..E
D6
STK1-B
IN_NP
ON
ED7..E
D12
STK1-E
IN_NP
ON
EM
STK1-B
IN_NP
ON
SETRONIK1
Pagina 46 di 56
SEA SYSTEMS
MSTK11-GB
Rev.01
30/12/05
LED
CARD
PORT
TYPE
STATUS
DESCRIPTION
FD
STK1-B
OUT_NP
ON
Down arrow
FFS
STK1-B
OUT_NP
ON
Out-of-service
FG
STK1-B
IN_P
ON
FM
STK1-B
IN_NP
ON
FS
STK1-B
OUT_NP
ON
Up arrow
HCB
AL01
IN_NP
ON
OFF
HPS
AL01
OUT_NP
ON
OFF
OFF
HSF
AL01
IN_NP
I1..I6
STK1-B
IN_NP
ON
I7..I12
STK1-E
IN_NP
ON
ID
STK1-B
IN_NP
ON
IS
STK1-B
IN_NP
ON
M-AB
STK1-B
IN_NP
ON
MP
STK1-B
IN_P
ON
MR
STK1-B
IN_P
ON
O1
STK1-B
OUT_P
ON
O2
STK1-B
OUT_P
ON
O3
STK1-E
OUT_P
ON
O4
STK1-E
OUT_P
ON
O5
STK1-B
OUT_P
ON
O6
STK1-B
OUT_P
ON
SETRONIK1
Pagina 47 di 56
SEA SYSTEMS
LED
CARD
PORT
TYPE
STATUS
DESCRIPTION
OCC
STK1-B
OUT_NP
ON
Flashing
Car moving
MSTK11-GB
Rev.01
30/12/05
PCP
STK1-B
IN_NP
ON
PS1..
PS6
STK1-B
OUT_NP
ON
Car position
PS7..
PS12
STK1-E
OUT_NP
ON
Car position
PST
STK1-B
IN_P
ON
STK1-B
IN_NP
ON
SCE
STK1-B
OUT_NP
ON
Overloaded car
SGG
STK1-B
OUT_NP
ON
Gong actived
SR
STK1-B
IN_NP
OFF
TC
STK1-B
IN_P
ON
X1
STK1-B
IN_P
ON
X10
STK1-B
IN_P
ON
X11
STK1-B
IN_P
ON
X2, X3,
X4, X5
STK1-E
IN_P
ON
X6
STK1-B
IN_P
ON
X7
STK1-E
IN_P
ON
X8
STK1-B
IN_P
ON
X9
STK1-B
IN_P
ON
SETRONIK1
Pagina 48 di 56
SEA SYSTEMS
MSTK11-GB
Rev.01
30/12/05
DESCRIPTION
001
002
Low speed timer action ( Timer 4.01.XXXX )_ Immediate Permanent Out of Order
003
004
Not used
005
The car has performed a number of levellings equal to the value set in Parameter
1.06.XXXX_Permanent Out of Order at floor
006
Run (KM)/ High (KA)/ Low (KB) contactors sticking_ Immediate Permanent Out of
Order
007
Up (KS)/ Star (KY)/ Delta (K) contactors sticking_Immediate Permanent Out of Order
008
009
010
011
012
Pit stop action (AF)/ Maintenance Stop (MA)/ Safety gear (PT)/ Approaches (ACC)/
End of Timer 4.13.XXXX at floor with doors kept open_ Immediate Permanent Out of
Order
013
Not used
014
Safety photocell action (for cars with no doors) _ Immediate Temporary Out of Order
015
Failed excitation of the Run (KM)/ High (KA)/ Low (KB) contactors
016
017
018
019
Safety circuit (CS1) active with car off floor (input function 11)_ Immediate Temporary
Out of Order
020
Safety circuit (CS1) not active with car at floor (input function 11)_ Immediate
Temporary Out of Order
021..044
045..068
069
SETRONIK1
Pagina 49 di 56
SEA SYSTEMS
MSTK11-GB
Rev.01
30/12/05
CODE
DESCRIPTION
070
Failed excitation of door opening minicontactor KAP for 1operator (if it exists)
071
Failed excitation of door opening minicontactor KAP1 for 2operator (if it exists)
072
Failed excitation of door closing minicontactor KCP for 1 operator (if it exists)
073
Failed excitation of door closing minicontactor KCP1 for 2 operator (if it exists)
074
Sticking of door opening/closing minicontactor KAP \ KCP for 1operator (if it exists)
075
Sticking of door opening/closing minicontactor KAP1 \ KCP1 for 2operator (if it exists)
CODE
DESCRIPTION
076
Door opening limit switch FCA did not open after the programmed time (Timer 4.04.)
(if it exists)
077
Door closing limit switch FCC did not open after the programmed time (Timer 4.04) (if
it exists)
078
Door opening limit switch FCA1 (for 2operator) did not open after the programmed
time (Timer 4.05) (if it exists)
079
Door closing limit switch FCC1 (for 2operator) did not open after the programmed
time (Timer 4.05) (if it exists)
080
Floating floor off for more than 5 consecutive runs (with programmed parameter 1.07)
090
Oil thermal sensor action (STO) in hydraulic lifts or Motor thermal sensor action (TS1TS2) in Electric lifts_ Temporary Out of Order at floor
091
Low and/or peak point pressure switch action (SP, SP1) (standard electrical
configuration)_ Immediate Permanent Out of Order
092
093
Not used
094
095
096
Alarm combined with Function 19 input (e.p. ACVV, VVVF, electronic valve GEV,)_
Immediate Permanent Out of Order
097
Failed start (Combined with Function 20 input, e.p. VVVF, )_ Permanent Out of
Order at floor
098
SETRONIK1
Pagina 50 di 56
SEA SYSTEMS
MSTK11-GB
Rev.01
30/12/05
CODE
DESCRIPTION
100..123
124..147
148..171
172..195
196..219
220..243
244
245
246
247
248
SETRONIK1
Pagina 51 di 56
SEA SYSTEMS
MSTK11-GB
Rev.01
30/12/05
5.MAINTENANCE
Before carrying out any cleaning or maintenance operations, unplug the appliance from
the power supply unit by turning OFF the master switch.
While maintenance procedures are in progress, refer to the safety regulations set out in
paragraph 2.
In no event shall SEA SYSTEMS Srl be liable for any damages whatsoever arising out of
the inability to comply with the above instructions and of any improvements as regards
configuration, fastening and connections in the originally supplied apparatus.
5.1.BATTERY REPLACEMENT
The control panel is fitted with the following batteries:
12v 2Ah. or
5.2.SHAFT SENSORS
Shaft indicators are formed by monostable and/or bistable sensors and their
corresponding magnets to enable switching.
In order to ensure that sensors switch over properly when placed opposite their
corresponding magnets, check out on a yearly basis that:
-
The distance between the sensor and its corresponding magnet is kept 1 cm apart,
including during machining stress;
The brackets for both the sensors and magnets are steadily fastened to the car roof
and the guides.
SETRONIK1
Pagina 52 di 56
SEA SYSTEMS
MSTK11-GB
Rev.01
30/12/05
SETRONIK1
Pagina 53 di 56
SEA SYSTEMS
MSTK11-GB
Rev.01
30/12/05
SETRONIK1
Pagina 54 di 56
SEA SYSTEMS
MSTK11-GB
Rev.01
30/12/05
SETRONIK1
Pagina 55 di 56
SEA SYSTEMS
MSTK11-GB
Rev.01
30/12/05
7.TECHNICAL DATA
Input voltages
Operating voltage
48 Vdc
ON DEMAND
Operating temperature
0 40 C
Logic type
MICROPROCESSOR CONTROLLED
Data storage
PERMANENT
Re-chargeable battery
NOTE 1:
If the Position and Arrow signallings require a power upper than that specified upon, its
necessary use STK1-RO card;
NOTE 2:
If the Position Arrow and Booking signallings require a power upper than that specified upon,
its necessary use STK1-RV card;
NOTE 3: (electronic gong)
if the Gong absorption current exceeds 200 ma, it is necessary to put the resistor (47 5w) given
with the controller in series with the gong.
SETRONIK1
Pagina 56 di 56