and switch-disconnectors
80 to 3200 A
As standards, specifications and designs change from time to time, please ask for confirmation
of the information given iin this publication
ce
document
a thas
imprim
This
document
been printed on ecological paper
sur du papier cologique.
http://www.schneiderelectric.com
Design: Schneider Electric - AMEG
Photos: Schneider Electric
Printed:
BTP550E
12-00
colibris
046751
045345
Compact NS 80 A
053100
Things
E45151
will
the
never be
same
New Compact NS,
setting the standard, once again...
E45178
Compact NS
Schneider Electric
Compact NS,
even more applications...
E20999
push
to
trip
E26988
p. 14
Protection for:
c distribution systems supplied by transformers
c distribution systems supplied by engine generator sets
c long cables in IT and TN systems.
Installation :
c in power switchboards
c on DIN rails (see page 42)
Special applications:
c single-phase and two-phase systems (see page 34)
c 1000 V distribution systems (see page 36)
c 400 Hz distribution systems (see page 38)
c DC systems (see page 40).
All circuit breakers in the Compact NS range offer positive contact indication
and are suitable for isolation in compliance with standards IEC 60947-1 and 2.
p. 44
When combined with a motor starter, Compact NS circuit breakers protect the
cables and the starter against short-circuits. Equipped with an electronic trip unit,
Compact NS circuit breakers also protect the cables, starter and motor against
overloads.
The exceptional current-limiting capacity of Compact NS circuit breakers
automatically ensures type-2 coordination with the motor starter, in compliance with
standard IEC 60947-4-1.
E44356
Protection of machines
p. 52
The different circuit-breaker versions in the Compact NS range are designed to
meet the specific requirements of machines:
c compliance with international standards IEC 60947-2 and UL 508 / CSA 22-2 No. 14
c compliance with U.S. standard UL 489
c protection against overloads and short-circuits
c positive contact indication
c installation in universal and functional enclosures.
E44357
Earth-leakage protection
M
G
p. 56
Additional earth-leakage protection protects life and property against the risks
of faulty insulation in the installation. Depending on the circuit breaker,
earth-leakage protection is provided by:
c adding a Vigi module to the circuit breaker
c using a specific Micrologic control unit
c using a Vigirex relay and separate toroids.
Compact NS
Schneider Electric
E21272
Switch-disconnectors
p. 60
A switch-disconnector version of Compact NS circuit breakers exists for circuit
control and isolation.
All the additional functions may be combined with the basic switch-disconnector
function, including:
c earth-leakage protection
c motor mechanism
c ammeter, etc.
For information on other switch-disconnector ranges, see the Interpact (offering
positive contact indication and visible break) and Fupact (fuse switch) catalogues.
push
to
trip
p. xx
E56631
Service connection
5...8
push
to
trip
STR
90 %Ir
105
22 DE
50/60Hz
test
Im
.9
.95
.98
.63
push
to
trip
STR
90 %Ir
105
alarm
Ir
.85
.8
.7
3
8
2
1.5
Ir Im
10
xIr
xIn
22 DE
50/60Hz
test
Im
.9
.95
.98
.63
alarm
Ir
.85
.8
.7
3
8
2
1.5
Ir Im
10
xIr
xIn
E32454
Source-changeover systems
N
UL 489 applications
Compact NS circuit breakers also meet the requirements of applications governed
by standard UL 489 (see the corresponding catalogue).
Compact NS
Schneider Electric
E27836
Ui750V Uimp8kV
Icu
(kA)
220/240
380/415
440
500
525
660/690
250
Breaking capacity
Icu at 415 V
compact
NS 250 N
Ue
(V)
85
36
35
30
22
8
50
IEC 947-2
cat A
E27837
N: standard breaking
capacity
compact
NS 250 H
Ui750V Uimp8kV
Ue
(V)
Icu
(kA)
220/240
380/415
440
500
525
660/690
250
100
70
65
50
35
10
85
IEC 947-2
cat A
Breaking capacity
Icu at 415 V
E58550
compact
NS 250 L
Ui750V Uimp8kV
Ue
(V)
Icu
(kA)
220/240
380/415
440
500
525
660/690
250
150
150
130
70
50
20
100
IEC 947-2
cat A
Total discrimination
as standard
E22051
E27838
push
to
trip
Compact NS
Schneider Electric
047313
041879
053100
041625
E45151
E45163
Withdrawable Compact
NS250 on chassis
E45178
Compact NS
Schneider Electric
...simplified installation
046751
045345
053100
80 A
100 to 250 A
400 to 630 A
E45178
E45151
630 to 1600 A
1600 to 3200 A
041650
Many connection
possibilities
Connection parts
for Compact NS
042788
Busways
Compact NS circuit breakers up to 630 A can be
installed in tap-off units of the Telemecanique Canalis
range of busbar trunking.
Compact NS
E32455
Schneider Electric
...optimised protection
and accurate measurements
Compact NS100 to 630
041638
041625
048287
TM thermal-magnetic
trip unit
Compact NS250
041641
045212
Ammeter module
Compact NS
056480
056479
E45151
Compact NS630b to 3200 circuit breakers are equipped with Micrologic control
units that are interchangeable on site.
Micrologic 2.0 and 2.0 A control units offer standard protection. Micrologic 5.0 and
5.0 A control units offer selective protection that can be completed by earth-fault
protection on Micrologic 6.0 A and earth-leakage protection on Micrologic 7.0 A
control units.
The ammeter version of Micrologic control units provides current measurements.
These units are equipped with a digital display and bargraph, used in conjunction
with simple navigation buttons. Access to the desired parameters and settings
is direct and navigation between screens is intuitive. Settings are greatly simplified
by direct display on the screen.
Micrologic 2.0 A,
5.0 A, 6.0 A, 7.0 A
Schneider Electric
16
15
12
E24603
1
8
11
9
10
13
2
2
4
3
6
14
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
Breaking unit
Trip units or control units
Vigi earth-leakage protection module
Insulation monitoring module
Voltage presence indicator
Ammeter module
MN and MX voltage releases
Multifunction auxiliary contact
Direct rotary handle
Extended rotary handle
Motor mechanism
Plug-in base
Connection of auxiliary circuits to plug-in base or withdrawable chassis
Connection accessories
Short terminal shields
Long terminal shields
Compact NS
Schneider Electric
...modern products
E37615
meter
circuit breaker
or other power
actuator
ModBus / JBus
CLS150 indication
and local-control
module
Digipact internal bus
Multi 9 control
DC150 data concentrator
UA150 automatic
source-changeover
controller
oiseaux
Compact NS
Schneider Electric
10
Compact NS
Schneider Electric
Compact NS
Presentation
General characteristics
Protection of distribution systems
12
14
Overview of solutions
Compact NB circuit breakers up to 600 A
Compact NS circuit breakers up to 630 A
Compact NS circuit breakers from 630 up to 3200 A
TM and STR trip units for Compact NS100 to 250
MP and STR trip units for Compact NS400 to 630
Micrologic control units for Compact NS630b to 3200
Special cases:
c Single-phase and two-phase systems
c 1000 V systems
c 400 Hz applications
c Circuit breaker selection for DC applications
c Incoming circuit breakers in final distribution NSA160
14
16
18
20
22
24
28
34
36
38
40
42
Motor protection
44
Overview of solutions
Compact NS80H-MA
NS100 to 630 circuit breakers with MA magnetic trip units
NS100 to 250 circuit breakers with STR22ME electronic trip unit
NS400 to 630 circuit breakers with STR43ME electronic trip unit
44
46
47
48
50
52
Overview of solutions
Circuit breaker NSC100N
Trip units, auxiliaries, installation enclosures
UL508 / CSA 22-2 no. 14 marking
52
53
54
55
Earth-leakage protection
56
Overview of solutions
Add-on Vigi module (Vigicompact) for Compact NS100 to 630
56
57
58
Overview of solutions
Compact NSA125NA and NSA160NA switch-disconnectors
Compact NSC100 and NS100 to 630NA switch-disconnectors
Compact NS630bNA to 1600NA switch-disconnectors
Compact NS1600b to 3200NA switch-disconnectors
58
60
62
64
66
Source-changeover systems
68
Presentation
Manual source-changeover systems
Remote-operated systems
Controllers
68
69
70
71
Communication
COM option in Compact
Compact in a communication network
72
74, 76
76
80
Test equipment
Display modules
Installation recommendations
Dimensions, volumes
Connection
Electrical diagrams
Additional characteristics
Catalogue numbers
11
Compact NS
139
140
143
165
205
221
251
267
Schneider Electric
General characteristics
E18567
Functions and
characteristics
compact
NS160 H
Ui 750V. Uimp 8kV.
Ue
(V)
220/240
380/415
440
500/525
660/690
250
Icu
(kA)
100
70
65
50
10
85
Pollution degree
Compact NS circuit breakers are certified for operation in pollution-degree III
environments as defined by IEC standard 60947 (industrial environments).
Tropicalisation
Compact NS circuit breakers have successfully passed the tests prescribed by the
following standards for extreme atmospheric conditions:
c IEC 68-2-1 - dry cold (-55 C)
c IEC 68-2-2 - dry heat (+85 C)
c IEC 68-2-30 - damp heat (95% relative humidity at 55C)
c IEC 68-2-52 - salt mist (severity level 2).
Environmental protection
Compact NS circuit breakers take into account important concerns for
environmental protection. Most components are recyclable and the parts of
Compact NS630b to NS3200 circuit breakers are marked as specified in applicable
standards.
Ambient temperature
c Compact NS circuit breakers may be used between -25 C and +70 C.
For temperatures higher than 40 C (65 C for circuit breakers used to protect
motor feeders), devices must be derated as indicated in the documentation.
c Circuit-breakers should be put into service under normal ambient operatingtemperature conditions. Exceptionally, the circuit breaker may be put into service
when the ambient temperature is between -35 C and -25 C.
c The permissible storage-temperature range for Compact NS circuit breakers in
the original packing is -50 C (1) to +85 C.
Discrimination
E22037
CB1
CB2
12
Compact NS
Schneider Electric
044 334
E18569
All Compact NS circuit breakers are suitable for isolation as defined in IEC
standard 60947-2:
c the isolation position corresponds to the O (OFF) position
c the operating handle cannot indicate the OFF position unless the contacts are
effectively open
c padlocks may not be installed unless the contacts are open.
Installation of a rotary handle or a motor mechanism does not alter the reliability
of the position-indication system.
The isolation function is certified by tests guaranteeing:
c the mechanical reliability of the position indication system
c the absence of leakage currents
c overvoltage withstand capacity between upstream and downstream connections.
Degree of protection
As per standards IEC 60529 (IP degree of protection) and EN 50102
(IK degree of protection against external mechanical impacts).
E18570
IP40
IK07
IP40
IK07
With toggle
IP40
IK07
IP40
IK07
IP435
IP547
IP55
IK08
IP40
IK07
E28439
push
to
trip
ON
I
push
to
trip
O
OFF
E21277
E28440
push
to
trip
ON
I
push
to
trip
E28441
O
OFF
ON
I
push
to
trip
ON
I
O
OFF
E28442
OFF
push
to
trip
1
manu
/auto
I
push
push
13
ON
OFF
Compact NS
Schneider Electric
E43842
E58563
Functions and
characteristics
E20999
Power distribution
Selection of circuit breakers up to 630 A
page 18
12.5 12.5
160
250
60
400
250
630
NS160
NS250
NS400
NS630
36
70
150
36
70
150
45
70
150
45
70
150
12.5 12.5
125
100
push
to
trip
NS125E NS100
045345
053100
Compact
Breaking capacity
(kA rms)
380/415 V
E
N
H
L
16
25
70
150
page 22
Interchangeable thermal-magnetic and electronic trip units for NS100 to 630 and built-in
thermal-magnetic trip unit for Compact NS125E
250 320
630
800
400
1000
500
1250
640
1600
NS630b NS800
NS1000
NS1250
NS1600
50
70
150
50
70
150
50
70
-
50
70
-
E45151
E43843
Breaking capacity
(kA rms)
380/415 V
N
H
L
50
70
150
1000 1250
2500
3200
NS1600b NS2000
NS2500
70
85
70
85
NS3200
E45178
Breaking capacity
(kA rms)
380/415 V
N
H
70
85
page 28
Micrologic electronic control units may be used on all Compact NS630b to 3200 circuit
breakers and can be changed on site.
14
Compact NS
Schneider Electric
page 34
160 250
125 160
NS100 1P/2P
NS160 1P/2P
NS250 1P
Built-in thermal-magnetic
trip units
Breaking capacity
(kA rms) 220 V
86101
86099
Compact
16 100
1P
25
40
N
H
2P
85
100
1000 V distribution
1P
25
40
2P
85
100
1P
25
-
page 36
60 400
NS400 1000V
Breaking capacity:
10 kA rms at 1000 V
053182
Compact
E21000
NSA160
048016
Compact installation on
a DIN rail
16 160
Breaking capacity
(kA rms) 380/415 V:
E : 16 kA
N : 30 kA
Built-in trip unit
15
Compact NS
Schneider Electric
Functions and
characteristics
054538
manual
Connections
electric
fixed
toggle
direct or extended rotary handle
front connection
rear connection
front connection
rear connection
withdrawable
Mounting
052163
Compact NB50N
Compact NB250N
on backplate or rails
on DIN rail
056605
Protection
Trip units
Overload protection
threshold (A)
Instantaneous short-circuit protection
threshold (x Ir)
Indication and control auxiliaries
Indication contacts
Voltage releases
240 V
480 V
600 V
thermal-magnetic
Ir
at 50 C
at 60 C
Im
MX shunt release
MN undervoltage release
Dimensions (mm)
Weight (kg)
16
Compact NS
Schneider Electric
NB50
3
c
c
c
50
690
6
500
N
NB100
NB250
NB400
NB600
3
c
c
c
c
3
c
c
-
3
c
c
c
-
3
c
c
c
-
400
690
6
500
N
30
25
25
18
15
50 %
c
A
5000
1000
600
690
6
500
N
30
25
25
18
15
50 %
c
A
5000
1000
N
30
18
-
N
30
18
-
non interchangeable
250 300 350 400
250 300 350 10 10 10 10
non interchangeable
500 600
500 10 10
10
10
7.5
5
50 %
A
10000
1500
100
690
6
500
F
15
10
10
5
2.5
50 %
A
10000
1500
N
15
18
15
7.5
5
-
250
690
6
500
N
25
18
15
15
7.5
50 %
c
A
8000
1000
N
15
7.5
-
F
15
5
-
N
25
7.5
-
N
30
15
-
non interchangeable
15 20 30 40 50
15 20 30 40 50
11 10 11 11 9
non interchangeable
15 20 30 40 50
15 20 30 40 50
11 10 11 11 9
c
c
-
c
c
-
c
c
c
c
c
c
c
c
c
c
90 x 155 x 68
1.2
c
c
c
105 x 161 x 86
1.9
c
c
c
140 x 255 x 110
6.0
c
c
c
140 x 255 x 110
6.0
c
75 x 130 x 68
0.7
-
60
60
12
80
80
8
17
non interchangeable
100 100 125 150 175 200 225 250
100 94 119 142 165 190 210 230
11 12 12 12 12 12 12 11
Compact NS
30
Schneider Electric
045345
Functions and
characteristics
manual
Connections
electric
fixed
toggle
direct or extended rotary handle
front connection
rear connection
front connection
rear connection
front connection
rear connection
048286
Compact NS250H
Compact NS630L
240 V
480 V
600 V
Protection
Trip units
Overload protection
Short-circuit protection
Earth-fault protection
Zone selective interlocking
Add-on earth-leakage protection
240 V
480 V
600 V
long time
Ir (In x )
short time
lsd (Ir x )
instantaneous Ii (In x )
lg (In x )
ZSI
add-on Vigi module
combination with Vigirex relay
Current measurements
Additional measurement, indication and control auxiliaries
Indication contacts
MX shunt and MN undervoltage releases
Voltage-presence indicator
Current-transformer module and ammeter module
Insulation-monitoring module
Remote communication by bus
Device-status indication
Device remote operation
Transmission of settings
Indication and identification of protection devices and alarms
Transmission of measured current values
Installation
Accessories
Dimensions (mm) W x H x D
Weight (kg)
18
Compact NS
Schneider Electric
NS125E
NS100
NS160
NS250
NS400
NS630
2(1), 3, 4
c
c
c
c
c
c
c
c
c
2(1), 3, 4
c
c
c
c
c
c
c
c
c
2(1), 3, 4
c
c
c
c
c
c
c
c
c
3, 4
c
c
c
c
c
c
c
c
c
3, 4
c
c
c
c
c
c
c
c
c
L
150
150
130
100
100
75
100
100
160
150
750
8
690
500
N
H
85
100
36
70
35
65
30
50
22
35
8
10
50
85
50
85
100%
c
A
40 000
40 000
20 000
L
150
150
130
70
50
20
100
100
250
220
750
8
690
500
N
H
85
100
36
70
35
65
30
50
22
35
8
10
50
85
50
85
100%
c
A
20 000
20 000
10 000
L
150
150
130
70
50
20
100
100
400
320
750
8
690
500
N
H
85
100
45
70
42
65
30
50
22
35
10(2) 20(2)
85
85
100%
c
A
15 000
12 000
6 000
L
150
150
130
100
100
75(2)
-
630
500
750
8
690
500
N
H
85
100
45
70
42
65
30
50
22
35
10(2) 20(2)
85
85
100%(3)
c
A
15 000
8 000
4 000
L
150
150
130
70
50
35(2)
-
50%
c
A
10 000
6 000
6 000
100
100
750
8
690
500
N
H
85
100
25
70
25
65
18
50
18
35
8
10
50
85
50
85
100%
c
A
50 000
50 000
30 000
E
5
5
-
N
85
25
10
H
100
65
35
L
200
130
50
N
85
35
20
H
100
65
35
L
200
130
50
N
85
35
20
H
100
65
35
L
200
130
50
N
85
42
20
H
100
65
35
L
200
130
50
N
85
42
20
H
100
65
35
L
200
130
50
E
-
N
85
25
10
H
85
65
10
L
-
N
85
35
10
H
85
65
10
L
-
N
85
35
18
H
85
65
18
L
-
N
85
42
18
H
85
65
18
L
-
N
85
42
30
H
85
65
30
L
-
non interchangeable
12.5 125 (A)
c
c
-
TM (thermal-magnetic)
c
c
c
c
-
c
c
-
c
c
c
c
c
c
c
-
c
c
c
105 x 161 x 86
1.7 / 2.3
c
c
c
105 x 161 x 86 / 140 x 161 x 86
1.6 to 1.9 / 2.1 to 2.3
c
c
c
140 x 255 x 110 / 185 x 255 x 110
6.0 / 7.8
3, 4
c
c
c
125
750
8
500
E
25
16/10
10
6
-
STR22 (electronic)
c
c
c
c
c
-
STR23 (electronic)
c
c
c
c
c
-
STR53 (electronic)
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
-
19
c
c
-
Compact NS
c
c
c
c
c
Schneider Electric
Functions and
characteristics
E45151
manual
toggle
direct or extended rotary handle
electric
Type of circuit breaker
Connections
fixed
withdrawable (on chassis)
E45178
Compact NS800H
Compact NS2000H
front connection
rear connection
front connection
rear connection
240 V
480 V
600 V
long time
Ir (In x )
short time
Isd (Ir x )
instantaneous Ii (In x )
lg (In x )
In
ZSI
MX shunt release
MN undervoltage release
20
Compact NS
Schneider Electric
NS630b NS800
3, 4
c
c
c
N
c
c
c
c
H
c
c
c
c
L
c
c
c
c
630
630
750
8
690
500
N
H
50
70
50
70
50
65
40
50
30
42
75% 50%
25
25
17
17
c
B
B
10000
6000
5000
4000
2000
III
800
800
N
50
35
25
L
125
100
-
H
65
50
50
NS1000
1000
1000
3, 4
c
c
c
N
c
c
c
c
3, 4
c
N
c
-
1250
1250
750
8
690
500
N
50
50
50
40
30
75%
25
17
c
B
10000
5000
4000
3000
2000
III
L
150
150
130
100
25
100%
10
7
A
Micrologic 2.0
c
c
c
-
NS1250 NS1600
N
50
35
25
Micrologic 5.0
c
c
c
c
-
H
c
c
c
c
1600
1510
1600
1550
750
8
690
500
N
85
70
65
65
65
65 kA
40
28
c
B
6000
3000
2000
2000
1000
III
H
70
70
65
50
42
50%
25
17
B
5000
2000
2000
1000
H
65
50
50
Micrologic 2.0 A
c
c
c
c
c
2000
1900
2500
2500
3200
2970
H
125
85
85
75%
40
28
B
N
85
65
50
Micrologic 5.0 A
c
c
c
c
c
c
Micrologic 6.0 A
c
c
c
c
c
c
c
c
c
c
c
c
-
H
c
-
H
125
85
-
Micrologic 7.0 A
c
c
c
c
c
c
c
c
c
c
c
c
-
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
350 x 420 x 160
350 x 535 x 160
24
36
c
c
c
327 x 210 x 147
327 x 280 x 147
14
18
c
21
Compact NS
Schneider Electric
Functions and
characteristics
13
E23160
16
25
40
63
80
100
125
200
250
TM-D
STR22SE
TM-G
STR22GE
TM-D
TM-G
Standard protection
Protection of systems
supplied by generators.
Protection of long
cables
Protection of DC
distribution systems
1
E19528
E58564
Ir
Im
10
9
.8
.9
1
2
Ir
Im
Ir
x 250A
Im
6
8
x 250A
0
TM 250 D
250A / 40C
Protection
The protection functions may be set using the adjustment dials.
Overload protection
Thermal protection with an adjustable threshold.
Short-circuit protection
Magnetic protection with a fixed or adjustable pick-up, depending on the rating.
Protection of the fourth pole
On four-pole circuit breakers, the trip units can be of the,
4P 3d type (neutral unprotected),
4P 3d + N/2 type (neutral protection at 0.5 In) or 4P 4d type (neutral protection at In).
TM16D to 250D
In at 40 C
Compact NS125 E
Compact NS100
Compact NS160
Compact NS250
16
c
c
c
c
25
c
c
c
c
32
c
c
c
c
40
c
c
c
c
50
c
c
c
c
TM16G to 63G
63
c
c
c
c
80
c
c
c
c
100
c
c
c
c
125
c
c
c
160
c
c
200
c
250
c
16
c
c
c
c
25
c
c
c
c
40
c
c
c
c
63
c
c
c
c
Ir
Im
Compact NS100
Compact NS160/250
fixed
adjustable fixed
190 300 400 500 500 500 640 800
63 80
190 300 400 500 500 500 1000 1250 1250 1250 5 to 10 x In 63 80
80
80
125
125
4P 3d
4P 3d + N/2
4P 4d
no protection
no protection
56
1 x Ir
22
56
63
0.5 x Ir
1 x Ir
Compact NS
Schneider Electric
E24096
In=100A
STR 22 SE
.8
.9
1
2
3
4
5
6
7
Ir Im
Im
Im
.93
.95
.85
.98
.5
Ir
%Ir
90
105
.88
.9
1
.63
alarm
Ir
Io
.7
E58711
.8
10
x Io
x In
test
x Ir
4P 4d
Protection
The protection functions may be set using the adjustment dials.
Overload protection
True rms long-time protection with an adjustable threshold.
Short-circuit protection
Short-time and instantaneous protection:
c short-time protection with an adjustable pick-up and fixed tripping delay;
c instantaneous protection with fixed pick-up.
Protection of the fourth pole
On four-pole circuit breakers, neutral protection is set using a three-position switch
to 4P 3d (neutral unprotected), 4P 3d + N/2 (neutral protection at 0.5 In) or 4P 4d
(neutral protection at In).
Indications
A LED on the front indicates the percent load:
c ON - load is > 90% of Ir setting
c flashing - load is > 105% of Ir setting.
Test
A mini test kit or a portable test kit may be connected to the test connector on the
front to check circuit-breaker operation after installing the trip unit or accessories.
STR22SE
In 20 to 70 C (*)
Compact NS100 N/H/L
Compact NS160 N/H/L
Compact NS250 N/H/L
40
c
c
c
80
c
c
100
c
c
c
STR22GE
160
c
c
250(*)
c
40
c
c
c
100
c
c
c
160
c
c
250(*)
c
Ir = In x
at 1.5 x Ir
at 6 x Ir
at 7.2 x Ir
0.4...1
48 settings
90...180
5...7.5
3.2...5.0
0.4...1
48 settings
1215
-
2...10
8 settings
fixed
i 40
i 60
2...10
8 settings
fixed
i 40
i 60
fixed u 11 x In
fixed u 11 x In
Im = Ir x
Ii
Setting example
What is the overload-protection threshold of a
Compact NS250 circuit breaker equipped with an
STR22SE 160 A trip unit set to Io = 0.5 and Ir = 0.8 ?
Answer:
In x Io x Ir = 160 x 0.5 x 0.8 = 64 A.
23
Compact NS
E25979
E58565
Io
.8 .9
.7
.63
.5
x In
Ir
.9 .93
1 .88
.95
.98
.85
.8
1
x Io
Schneider Electric
Functions and
characteristics
60
E23161
250
400
500
630
STR23SE / STR53UE
STR23SE / STR53UE
STR23SV / STR53SV
MP
Standard protection
with selectivity
Protection of DC
distribution systems
Selection of the trip unit depends on the type of distribution system protected and
the operational voltage of the circuit breaker.
Protection for all types of circuits, from 60 to 630 A, is possible with only four tripunit catalogue numbers, whatever the circuit-breaker operational voltage:
c U i 525 V: STR23SE or STR53UE
c U > 525 V: STR23SV or STR53SV.
Trip units do not have a predefined rating. The tripping threshold depends on the
circuit breaker rating and the LT (long time) current setting.
For example, for an STR23SE trip unit set to the maximum value, the tripping
threshold is:
v 250 A, when installed on a Compact NS400 250 A
v 630 A, when installed on a Compact NS630.
1
2
STR 23 SE
E24094
E21003
Io
.8 .9
.7
.63
x In
1
2
3
4
5
6
7
Ir Im
.5
5
I
90
105 %Ir
alarm
Ir
.88
.85
.8
.9 .93
.95
.98
1
Isd
5
4
3
2
x Io
7
8
10
x Ir
Ir
Isd
test
Protection
The protection functions may be set using the adjustment dials.
Overload protection
Long-time protection with an adjustable threshold and fixed tripping delay:
c Io base setting (6-position dial from 0.5 to 1)
c Ir fine adjustment (8-position dial from 0.8 to 1).
Short-circuit protection
Short-time and instantaneous protection:
c short-time protection with an adjustable pick-up and fixed tripping delay
c instantaneous protection with fixed pick-up.
Protection of the fourth pole
On four-pole circuit breakers, neutral protection is set using a three-position switch
to 4P 3d (neutral unprotected), 4P 3d + N/2 (neutral protection at 0.5 In) or 4P 4d
(neutral protection at In).
Indications
A LED on the front indicates the percent load:
c ON - load is > 90% of Ir setting
c flashing - load is > 105% of Ir setting.
Test
A mini test kit or a portable test kit may be connected to the test connector on the
front to check circuit-breaker operation after installing the trip unit or accessories.
24
Compact NS
Schneider Electric
(*)
7 (*)
1
6
STR 53 UE
E33944
E21004
3
4
Io
.7
.8 .9
1
.6
1
.5
tr
+
Isd
Ii
.8
tsd
(s).2
8 16
10
x Ir
16
(s) @ 6 Ir
1.5
.2
.1
0
0
on
I2t
test
off
fault
P
.5 .6
.4
8
10
.3 .3
.1
>Ig
Ig
4 6
6
8
1.5
2
1
1
2
3
4
5
6
7
8
9
3
2
>Isd
Ii
4 5
.95
x Io
test
Ir
.9 .93
.98
x In
5
0
.88
.85
>Ir
%Ir
Isd
Ir
.7
11
.2
x In
tg
(s) .3
x In
.3
tr
> Im
> Ih
.4 .4
In
tsd
I1
I2
I3
Ir Isd li
.2
.2
.1
.1
on
> Ir
.8
.3
I2t
off
Protection
The protection functions may be set using the adjustment dials.
Overload protection
Long-time protection with adjustable threshold and tripping delay:
c Io base setting (6-position dial from 0.5 to 1)
c Ir fine adjustment (8-position dial from 0.8 to 1).
Short-circuit protection
Short-time and instantaneous protection:
c short-time protection with adjustable pick-up and tripping delay,
with or without constant I2t
c instantaneous protection with adjustable pick-up.
Protection of the fourth pole
On four-pole circuit breakers, neutral protection is set using a three-position switch
to 4P 3d (neutral unprotected), 4P 3d + N/2 (neutral protection at 0.5 In) or 4P 4d
(neutral protection at In).
Fault indications
A LED signals the type of fault:
c overload (long-time protection) or abnormal internal temperature (> Ir)
c short-circuit (short-time protection) or instantaneous (> Isd)
c earth fault (if earth-fault protection option installed) (> Ig)
c microprocessor malfunction:
v both (> Ig) and (> Isd) LEDs ON
v (> Ig) LED ON (if earth-fault protection option (T) installed).
Battery powered. Spare batteries are supplied in an adapter box. The LED
indicating the type of fault goes OFF after approximately ten minutes to conserve
battery power. The information is however stored in memory and the LED can be
turned back ON by pressing the battery/LED test pushbutton. The LED
automatically goes OFF and the memory is cleared when the circuit breaker is reset.
Test
A mini test kit or a portable test kit may be connected to the test connector on the
front to check circuit-breaker operation after installing the trip unit or accessories.
The test pushbutton tests the battery and the (% Ir), (> Ir), (> Isd) and (> Ig) LEDs.
Self monitoring
The circuit breaker trips if a microprocessor fault or an abnormal temperature
is detected.
Options
Four options are available:
c earth-fault protection T
c ammeter I
c zone selective interlocking ZSI
c communications option COM.
25
Compact NS
Schneider Electric
Functions and
characteristics
Trip units
STR23SE (U i 525V)
STR23SV (U > 525V)
Ratings (A)
Circuit breaker
In 20 to 70 C (1)
Compact NS400 N/H/L
Compact NS630 N/H/L
150
c
-
250
c
-
400
c
-
630
c
STR53UE (U i 525V)
STR53SV (U > 525V)
150
c
-
250
c
-
400
c
-
630
c
Ir = In x
0.4...1
adjustable, 48 settings
fixed
90...180
5...7.5
3.2...5.0
0.4...1
adjustable, 48 settings
adjustable
8...15
34...50
69...100
0.4...0.5 1.5...2
3...4
0.2...0.74 1...1.4
2...2.8
2...10
adjustable, 8 settings
fixed
i 40
i 60
1.5...10
adjustable, 8 settings
adjustable, 4 settings + "constant I2t" option
i 15
i 60
i 140
i 230
i 60
i 140
i 230
i 350
11
fixed
1.5...11
adjustable, 8 settings
4P 3d
4P 3d + N/2
4P 4d
no protection
0.5 x Ir
1 x Ir
no protection
0.5 x Ir
1 x Ir
ZSI
COM
I
T
c (standard)
c (2)
c (2)
c (2)
c (2)
at 1.5 x Ir
at 6 x Ir
at 7.2 Ir
138...200 277...400
6...8
12...16
4...5.5
8.2...11
Isd = Ir x
Ii = In x
Options
Indication of fault type
Zone selective interlocking
Communications
Built-in ammeter
Earth-fault protection
Setting example
What is the overload-protection threshold of a
Compact NS400 circuit breaker equipped with
an STR23SE (or STR23SV) trip unit set
to Io = 0.5 and Ir = 0.8 ?
Answer.
In x Io x Ir = 400 x 0.5 x 0.8 = 160 A.
The identical trip unit, with identical settings but
installed on a Compact NS630 circuit breaker, will
have an overload-protection threshold of:
630 x 0.5 x 0.8 = 250 A.
26
Compact NS
E25979
(1) If the trip units are used in high-temperature environments, the setting must take into account the thermal limitations of the circuit breaker. The overload
protection setting may not exceed 0.95 at 60 C or 0.9 at 70 C for the Compact NS400, and 0.95 at 50 C, 0.9 at 60 C or 0.85 at 70 C for the Compact NS630.
(2) This option is not available for the STR53SV trip unit.
Io
Ir
.8 .9
.7
.63
1 .88
.85
.8
.5
x In
.9 .93
.95
.98
1
x Io
Schneider Electric
Possible
combinations:
cI
cT
cI+T
c I + COM
c I + T + COM
c ZSI
c ZSI + I
c ZSI + T
c ZSI + I + T
c ZSI +I + COM
c ZSI + I + T + COM
Residual
Pick-up
Accuracy 15%
Time delay
constant I2t function
Ig = In x
0.2 to 1
adjustable, 8 settings
adjustable, 4 settings
60
140
230
350
i 140 i 230 i 350 i 500
Ammeter (I)
A digital display continuously indicates the current of the phase with the greatest
load. The value of each current (I1, I2, I3, Ineutral) may be successively displayed
by pressing a scroll button.
LEDs indicate the phase for which the current is displayed.
Ammeter display limits:
c minimum current u 0.2 x In. Lower currents are not displayed
c maximum current i 10 x In.
E26028
MP DC trip units
Im(A)
30005000
4400
2500
3500
3800
5700
2000
4000
In Im
Magnetic trip units for Compact NS400/630 three-pole, type H circuit breakers.
These trip units are specifically designed to protect DC distribution systems.
They are not interchangeable. The circuit breaker and trip unit are supplied
fully assembled.
Built-in trip units
Circuit breaker
Compact NS400H
Compact NS630H
27
Compact NS
MP1
MP2
MP3
c
c
c
c
adjustable
800...1600
adjustable
1250...2500
adjustable
2000...4000
Schneider Electric
Protection
E46026A
Functions and
characteristics
Protection thresholds and delays are set using the adjustment dials.
Setting accuracy may be enhanced by limiting the setting range using a different
long-time rating plug.
Overload protection
True rms long-time protection.
Thermal memory: thermal image before and after tripping.
Short-circuit protection
Short-time (rms) and instantaneous protection.
Selection of I2t type (ON or OFF) for short-time delay.
Neutral protection
On three-pole circuit breakers, neutral protection is not possible.
On four-pole circuit breakers, neutral protection may be set using a three-position
switch: neutral unprotected (4P 3d), neutral protection at 0.5 In (4P 3d + N/2) or
neutral protection at In (4P 4d).
Micrologic 5.0
Indications
Overload indication by alarm LED on the front; the LED goes on when the current
exceeds the long-time trip threshold.
Test
A mini test kit or a portable test kit may be connected to the test connector on the
front to check circuit-breaker operation after installing the trip unit or accessories.
long time
Ir
.7
.6
.5
.4
.8
x In
alarm
tr
8
(s) 4
.9
12
16
.95 2
.98 1
20
24
1
.5
@ 6 Ir
instantaneous
short time
Isd
4
5
3
2.5
6
2
8
1.5
10
x Ir
setting
tsd
(s)
Ii
.4 .4 .3
.3
.2
.1
on
.2
.1
2
I t
0
off
3
2.5
2
1.5
x In
6
8
10
delay
1
2
3
4
5
6
Note.
Micrologic control units that do not include measurement
functions are equipped with a transparent lead-seal cover as
standard.
28
Compact NS
Schneider Electric
Micrologic 2.0
Long time
Current setting (A)
Ir = In x
Tripping between 1.05 and 1.20 Ir
Time delay (s)
accuracy 0 to -30%
accuracy 0 to -20%
accuracy 0 to -20%
Thermal memory
500
20
13.8
600
24
16.6
1.5
10
t
Ir
tr
2.5
fixed: 20 ms
Micrologic 5.0
Long time
Current setting (A)
Ir = In x
Tripping between 1.05 and 1.20 Ir
Time delay (s)
accuracy 0 to -30%
accuracy 0 to -20%
accuracy 0 to -20%
Thermal memory
Instantaneous
Pick-up (A)
accuracy 10%
Isd
Isd = Ir x
Protection
Short time
Pick-up (A)
accuracy 10%
Time delay (ms) at 10 x Ir
0.98
0.4 0.5
0.6
0.7
0.8
0.9
0.95
other ranges or disable by changing rating plug
12.5 25
50
100
200
300
400
0.5 1
2
4
8
12
16
0.34 0.69 1.38 2.7
5.5
8.3
11
20 minutes before and after tripping
0.98
500
20
13.8
600
24
16.6
Isd = Ir x
1.5
2.5
I2t Off
I2t On
tsd (max resettable time)
tsd (max break time)
0
20
80
0.1
0.1
80
140
0.2
0.2
140
200
0.3
0.3
230
320
0.4
0.4
350
500
Ii = In x
tr at 1.5 x Ir
tr at 6 x Ir
tr at 7.2 x Ir
E46023A
Instantaneous
Pick-up (A)
accuracy 10%
Time delay
tr at 1.5 x Ir
tr at 6 x Ir
tr at 7.2 x Ir
0.4 0.5
0.6
0.7
0.8
0.9
0.95
other ranges or disable by changing rating plug
12.5 25
50
100
200
300
400
0.5 1
2
4
8
12
16
0.34 0.69 1.38 2.7
5.5
8.3
11
20 minutes before and after tripping
E46022
Protection
Ir
tr
Isd
tsd
Ii
settings
29
Compact NS
10
10
12
15
off
Schneider Electric
Protection
E46028A
Functions and
characteristics
Micrologic 6.0 A
9
10
Ir= tr= tsd= tg= t=
Isd=
Ii=
Ig=
I n=
MAX
s
kA
11
100 %
12
40 %
Protection thresholds and delays are set using the adjustment dials.
The selected values are momentarily displayed on the screen, in amperes and in
seconds.
Setting accuracy may be enhanced by limiting the setting range using a different
long-time rating plug.
Overload protection
True rms long-time protection.
Thermal memory: thermal image before and after tripping.
Short-circuit protection
Short-time (rms) and instantaneous protection.
Selection of I2t type (ON or OFF) for short-time delay.
Earth-fault protection
Residual or source ground return earth fault protection.
Selection of I2t type (ON or OFF) for delay.
Residual earth-leakage protection (Vigi).
Operation without an external power supply.
d Protected against nuisance tripping.
k DC-component withstand class A up to 10 A.
Neutral protection
On three-pole circuit breakers, neutral protection is not possible.
On four-pole circuit breakers, neutral protection may be set using a three-position
switch: neutral unprotected (4P 3d), neutral protection at 0.5 In (4P 3d + N/2),
neutral protection at In (4P 4d).
Zone selective interlocking (ZSI)
A ZSI terminal block may be used to interconnect a number of control units to
provide total discrimination for short-time and earth-fault protection, without a delay
before tripping.
13
Overload alarm
A red alarm LED goes on when the current exceeds the long-time trip threshold.
menu
long time
Ir
.7
.6
.5
.4
tr
.8
.9
.95
.98
1
x In
(s)
2
1
.5
12
16
20
24
Isd
4
5
3
2.5
6
2
8
1.5
10
x Ir
Ig
D
C
B
A
(s)
Ii
.4 .4 .3
.3
.2
.1
on
.2
.1
2
I t
0
off
delay
tg
F
G
H
J
(s)
3
2.5
2
1.5
6
8
10
x In
test
.4 .4 .3
.3
.2
.1
on
.2
.1
2
I t
0
off
ground fault
1
2
3
4
5
6
7
8
9
10
11
12
13
Communication option
@ 6 Ir
instantaneous
tsd
setting
short time
"Ammeter" measurements
Micrologic A control units measure the true (rms) value of currents.
A digital LCD screen continuously displays the most heavily loaded phase (Imax) or
displays the I1, I2, I3, IN, Ig,In, stored-current (maximeter) and setting values by
successively pressing the navigation button. The load on each phase is indicated
continuously by bargraphs.
The optional external power supply makes it possible to display currents < 20% In.
alarm
In conjunction with the COM communication option, the control unit transmits the
following:
c settings
c all ammeter measurements
c tripping causes
c maximeter readings.
Fault indications
LEDs indicate the type of fault:
c overload (long-time protection) or abnormal internal temperature (Ir)
c short-circuit (short-time protection) or instantaneous (Isd)
c earth fault or earth leakage (Ig or In)
c microprocessor malfunction (Ap).
Battery power
The fault indication LEDs remain on until the test/reset button is pressed. Under
normal operating conditions, the battery supplying the LEDs has a service life of
approximately 10 years.
Test
A mini test kit or a portable test kit may be connected to the test connector on the
front to check circuit-breaker operation. For Micrologic 6.0 A and 7.0 A control units,
the operation of earth-fault or earth-leakage protection can be checked by pressing
the test button located above the test connector.
Note.
Micrologic A control units come with a transparent lead-seal
cover as standard.
30
Compact NS
Schneider Electric
Micrologic 2.0 A
long time
current setting (A)
Ir = In x
tripping between 1.05 and 1.20 x Ir
time delay (s)
accuracy 0 to -30% tr at 1.5 x Ir
accuracy 0 to -20 % tr at 6 x Ir
accuracy 0 to -20 % tr at 7.2 x Ir
thermal memory
Isd = Ir x
1.5
10
2.5
Ir
tr
Isd
I
menu
I1
I2
I3 IN
no auxiliary source (where I > 20 % In)
I1 max I2 max I3 max IN max
0.98
500
20
13.8
600
24
16.6
10
E46023
long time
current setting (A)
Ir = In x
tripping between 1.05 and 1.20 x Ir
time delay (s)
accuracy 0 to -30 % tr at 1.5 x Ir
accuracy 0 to -20 % tr at 6 x Ir
accuracy 0 to -20 % tr at 7.2 x Ir
thermal memory
600
24
16.6
Micrologic 2.0 A
Protection
Ir
tr
Isd
tsd
Isd = Ir x
1.5
2.5
Off
I2t On
tsd (max resettable time)
tsd (max break time)
0
20
80
0.1
0.1
80
140
0.2
0.2
140
200
0.3
0.3
230
320
0.4
0.4
350
500
Ii = In x
10
12
15
off
Ig = In x
In i 400 A
400 A < In i 1200 A
In > 1200 A
settings
I2t Off
I2t On
tg (max resettable time)
tg (max break time)
Micrologic 6.0 A
A
B
C
0.3
0.3
0.4
0.2
0.3
0.4
500
640
720
0
0.1
0.2
0.1
0.2
20
80
140
80
140
200
D
0.5
0.5
800
0.3
0.3
230
320
E
0.6
0.6
880
0.4
0.4
350
500
F
0.7
0.7
960
G
0.8
0.8
1040
H
0.9
0.9
1120
J
1
1
1200
Micrologic 7.0 A
0.5
1
2
60
80
140
350
350
500
800
800
1000
settings
I2t
Ammeter
continuous current measurements
measurements from 20 to 200 % of In
accuracy: 1.5 % (including sensors)
maximeters
140
140
200
230
230
320
Ii
0
E46024
earth fault
pick up (A)
accuracy: 10 %
500
20
13.8
instantaneous
pick-up (A)
accuracy: 10 %
fixed: 20 ms
Ammeter
short time
pick-up (A)
accuracy: 10 %
time delay (ms) at 10 Ir
0.98
I t on
Ig
2
tg
I t off
10
20
30
E46243A
instantaneous
pick-up (A)
accuracy: 10 %
time delay
0.4
0.5
0.6
0.7
0.8
0.9
0.95
other ranges or disable by changing rating plug
12.5 25
50
100
200
300
400
0.5
1
2
4
8
12
16
0.34 0.69 1.38 2.7
5.5
8.3
11
20 minutes before and after tripping
E46022
Protection
In
tn
I
menu
I1
I2
I3
IN
Ig
In
no auxiliary source (where I > 20 % In)
I1 max I2 max I3 max IN max Ig max In max
Note.
All current-based protection functions require no auxiliary source.
The test / reset button resets maximeters, clears the tripping indication and tests the battery.
31
Compact NS
Schneider Electric
Functions and
characteristics
External sensors
External sensor for earth-fault protection
The sensor is used with 3P circuit breakers and the Micrologic 6.0 A control unit.
It is installed on the neutral conductor for residual type earth-fault protection.
The rating of the sensor (CT) must be compatible with the rating of the circuit
breaker:
c NS630b to NS1600 - 400/1600 CT
c NS1600b to NS2000 - 400/2000 CT
c NS2000 to NS3200 - 1000/3200 CT.
Rectangular sensor for earth-leakage protection
The sensor is installed around the busbars (phases + neutral) to detect the zerophase sequence current required for the earth-leakage protection.
Rectangular sensors are available in two sizes.
Inside dimensions (mm)
c 280 x 115 up to 1600 A
c 470 x 160 up to 3200 A.
External sensor for source ground return protection
The sensor is installed around the connection of the transformer neutral point to
earth and connects to the Micrologic 6.0 control unit to provide the source ground
return (SGR) protection.
External voltage measurement inputs
External voltage measurement inputs are used to supply power for earth leakage
protection.
As standard, the Micrologic 7.0 control unit is supplied by internal voltage
measurement inputs placed downstream of the pole for voltages between 100 and
690 V AC.
On request, external voltage measurement inputs may be ordered for circuit
breakers fed from the load side or for voltages exceeding 690 V.
056467
Four interchangeable plugs may be used to limit the long-time threshold setting
range for higher accuracy.
As standard, control units are equipped with the 0.4 to 1 plug.
Setting ranges
Standard
Low-setting option
High-setting option
Off plug
Ir = In x 0.4 0.5
0.6
Ir = In x 0.4 0.45 0.50
Ir = In x 0.80 0.82 0.85
no long-time protection
0.7
0.55
0.88
0.8
0.60
0.90
0.9
0.65
0.92
0.95
0.70
0.95
0.98
0.75
0.98
1
0.8
1
025173
32
Compact NS
Schneider Electric
056429
Spare battery
Lead-seal cover for
Micrologic A
A battery supplies power to the LEDs identifying the tripping causes. Battery
service life is approximately ten years.
A test button on the front of the control unit is used to check the battery condition.
The battery may be replaced on site when discharged.
33
Compact NS
Schneider Electric
86099
Functions and
characteristics
manual
Connections
electric
fixed
toggle
direct or extended rotary handle
front connection
rear connection
front connection
rear connection
withdrawable
86101
240 V
277 V
480 V
600 V
In
long time
Ir
threshold
instantaneous lm
pickup
add-on Vigi module
combination with Vigirex relay
MX shunt release
MN undervoltage release
Dimensions (mm)
Weight (kg)
34
Compact NS
Schneider Electric
NS100
NS160
1
c
c
c
-
2
c
c
c
-
100
750
8
277
250
N
25
25
25
100%
c
A
20 000
20 000
10 000
N
25
25
-
H
40
40
-
built-in thermal-magnetic
16
20
25
30
fixed
16
20
25
30
fixed
190 300
300
300
c
N
85
25
10
2
c
c
c
-
100
750
8
690
500
N
85
25
25
18
18
8
50
50
100%
c
A
20 000
20 000
10 000
H
40
40
40
-
NS250
1
c
c
c
-
160
750
8
277
250
N
25
25
25
100%
c
A
20 000
20 000
10 000
H
100
70
65
50
35
10
85
85
H
100
65
35
N
25
25
-
40
50
63
80
100
40
50
63
80
100
500
500
500
640
800
H
40
40
40
-
H
40
40
-
1
c
c
c
-
160
750
8
690
500
N
85
36
35
30
22
8
50
50
100%
c
A
20 000
20 000
10 000
N
85
25
10
H
100
70
65
50
35
10
85
85
H
100
65
35
built-in thermal-magnetic
125 160
fixed
125 160
fixed
1000 1250
c
250
750
8
277
250
N
25
25
25
100%
c
A
10 000
10 000
5 000
N
25
25
built-in thermal-magnetic
160 200
250
fixed
160 200
250
fixed
850 850
850
c
c
c
c
c
c
c
c
c
c
35 x 161 x 86
0.7
c
c
c
70 x 161 x 86
1.2
c
c
c
35 x 161 x 86
0.7
c
c
c
70 x 161 x 86
1.2
c
c
c
35 x 161 x 86
0.7
35
Compact NS
Schneider Electric
053182
Functions and
characteristics
manual
Connections
electric
fixed
toggle
direct or extended rotary handle
Ue
lcu
lcs
front connection
rear connection
front connection
rear connection
front connection
rear connection
AC 50/60 Hz
AC 1000 V
% Icu
long time
Ir (In x )
short time
Isd (Ir x )
instantaneous Ii (In x )
lg (In x )
In
ZSI
combination with Vigirex relay
MX shunt release
MN undervoltage release
Dimensions (mm)
WxHxD
Weight (kg)
36
Compact NS
Schneider Electric
NS400 1000V
3
150, 250, 400
c
c
c
c
consult us
consult us
consult us
consult us
consult us
1150
10
100%
150, 250, 400
1250
8
1000
10
100%
c
standardised
standardised
A
15000
4000
2000
III
STR23SP
c
c
c
c
c
c
c
c
c
c
c
c
c
480 x 140 x 110
13
consult us
37
Compact NS
Schneider Electric
Functions and
characteristics
Tripping thresholds
The 400 Hz current settings are obtained by multiplying the 50 Hz values by the
following coefficient:
b K1 for thermal trip units;
b K2 for magnetic trip units.
On adjustable trip units, these adaptation coefficients are independent of the unit
adjustment knob position.
Thermal trip units
The current settings are lower at 400 Hz than at 50 Hz (K1 < 1).
Magnetic trip units
The current settings are conversely higher at 400 Hz than at 50 Hz (K2 > 1).
Adjustable trip units should be set to minimum, or use Compact circuit breakers
equipped with low magnetic trip units
(type G).
Electronic trip units
The use of electronics offers the advantage of greater operating stability when the
frequency is varied. However, the devices are still subjected to frequency related
temperature effects which may sometimes pose restrictions on their use.
Column K1 of the table gives the maximum permissible current to be used for the
current setting (knob position).
trip unit
NS100N
TM16G
TM25G
TM40G
TM63G
TM16D
TM25D
TM40D
TM63D
TM80D
TM100D
TM125D
TM160D
TM200D
TM250D
NS250N
thermal setting K1
magnetic
setting
K2
16
25
40
63
16
25
40
63
80
100
125
160
200
250
63
80
80
125
240
300
500
500
650
800
1000
1250
1000 (*)
1250 (*)
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
at 40 C
0.95
0.95
0.95
0.95
0.95
0.95
0.95
0.95
0.9
0.9
0.9
0.9
0.9
0.9
NS100N
NS250N
NS400N
NS630N
NS400N
NS630N
C801N
C1001N
C1251N
38
STR22SE
STR22SE
STR23SE
STR23SE
STR53SE
STR53SE
STR25DE
STR35SE/GE
STR25DE
STR35SE/GE
STR25DE
STR35SE/GE
Compact NS
rating
long-time
short-time
Ir at 50 Hz
(A at 40 C)
Ir maxi
K1
Irm at 50 Hz
(A)
40...100
100...250
400
630
400
630
800
800
1000
1000
1250
1250
0.4 to 1
0.4 to 0.9
0.4 to 0.8
0.4 to 0.8
0.4 to 0.8
0.4 to 0.8
0.4 to 0.75
0.4 to 0.75
0.4 to 0.75
0.4 to 0.75
0.4 to 0.75
0.4 to 0.75
2 to 10 Ir
2 to 10 Ir
1.5 to 10 Ir
1.5 to 10 Ir
1.5 to 10 Ir
1.5 to 10 Ir
1.5 to 10 Ir
1.5 to 10 Ir
1.5 to 10 Ir
1.5 to 10 Ir
1.5 to 10 Ir
1.5 to 10 Ir
K2
1
1
1
1
1
1
0.97
0.97
0.97
0.97
0.97
0.97
Schneider Electric
E22347
NS100N
NS250N
NS400N
NS630N
C801N
C1001N
C1251N
MN or MX auxiliary releases
R
MN/MX
U volt
400 Hz
Connection
breaking capacity
12 kA
4,5 kA
10 kA
10 kA
25 kA
25 kA
25 kA
125 V CC
380/420 V
rectifier
additional resistor
4.2 k-5 W
10.7 k-10 W
Note : other models of rectifier bridges can be used if their characteristics are at least
equivalent to those stated above.
39
Compact NS
catalogue number
44925
44926
44932
44914
Schneider Electric
Functions and
characteristics
Selection criteria
The selection of the type of circuit breaker most suitable for protection of a
DC installation depends mainly on the following criteria:
b the rated current, which determines the rating of the equipment;
b the rated voltage, which determines the number of poles in series necessary for
breaking;
b the maximum short-circuit current at the point of installation, which determines
the breaking capacity;
b the type of network (see below).
insulated systems
R
B
U/2
+
U/2
fault effect
fault A
fault B
fault C
E79370
Isc
max. Isc
the positive polarity
is the only one involved
max. Isc
both polarities are involved
no effect
240 V DC
300 A
500 Ah
Ri = 0.5 m/cell
B
b
fault A
the poles required to perform
the break are in series
on the positive polarity
i
+
R
B
b
b C
E22348
E22350
diagrams
and various
cases of faults
earthed systems
one polarity of the DC supply is
earthed
i
a
E22349
type of system
no effect
max. Isc
both polarities are involved
no effect
fault B
the poles required to perform
the break are shared between
the 2 polarities
Vb
Ri
240
= 4.4kA
55 103
40
Compact NS
Schneider Electric
E79371
Example 1
Determine the protection required for a 80 A feeder on a 125 V DC network with an
earthed negative pole and an Isc of 15 kA.
The table below indicates that a NC100H circuit breaker (30 kA, 2P, 125 V) should
be used.
The table opposite indicates that both circuit breaker poles should be fitted on the
positive pole of the network.
An additional circuit breaker pole can be fitted on the negative pole of the network
for isolation purposes.
+
125 V =
-
NC100 H
3P
80 A
E79372
load
+
250 V =
-
NC100 H
4P
100 A
E79373
load
+
250 V =
-
NS400H
2P
400 A
load
Example 2
Determine the protection required for a 100 A feeder on a 250 V DC network with
an earthed middle point and an Isc of 15 kA.
Each pole will be exposed to a maximum of U/2 = 125 V.
The table below indicates that NC100H (30 kA, 2P, 125 V), NS100N (50 kA, 1P,
125 V) or NS160N (50 kA, 1P, 125 V) circuit breakers should be used.
The table opposite indicates that both circuit breaker poles must take part in the
breaking at a voltage of 125 V.
Example 3
Determine the protection required for a 400 A feeder on an unearthed 250 V DC
network with an Isc of 35 kA.
The table above indicates that NS400H circuit breakers (85 kA, 1P, 250 V) should
be used. At least 2 poles must take part in breaking.
The table opposite indicates that the half the number of circuit breaker poles
required for breaking should be fitted on the positive pole of the network and the
other half on the negative pole.
NS100N
NS100H
NS100L
NS160N
NS160H
NS160L
NS250N
NS250H
NS250L
NS400H
NS630H
C1251N-DC
41
Compact NS
Schneider Electric
Functions and
characteristics
048016
Compact NSA160
Connections
manual (toggle,
direct or extended rotary handle)
electric
fixed
Front connection
Rear connection
withdrawable Front connection
Rear connection
NSA160
3, 4
c
c
c
c
height 45 mm
160
500
8
500
250
E
25
16
10
5
5
50%
A
c
10 000
5 000
N
50
30
15
10
10
Protection
Built-in thermal-magnetic trip unit
Ratings In
16
25
32
40
50
63
80
100 125 160
Thermal overload protection Ir fixed threshold
16
25
32
40
50
63
80
100 125 160
Magnetic short-circuit
fixed pick-up
protection lm
600 600 600 600 1000 1000 1000 1250 1250 1250
Add-on earth-leakage
add-on Vigi module
protection
combination with Vigirex relay
Indication and control auxiliaries
Indication contacts
Voltage releases
1 OF + 1 SD
MN or MX
42
Compact NS
Schneider Electric
048018
3, 4
0.03 / 0.3 / 1 / 3
intentional (ms)
0
60 (1) 150 (1)
max. break time
< 40 < 140 < 150
Rated voltage (V)
50/60 Hz
200 to 440 V
Reset
pushbutton
Test
pushbutton
Protection against nuisance tripping
c
DC-component withstand
class A
(1) If the sensitivity is set to 30 mA, there is no time delay, whatever the time-delay setting.
43
Compact NS
Schneider Electric
Functions and
characteristics
Motor protection
Overview of solutions
Motor protection up to 37 kW
Motor rating (kW)
0.37 37
NS80
046751
Compact
Breaking
capacity (kA rms)
380/415 V
70
page 46
E26988
1.1 110
18.5250
NS100
NS160/250
25
70
150
36
70
150
NS400/630
041624
045198
Compact
Breaking
capacity (kA rms)
380/415 V
N
H
L
45
70
150
160750
Compact
NS630b to 1600
E45151
Breaking
capacity (kA rms)
380/415 V
N
H
L
50
70
150
44
Compact NS
Schneider Electric
E26530
Compact
NS400 NS630
0.37
1.5
1.1
2.5
5.5
12
18.5
40
50
37
80
100
160
200
110
220
160
320
250
500
800
560
1000
750
1350
MA
MA
STR22ME
MA
STR43ME
Compact
NS630b NS1600
45
Compact NS
Schneider Electric
Functions and
characteristics
046751
Motor protection
Compact NS80H-MA
Connections
NS80 H-MA
3
c
c
c
-
manual (toggle,
direct or extended rotary handle)
electric
fixed
front connection
rear connection
withdrawable
front connection
rear connection
Protection
Magnetic trip unit
Rating In
Instantaneous short-circuit lm
protection
Earth-leakage protection
Compact NS
690
100
70
65
25
25
6
100%
A
c
20 000
10 000
7 000
100
65
10
46
240 V
480 V
600 V
built-in
1.5
2.5
6.3
12.5 25
adjustable pick-up
6 14 x In
combination with Vigirex relay
80
750
50
80
1 OF + 1 SD
MN or MX
Built-in terminals
c
c
90 x 120 x 80
1.0
Schneider Electric
page 18
MA trip units
Rating (A)
at 65C
In
Compact
N/H/L NS100
circuit breaker
NS160
NS250
H/L
NS400
NS630
2.5
c
-
6.3
c
-
12.5
c
-
25
c
c
-
50
c
c
-
100
c
c
c
-
150
c
c
-
220
c
-
320
c
-
500
c
041624
Pick-up
setting
6...14 x In
setting
setting
9...14 x In 9...14 x In
045198
Compact NS250H
Compact NS400H-MA
47
Compact NS
Schneider Electric
Motor protection
Compact NS100 to 250
circuit breakers with STR22ME
electronic trip unit
052163
Functions and
characteristics
Test
A mini test kit or a portable test kit may be connected to the test connector on the
front to check circuit-breaker operation after installing the trip unit or accessories.
48
Compact NS
Schneider Electric
1
2
E26984
E26985
Ir
In=50A
ImSTR 22 ME
37.5 40
35.5
42.5
Ir
33.5
1
2
3
4
5
6
7
Ir
13Ir
45
31.5
u1,05 Ir
7,2Ir
7,0s
47.5
30
50
Ir
13 Ir
test
long-time threshold
tripping class 10 as defined by IEC 60947-4
short-time pick-up
short-time tripping delay
instantaneous pick-up
test connector
percent load indication
Ratings (A)
20100
c
c
c
150
c
c
220
c
Ir
Tripping class
(IEC 60947-4)
Time delay (s)
(minmax.)
adjustable, 10 settings
0.6...1 x In
10
fixed
120320
615
410
LED
at 1.5 x Ir
at 6 x Ir
at 7.2 Ir
Motor-overload indication
u 40% imbalance
3.5 to 6 seconds
Isd
fixed
13 x Ir
20 %
fixed
10
60
Accuracy
Max. resettable time (ms)
Max. break time
Ii
fixed
15 x In
Options
SDTAM module
49
Compact NS
thresholds (A)
12
12.6 13.4
15
15.7 16.7
24
25.5 27
30
31.5 33.5
48
51
54
60
63
67
90
95
101
132
140
148
14.2
17.7
28.5
35.5
57
71
107
157
15
18.7
30
37.5
60
75
113
166
16
20
32
40
64
80
120
177
17
21.2
34
42.5
68
85
127
187
18
22.5
36
45
72
90
135
198
19
23.7
38
47.5
76
95
142
209
20
25
40
50
80
100
150
220
Schneider Electric
Motor protection
Compact NS400 to 630
circuit breakers with STR43ME
electronic trip unit
053192
Functions and
characteristics
Fault indications
LEDs indicate the type of fault that caused tripping:
c overload (long-time protection) or abnormal component temperature (> Ir)
c short-circuit (short-time protection) or instantaneous (> Isd)
c phase imbalance (LED on the right)
c microprocessor malfunction:
v all four (% Ir), (> Ir), (> Isd) and (phase imbalance) LEDs ON.
Battery powered. Spare batteries are supplied in an adapter box. When a fault
occurs, the LED indicating the type of fault goes OFF after approximately ten
minutes to conserve battery power. The information is however stored in memory
and the LED can be turned back ON by pressing the battery/LED test pushbutton.
The LED automatically goes OFF and the memory is cleared when the circuit
breaker is reset.
Test
A mini test kit or a portable test kit may be connected to the test connector on the
front to check circuit-breaker operation after installing the trip unit or accessories.
The test pushbutton tests the battery and the LEDs.
Self monitoring
The circuit breaker trips if a microprocessor fault or an abnormal temperature is
detected.
Options
Three options are available:
c ammeter (I)
c contactor tripping module (SDTAM)
c communication (COM).
50
Compact NS
Schneider Electric
1
2
E32566
E26987
.63
.71 .8
.88
.5
1
2
3
4
5
6
7
long-time threshold
tripping class
short-time pick-up
short-time tripping delay
instantaneous pick-up
test connector
percent load indication
.8
x Io
tr
+
.95
.98
x In
test
Isd Ii
.90 .93
.85
.8
%Ir
>Ir
>Isd
test
9 10
8
11
> Ir
12
7
6
13
tr
> Im
x Ir
> Ih
20 20
10
fault
Isd
Ir
.56
5
Ir
STR 43 ME
Io
3
4
Ir
10
tsd
I1
I2
I3
Ir Isd li
10A
10A
IEC 947-4-1
class
20 to 70 C
NS400N/H/L
NS630N/H/L
120
c
-
200
c
-
320
c
-
500
c
Ir
270357
10.913.1
7.39.1
433595
17.421.8
1215
u 40% imbalance
4 s 10 %
Ii
fixed - 13 x Ir max.
Other functions
Motor-overload LED
Indications module
c
c
Options
Ammeter (I)
SDTAM module
Communication (COM)
c
c
c
Ammeter (I)
A digital display continuously indicates the current of the phase with the greatest
load. The value of each current I1, I2, I3 and the long-time current setting Ir may be
successively displayed by pressing a scroll button.
LEDs indicate the phase for which the current is displayed.
Ammeter display limits
c minimum current u 0.2 x In. Lower currents are not displayed.
c maximum current i 10 x In.
Communication (COM)
This option transmits data to Digipact distribution monitoring and control modules.
Transmitted data:
c settings;
c phase currents (rms values);
c highest current of the three phases;
c overload-condition alarm;
c cause of tripping (overload, short-circuit, etc.).
51
Compact NS
Schneider Electric
Functions and
characteristics
Protection of industrial
control panels
Overview of solutions
Breaking
capacity (kA rms)
380/480 V
18
E44356
page 53
12.5 ...
250
60...
400
250...
630
NS100
NS160
NS250
NS400
NS630
25
65
35
65
35
65
42
65
42
65
045198
Compact
041624
push
to
trip
Breaking
capacity (kA rms)
380/480 V
N
H
52
Compact NS
Schneider Electric
Connections
NSC100N
manual (toggle,
direct or extended rotary handle)
electric
fixed
front connection
rear connection
withfront connection
drawable rear connection
054556
Compact NSC100N
240 V
480 V
600 V
3, 4
c
c
c
c
100
750
8
690
250
42
18
18
10
10
5
5
100%
A
c
20 000
10 000
7 000
42
18
10
054556
Protection
Built-in thermal-magnetic trip unit
Ratings In
16 20 25 32 40 50 63 70 80 100
Instantaneous short-circuit lm fixed pick-up
protection (A)
600 600 600 600 1000 1000 1000 1000 1000 1250
Add-on earth-leakage
add-on Vigi module
protection
combination with Vigirex relay
Indication and control auxiliaries
Auxiliary contacts
Early-make or early-break contact
Voltage releases
c
c
MN or MX
c
c
90 x 120 x 80
120 x 120 x 80
1.0
1.3
Vigicompact NSC100N
3, 4
0.03 / 0.3 / 1 / 3
intentional (ms)
0
60(1) 150(1)
max. break time
< 40 < 140 < 150
Rated voltage (V)
50/60 Hz
200 to 440 V
Reset
pushbutton
Test
pushbutton
Protection against nuisance tripping
c
DC-component withstand
class A
(1) If the sensitivity is set to 30 mA, there is no time delay, whatever the time-delay setting.
53
Compact NS
Schneider Electric
Protection of industrial
control panels
Trip units, auxiliaries,
installation enclosures
Functions and
characteristics
Trip-unit selection
3
12
E58713
10
16
15
25
20
32
30
40
30
48
40
63
50
70
60
80
75
100
125
160
150
205
150
220
250
320
400
500
TMD
Compact
NS100 NS250
STR22ME
Compact
NS400 NS630
UL/CSA approvals
NSC100N
Circuit breakers
TMD
NA
NS100/160/250 N/H
STR22ME
NA
TMD
STR22SE/GE
STR43ME
NA
STR23SE
STR53UE
NS400/630 N/H
Auxiliaries
All auxiliaries can be added to the circuit breaker by the user:
c padlocking devices (in the OFF position);
c rotary handle
c status-indication auxiliary contacts (ON, OFF and tripped)
c shunt (MX) or undervoltage (MN) releases
c early-make or early-break contacts.
Rotary handle
Available in direct or extended versions for mounting up to 590 mm behind front.
Versions include:
c black front with black handle
c yellow front with red handle (for machine tools or emergency off as per IEC 204 /
VDE 0013).
All rotary handles can be padlocked in the OFF position.
Optional door interlock, recommended for MCC panels (motor control centres).
Early-make or early-break contacts
These auxiliary contacts make it possible to de-energise the downstream auxiliary
circuits of the control panel as well as the auxiliary circuits supplying the MN
release, if applicable.
E44458
Installation in an enclosure
Compact circuit breakers can be installed in a metal enclosure together with other
devices (contactors, motor-protection circuit breakers, LEDs, etc.)
Minimum enclosure dimensions
Circuit breakers
NSC100N
NS100 N/H
NS160 N/H
NS250 N/H
NS400 N/H
NS630 N/H
Height (mm)
300
457
457
457
-
Depth (mm)
150
130
130
130
-
Width (mm)
200
208
208
208
-
Installation enclosure
54
Compact NS
Schneider Electric
UL / CSA logo
Breaking capacity
Horsepower rating
Cable cross-section
and tightening torques
E42650
UL / CSA logo
180
20
230
26
29259
Breaking capacity
Cable cross-section
and tightening torques
29260
E42651
E42651
In=220A
Ir 166 177
STR 22 ME
7,2 Ir
187
198
157
148
140
132
209
220
Ir
> 1,05 Ir
13Ir
test
Trip-unit marking
55
Compact NS
Schneider Electric
Functions and
characteristics
Earth-leakage protection
Overview of solutions
100 630
NSC100 N
NSA160 N/E
NS125 E
054556
044333
Vigicompact
630 3200
NS630b to 1000 N/H/L
NS1250 and 1600 N/H
NS1600b to 3200
E45178
E45151
Compact
Separate toroids
044322
051352
Vigirex
56
Compact NS
Schneider Electric
NS100/160
105 x 236 x 86
140 x 236 x 86
2.5
3.2
NS250
2.8
3.4
NS400/630
135 x 355 x 110
180 x 355 x 110
8.8
10.8
E21007
310
150
t(ms)
60
0
T R
vigi
NS 250
200 / 440 V - 50 / 60 Hz
vigi MH
3
10
N 1 3 5
1
0,3
In(A)
HS 0,03 ( t = 0 )
1
2
3
4
5
6
7
T
2 4 6
sensitivity setting
time-delay setting (for selective earth-fault protection)
lead-seal fixture for controlled access to settings
test button simulating an earth-fault for regular
checks on the tripping function
reset button (reset required after earth-fault tripping)
rating plate
housing for SDV auxiliary contact
Vigi ME Vigi MH
Vigi MB
3, 4 (1)
c
c
c
-
3, 4 (1)
c
c
3, 4 (1)
c
c
c
c
-
Protection characteristics
Sensitivity
fixed
adjustable
adjustable
In (A)
0.3
0.03 - 0.3 - 1 - 3 - 10
0.3 - 1 - 3 - 10 - 30
Time delay
Intentional
fixed
adjustable
adjustable
delay (ms)
< 40
0
60 (2) 150 (2) 310 (2)
0
60
150
310
Max. breaking
< 40
< 40 <140 <300 <800
< 40 < 140 < 300 < 800
time (ms)
Rated voltage
200...440 200... 440 - 440...550
200...440 - 440...550
V AC 50/60 Hz
(1) Vigi 3P modules may also be used on 3P circuit breakers used for single-phase or twophase protection.
(2) If the sensitivity is set to 30 mA, there is no time delay, whatever the time-delay setting.
Note.
The Vigi module for the Compact NSA160 circuit breaker is presented on page 39.
57
Compact NS
Schneider Electric
E58562
Functions
and characteristics
Masterpact
NT
Masterpact
NW
source coupling
switch-disconnector
Masterpact
NW or NT
main power
distribution board for
industrial applications
15 -40 kA
i 1000 A
20 -80 kA
i 1600 A
replacement
source
industrial
distribution
board
15 - 25 kA
i 160 A
i 400 A
final distribution
enclosure for
commercial
applications
local
isolation
enclosure
local
isolation
enclosure
automation
cabinet
sourcechangeover
system
i 160 A : 15 - 25 kA
i 400 A : 20 - 80 kA
local
isolation
enclosure
control panel
i 25 kA
i 10 kA
i 63 A
i 10 kA
i 630 A
i 63 A
5-15 kA
i 5 kA
i 40 A
i 125 A
Circuit breakerdisconnector
building utilities
building final
distribution
continuous processes
manufacturing processes
individual machines
Switchdisconnector
standardised symbols
Interpact IN
58
054361
035050
056385
E45182
Compact NS
Interpact INS
Compact NS
Vario
Compact NS
Interpact INS
054629
Compact NS
Masterpact
086106
86087
052164
E58880
056470
Switch-disconnectors
NG125
Multi 9
Schneider Electric
86087
044313
053041
053039
Compact switch-disconnector
equipped with a Vigi earthleakage module
59
Compact NS
Compact switch-disconnector
equipped with a motor mechanism
MN/MX
voltage
release
Schneider Electric
Functions
and characteristics
manual
Connections
electric
fixed
toggle
direct or extended rotary handle
front connection
rear connection
front connection
rear connection
86085
withdrawable
Built-in connectors
Mounting
Front-panel cutout
Compact NSA125NA
lcm
(kA peak)
lcw
(A rms)
mechanical
electrical
AC
electrical
AC
220/240 V
380/415 V
440/480 V (1)
500 V
minimum (switch-disconnector alone)
maximum (with protection circuit
breaker upstream)
1s
3s
20s
690 V
440 V
250 V
AC 22A
AC 23A
AC 23A
2/3P
4P
3P
4P
60
Compact NS
Schneider Electric
NSA125NA
NSA160NA
3. 4
c
c
c
c
c
c
3. 4
c
c
c
c
c
c
125
500
8
500
250
AC 22 A
125
125
125
125
2.1
330
160
500
8
500
250
AC 22 A
160
160
160
160
AC 23 A
125
125
125
100
AC 23 A
160
160
160
125
1500
1500
580
c
10 000
5 000
5 000
5 000
c
III
c
c
1 OF + 1 SD
MN or MX
terminal shields
depth adjuster
90 x 120 x 82.5
120 x 120 x 80
1.1
1.4
c
61
Compact NS
Schneider Electric
Functions
and characteristics
manual
Connections
electric
fixed
toggle
direct or extended rotary handle
front connection
rear connection
front connection
rear connection
front connection
rear connection
86087
220/240 V
380/415 V
440/480 V (2)
500/525 V
660/690 V
Compact NS100NA
DC
lcm
(kA peak)
lcw
(A rms)
mechanical
electrical
AC
DC
250 V (1 P)
500 V (2 P in series)
minimum (switch-disconnector alone)
maximum (with protection
circuit breaker upstream)
1s
3s
20 s
690 V
440 V
250 V
AC 22A
AC 23A
DC 23A
MX shunt release
MN undervoltage release
Voltage-presence indicator
Current-transformer module
Ammeter module
Insulation-monitoring module
Remote communication by bus
Device status indications (communicating auxiliary contacts)
Device remote operation (communicating motor mechanism)
Installation
Accessories
Dimensions (mm)
WxHxD
Weight (kg)
(1) 2P in 3P case
(2) Suitable for 480 V NEMA
62
Compact NS
Schneider Electric
NSC100NA
NS100NA
NS160NA
NS250NA
NS400NA
NS630NA
3, 4
c
c
c
-
2 (1), 3,4
c
c
c
c
c
c
c
c
c
2 (1), 3,4
c
c
c
c
c
c
c
c
c
2 (1), 3,4
c
c
c
c
c
c
c
c
c
3, 4
c
c
c
c
c
c
c
c
c
3, 4
c
c
c
c
c
c
c
c
c
100
750
8
690
500
AC 23 A AC 22 A
100
100
100
100
100
100
100
100
100
DC 23 A DC 22 A
100
100
2.6
330
160
750
8
690
500
AC 22 A
160
160
160
160
160
DC 22 A
160
160
3.6
330
250
750
8
690
500
AC 22 A
250
250
250
250
250
DC 22 A
250
250
4.9
330
400
750
8
690
500
AC 22 A
400
400
400
400
400
DC 22 A
400
400
7.1
330
630
750
8
690
500
AC 22 A
630
630
630
630
630
DC 22 A
630
630
8.5
330
100
750
8
690
250
AC 22 A
100
100
100
100
DC 22 A
2.1
330
AC 23 A
100
100
100
100
100
DC 23 A
100
100
AC 23 A
160
160
160
160
160
DC 23 A
160
160
1500
1500
580
c
20000
7000
7000
7000
c
III
1800
1800
690
c
50000
50000
30000 (50000 - In/2)
30000 (50000 - In/2)
c
III
c
c
c
c
c
c
c
c
c
-
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
-
c
c
c
c
2500
2500
960
c
40000
40000
20000 (40000 - In/2)
20000 (40000 - In/2)
c
III
AC 23 A
250
250
250
250
250
DC 23 A
250
250
3500
3500
1350
c
20000
20000
10000 (20000 - In/2)
10000 (20000 - In/2)
c
III
AC 23 A
400
400
400
400
400
DC 23 A
400
400
5000
5000
1930
c
15000
15000
6000 (12000 - In/2)
6000 (12000 - In/2)
c
III
6000
6000
2320
c
15000
15000
4000 (8000 - In/2)
4000 (8000 - In/2)
c
III
c
90 x 120 x 80
120 x 120 x 80
0.9
1.2
c
105 x 161 x 86
140 x 161 x 86
1.5 to 1.8
2.0 to 2.2
c
c
140 x 255 x 110
185 x 255 x 110
5.2
6.8
c
c
c
c
c (locking)
AC 23 A
630
630
630
630
630
DC 23 A
630
630
63
Compact NS
Schneider Electric
Functions
and characteristics
E45179
manual
Connections
electric
fixed
toggle
direct or extended rotary handle
front connection
rear connection
front connection
rear connection
220/240 V
380/415 V
440/480 V (1)
500/525 V
660/690 V
DC
Compact NS800NA
lcm
(kA peak)
lcw
(A rms)
mechanical
electrical
AC
250 V (1 P)
500 V (2 P in series)
minimum (switch-disconnector alone)
maximum (with protection
circuit breaker upstream) (2)
0.5 s
1s
20 s
690 V
440 V
AC 22A/In
AC 23A/In
MX shunt release
MN undervoltage release
Dimensions (mm)
WxHxD
Weight (kg)
64
Compact NS
Schneider Electric
NS630bNA
NS800NA
NS1000NA
NS1250NA
NS1600NA
3. 4
c
c
c
c
c
c
c
3. 4
c
c
c
c
c
c
c
3. 4
c
c
c
c
c
c
c
3. 4
c
c
c
c
c
c
c
3. 4
c
c
c
c
c
c
c
1250
750
8
690
500
AC 22 A
1250
1250
1250
1250
1250
DC 22 A
50
330
1600
750
8
690
500
AC 22 A
1600
1600
1600
1600
1600
DC 22 A
50
330
630
750
8
690
500
AC 22 A
630
630
630
630
630
DC 22 A
50
330
25
17
4
c
10000
2000
2000
c
III
AC 23 A
630
630
630
630
630
DC 23 A
-
800
750
8
690
500
AC 22 A
800
800
800
800
800
DC 22 A
50
330
AC 23 A
800
800
800
800
800
DC 23 A
-
1000
750
8
690
500
AC 22 A
1000
1000
1000
1000
1000
DC 22 A
50
330
25
17
4
c
10000
2000
2000
c
III
AC 23 A
1000
1000
1000
1000
1000
DC 23 A
-
25
17
4
c
10000
2000
2000
c
III
25
17
4
c
10000
2000
2000
c
III
AC 23 A
1250
1250
1250
1250
1250
DC 23 A
-
AC 23 A
1600
1600
1600
1600
1520
DC 23 A
-
25
17
4
c
10000
1000
1000
c
III
c
c
c
c
c
c
c
c
c
327 x 210 x 147
327 x 280 x 147
14
18
c
65
Compact NS
Schneider Electric
Functions
and characteristics
manual
Connections
electric
fixed
toggle
direct or extended rotary handle
front connection
rear connection
front connection
rear connection
E45182
lcm
(kA peak)
lcw
(A rms)
mechanical
electrical
AC
Compact NS2000NA
220/240 V
380/415 V
440/480 V (1)
500/525 V
660/690 V
minimum (switch-disconnector alone)
maximum (with protection
circuit breaker upstream) (2)
0.5 s
1s
20 s
690 V
440 V
AC 22A/In
AC 23A/In
MX shunt release
MN undervoltage release
escutcheons
fixed
3P
4P
3P
4P
fixed
66
Compact NS
Schneider Electric
NS1600bNA
NS2000NA
NS2500NA
NS3200NA
3. 4
c
c
-
3. 4
c
c
-
3. 4
c
c
-
3. 4
c
c
-
1600
750
8
690
500
AC 22 A
1600
1600
1600
1600
1600
115
187
2000
750
8
690
500
AC 22 A
2000
2000
2000
2000
2000
115
187
2500
750
8
690
500
AC 22 A
2500
2500
2500
2500
2500
115
187
3200
750
8
690
500
AC 22 A
3200
3200
3200
3200
3200
115
187
40
28
4.7
c
6000
1000
1000
c
III
AC 23 A
1600
1600
1600
1600
1600
AC 23 A
2000
2000
2000
2000
2000
40
28
4.7
c
6000
1000
1000
c
III
AC 23 A
2500
2500
2500
2500
2500
40
28
4.7
c
6000
1000
1000
c
III
AC 23 A
3200
3200
3200
3200
3200
40
28
4.7
c
6000
4000
2000
c
III
c
c
c
c
c
350 x 420 x 160
350 x 535 x 160
23
36
-
67
Compact NS
Schneider Electric
Source-changeover systems
Presentation
87921
Functions
and characteristics
This is the most simple type. Intervention by technical personnel is required, i.e.
transfer from the normal source to the replacement source is not immediate.
A manual source-changeover system can be installed on two to three manuallycontrolled circuit breakers or switch-disconnectors. Interlocking is mechanical.
Interlocks prevent connection to both sources at the same time, even momentarily.
029693
Service sector
c hospital operating rooms.
c safety systems for tall buildings.
c computer rooms (banks, insurance companies, etc.).
c lighting systems in shopping centres.
IMG0021
Industry
c assembly lines.
c engine rooms on ships.
c critical auxiliaries in thermal power stations.
Infrastructure
c port and railway installations.
c runway lighting systems.
c control systems for military installations.
68
Compact NS
Schneider Electric
E21287
E21399
ON
I
ON
I
ON
I
tripped
ON
I
reset
O
OFF
O O FF
tripped
reset
O
OFF
O O FF
E26766
A base plate designed for two Compact devices can be installed horizontally or
vertically on a mounting rail. Interlocking is carried out on the base plate by a
mechanism located behind the devices. Access to the device controls and trip units
is not blocked.
Combinations of Normal and Replacement devices
All manually operated Compact NS100 to 630 circuit breakers and switchdisconnectors can be interlocked.
Devices must be fixed or plug-in versions, with or without earth-leakage protection
or measurement modules.
ON
ON
I
reset
O
OFF
O
OFF
E33943
push
to
trip
push
to
trip
69
Compact NS
Schneider Electric
Source-changeover systems
Remote-operated systems
Functions
and characteristics
053042
E32699
053060
QN
053058
Controller
E32700
E79368
E79369
In this case, changeovers between the Normal and Replacement sources under
predefined conditions are initiated by a Merlin Gerin controller.
IN
LIN GER
MER
0 . OFF
0 . OFF
R
N
UN =
UN =
0,5s
ON /
OFF
Test
UR
UN
ON /
Test
OFF
0,5s
/O
/O
fault
fault
FFO
hsup
hsup
FFO
test
NO h
sup
R
N
FFO
d e gr
ahcs
id
10
degr
ahcs
id
352
10
B US
352
stop
u
man
FFO
hsup
I
NO
IN
LIN GER
MER
N
R
UN =
UN =
UR
UN
ON /
ON /
OFF
OFF
I
/O
/O
fault
fault
auto
stop
u
man
test
STOP
rator
gene
R
N
FFO
hsup
NO h
sup
FFO
hsup
NO h
sup
FFO
O
d e gr
ahcs
id
FFO
O
degr
ahcs
id
352
Coupling accessory
10
352
This accessory may be used with the source-changeover system (with or without a
controller) to facilitate connections.
10
Interlocking by rods
7
A remote-operated source-changeover system is made up of:
1 circuit breaker QN equipped with a motor mechanism and auxiliary contacts, connected to
the Normal source
2 circuit breaker QR equipped with a motor mechanism and auxiliary contacts, connected to
the Replacement source
3 mounting base plate with mechanical interlocking (NS100 to 630) or an interlocking system
using rods or cables (NS630b to 1600)
4 electrical interlocking unit. IVE for NS100 to 630 or an electrical system provided by the
installer for NS630b to 1600. Electrical interlocking system example: part no. 51156903 in the
source-changeover system catalogue.
Switching between sources can be automated by adding:
5 ACP auxiliary control plate
6 BA or UA controller, or an electrical system provided by the installer for NS630b to 1600.
Electrical system example: part no. 51156904 and 51156904 in the sourcechangeover system catalogue.
Accessory:
7 coupling accessory (downstream connection) for NS100 to 630.
70
Compact NS
Schneider Electric
Controllers
Controller
BA
UA
c
c
c
c
c
c
c
c
c
c
c
c
c
Four-position switch
Automatic operation
Forced operation on Normal source
Forced operation on Replacement source
Stop (both Normal and Replacement sources OFF)
Automatic operation
053058R
Test
By opening of the P25M circuit breaker upstream
of the controller
By pressing the test button on the front of the controller
c
c
Indications
Circuit-breaker status indication on the front
of the controller: ON, OFF, fault trip
Automatic-mode indication contact
Other functions
053058
BA controller
c
c
Options
Communications option
Power supply
Control voltages (1)
c
c
c
c
c
c
c
c
c
Operating thresholds
UA controller
Undervoltage
Phase failure
Voltage presence
8
10 mA at 12 V
AC
DC
Utilisation category (IEC 60947-5-1)
AC12 AC13 AC14 AC15 DC12 DC13
Operational current (A)
24 V
8
7
5
6
8
2
48 V
8
7
5
5
2
110 V
8
6
4
4
0.6
220/240 V
8
6
4
3
250 V
0.4
380/415 V
5
440 V
4
660/690 V
(1) Power supplied by the ACP auxiliary control plate. The supply voltage must be the same for
the ACP plate, the IVE unit and the circuit breaker operating mechanisms. If this voltage is the
same as the distribution-system voltage, the Normal and Replacement sources can be used
directly for the power supply. If not, a BC-type or equivalent isolation transformer must be used.
71
Compact NS
Schneider Electric
Communication
Compact NS100 to 630
053172
Functions and
characteristics
054481
056146
(1) For voltages other than 220 V AC, use a standard motor-mechanism module (noncommunicating) together with an SC150 indication and control interface.
72
Compact NS
Schneider Electric
E79336
Overview of functions
Software
Communication
interface
RS 232C,Ethernet
RS 485
Communication
Bus
IN
LIN GER
MERSV
pulsar
JBus
BBus
com
error
com
24V
Data concentrator
DC150
OK
error
3
N1
N1
Device
SC150 indication and
control interface
comp
act
0NH
Digipact Bus
-2
BS CEI
IEC947
VDE
UNE
2
ed
discharg
compactL
NS250 Uimp 8kV.
Ui 750V. Icu(kA)
150
Ue(V)
150
220/240
130
380/415
70
440
20
500
100
600/690
NEMA
5...8
push
to
trip
Im 10
O OFF
250
250
cat A TM Icu C
100%
Ics = 250A/40
0
125/16
UTE
VDE
UTE
947-2UNE NEMA
IEC
CEI
BS
5
6
Ir
.8
.9
Ir
Im
x 250A
x 250A
auto
manu
O
push
OFF
I
push
ON
comp
Compact NS with
communicating
auxiliary contacts
and motor mechanism
act
0NH
UNE
2
ed
discharg
compactL
NS250 Uimp 8kV.
Ui 750V. Icu(kA)
150
Ue(V)
150
220/240
130
380/415
70
440
20
500
100
600/690
NEMA
5...8
push
to
trip
Im 10
O OFF
250
250
cat A TM Icu C
100%
Ics = 250A/40
0
125/16
UTE
VDE
UTE
947-2UNE NEMA
IEC
CEI
BS
5
6
Ir
.8
.9
Ir
Im
x 250A
x 250A
auto
manu
O
push
OFF
I
push
ON
: hard wire
: communication bus
Compact with
communicating SC150
auxiliaries
Device identification
Address
Rating
c
-
c
-
c
c
c
c
c
c
c
c
c
c
c
c
Controls
ON/OFF
LED reset
Protection settings
Reading of the protection settings
73
Compact NS
currents
type of fault
operation counter
c
c
c
Schneider Electric
Communication
Compact NS630b to 1600
COM option in Compact
Digipact "device"
communication module.
Digipact "chassis"
communication module
E59437A
056431
056401
Functions and
characteristics
Communication
bus
Communication
bus
OF
SD
SDE
OF
SDE
056431
Modbus "device"
communication module
I on
tripped
reset
modb
C
CT
C
CE
OF
SD
SDE
4
C
CE
C
CD
C
CT
OF
SDE
3
5
Electrically operated
drawout device
Manually operated
drawout device
us
+
CT
CE
CCM
1
2
3
++
us
CD
CT
E45183
modb
CD
Modbus "chassis"
communication module
Communication
bus
++
CCM
Electrically operated
fixed device
CD
Communication
bus
CE
0 OF
Manually operated
fixed device
4
5
74
Compact NS
Schneider Electric
File
Time
Compact switch-disconnectors are compatible only with the Digipact COM option.
Event
Module
1,20
Harmonics(RMS)
Fundamental:
1,00
RMS:
RMS-H:
0,80
% Fundamental
E47071
Overview of functions
Peak:
CF:
THD:
H1: 118.09
H2: 0.01
H3: 0.45
H4: 0.03
H5: 0.45
H6: 0.04
H7: 1.27
H8: 0.05
H9: 0.42
H10: 0.01
H11: 1.03
H12: 0.07
0,60
OK
0,40
Compact circuit breakers are compatible with the Digipact or Modbus COM option.
The COM option may be used with all types of control units to:
c identify the device
c indicate status conditions
c control the device.
Depending on the different types of Micrologic (S, A) control units, the COM option
also offers:
c setting of the protections functions
c analysis of the AC-power parameters for operating-assistance and maintenance
purposes
0,20
0,00
H2
H3
H4
H5
H6
H7
H8
H9
H10
H11
H12
Harmonics
Ready
ONLINE: DEMO
No working system
9:30
Digipact
Modbus
Digipact
Modbus
c
-
c
c
c
c
device identification
address
rating
type of device
type of control unit
type of long-time rating plug
A
A
A
A
A
A
A
A
S
S
S
S
A
A
A
A
A
A
A
A
status indications
OF (on/off)
SD (trip indication)
SDE (fault-trip indication)
CE/CD (connected/
disconnected position)
controls
MX/XF ON/OFF
spring charging
reset of the mechanical
indicator
protections settings
reading of protections settings
75
Compact NS
A
A
Schneider Electric
Communication
Compact NS630b to 1600 (cont.)
Compact in a communication network
E79039
Functions and
characteristics
Software
Communication
interface
RS 232C,Ethernet
RS 485
Communication
Bus
IN
LIN GER
MERSV
pulsar
JBus
BBus
com
com
error
24V
OK
error
3
N1
N1
Data concentrator
DC150
Device
Digipact Bus
Modbus Bus
Compact
Compact
Devices
Circuit breakers equipped with Micrologic control units may be connected to either
a Digipact or Modbus communication bus. The information made available
depends on the type of Micrologic control unit (S, A) and on the type of
communication bus (Digipact or Modbus).
Switch-disconnectors may be connected exclusively to the Digipact communication
bus.
Communication bus
Digipact
The Digipact bus is the internal bus of the low-voltage switchboard in which the
Digipact communicating devices are installed (Compact with Digipact COM,
PM150, SC150, UA150, etc.). This bus must be equipped with a DC150 data
concentrator (see the Powerlogic System catalogue).
Addresses
Addressing is carried out by the DC150 data concentrator.
Number of devices
The maximum number of devices that may be connected to the Digipact bus is
calculated in terms of communication points. These points correspond to the
amount of traffic the bus can handle. The total number of points for the various
devices connected to a single bus must not exceed 100.
If the required devices represent more than 100 points, add a second Digipact
internal bus.
Communicating device
DC150 data concentrator
Micrologic + Digipact COM
PM150
SC150
UA150
Number of points
4
4
4
4
4
Length of bus
The maximum recommended length for the Digipact internal bus is 200 meters.
Bus power source
Power is supplied by the DC150 data concentrator (24 V)..
76
Compact NS
Schneider Electric
Modbus
The Modbus RS485 (JBus) system is an open bus on which communicating
Modbus devices (Compact with Modbus COM, PM300, Sepam, Vigilohm, etc.) are
installed. All types of PLCs and microcomputers may be connected to the bus.
Addresses
The software layer of the Modbus protocol can manage up to 255 addresses (1 to 255).
The device communication module comprises three addresses linked to:
b circuit-breaker manager;
b measurement manager;
b protection manager.
The chassis communication module comprises one address linked to:
b the chassis manager.
The division of the system into four managers secures data exchange with the
supervision system and the circuit-breaker actuators.
The manager addresses are automatically derived from the circuit-breaker address
@xx entered via the Micrologic control unit (the default address is 47).
logic addresses
@xx
@xx + 50
@xx + 200
@xx + 100
Circuit-breaker manager
Chassis manager
Measurement managers
Protection manager
(1 to 47)
(51 to 97)
(201 to 247)
(101 to 147)
Number of devices
The maximum number of devices that may be connected to the Modbus bus
depends on the type of device (Compact with Modbus COM, PM300, Sepam,
Vigilohm, etc.), the baud rate (19200 is recommended), the volume of data
exchanged and the desired response time. The RS485 physical layer offers up to
32 connection points on the bus (1 master, 31 slaves).
A fixed device requires only one connection point (communication module on the
device).
A drawout device uses two connection points (communication modules on the
device and on the chassis).
The number must never exceed 31 fixed devices or 15 drawout devices.
Length of bus
The maximum recommended length for the Modbus bus is 1200 meters.
Bus power source
A 24 V DC power supply is required (less than 20% ripple, insulation class II).
Communication interface
The Modbus bus may be connected to the central processing device in any of
three manners:
b direct link to a PLC. The communication interface is not required if the PLC is
equipped with a Modbus port;
b direct link to a computer. The Modbus (RS485) / Serial port (RS232)
communication interface is required;
b connection to a TCP/IP (Ethernet) network. The Modbus (RS485) / TCP/IP
(Ethernet) communication interface is required.
Software
To make use of the information provided by the communicating devices, software
with a Modbus driver must be used.
Micrologic utilities
This is a set of Modbus drivers that may be used with a PC to:
b display the variables (I, U, P, E, etc.) with the DDS (Data Display Software)
application;
b read/write the settings with the RSS (Remote Setting Software) application;
b remotely control (ON / OFF) the device with the CSS (Control Command
Software) application.
This software is available on request.
77
Compact NS
Schneider Electric
056431
Communication
Compact NS1600b to 3200
COM option in Compact
Functions and
characteristics
Communication
bus
Digipact "device"
communication module.
OF
SD
SDE
2
1
OFF
OFF
056431
COM
module
Modbus "device"
communication module
1
2
78
Compact NS
Schneider Electric
File
Time
Compact switch-disconnectors are compatible only with the Digipact COM option.
Event
Module
1,20
Harmonics(RMS)
Fundamental:
1,00
RMS:
RMS-H:
0,80
% Fundamental
E47071
Overview of functions
Peak:
CF:
THD:
H1: 118.09
H2: 0.01
H3: 0.45
H4: 0.03
H5: 0.45
H6: 0.04
H7: 1.27
H8: 0.05
H9: 0.42
H10: 0.01
H11: 1.03
H12: 0.07
0,60
OK
0,40
Compact circuit breakers are compatible with the Digipact or Modbus COM option.
The COM option may be used with all types of control units to:
c identify the device
c indicate status conditions
c control the device.
Depending on the different types of Micrologic (S, A) control units, the COM option
also offers:
c setting of the protections functions
c analysis of the AC-power parameters for operating-assistance and maintenance
purposes
0,20
0,00
H2
H3
H4
H5
H6
H7
H8
H9
H10
H11
H12
Harmonics
Ready
ONLINE: DEMO
No working system
9:30
Digipact
Modbus
Digipact
Modbus
c
-
c
c
c
S
S
S
device identification
address
rating
type of device
type of control unit
type of long-time rating plug
A
A
A
A
A
A
A
A
A
A
A
A
A
A
status indications
OF (on/off)
SD (trip indication)
SDE (fault-trip indication)
protections settings
reading of protections settings
79
Compact NS
A
A
Schneider Electric
Installation, connection
and accessories
Compact NB50 and 100
E58520
Functions
and characteristics
Sealable terminal
shield
Interphase barriers
Voltage release
Auxiliary contact
DIN-rail
adapter
Sealable terminal
shield
80
Compact NS
Schneider Electric
E58519
E58547
com
pact
NH
NB250Uimp 8kV.
V.
Icu
Ui 750
(kA)
100
70
65
50
10
85
Ue
(V)
220/240
380/415
440
500/525
660/690
Sealable terminal
shield
250
Icu
100%
Ics=
cat A
-2 CEI
947BS
IECVDE
UNE
NEMA
UTE
125/160
push
to
trip
Compact NB250
NB250
connectors
NB400/600
connectors
Terminal extensions
pact
com N
NB400
.
Ui 750V
Ue
(V)
240
220/
415
380/
440
Uimp
8kV.
Icu
(kA)
35
22
18
Interphase barriers
cat A
Ics =
IEC
50%
Icu
947 -2BS
CEI
VDE
UTE NEMA
UNE
400
push
to
trip
Auxiliary
contact
Rear insulating
screens
Voltage release
Sealable terminal
shield
81
Compact NS
Schneider Electric
Installation, connection
and accessories
Compact NB50 and 100
Functions
and characteristics
Installation
E58525
E58524
Installation positions
Mounting on a backplate
Mounting on rails
Terminal shields
Insulating accessories used for protection against
direct contact with power circuits (degree of protection
IP 40, IK07). They are supplied with sealing
accessories.
Interphase barriers
Safety accessories for maximum insulation at the
power-connection points.
c they clip easily onto the circuit breaker.
c not compatible with terminal shields.
E58527
Terminal shields
E58528
E54456
E58526
E59278
Compact NB50 and 100 circuit breakers may be mounted vertically, horizontally or
flat on their back without any derating of characteristics.
They are designed for easy installation in the various types of switchboards of each
market and country.
Mounting on a DIN rail is possible using a special adapter.
Plug-in and withdrawable versions are not available for these circuit breakers.
Interphase barriers
82
Compact NS
Schneider Electric
E59276A
Indication contacts
Contacts are available in three versions that all comply with international standard
IEC 60947-5 and offer the following indication functions:
c OF (ON/OFF): indicates the position of the circuit-breaker main contacts
c SD (trip indication): indicates that the circuit-breaker has tripped due to:
v overload
v short-circuit
v operation of a voltage release.
Returns to de-energised state when the circuit breaker is reset.
c OF + SD
Electrical characteristics of indication contacts
Rated thermal current (A)
Minimum load
Utilisation category (IEC 60947-5-1)
Operational 24 V
current (A)
48 V
110 V
220/240 V
250 V
380/440 V
660/690 V
6
10 mA at 24 V
AC12
6
6
6
6
6
6
AC15
6
6
5
4
3
0.1
DC12
2.5
2.5
0.8
0.3
-
DC14
1
0.2
0.05
0.03
-
E59277A
Remote tripping
MX shunt release
MX shunt release
The MX release trips the circuit breaker when the control voltage rises above 0.7 x Un.
Control signals can be of the impulse type (u 20ms) or maintained.
Operation
When the circuit breaker has been tripped by a release, it must be reset locally.
MN or MX tripping has priority over manual closing. In the presence of a standing
trip order, the main contacts cannot be closed, even temporarily.
Mechanical characteristics
c endurance: 50% of the rated circuit-breaker mechanical endurance
c releases snap in behind the front of the circuit breaker
c connection using wires with a cross-sectional area of up to 1.5 mm2, to a built-in
terminal block.
Electrical characteristics
c consumption:
v pick-up (MX): < 10 W
v seal-in (MN): < 5 VA.
c response time < 50 ms.
83
Compact NS
Schneider Electric
Installation, connection
and auxiliaries
Compact NB250 to 600
Functions
and characteristics
Installation
E59278
E58530
E58529
Installation positions
Mounting on rails
E58534
E58535
Right-angle terminal
extensions
E58536
E58532
E58531
E58537
E58531
Connection
E58539
E58533
Spreaders
84
Compact NS
Schneider Electric
E54471
E54468
E54469
E54470
E58541
Terminal shields
Terminal shields
E58542
Interphase barriers
E58543
E58540
E54457
85
Compact NS
Schneider Electric
044314
Functions
and characteristics
Installation, connection
and auxiliaries
Compact NB250 to 600 (cont.)
Indication contacts
Indication contacts
6
10 mA at 24 V
AC12
6
6
6
6
6
6
AC15
6
6
5
4
3
0.1
DC12
2.5
2.5
0.8
0.3
-
DC14
1
0.2
0.05
0.03
-
044313
Remote tripping
MX or MN release
86
Compact NS
Schneider Electric
Padlocking
E58545
E58544
Locking in the OFF position guarantees isolation as defined by the IEC 947-2
standard. Devices may be locked by up to three padlocks, shackle diameter 5 to 8 mm
(not supplied).
Front-panel escutcheons
E58546
E23936
Front-panel escutcheon,
secured to the panel from
the front.
Toggle cover:
c degree of protection IP 43,
IK 07
c fits on the front of the
circuit breaker.
Sealing accessories
E18596
This option includes the elements required to fit lead seals to prevent:
c front removal
c access to auxiliaries
c terminal-shield removal
c access to power connections.
Sealing accessories
87
Compact NS
Schneider Electric
Installation, connection
and accessories
Compact NS80H-MA
E58516
Functions
and characteristics
Sealable terminal
shield
Direct rotary
handle
Auxiliary
contact
pact
com
A
H-M
.
NS 80 Uimp 8kV
0V.
Icu (kA)
100
Ue (V)
70
220/240
65
380/415
25
440
6
500/525
10
660/690
250
Ui75
ON
I
cat A
Icu
100%
Ics =
DIN-rail
plate
IEC
UTE
2
UNE
947. BS CEI
push
to
trip
VDE
push
to
trip
O
OFF
2
push
to
trip
ON
I
ed
tripp
C2
C1
SHT z
MX/
/50-60H
240V
220-
Voltage release
5...8
t
rese
O
OFF
Sealable terminal
shield
Extended rotary
handle
Auxiliary
contact
88
Compact NS
Schneider Electric
E58517
pact
com
.
125E
p 6kV
NSA
V. Uim (kA)
U 500
Icu
25
16
10
5
Ue (V)
220/240
380/415
440
125
Ics =
50%
Icu
CEI
947.2
IEC VDE BS
UNE
UTE
E58518
45 mm front
Sealable terminal
shield
Auxiliary
contact
pact
com
.
125E
p 6kV
NSA
V. Uim (kA)
U 500
Icu
25
Ue (V)
16
220/240
10
380/415
5
440
125
Ics
= 50%
Icu
CEI
947.2
IEC VDE BS
UNE
UTE
ON
I
ed
tripp
C2
C1
SHT z
MX/
/50-60H
240V
220-
Voltage release
5...8
t
rese
O
OFF
Extended rotary
handle
Sealable terminal
shield
89
Compact NS
Schneider Electric
Installation, connection
and accessories
Compact NS80H-MA,
NSC100N and NSA160
Functions
and characteristics
Installation
E43597
E43595
Installation positions
E43596
E59278
OFF
push
to
trip
Standard 45 mm front,
optional on NSC100N,
standard on NSA160.
E39432
Distribution connector
E58553
E54455
Terminal shields
90
Compact NS
Schneider Electric
044314
Indication contacts
Indication contacts
Common-point changeover contacts provide remote circuitbreaker status information. They can be used for indications,
electrical locking, relaying, etc.
054550
Standard
6
10 mA at 24 V
AC12 AC15 DC12
6
6
2.5
6
6
2.5
6
5
0.8
6
4
0.3
6
3
-
Low level
DC14
1
0.2
0.05
0.03
-
5
1 mA at 4 V
AC12 AC15
5
3
5
3
5
2.5
5
2
5
5
1.5
DC12
5
2.5
0.8
0.3
-
DC14
1
0.2
0.05
0.03
-
Remote tripping
MX or MN voltage release
91
Compact NS
Schneider Electric
Functions
and characteristics
Installation, connection
and accessories
Compact NS80H-MA, NSC100N and
NSA160 (cont.)
054558
Rotary handles
054563
92
Compact NS
Schneider Electric
Locking systems
E58552
Outgoing-circuit identification
E18595
Compact NS80H-MA and NSC100N devices come with clip-in labels for handwritten indications.
It is also possible to use pre-printed Telemecanique labels (part number AB1-** (8 digits).
P
D E P. P O M
.P
DE P
push
to
trip
Identification accessories
93
Compact NS
Schneider Electric
Installation, connection
and accessories
Compact NS100 to 630 (fixed version)
E58523
Functions
and characteristics
Sealable terminal
shield
que
dilectri rnes
test
avant ce cache-bo
c test
enlever
dielectri shield
terminal
before
this
L3
remove
L2
L1
0V 220/60
z
50/60H
Voltage-presence
indicator
Rear connector
Connectors
One-piece
spreader
Interphase barriers
2
arged
disch
ct
compa L
0
NS25 Uimp 8kV.
Ui 750V. Icu(kA)
150
Ue(V)
0
150
220/245
130
380/41
70
440
20
500 0
100
600/69
ON
I
O OFF
5...8
250
Icu
cat A
100%
Ics =
VDE
UTE
947-2UNE NEMA
IEC
CEI
BS
1
5..
.8
auto
Icu
(kA)
100
70
65
50
10
85
Ue
(V)
40
220/2
15
380/4
440
25
500/5
90
660/6
250
Icu
00%
Ics=1
cat A
47-2
BS CEI
IEC9
VDE
OFF
I
push
ON
ON
I
com
50NH
NB2 . Uimp 8kV.
Ui 750V
O
push
manu
ct
compa L
pact
UNE
push
to
trip
OFF
VDE
UTE
947-2UNE NEMA
IEC
CEI
BS
NEMA
125/
UTE
Im 10
act
comp L
0
NS25 Uimp 8kV.
Ui 750V. Icu(kA)
150
Ue(V) 0
150
220/245
130
380/41
70
440
20
500 0
100
600/69
250
Icu
cat A
100%
Ics =
D
TM 250
40C
250A/
160
push
to
trip
5
6
Ir
reset
.8
Ir
Im
reset
push
to
trip
OFF
Motor-mechanism
module
VDE
UTE
947-2UNE NEMA
IEC
CEI
BS
x 250A
.9
Direct rotary
handle
x 250A
Rear insulating
screens
ON
I
Auxiliary contact
tripped
5..
reset
O
OFF
.8
Extended rotary
handle
Voltage release
80
40
120
Ammeter module
que
dilectri le
test
avant ce couverc
enlever
c test
dilectri
cover
before this
remove
vigi
Hz
NS 250 V-50/60
200/525
-25
310
5
50
t(ms)
60
0
H
vigiM
6
2 4
10
1
In(A)
0,3
HS
0A
160/25
STR
t=0)
0,03(
22 SE
90 %Ir
105
Current-transformer
module
test
Im
.9
0A
In=25
.85
.95
.8
.98
.7
.63
alarm
Ir
8
2
1.5
Insulation-monitoring
module
Ir Im
10
xIr
xIn
Trip unit
Sealable terminal
shield
94
Compact NS
Schneider Electric
E58715
Sealable terminal
shield
que
dilectri rnes
test
avant ce cache-bo
c test
enlever
dielectri shield
terminal
before
this
L3
remove
L2
L1
0V 220/60
z
50/60H
Voltage-presence
indicator
Rear connectors
Connectors for
withdrawable
devices
One-piece
spreader
Connectors
Interphase barriers
Plug-in base
2
arged
disch
O OFF
ct
compa L
0
NS25 Uimp 8kV.
Ui 750V. Icu(kA)
150
150
130
70
20
100
Ue(V)
0
220/245
380/41
440
500 0
600/69
ON
I
5...8
250
Icu
cat A
100%
Ics =
VDE
UTE
947-2UNE NEMA
IEC
CEI
BS
Chassis side
plate
Control-wire
connection
plate
1
2
3
4
5
6
7
8
9
1
5..
.8
auto
push
manu
OFF
I
push
ON
ct
pact
com
H
ON
I
50N
NB2 . Uimp 8kV.
Icu
Ui 750V
(kA)
Ue
100
(V)
40
70
220/2
15
65
380/4
50
440
25
10
500/5
90
85
660/6
250
Icu
00%
Ics=1
A
cat
47-2
BS CEI
IEC9
VDE
UNE
Ui 750V. Icu(kA
150
Ue(V)
0
150
220/245
130
380/41
70
440
20
500 0
100
600/69
250
Icu
cat A
100%
Ics =
reset
push
to
trip
OFF
VDE
UTE
947-2UNE NEMA
IEC
CEI
BS
NEMA
push
to
trip
Im 10
act
comp L
0
NS25 Uimp 8kV.
Ui 750V. Icu(kA)
150
Ue(V) 0
150
220/245
130
380/41
70
440
20
500 0
100
600/69
250
Icu
cat A
100%
Ics =
D
TM 250
40C
250A/
160
125/
UTE
5
6
Ir
compa L
0
NS25 Uimp 8kV.
)
.8
Ir
Im
reset
push
to
trip
OFF
VDE
UTE
947-2UNE NEMA
IEC
CEI
BS
x 250A
.9
Direct rotary
handle
Motor-mechanism
module
x 250A
ON
I
Auxiliary contact
tripped
5..
reset
Circuit-breaker
side plate
O
OFF
.8
Extended rotary
handle
Voltage release
Control-wire
connection
on chassis
80
40
120
que
dilectri le
test
avant ce couverc
enlever
c test
dilectri
cover
before this
remove
Ammeter module
vigi
Hz
NS 250 V-50/60
200/525
-25
310
5
50
t(ms)
60
0
H
vigiM
6
2 4
10
1
In(A)
0,3
HS
160/250A
STR
t=0)
0,03(
Current-transformer module
22 SE
90 %Ir
105
test
Im
4
Ir
.9
0A
In=25
.85
.95
.8
.98
.7
.63
alarm
8
1.5
3
2
Insulation-monitoring
module
Ir Im
10
xIr
xIn
Trip unit
Sealable terminal
shield
95
Compact NS
Schneider Electric
Installation, connection
and accessories
Compact NS100 to 630
Functions
and characteristics
045345
Installation
Fixed circuit breakers
E58530
E58714
E58529
E59278
Mounting on a backplate
(solid or slotted)
Mounting on rails
E18850
Installation positions
041632
E21019
E21017
E21018
Mounting on a backplate
Mounting on rails
E59279
Installation positions
96
Compact NS
Schneider Electric
E21282
Connected
Disconnected
Removed
The chassis is made up of two side plates installed on the base and two other
plates mounted on the circuit breaker.
Accessories
c auxiliary contacts for installation on the fixed part, indicating the connected and
disconnected positions
c toggle collar for circuit breakers with a toggle mounted through a front panel,
intended to maintain the degree of protection whatever the position of the circuit
breaker (supplied with a toggle extension)
c keylock which, depending on the bolt fitted, can be used to:
v prevent insertion for connection
v lock the circuit breaker in the connected or disconnected positions.
c telescopic shaft for extended rotary handles.
041879
Installation positions
E58716
E58733
Fixed, plug-in and withdrawable Compact devices may all be equipped with front
and rear connections.
Fixed device
Front connection
Rear connection
E58718
E58717
E58719
Front connection
97
Compact NS
Rear connection
Schneider Electric
E54456
E58534
Installation, connection
and accessories
Compact NS100 to 630 (cont.)
Functions
and characteristics
E58535
E58536
E58537
Edgewise terminal
extensions for NS400 to 630
E58539
E58532
E58720
Right-angle terminal
extensions
E58538
E58531
E58533
E58721
Spreaders
One-piece spreader
98
Compact NS
Schneider Electric
E58722
E54468
E54469
1-cable connector
for NS100 to 250
1-cable connector
for NS400 to 630
E54470
E58540
2-cable connector
for NS400 to 630
E54471
E54457
E54472
Distribution connector
for NS100 to 250
Two lengths
E58725
Four positions
E58726
E58723
E54456
Rear connection
E58724
Connection
of bare cables
to NS100 to 250.
99
Compact NS
Schneider Electric
Installation, connection
and accessories
Compact NS100 to 630 (cont.)
E54456
Functions
and characteristics
E58718
E58727
E58717
The plug-in base is equipped with terminals which, depending on their orientation,
serve for front and rear connection. For rear connection of a base mounted on a
backplate, the terminals must be replaced by insulated, long right-angle terminal
extensions.
For Compact NS630 devices, connection most often requires the 52.5 or 70 mm
pitch spreaders.
Connection accessories
See the Connection of fixed devices section.
Rear connection
E58719
Front connection
E58728
E58729
All terminals may be equipped with bare-cable connectors. See the Connection of
fixed devices section.
100
Compact NS
Schneider Electric
056384
One-piece spreader
E58730
One-piece spreader
35
45
45
52.5 or 70
45
70
Mounting
E58732
E58731
101
Compact NS
Schneider Electric
049221
Functions
and characteristics
Installation, connection
and accessories
Compact NS100 to 630 (cont.)
Terminal shields
Interphase barriers
Interphase barriers
Safety accessories for maximum insulation at the
power-connection points:
c they clip easily onto the circuit breaker
c not compatible with terminal shields
c special version for plug-in bases.
E58543
E58542
Terminal shields
E58541
102
Compact NS
Schneider Electric
E28443
OF1
SD
SDE OF2
Fixed configuration
MN/MX
motor mechanism
Auxiliary circuits exit the device through a knock-out in the front cover.
OR
E18585
rotary handle
SDV
SD
SDE
motor mechanism
E18586
OR
rotary handle
SDV
E21398
E21397
connector 2
connector 1 OF2/SDV
OF1
SDE/MT
SD
MT
MN/MX
connector 3
OF3/SDV
connector 2 COM
connector 1 OF2
T
OF1
SDE/MT
SD
MT
MN/MX
E28444
Compact NS100/160/250
103
Compact NS
Schneider Electric
044314
Functions
and characteristics
Installation, connection
and accessories
Compact NS100 to 630 (cont.)
Indication contacts
Changeover contacts
104
Compact NS
Standard
Low level
6
10 mA at 24 V
AC12 AC15 DC12
6
6
2.5
6
6
2.5
6
5
0.8
6
4
0.3
6
3
6
0.1
-
5
1 mA at 4 V
AC12 AC15
5
3
5
3
5
2.5
5
2
5
5
1.5
-
DC14
1
0.2
0.05
0.03
-
DC12
5
2.5
0.8
0.3
-
DC14
1
0.2
0.05
0.03
-
Schneider Electric
045349
Rotary handles
There are two types of rotary handle:
c direct rotary handle
c extended rotary handle.
There are two models:
c standard with a black handle
c VDE with a red handle and yellow front for machine-tool control.
044316
105
Compact NS
Schneider Electric
044313
Functions
and characteristics
Installation, connection
and accessories
Compact NS100 to 630 (cont.)
Remote tripping
MX or MN voltage release
106
Compact NS
Schneider Electric
047313
Motor-mechanism module
When equipped with a motor-mechanism module, Compact NS circuit breakers
feature very high mechanical endurance as well as easy and sure operation:
c all circuit-breaker indications and information remain visible and accessible,
including trip-unit settings and indications;
c suitability for isolation is maintained and padlocking remains possible;
c double insulation of the front face.
Applications
c local motor-driven operation, centralised operation, automatic distribution control
c normal/standby source changeover or switching to a replacement source to
optimise energy costs
c load shedding and reconnection to optimise energy costs
c synchrocoupling.
Automatic operation
c circuit-breaker ON and OFF controlled by two impulse-type or maintained control
signals
c automatic spring charging following voluntary tripping (by MN or MX),
with standard wiring
c mandatory manual reset following tripping due to an electrical fault.
Manual operation
c transfer to manual mode using a switch (9) with possibility of remote mode
indication
c circuit-breaker ON and OFF controlled by 2 pushbuttons
c recharging of stored-energy system by pumping the lever 9 times
c padlocking in OFF position.
Installation and connection
All installation (fixed, plug-in/withdrawable) and connection possibilities are
maintained.
Motor-mechanism module connections are made behind its front cover to
integrated terminals, for cables up to 2.5 mm2.
Accessories
c keylock for locking in OFF position
c operations counter for the Compact NS400 and NS630, indicating the number of
ON and OFF cycles. The counter must be installed on the front of the motormechanism module.
Characteristics
E21006
compact
NS400 H
Ui 750V. Uimp 8kV.
Ue
Icu
(V)
(kA)
220/240
380/415
440
500/525
600/690
100
70
65
50
20
cat A
Ics = 100% Icu
O OFF
charged
IEC 947-2
UTE VDE BS
UNE NEMA
CEI
In = 400A
manu
10
auto
push OFF
push ON
Motor mechanism
MT100 to MT630
1
2
3
4
5
opening
closing
cycles/minute max.
DC
Rate
Control voltage (V)
< 600
< 80
4
24/30 - 48/60
110/130 - 250
48 (50 Hz) - 110/130
220/240 - 380/440
i 500
i 500
i 500
i 500
AC 50/60 Hz
Consumption (1)
DC (W)
AC (VA)
opening
closing
opening
closing
E21300
Electrical endurance
Circuit breaker + motor-mechanism module, in thousands of operations
(IEC 60947-2), at 440 V.
50
40
30
NS100
20
NS160
15
10
NS250
NS400
NS630
0,1
0,2
0,3
0,5
0,7
I/In
107
Compact NS
Schneider Electric
Functions
and characteristics
Installation, connection
and accessories
Compact NS100 to 630 (cont.)
048287
Current-transformer module
041892
045212
Ammeter module
Measures and displays (dial-type ammeter) the current of each phase (selection of
phases by 3-position switch in front).
Imax ammeter module
Measures and displays (dial-type ammeter) the maximum current flowing in the
middle phase. The Imax value can be reset on the front.
Installation
c identical for both types of ammeter module
c directly on the downstream circuit-breaker terminals
c ammeter clips into module in any of four 90 positions, i.e. can be installed of
devices mounted both vertically and horizontally
c degree of protection IP40, IK04
c class II insulation between front and the power circuits.
Electrical characteristics
c ammeter module: accuracy class 4.5
c Imax ammeter module:
v accuracy 6 %
v maximum currents are displayed only if they last at least 15 minutes.
108
Compact NS
Schneider Electric
041896
Insulation-monitoring module
This module detects and indicates an insulation drop on a load circuit (TN-S or TT
systems).
Operation is identical to that of a Vigi module, but without circuit-breaker tripping.
Indication by a red LED in front.
An auxiliary contact may be installed for remote insulation-drop indications.
Installation
c directly on the downstream circuit-breaker terminals
c degree of protection: IP40, IK04
c double insulation of the front face.
Electrical characteristics
c settings: 100, 200, 500 and 1000 mA
c accuracy: -50 +0%
c time delay following drop: 5 to 10 seconds
c AC-system voltage: 200 to 440 V AC and 440 to 550 V AC.
053172
Communication
Communicating versions of the auxiliary contacts and the motor-mechanism
module also exist for integration in a Digipact communications system. They simply
replace the standard electrical auxiliaries.
Using the STR53UE and STR43ME trip units equipped with the COM
communications option, it is possible to transmit data to Digipact modules:
c settings
c rms values of phase and neutral currents
c current of the most heavily loaded phase
c overload alarm in progress
c tripping cause (overload, short-circuit, etc.).
054481
109
Compact NS
Schneider Electric
Installation, connection
and accessories
Compact NS100 to 630 (cont.)
Functions
and characteristics
Locking systems
Locking in the OFF position guarantees isolation as per IEC 60947-2.
Padlocking systems can receive up to three padlocks with shackle diameters
ranging from 5 to 8 mm (padlocks not supplied).
Control device
Toggle
Means
Required
accessories
padlock
padlock
removable device
fixed device
Motor mechanism
padlock
keylock
padlock
padlock
keylock
padlock
keylock
locking
device + keylock
keylock
locking device
(keylock incorporated)
E18620
E58545
E58544
Function
ON
I
pr
of
al
ux
O
OFF
110
Compact NS
Schneider Electric
048803
Individual enclosures
E44458
Compact NS and Vigicompact NS devices with two, three or four poles may be
installed in individual enclosures.
All fixed, front connections are possible, except right-angle and edgewise terminal
extensions. Spreaders may be installed in the enclosures intended for Interpact
Compact and Vigicompact NS250 to 630 devices.
There are two models of enclosures:
c heavy-duty metal individual enclosure, with:
v metal enclosure
v door with keylock and cut-out for rotary handle
v direct rotary handle (CNOMO, IP 55, IK 08)
v device mounting plate
v removable plate (without holes) for cable entry through bottom.
c heavy-duty insulating individual enclosure, with:
v insulating enclosure
v transparent cover, screwed, lead sealable, with cut-out for rotary handle
v extended rotary handle
v device mounting plate
v removable plates (without holes) for cable entry through bottom and/or top.
Dimensions (W x H x D in mm)
c metal enclosures:
W
D
v Compact NS100 to 160:
300 x 400 x 200
v Vigicompact NS100 to 160:
400 x 500 x 200
v Compact NS250 to 400:
400 x 600 x 200
v Compact NS630:
600 x 800 x 275
v Vigicompact NS250 to 630:
600 x 800 x 275
c insulating enclosures:
H
v Compact/Vigicompact NS100 to 160: 270 x 360 x 235
v Compact NS250:
270 x 540 x 235
v Compact NS400 to 630:
360 x 720 x 235
v Vigicompact NS250 to 630:
360 x 720 x 235
111
Compact NS
Schneider Electric
Installation, connection
and accessories
Compact NS100 to 630 (cont.)
Functions
and characteristics
E23938
E23936
E23935
E21265
Escutcheons
ON
I
push
to
trip
Toggle cover
c degree of protection IP43,
IK07
c fits on the front of the
circuit breaker.
E22039
O
OFF
80
40
0
120
E21267
112
Compact NS
Schneider Electric
Outgoing-circuit identification
E18595
Compact NS100 to 630 devices come with clip-in labels for hand-written indications.
It is also possible to use pre-printed Telemecanique labels part number AB1-** :
v Compact NS100 to 250: 8 digits
v Compact NS400 to 630: 16 digits.
P
D E P. P O M
.P
DE P
push
to
trip
Identification accessories
Sealing accessories
E18596
This option includes the elements required to fit lead seals to prevent:
c front removal
c rotary-handle removal
c opening of the motor-mechanism module
c access to auxiliaries
c access to trip-unit settings
c trip-unit removal
c access to earth-leakage protection settings
c terminal-shield removal
c access to power connections.
Sealing accessories
113
Compact NS
Schneider Electric
Installation, connection
and accessories
Compact NS630b to 1600
(fixed version)
E59224
Functions
and characteristics
Sealable terminal
shield
Connection kit
for connectors
Vertical connection
adapter
Spreader
Phase
barriers
Spreader
Rear connectors
Auxiliary contact
Voltage release
I on
I
O
push
push
ON
OFF
arged
disch
O OFF
trippe
0 OF
I on
012
53
reset
trippe
Direct rotary
handle
reset
0 OF
tripped
reset
Extended rotary
handle
Communications
module
Connection kit
for connectors
Sealable terminal
shield
Escutcheon
114
Compact NS
Schneider Electric
E59225
Interphase barriers
Vertical connection
adapter
Spreader
Rear connectors
Spreader
Auxiliary contact
Voltage release
I on
Manual operation
I ON
OOFF
push
push
trippe
arged
disch
O OFF
reset
0 OF
I on
012
trippe
53
Direct rotary
handle
reset
0 OF
Electrical operation
I
ON
Communications
module
Escutcheon
115
Compact NS
Extended rotary
handle
tripped
reset
OFF
Transparent cover
Schneider Electric
Installation, connection
and accessories
Compact NS630b to 1600
Functions
and characteristics
E45151
Installation
Fixed configuration
E59227A
E59226A
E59278
Mounting on a backplate
Withdrawable configuration
E59228A
E59229A
E45176
Mounting on rails
E59231
E59230
Mounting on a backplate
E59281A
116
Compact NS
Device on rails
Schneider Electric
E59232A
Connected
Test
Disconnected
Removed
E59267A
3
4
5
6
7
8
9
10
2
1
2
3
4
5
6
7
8
9
10
117
mismatch protection
door interlock
racking interlock
keylock locking
padlock locking
position indicator
chassis front plate (accessible with cubicle door closed)
crank entry
reset button
crank storage
Compact NS
Schneider Electric
Functions
and characteristics
Installation, connection
and accessories
Compact NS630b to 1600 (cont.)
Types of connection
E59235
Front connection
Rear connection
Vertical
E59233A
E59234A
Horizontal
E59236
E59237
Note.
Compact circuit breakers can be connected indifferently with
bare-copper, tinned-copper and tinned-aluminium conductors,
requiring no particular treatment.
118
Compact NS
Schneider Electric
E54540
Vertical-connection adapters
E59239A
E59238A
E46431A
E46426A
Bars
E70750
E59240A
Spreaders.
E59241A
E46887A
E54457
Bare cables
4-cable connectors
E59243A
E70751
E59242A
E46427A
E54456
E59235
119
Compact NS
Schneider Electric
Installation, connection
and accessories
Compact NS630b to 1600 (cont.)
Functions
and characteristics
E54540
Spreaders.
E54456
E59247A
E59248A
E59257A
E59236
E46431A
Bars
E46427A
E59250A
E59249A
120
Compact NS
Schneider Electric
Vertical-connection adapters
E59253A
E46431A
E59252A
E59280
E46426A
E54540
Bars
E59254A
Spreaders
E54456
E46427A
E59255A
E59253A
121
Compact NS
Schneider Electric
Installation, connection
and accessories
Compact NS630b to 1600 (cont.)
Functions
and characteristics
E54540
Spreaders
E46427A
E54456
E59260A
E59259A
E59258A
E59282A
E46431A
Bars
E59262A
E59261A
122
Compact NS
Schneider Electric
E59263A
E45190
Connection shield
Connection shield
E79056
Interphase barriers
E79057
E59264A
123
Compact NS
E59265A
Safety shutters
Safety shutters
Schneider Electric
Installation, connection
and accessories
Compact NS630b to 1600 (cont.)
Functions
and characteristics
E59283A
rotary handle
Connections are made directly to the auxiliaries once the front has been removed.
Wires exit the circuit breaker through a knock-out in the top.
OF1
OF2
OF3
E59286A
CAO2
CAO1
CAF2
CAF1
Fixed devices
SD
MN
or
MX
SDE
COM
OF1
OF2
OF3
Withdrawable devices
Auxiliary circuits are connected to terminal blocks located in the top part of the
chassis.
The auxiliary terminal block is made up of a fixed and moving part. The two parts
are in contact when the device is in the test and connected positions.
E59287A
COM
MN
ou
or
MX
SDE
E59284A
CT1
CE1
CE2
CE3
CD1
CD2
E59285A
Withdrawable device
124
Compact NS
Schneider Electric
044314
Indication contacts
Contacts installed in the device
Changeover contacts are used to remote circuit-breaker status information and can
thus be used for indications, electrical locking, relaying, etc.
They comply with the IEC 60947-5 international recommendation.
Functions
c OF (ON/OFF) - indicates the position of the main circuit breaker contacts
c SD (trip indication) - indicates that the circuit breaker has tripped due to:
v an overload
v a short-circuit
v an earth-leakage fault.
v operation of a voltage release
v operation of the "push to trip" button
v disconnection when the device is ON.
Returns to de-energised state when the circuit breaker is reset.
c SDE (fault indication) - indicates that the circuit breaker has tripped due to:
v an overload
v a short-circuit
v an earth-leakage fault.
Returns to de-energised state when the circuit breaker is reset.
c CAF / CAO (early-make or early-break function) - indicates the position of the
rotary handle. Used in particular for advanced opening of safety trip devices (early
break) or to energise a control device prior to circuit-breaker closing (early make).
Installation
c OF, SD and SDE functions - a single type of contact provides all these different
indication functions, depending on where it is inserted in the device. The contacts
clip into slots behind the front cover of the circuit breaker.
c CAF / CAO function - the contact fits into the rotary-handle unit (direct or
extended).
Electrical characteristics of the OF/SD/SDE/CAF/CAO auxiliary contacts
Contacts
056456
Standard
Low level
6
10 mA at 24 V
AC12 AC15 DC12
6
6
2.5
6
6
2.5
6
5
0.8
6
4
0.3
6
3
6
0.1
-
5
1 mA at 4 V
AC12 AC15
5
3
5
3
5
2.5
5
2
5
5
1.5
-
DC14
1
0.2
0.05
0.03
-
DC12
5
2.5
0.8
0.3
-
DC14
1
0.2
0.05
0.03
-
125
Compact NS
Standard
Low level
8
10 mA at 24 V
AC12 AC15 DC12
8
6
2.5
8
6
2.5
8
5
0.8
8
4
0.3
8
3
6
0.1
-
5
1 mA at 4 V
AC12 AC15
5
3
5
3
5
2.5
5
2
5
5
1.5
-
DC14
1
0.2
0.05
0.03
-
DC12
5
2.5
0.8
0.3
-
DC14
1
0.2
0.05
0.03
-
Schneider Electric
E45159
Functions
and characteristics
Installation, connection
and accessories
Compact NS630b to 1600 (cont.)
Rotary handles
There are two types of rotary handle:
c direct rotary handle
c extended rotary handle.
There are two models:
c standard with a black handle
c VDE with a red handle and yellow front for machine-tool control.
E45161
126
Compact NS
Schneider Electric
056421
Remote tripping
opening
order
E46554A
E46553A
This function opens the circuit breaker via an electrical order. It is made up of a
shunt release (MX), or an undervoltage release (MN) or a delayed undervoltage
release (MN + delay unit).
The delay unit, installed outside the circuit breaker, may be disabled by an
emergency power OFF button to obtain instantaneous opening of the circuit
breaker.
Wiring diagram for the remote-tripping function
E59433A
opening
order
delayed
opening
order
MX voltage release
10
12
delay
unit
C2
D2
C1
D2
MN
MN
MX
instantaneous
opening
order
D1
D1
MN delay units
To eliminate circuit-breaker nuisance tripping during short voltage dips, operation of
the MN release can be delayed. This function is achieved by adding an external
delay unit in the MN voltage-release circuit. Two versions are available, adjustable
and non-adjustable.
Characteristics
Power supply
V AC 50/60 Hz /DC
Operating threshold
Consumption (VA or W)
Circuit-breaker response
time at Un
127
Compact NS
non-adjustable
adjustable
opening
closing
adjustable
non-adjustable
100/130 - 200/250
48/60 - 100/130 - 200/250 - 380/480
0.35 to 0.7 Un
0.85 Un
pick-up: 200 - hold: 4.5
0.5s - 0.9s - 1.5s - 3s
0.25s
Schneider Electric
Functions
and characteristics
Installation, connection
and accessories
Compact NS630b to 1600 (cont.)
E45163
E59434A
The motor mechanism module is used to remotely open and close the circuit
breaker. It is made up of a spring-charging motor equipped with an opening release
and a closing release.
An electrical operation function is generally combined with:
c device ON/OFF indication (OF)
c "fault-trip" indication (SDE).
Wiring diagram of a point-to-point electrical operation solution
opening
order
closing
order
A4
fault
A2
B4
electrical
operation
82
closed
open
84
12
14
OF1
SDE
A1
81
11
E59435A
opening
order
closing
order
A4
A2
B4
electrical
operation
A1
COM
OF
supervisor
SDE
128
Compact NS
Schneider Electric
Spring-charging motor
Power supply V AC 50/60 Hz
V DC
Operating threshold
Consumption (VA or W)
Motor overcurrent
Charging time
Operating frequency
129
Compact NS
Schneider Electric
Installation, connection
and accessories
Compact NS630b to 1600 (cont.)
E45194
Functions
and characteristics
E45159
Function
Means
Required
accessories
padlock
padlock
removable device
fixed device
padlock
keylock
padlock
keylock
padlock
keylock
locking
device + keylock
locking
device + keylock
keylock
Access to pushbuttons
protected by transparent
cover
E59436A
056447
Locking in ON position does not prevent the device from tripping in the event of a fault or
remote tripping order.
056446
4
I
O
push
push
ON
OFF
1 reset of mechanical
trip indicator
2 OFF pushbutton
3 OFF position locking
4 ON pushbutton
5 springs charged indication
6 pushbutton locking
7 contact position indication
8 operation counter
ed
harg
disc
O OFF
6
7
012
53
056448
Pushbutton locking
The transparent cover blocks access to the pushbuttons used to open and close
the device.
It is possible to independently lock the opening OFF button and the closing ON
button.
The pushbuttons may be locked using either:
c three padlocks (not supplied)
c lead seal
c two screws.
056449
The circuit breaker is locked in the OFF position by physically maintaining the
opening pushbutton pressed down:
c using padlocks (one to three padlocks, not supplied)
c using a keylock (supplied).
Keys may be removed only when locking is effective (Profalux or Ronis type locks).
The keylocks are available in any of the following configurations:
c one keylock
c one keylock mounted on the device + one identical keylock supplied separately
for interlocking with another device.
A locking kit (without lock) is available for installation of a keylock (Ronis, Profalux,
Kirk or Castell).
130
Compact NS
Schneider Electric
E59267A
Chassis locking
3
4
5
6
7
8
9
1
2
3
4
5
6
7
mismatch protection
door interlock
racking interlock
keylock locking
padlock locking
position indicator
chassis front plate
(accessible with cubicle
door closed)
8 crank entry
9 reset button
10 crank storage
10
Disconnected position
locking by padlocks
056417
056451
056450
Mounted on the chassis and accessible with the door closed, these devices lock
the circuit breaker in the disconnected position in two manners:
c using padlocks (standard), up to three padlocks (not supplied)
c using keylocks (optional), one or two different keylocks are available.
Profalux and Ronis keylocks are available in different options:
c one keylock
c one keylock mounted on the device + one identical keylock supplied separately,
using the same key, for interlocking with another device
c one (or two) keylocks mounted on the device + one (or two) identical keylocks
supplied separately, for interlocking with another device.
A locking kit (without locks) is available for installation of one or two keylocks
(Ronis, Profalux, Kirk or Castell).
Disconnected position
locking by keylocks
Door interlock
Door interlock
056452
Mounted on the right or left-hand side of the chassis, this device inhibits opening of
the cubicle door when the circuit breaker is in connected or test position. It the
breaker is put in the connected position with the door open, the door may be closed
without having to disconnect the circuit breaker.
Racking interlock
Racking interlock
This device prevents insertion of the crank when the cubicle door is open (device
cannot be connected).
Mismatch protection
056453
Mismatch protection ensures that a circuit breaker is installed only in a chassis with
compatible characteristics. It is made up of two parts (one on the chassis and one
on the circuit breaker) offering twenty different combinations that the user may
select.
Mismatch protection
131
Compact NS
Schneider Electric
056463
Functions
and characteristics
Installation, connection
and accessories
Compact NS630b to 1600 (cont.)
Other accessories
Auxiliary terminal shield (CB)
Optional equipment mounted on the chassis, the shield prevents access to the
terminal block of the electrical auxiliaries.
056464
The operation counter sums the number of operating cycles and is visible on the
front panel. It is compatible with electrically operated devices.
Escutcheon (CDP)
Optional equipment mounted on the door of the cubicle, the escutcheon increases
the degree of protection to IP 40. It is available in fixed and withdrawable versions.
E45184
Optional equipment mounted on the escutcheon, the cover is hinged and secured
by a screw. It increases the degree of protection to IP 54 and the degree of
protection against mechanical impacts to IK 10. It may be used for withdrawable
devices only.
E45187
Transparent cover
E59987
Used with the escutcheon, this option closes off the door cutout of a cubicle not yet
equipped with a device. It may be used with the escutcheon for both fixed and
withdrawable devices.
Blanking plate
132
Compact NS
Schneider Electric
133
Compact NS
Schneider Electric
Installation, connection
and accessories
Compact NS1600b to 3200 (fixed version)
E59269B
Functions
and characteristics
Vertical-connection adapters
Circuit breaker
NS1600b / 2500A
Auxiliary
contact
Circuit breaker
NS3200
OFF
OFF
OFF
OFF
Voltage
release
Communication
module
134
Compact NS
Schneider Electric
E45178
Installation
Fixed circuit breakers
E59271A
OFF
OFF
Fixed Compact NS
Mounting on rails
E59281A
Connection
Front connection
NS3200
E59272A
E59726A
NS1600 to 2500
OFF
OFF
OFF
OFF
Bars
E59273
E59275A
OFF
OFF
E59728A
E59274A
E59727A
OFF
OFF
135
Compact NS
OFF
OFF
Schneider Electric
Installation, connection
and accessories
Compact NS1600b to 3200 (cont.)
Functions
and characteristics
044314
Indication contacts
Contacts installed in the device
Changeover contacts are used to remote circuit-breaker status information and can
thus be used for indications, electrical locking, relaying, etc.
They comply with the IEC 60947-5 international recommendation.
Functions
c OF (ON/OFF) - indicates the position of the main circuit breaker contacts
c SD (trip indication) - indicates that the circuit breaker has tripped due to:
v an overload
v a short-circuit
v an earth-leakage fault
v operation of a voltage release
v operation of the "push to trip" button
Returns to de-energised state when the circuit breaker is reset.
c SDE (fault indication) - indicates that the circuit breaker has tripped due to:
v an overload
v a short-circuit
v an earth-leakage fault.
Returns to de-energised state when the circuit breaker is reset.
Installation
c OF, SD and SDE functions - a single type of contact provides all these different
indication functions, depending on the position where it is inserted in the device.
The contacts clip into slots behind the front cover of the circuit breaker.
Electrical characteristics of the OF/SD/SDE auxiliary contacts
Contacts
Rated thermal current (A)
Minimum load
Utilisation category (IEC 60947-5-1)
Operational 24 V
current (A)
48 V
110 V
220/240 V
250 V
380/440 V
660/690 V
136
Compact NS
Standard
6
10 mA at 24 V
AC12 AC15 DC12
6
6
2.5
6
6
2.5
6
5
0.8
6
4
0.3
6
3
6
0.1
-
Low level
5
1 mA at 4 V
DC14 AC12 AC15
1
5
3
0.2
5
3
0.05 5
2.5
5
2
0.03 5
5
1.5
-
DC12
5
2.5
0.8
0.3
-
DC14
1
0.2
0.05
0.03
-
Schneider Electric
Remote tripping
opening
order
E46554A
MX voltage release
E46553A
This function opens the circuit breaker via an electrical order. It is made up of a
shunt release (MX), or an undervoltage release (MN) or a delayed undervoltage
release (MN + delay unit).
The delay unit, installed outside the circuit breaker, may be disabled by an
emergency power OFF button to obtain instantaneous opening of the circuit
breaker.
Wiring diagram for the remote-tripping function
E59433A
056421
opening
order
delayed
opening
order
10
12
delay
unit
C2
D2
C1
D2
MN
MN
MX
instantaneous
opening
order
D1
D1
MN delay units
To eliminate circuit-breaker nuisance tripping during short voltage dips, operation of
the MN release can be delayed. This function is achieved by adding an external
delay unit in the MN voltage-release circuit. Two versions are available, adjustable
and non-adjustable.
Characteristics
Power supply
V AC 50/60 Hz /DC
Operating threshold
Consumption (VA or W)
Circuit-breaker response
time at Un
137
Compact NS
non-adjustable
adjustable
opening
closing
adjustable
non-adjustable
100/130 - 200/250
48/60 - 100/130 - 200/250 - 380/480
0.35 to 0.7 Un
0.85 Un
pick-up: 200 - hold: 4.5
0.5s - 0.9s - 1.5s - 3s
0.25s
Schneider Electric
Installation, connection
and accessories
Compact NS1600b to 3200 (cont.)
E45193
Functions
and characteristics
Device locking
Locking in the OFF position guarantees isolation as per IEC 60947-2.
Padlocking systems can receive up to three padlocks with shackle diameters
ranging from 5 to 8 mm (padlocks not supplied).
Control device
Toggle
Function
Means
Required
accessories
padlock
padlock
removable device
fixed device
E45194
138
Compact NS
Schneider Electric
Test equipment
052172
047035
The portable test kit is used to check all aspects of the protection functions:
c long time protection
c short time protection
c instantaneous protection
c earth-fault protection.
Required power source: 110 or 220 V AC, 50/60 Hz.
139
Compact NS
Schneider Electric
Display modules
DMB300 and DMC300 display modules use the power and communications
capabilities of the Micrologic control units to centralise the display of electrical
values, status conditions and alarms of one or more Compact
or Compact circuit breakers.
The mounting and cabling system for the display modules ensures fast,
easy and reliable installation.
Start-up is immediate with no configuration or programming required.
Display modules are high-performance devices combining:
c simple and easy-to-read dials
c powerful and accurate digital processing.
Their small size and extensive communications capabilities make for easy and
flexible installation and operation.
057454
Functions
and characteristics
Display modules
DMB300
DMC300
Number
Display
DMB300 display module: basic and harmonic measurements
Screen type
Screen size
Entry
A
A
A
A
A
A
Information displayed
E79078
P
P
P
P
P
H
H
H
H
H
H
H
P
P
P
P
P
P
H
H
H
H
H
H
H
H
H
Power
Active (P), reactive (Q) and apparent (S) power
Power factor and cos
Maximum power (P, Q, S)
Demand power (P, Q, S)
Maximum demand power (P, Q, S)
P
P
P
P
P
Metering
Active, reactive and apparent energy
Voltages
Phase-to-phase voltages (U1-2, U2-3, U3-1)
Minimum/maximum phase-to-phase voltages
Phase-to-neutral voltages (V1-N, V2-N, V3-N)
Minimum/maximum phase-to-neutral voltages
Frequency
Voltage imbalance (% per phase)
Total harmonic distortion (% per phase)
Maximum total harmonic distortion (% per phase)
Amplitudes of individual harmonics
P
P
P
P
P
H
H
H
H
H
H
H
H
H
P
P
P
H
H
H
P
P
H
H
H
H
H
H
H
H
H
H
P
P
P
P
P
H
H
H
H
H
On-line help
On-line help is available for each type
of information supplied by the module
Circuit-breaker diagnostics
Identification of control units
Reading of protections
Circuit-breaker status
Type of trip
Current alarms
Maintenance indicator
Installation diagnosis
Indication of faulty devices
Fault log
A
A
A
A
P
P
P
P
P
H
H
H
H
H
A
A
A
A
P
P
P
P
P
P
H
H
H
H
H
H
A
P
P
H
140
Compact NS
Schneider Electric
24 V DC
power
E59178
Wiring system
The wiring system is designed for low-voltage
power switchboards. Installation requires no tools
or special skills.
The prefabricated wiring ensures both data
transmission (ModBus protocol) and 24V DC power
distribution for the display module and the
communications modules on the Micrologic control
units.
2
E59081A
ON ON
ON
n 4n 4 4 ON
n
n 3n 3
n 4
n 2n 2 n 3
n 3
n 1n 1 n 2
n 2
OUTOUT n 1
IN IN
T
IN
ON
OU
3
Reset
push
push
70
NX 32
ON
Ir
Ig
Isd I n
Ii
Ap
reset
Icu (kA)
100
100
85
Icw 85kA/1s
cat.B
Ics =
discharge
CDM 303:
Connection cable between
display module and junction
block
H2
Ue (V)
220/440
525
690
OFF
Micrologic
100%
Icu
50/60Hz
O OFF
947-2
AS NEMA
IEC
UNE
EN 60947-2
BS CEI
UTE
012
VDE
53
com
DMB300
Digipact
volets
shutters
Test
1
2
I
select
E59180A
NW
1251
12kV
Icu
(kA)
100
85
Ue
(V)
220/240
480/690
70
H1
Uimp
Ui 1000V
8kV
Uimp
Micrologic
Ir
Ig
Isd I n
Ii
Ap
reset
I ON
OOFF
push
push
discharged
ON
O OFF
Ics =
IEC
100%
Icu
947-2
UTE VDE
012
BS CEI
NEMA
UNE
53
IN
NW
1251
n 2
n 3
n 4
ON
H1
Uimp
Ui 1000V
8kV
Uimp
12kV
Icu
(kA)
100
85
Ue
(V)
220/240
480/690
70
n 1
OUT
Micrologic
Ir
Ig
Isd I n
Ii
Ap
reset
I ON
OOFF
push
push
discharged
O OFF
Ics =
IEC
100%
947-2
UTE VDE
BS CEI
NEMA
UNE
53
E59179
012
Icu
E59082A
E59176A
NW
1251
H1
Uimp
Ui 1000V
8kV
Uimp
NW
12kV
Ir
Ap
reset
Ir
I ON
OOFF
Ig
Isd I n
Ii
Ap
I ON
OOFF
discharged
O OFF
Ics =
IEC
100%
NX 32
ON
d
discharge
Icu (kA)
100
100
85
Icw 85kA/1s
cat.B
Ics =
012
H2
Ue (V)
220/440
25
525
690
OFF
reset
100%
Icu
50/60Hz
O OFF
947-2
AS NEMA
IEC
UNE
EN 60947-2
BS CEI
UTE
VDE
Ics =
BS CEI
UNE
NEMA
IEC
012
NW
1251
H1
Uimp
Ui 1000V
8kV
Uimp
NW
12kV
Ap
Ir
I ON
OOFF
Ig
Isd I n
Ii
Ap
I ON
OOFF
discharged
Ics =
IEC
push
push
NX 32
ON
100%
d
discharge
O OFF
BS CEI
UNE
NEMA
IEC
100%
947-2
UTE VDE
012
BS CEI
UNE
NEMA
53
Icu (kA)
100
100
85
100%
Icu
NW
50/60Hz
1251
70
NW
12kV
Ig
Isd I n
Ii
H1
Uimp
12kV
Icu
(kA)
100
85
Ue
(V)
220/240
480/690
70
Micrologic
Ir
1251
Ui 1000V
8kV
Uimp
Icu
(kA)
100
85
Ue
(V)
220/240
480/690
VDE
H1
Uimp
Ui 1000V
8kV
Uimp
947-2
AS NEMA
IEC
UNE
EN 60947-2
BS CEI
UTE
Ics =
947-2
53
Icu
Icw 85kA/1s
cat.B
Ics =
Icu
H2
Ue (V)
220/440
525
690
OFF
reset
push
push
O OFF
UTE VDE
012
Ap
12kV
Icu
(kA)
100
85
reset
push
discharged
70
CCR 301:
Roll of RS485 cable
(2 RS485 wires + 2 power
supply wires)
H1
Uimp
Ue
(V)
220/240
480/690
70
reset
push
Ig
Isd I n
Ii
NEMA
Micrologic
Ig
Isd I n
Ii
O OFF
Reset
UNE
1251
Ui 1000V
8kV
Uimp
Icu
(kA)
100
85
Ue
(V)
220/240
480/690
70
Ir
Ir
Icu
BS CEI
53
Micrologic
Micrologic
100%
947-2
UTE VDE
53
E59177A
Ap
Icu
947-2
UTE VDE
push
push
70
Ig
Isd I n
Ii
push
push
discharged
Reset
12kV
Icu
(kA)
100
85
reset
push
push
Ir
H1
Uimp
Ue
(V)
220/240
480/690
70
Micrologic
Ig
Isd I n
Ii
O OFF
Micrologic
1251
Ui 1000V
8kV
Uimp
Icu
(kA)
100
85
Ue
(V)
220/240
480/690
70
Micrologic
Micrologic
Ap
reset
Ir
I ON
OOFF
Ig
Isd I n
Ii
Ap
reset
I ON
push
OOFF
push
discharged
O OFF
Ics =
IEC
100%
947-2
UTE VDE
012
push
push
discharged
O OFF
Icu
BS CEI
Ics =
UNE
NEMA
IEC
100%
947-2
UTE VDE
53
012
Icu
BS CEI
UNE
NEMA
53
CSD 309:
SubD 9-pin connector for
colour-coded connection of
wires to screw terminals
Compact circuit breakers equipped with Micrologic control units and the ModBus eco COM option
141
Compact NS
Schneider Electric
142
Compact NS
Schneider Electric
Installation recommendations
Compact NS
Presentation
Functions and characteristics
Operating conditions
Installation in switchboards
144
145
145
146
148
149
150
151
152
152
153
154
155
Sizing of bars
Recommended drilling dimensions
157
159
Temperature derating
Power dissipation / Resistance
161
163
Dimensions, volumes
Connection
Electrical diagrams
Additional characteristics
Catalogue numbers
143
1
11
Compact NS
165
205
221
251
267
Schneider Electric
E59432A
Installation
recommendations
Operating conditions
2000 m
Altitude derating
Altitude does not significantly affect circuit-breaker characteristics up to 2000 m.
Above this altitude, it is necessary to take into account the decrease in the dielectric
strength and cooling capacity of air.
The following table gives the corrections to be applied for altitudes above 2000
metres. The breaking capacities remain unchanged.
Compact NS80 to 630
Altitude (m)
Dielectric resistance voltage (V)
Average insulation level (V)
Maximum utilisation voltage (V)
Average thermal current (A) at 40 C
2000
3000
4000
5000
3000
750
690
1 x In
2500
700
550
0.96 x In
2100
600
480
0.93 x In
1800
500
420
0.9 x In
2000
3000
4000
5000
3500
750
690
1 x In
3150
750
590
0.99 x In
2500
700
520
0.96 x In
2100
600
460
0.94 x In
E59571A
Vibrations
Compact NS devices resist electromagnetic or mechanical vibrations.
Tests are carried out in compliance with standard IEC 68-2-6 for the levels required
by merchant-marine inspection organisations (Veritas, Lloyds, etc.):
c 2 13.2 Hz: amplitude 1 mm
c 13.2 100 Hz: constant acceleration 0.7 g.
Excessive vibration may cause tripping, breaks in connections or damage to
mechanical parts.
E59572A
Electromagnetic disturbances
Compact NS devices are protected against:
c overvoltages caused by devices that generate electromagnetic disturbances
c overvoltages caused by an atmospheric disturbances or by a distribution-system
outage (e.g. failure of a lighting system)
c devices emitting radio waves (radios, walkie-talkies, radar, etc.)
c electrostatic discharges produced by users.
Compact NS devices have successfully passed the electromagnetic-compatibility
tests (EMC) defined by the following international standards:
c IEC 60947-2, appendix F
c IEC 60947-2, appendix B (trip units with Vigi earth-leakage function).
The above tests guarantee that:
c no nuisance tripping occurs
c tripping times are respected.
144
Compact
Schneider Electric
Installation in switchboards
Power supply and weights
E23947
Power supply
Compact NS circuit breakers can be supplied from either the top or the bottom
without any reduction in performance. This capability facilitates connection when
installed in a switchboard.
push
to
trip
Weights
Circuit breaker
NS80H-MA
NSC100N
3P/3D
3P/3D
4P/4D
NS100N/H
1P/1D
2P/2D
NS100N
3P/2D
NS100N/H/L
3P/3D
4P/4D
NS125E
3P/3D
4P/4D
NS160N/H
1P/1D
2P/2D
NS160N
3P/2D
NS160N/H/L
3P/3D
4P/4D
NS250N
3P/2D
NS250N/H/L
3P/3D
4P/4D
NS400/630N/H/L
3P/3D
4P/4D
NS630b to 1600
3P
manual operation 4P
NS630b to 1600
3P
electrical operation 4P
NS1600b to 3200
3P
4P
1.09
1
1.3
0.5
1.45
1.79
2.05
2.57
1.8
2.3
0.5
1.45
1.85
2.10
2.58
1.94
2.2
2.78
6.19
8.13
14
18
14
18
24
36
NSA
1.1
1.4
0.7
1.2
1.94
6.19
NB50N
NB100F/N
NB250N
NB400/600N
3P/3D
4P/4D
3P/3D
3P/3D
3P/3D
3P/3D
Plug-in
base
Chassis
Vigi module
Positive contact
indication (Interpact INV)
Motor-mechanism
module
1.5
1.7
0.8
0.8
1.05
0.8
1.1
2.2
2.2
2.2
0.87
0.87
1.13
0.9
1.2
2
2
2.2
1.2
1.2
1.2
0.8
0.8
1.05
0.8
0.8
1.05
2.4
2.8
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
14
18
16
21
0.87
0.87
1.13
0.87
0.87
1.13
2.8
3
2
2
2.2
2
2
2.2
4.6
4.9
1.2
1.2
1.2
1.2
1.2
1.2
2.8
2.8
1.5
1.7
The table above presents the weights (in kg) of the circuit breakers and the main accessories, which must be summed to obtain the total weight of complete
configurations.
145
Compact
Schneider Electric
Installation in switchboards
Safety clearances
and minimum distances
Installation
recommendations
E23942
A1
A2
E50700
E50701
F
if F < 8 mm : an
insulating screen
is mandatory
D1
C1
C2
D2
Bare sheetmetal
or painted sheetmetal
Compact circuit breaker
C1
D1
D2
C2
D1
D2
A1 (2)
A2 (3)
B
NS80H-MA
U i 440 V
0
30
30
5
35
35
0
10
0
NSC100N
U < 600 V
0
30
30
10 (1)
35
35
0
20
0
U u 600 V
0
30
30
20 (1)
35
35
0
40
0
NS100-250
U i 440 V
0
30
30
5
35
35
0
10
0
U < 600 V
0
30
30
10 (1)
35
35
0
20
0
U u 600 V
0
30
30
20 (1)
35
35
0
40
0
NS400-630
U i 440 V
0
30
30
5
60
60
0
10
0
U < 600 V
0
30
30
10 (1)
60
60
0
20
0
U u 600 V
0
30
30
20 (1)
100
100
0
40
0
(1) Distance must be doubled with interphase barriers.
(2) For Compact NS with long or short terminal shields.
(3) For Compact NS without terminal shields.
The mandatory distances when installing Compact NS circuit breakers are calculated from the device case, not taking into account the terminal shields or the
interphase barriers.
146
Compact
Schneider Electric
E50781
side panel
F
30
40
insulating kit
40
bare or painted
sheetmetal;
insulation or
insulated bars
B=0
30
A (*)
E59718A
E59717A
146,5
Metal parts
Live parts
NS630b to 1600
A
0
B
0
Insulated parts
0
0
180
60
NS1600b to 2500
A
0
B
0
30
0
180
60
NS3200
A
0
B
0
30
30
180
60
B
C
E59720A
E59719A
40
180
F
A
B
C
Insulated parts
Metal parts
Live parts
0
10
0
0
10
0
30
60
90
F Datum
147
Compact
Schneider Electric
Installation in switchboards
Installation example
Installation
recommendations
E50704
painted sheetmetal
Direct connection by
bare cables, devices
with terminal shields.
Connection by cables
with lugs, devices with
terminal shields.
Connection by insulated
bars, devices with
terminal shields.
148
Compact
A
0
0
250
300
Schneider Electric
E59429A
Door interlock
for Compact NS630b to 1600
4
61
2
(1)
(2)
11
Dimensions (mm)
Type
NS630b to 1600 (3P)
NS630b to 1600 (4P)
(1)
135
205
(2)
168
168
Door locked
door
F
5
23
E59431A
149
Compact
Schneider Electric
Connection of MN and MX
voltage releases for
Compact NS630b to 3200
Installation
recommendations
Release wiring
During pick-up, the power drawn is approximately 150 to 200 VA. For low supply
voltages (12, 24, 48 V), the maximum cable length therefore depends on the
supply voltage and the size of the cables.
Indicative values for maximum wire lengths (in metres)
12 V
24 V
58
35
85 % U source
16
10
MX
100 % U source 21
12
115
70
85 % U source
10
6
75
44
Note. The lengths mentioned are for each of the two supply wires.
150
Compact
48 V
2.5 mm2
280
75
550
350
1.5 mm2
165
45
330
210
Schneider Electric
E59291A
E54545
OFF
L (mm)
S (mm2) Cu / Al
Tightening
torque (Nm)
Standard
device
With distribution
connector
18
1.5 to 70 rigid
1.5 to 50 flexible
5
i 10
1.5 to 16 rigid
1.5 to 10 flexible (1)
2
(1) For flexible cables from 1.5 to 4 mm2, connection with crimped or self-crimping ferrule.
E39432
push
to
trip
Distribution connector
151
Compact
Schneider Electric
Installation
recommendations
L (mm)
I (mm)
d (mm)
e (mm)
(mm)
E59292A
E50702
Bars
400
NS100
NS160/250
NS400/630
i 25
d + 10
i 10
i6
6.5
i 25
d + 10
i 10
i6
8.5
i 32
d + 15
i 15
3 i e i 10
10.5
L
e
push
to
trip
Lugs
L (mm)
i 25
i 25
i 32
(mm)
6.5
8.5
10.5
Tightening torque (Nm) (1)
10
15
50
Tightening torque (Nm) (2)
5
5
20
(1) Tightening torque for lugs or bars on the circuit breaker
(2) Tightening torque for rear connections or terminal extensions on plug-in base
NS100 to 250
Spreader
Separate parts
Tinned copper
Pole pitch
Without spreaders
With spreaders
One-piece spreader
Lugs
L (mm)
l (mm)
d (mm)
e (mm)
(mm)
L (mm)
(mm)
(Nm)
i 25
20 i I i 25
i 10
i6
6.5
i 25
6.5
10 (1), 5 (2)
i 25
20 i I i 25
i 10
i6
8.5
i 25
8.5
15 (1), 5 (2)
Tighten.
torque
(1) Tightening torque for spreaders or terminal extensions on the circuit breaker
(2) Tightening torque for spreaders or terminal extensions on plug-in base
E18601
E18600
Spreaders, straight and right-angle terminal extensions are supplied with flexible
interphase barriers.
Without spreaders
With spreaders
45 mm
52.5 ou 70 mm
E50702
Dimensions
Bars
400
Lugs
L (mm)
l (mm)
d (mm)
e (mm)
(mm)
L (mm)
(mm)
(Nm)
With spreaders
i 40
d + 15
i 20
3 i e i 10
12,5
i 40
12,5
50 (1), 20 (2)
i 32
30 i I i 34
i 15
3 i e i 10
10,5
i 32
10,5
50 (1), 20 (2)
Tighten.
torque
(1) Tightening torque for spreaders or terminal extensions on the circuit breaker
(2) Tightening torque for spreaders or terminal extensions on plug-in base
E18600
Spreaders, straight and right-angle terminal extensions are supplied with flexible
interphase barriers.
E25961
E18599
E21276
400
Right-angle terminal
extensions
Tinned copper.
Upstream side.
E50702
E18599
E55599
Dimensions
35 mm
45 mm
152
Compact
Schneider Electric
E54472
E54471
E54468
E59293A
Distribution connector
E54545
1-cable connector
1-cable connector
Steel
i 160A
Aluminium
i 250A
L (mm)
S (mm2) Cu / Al
Tightening torque (Nm)
20
1.5 to 95 (1)
12 15
20
1016
20
2535
26
50185
L (mm)
S (mm2) Cu / Al
Tightening torque (Nm)
15 or 30
1.5 to 6 (1) 8 to 35
4
6
E54469
E54470
1-cable connector
E54545
E58540
NS100 to 250
L (mm)
S (mm2) Cu / Al
Tightening torque (Nm)
2-cable connector
1-cable connector
1 cable
2-cable connector
2 cables
20
35 to 300
rigid / flexible
31
30 or 60
2 x 85 to 2 x 240
rigid / flexible
31
153
Compact
Schneider Electric
Installation
recommendations
NS400/630N/H
NS400/630L
U < 500 V
Interphase barriers
Interphase barriers
or long terminal
or long terminal
shields recommended.
shields recommended.
Insulated bars
Insulated bars
are mandatory.
are mandatory.
500 V i U i 600 V
Interphase barriers
Interphase barriers
Interphase barriers
or long terminal
or long terminal
or long terminal
shields are
shields are
shields are
mandatory.
mandatory.
mandatory.
Insulated bars
Insulated bars
Insulated bars
are mandatory.
are mandatory.
are mandatory.
U > 600 V
Insulation kit
Insulation kit
Insulation kit
and insulated bars
and insulated bars
and insulated bars
are mandatory.
are mandatory.
are mandatory.
The insulation kit is not compatible with:
c separate spreaders for Compact NS100 to 250. The one-piece spreader must be used
c separate spreaders (70 mm) for Compact NS400 and 630. For the 52.5 mm spreaders, there
is a specific insulation kit.
NS100/250N/H/L
NS400/630N/H
NS400/630L
NS400/630N/H
NS400/630L
154
Compact
Schneider Electric
aa
Power connections for
Compact NS630b to 3200
E59565A
Compact circuit breakers can be connected indifferently with bare-copper, tinnedcopper and tinned-aluminium conductors (flexible or rigid bars, cables.
In the event of a short-circuit, thermal and electrodynamic stresses will be exerted
on the conductors. They must therefore be correctly sized and maintained in place
using supports.
Electrical connection points on all types of devices (switch-disconnectors,
contactors, circuit breakers, etc.) should not be used for mechanical support.
The table below indicates the maximum distance between ties depending on the
prospective short-circuit current.
The maximum distance between ties attached to the switchboard frame is 400 mm.
Type of
tie
"Sarel" ties
Width: 9 mm
Maximum load: 90 kg
Colour: black
200
100
50
350
200
100
70
10
15
20
20
27
35
45
aa
"Panduit" ties
Width: 4.5 mm
Maximum load: 22 kg
Colour: white
Maximum distance
between ties (mm)
Short-circuit
current (kA rms)
50 (double
ties)
100
E59567A
E59566A
Connection of bars
Bars must be adjusted to ensure correct positioning on the terminals before bolting (B)
Bars must rest on a support firmly attached to the switchboard frame, such that the
circuit-breaker terminals do not bear any weight (C).
Electrodynamic forces
The first spacer between bars must be positioned within a maximum distance (see
table below) of the connection point to the circuit breaker. This distance is
calculated to resist the electrodynamic stresses exerted between the bars of each
phase during a short-circuit.
Maximum distance A between the circuit-breaker connection and the first spacer
between bars, depending on the short-circuit current
Isc (kA)
30
50
65
80
100
150
Distance (mm)
350
300
250
150
150
150
E59570A
E59569A
E59568A
155
Compact
Schneider Electric
Connections
E47665
E47667B
E47668
The quality of bar connections depends, among other things, on the tightening
torques used for the nuts and bolts. Over-tightening may have the same
consequences as under-tightening.
The correct tightening torques for the connection of bars to the circuit-breaker
terminals are indicated in the table below.
The values below are for copper bars (Cu ETP-NFA51-100) and steel nuts and
bolts (class 8.8).
The same values apply to AGS-T52 quality aluminium bars
(French standard NFA 02-104 and American National Standard H-35-1).
Examples of bar connections
6
1 terminal screws, factory tightened to 13 Nm
2 circuit-breaker terminal
3 bars
4 bolt
5 washer
6 nut
11
Bar drilling
E47331A
E47330A
E47329A
Examples
E47680A
Insulation distance
X
Dimensions (mm)
Utilisation voltage
Ui i 600 V
Ui i 1000 V
X minimum
8 mm
14 mm
Bar bending
Bars must be bent according to the table below. A tighter bend may cause cracks.
E47679A
E47678A
Installation
recommendations
r
e
Dimensions (mm)
e
5
10
156
radius r
Minimum
Recommended
5
15
7.5
18 to 20
Compact
Schneider Electric
Sizing of bars
The following tables are based on the following assumptions:
c maximum permissible temperature of bars is 100 C
c Ti: temperature around the circuit breaker and its connections
c busbars made of copper and not painted.
Note.
The values presented in the tables are the result of trials and theoretical calculations on the
basis of the assumptions mentioned above.
These tables are intended as an aid in designing connections, however, the actual values must
be confirmed by tests on the installation.
E59294A
Compact
Maximum
service
current
Ti : 40 C
Number of bars
5 mm thick
10 mm thick
Ti : 50 C
Number of bars
5 mm thick
10 mm thick
Ti : 60 C
Number of bars
5 mm thick
10 mm thick
NS630b
NS630b
NS800
NS1000
NS1250
400
630
800
1000
1250
2b.30 x 5
2b.40 x 5
2b.50 x 5
3b.63 x 5
3b.63 x 5
1b.30 x 10
1b.40 x 10
1b.63 x 10
2b.50 x 10
2b.50 x 10
1400
1600
1800
2000
2200
2500
2800
3000
3200
2b.30 x 5
2b.40 x 5
2b.50 x 5
3b.50 x 5
3b.50 x 5
2b.80 x 5
2b.80 x 5
3b.80 x 5
3b.80 x 5
3b.100 x 5
3b.100 x 5
4b.100 x 5
4b.100 x 5
6b.100 x 5
8b.100 x 5
1b.30 x 10
1b.40 x 10
1b.50 x 10
2b.50 x 10
2b.50 x 10
NS1600 / 1600b
NS1600 / 1600b
NS2000
NS2000
NS2500
NS2500
NS3200
NS3200
NS3200
2b.30 x 5
2b.40 x 5
2b.50 x 5
3b.50 x 5
3b.50 x 5
2b.80 x 5
3b.50 x 5
3b.63 x 5
3b.80 x 5
3b.100 x 5
3b.100 x 5
4b.100 x 5
4b.100 x 5
5b.100 x 5
6b.100 x 5
2b.50 x 10
2b.63 x 10
2b.63 x 10
2b.80 x 10
2b.80 x 10
2b.100 x 10
3b.80 x 10
3b.100 x 10
3b.100 x 10
3b.80 x 5
3b.80 x 5
3b.100 x 5
3b.100 x 5
4b.80 x 5
4b.100 x 5
5b.100 x 5
8b.100 x 5
2b.63 x 10
3b.50 x 10
2b.80 x 10
3b.63 x 10
2b.100 x 10
3b.80 x 10
3b.100 x 10
4b.80 x 10
4b.100 x 10
1b.30 x 10
1b.40 x 10
1b.50 x 10
1b.63 x 10
2b.40 x 10
2b.40 x 10
2b.40 x 10
2b.50 x 10
2b.63 x 10
2b.80 x 10
2b.80 x 10
2b.100 x 10
3b.80 x 10
3b.80 x 10
3b.100 x 10
Note
With Compact NS630b to NS1600, it is recommended to use 50 mm wideness bars (see "Recommanded busbars drilling")
157
Compact
Schneider Electric
Installation
recommendations
E59422A
Compact
Maximum
service
current
Ti : 40 C
Number of bars
5 mm thick
10 mm thick
Ti : 50 C
Number of bars
5 mm thick
10 mm thick
Ti : 60 C
Number of bars
5 mm thick
10 mm thick
NS630b
NS630b
NS800
NS1000
NS1250
NS1600
NS1600
400
630
800
1000
1250
1400
1600
2b.30 x 5
2b.40 x 5
2b.50 x 5
2b.50 x 5
2b.63 x 5
2b.63 x 5
2b.80 x 5
2b.30 x 5
2b.40 x 5
2b.50 x 5
2b.50 x 5
2b.63 x 5
2b.63 x 5
2b.80 x 5
2b.30 x 5
2b.40 x 5
2b.50 x 5
2b.63 x 5
3b.50 x 5
3b.50 x 5
3b.63 x 5
1b.30 x 10
1b.40 x 10
1b.50 x 10
1b.50 x 10
1b.63 x 10
1b.63 x 10
1b.80 x 10
158
Compact
1b.30 x 10
1b.40 x 10
1b.50 x 10
1b.50 x 10
1b.63 x 10
1b.63 x 10
1b.80 x 10
1b.30 x 10
1b.40 x 10
1b.50 x 10
1b.63 x 10
2b.50 x 10
2b.50 x 10
2b.50 x 10
Schneider Electric
12,5
12,5
25,5
12,5
12 maxi
25
25
38,5
=
25
9,5 12,5
13,5
25 25
12,5
77
38,5
25
13,5
82 52
12,5
38,5
=
25
13,5
5 11
15
5 11
5 11
25
25
13,5
=
30
82 52
15
2 11
25
25
52
52
38,5
=
25
30
82 52
15
77
30
82 52
15
5 11
77
30
60
12,5
15
12 maxi
E59326A
E59325A
E59324B
25
77
80
15
12,5
12 maxi
12,5
44
E59310A
63
E59328A
25
50
E59327A
12,5
12 maxi
E59309A
50
12,5
E59308A
Rear connection
52
52
12 maxi
12,5
12,5
50
12 maxi
25
12,5
12 maxi
25
12,5
12,5
E59315 A
40
E59314A
E59313A
32
25
E59329B
E59312A
E59311A
12 maxi
25
12,5
80
12 maxi
25
12,5 12,5
12,5
12,5
60
12,5
9,5
12,5
25 44
2 11
12,5
12 maxi
25
44
25
12,5
12,5
12 maxi
9,5
15
25
Bottom terminal
2 vis M10
25
15
89
= =
63
25,5
80
15
15
12,5
12 maxi
25
12,5
E59310A
50
12,5
Top terminal
E59309A
E59308A
50
12,5
E59423B
E59332A
E59308A
Front connection
12,5
12 maxi
25 25
12,5
12,5
15
21
101
21
3 11
2 vis M10
15
25
44
15
15
9,5
159
20
Compact
Schneider Electric
Installation
recommendations
50
12,5
E59462B
63
12,5
12 maxi
25
25,5
80
15
15
12,5
12 maxi
12,5
25
12 maxi
25 25
12,5
12,5
25
76
= =
13
E59310A
E59309A
E59308A
=
=
3 11
15
12 maxi
80
12 maxi
12 maxi
25
25
25
25
25
25
25
25
25
12,5
12,5
100
12,5
12,5
12,5
12 maxi
E59734A
63
E59733A
E59732A
E59731A
25
25
100
25
12,5
12,5
12,5
E59735A
4 11
25
60 100
25
25
20
20
12,5
45
20
15
25 25
60
80
100
12 maxi
12 maxi
25
E59734A
E59733A
25
25
100
25
25
25
12,5
12,5
12,5
12,5
E59735A
4 11
25
60 100
25
25
20
45
60
20
12,5
20
15
25 25
80
160
Compact
Schneider Electric
Temperature derating
Compact NS devices equipped
with thermal-magnetic trip units
The values opposite are valid for fixed circuit
breakers equipped with one of the following modules:
c Vigi module
c ammeter module
c insulation-monitoring module
c current-transformer module.
They also apply to plug-in / withdrawable circuit
breakers equipped with one of the following modules:
c ammeter module
c current-transformer module.
However, for plug-in / withdrawable circuit breakers
equipped with a Vigi module or an insulationmonitoring module, the coefficients in the table below
must be applied.
Trip unit
TM16 to TM125
TM160 to TM250
Coefficient
1
0.9
40 C
45 C
50 C
55 C
60 C
65 C
70 C
16
25
40
63
80
100
125
160
200
250
15.6
24.5
39
61.5
78
97.5
122
156
195
244
15.2
24
38
60
76
95
119
152
190
238
14.8
23.5
37
58
74
92.5
116
147.2
185
231
14.5
23
36
57
72
90
113
144
180
225
14
22
35
55
70
87.5
109
140
175
219
13.8
21
34
54
68
85
106
136
170
213
Compact NS100 to 250 equipped with TM-D and TM-G trip units
Rating (A)
16
25
32
40
50
63
80
100
125
160
200
250
40 C
45 C
50 C
55 C
60 C
65 C
70 C
16
25
32
40
50
63
80
100
125
160
200
250
15.6
24.5
31.3
39
49
61.5
78
97.5
122
156
195
244
15.2
24
30.5
38
48
60
76
95
119
152
190
238
14.8
23.5
30
37
47
58
74
92.5
116
147.2
185
231
14.5
23
29.5
36
46
57
72
90
113
144
180
225
14
22
29
35
45
55
70
87.5
109
140
175
219
13.8
21
28.5
34
44
54
68
85
106
136
170
213
Compact NSA160
Rating (A)
16
25
32
40
50
63
80
100
125
160
40 C
45 C
50 C
55 C
60 C
65 C
70 C
16
25
32
40
50
63
80
100
125
160
15.6
24.5
31.3
39
49
61.5
78
97.5
122
156
15.2
24
30.5
38
48
60
76
95
119
152
14.8
23.5
30
37
47
58
74
92.5
116
147.2
14.5
23
29.5
36
46
57
72
90
113
144
14
22
29
35
45
55
70
87.5
109
140
13.8
21
28.5
34
44
54
68
85
106
136
Compact NB50NB600
NB50 / NB100
NB50N
NB100F/N
NB250N
Rating (A)
125
150
175
200
225
NB400N
Rating (A)
400
NB600N
Rating (A)
600
161
Compact
40 C
45 C
50 C
55 C
60 C
1
1
1
1
1
1
1
1
1
1
50 C
55 C
60 C
65 C
70 C
125
150
175
200
225
122
146
171
195
220
119
143
166
190
214
116
139
162
185
208
113
135
158
180
203
50 C
55 C
60 C
65 C
70 C
400
390
380
370
360
50 C
55 C
60 C
65 C
70 C
600
585
570
550
535
Schneider Electric
Installation
recommendations
Temperature derating
Compact NS devices equipped with
electronic trip units
Electronic trip units are not affected by variations in temperature. However, the
maximum permissible current in the circuit breaker still depends on the ambient
temperature.
Compact NS100...NS250
The table below indicates the maximum long-time (LT) protection setting depending
on the ambient temperature.
NS250N/H/L
In: 100 to 160A
Ir max
In: 250A
Ir max
Coeff.
STR22SE/GE 40 to 100
STR22SE/GE 40 to 160
STR22SE/GE 100 and 160
STR22SE/GE 250
1
1
1
0.86
50 C
55 C
no derating
1
1
45 C
40 C
50 C
55 C
60 C
65 C
70 C
1
250
1
1
237.5
0.95
1
237.5
0.95
1
225
0.90
1
225
0.90
45 C
no derating
1
1
250
250
1
1
60 C
65 C
70 C
40 C
NS100N/H/L
In: 40 to 160 A
Ir max
Coeff.
NS400N/H/L
Fixed
In: 400A
Io/Ir max
Plug-in /
In: 400
withdrawable Io/Ir max
NS630N/H/L
Fixed
In: 630A
Io/Ir max
Plug-in /
In: 570A
withdrawable Io/Ir max
40 C
45 C
50 C
55 C
60 C
65 C
70 C
400
1/1
400
1/1
400
1/1
390
1/0.98
400
1/1
380
1/0.95
390
1/0.98
370
1/0.93
380
1/0.95
360
1/0.9
370
1/0.93
350
1/0.88
360
1/0.9
340
1/0.85
40 C
45 C
50 C
55 C
60 C
65 C
70 C
630
1/1
570
1/0.9
615
1/0.8
550
1/0.88
600
1/0.95
535
1/0.85
585
1/0.93
520
1/0.83
570
1/0.9
505
1/0.8
550
1/0.88
490
0.8/0.98
535
1/0.85
475
0.8/0.95
NS400N/H/L
Version
Connection
temp. Ti (2)
NS630b N/H/L
NS800 N/H/L
NS1000 N/H/L
NS1250 N/H
NS1600 N/H
Fixed device
Front or horizontal rear
40
45
50
55
60
65
70
Vertical rear
40
45
50
55
60
65
70
630
800
1000
1250
1600
630
800
1000
1250
1470
630
800
1000
1170
1420
630
800
1000
1000
1360
630
800
1000
1250
1600
630
800
1000
1250
1600
630
800
1000
1250
1600
630
800
1000
1250
1600
630
800
1000
1250
1510
630
800
1000
1090
1460
Withdrawable device
Front or horizontal rear
40
45
50
55
60
65
70
Vertical rear
40
45
50
55
60
65
70
630
800
1000
1250
1600
630
800
1000
1250
1430
630
800
1000
1240
1330
630
800
920
1090
1160
630
800
1000
1250
1600
630
800
1000
1250
1600
630
800
1000
1250
1560
630
800
1000
1250
1510
630
800
1000
1250
1420
630
800
990
1180
1250
60
65
70
Vertical rear
40
45
50
55
60
65
70
630
800
1000
1250
1600
630
800
1000
1250
1600
630
800
1000
1250
1560
630
800
1000
1250
1520
630
800
1000
1250
1510
630
800
1000
1250
1480
630
800
1000
1250
1600
630
800
1000
1250
1600
Fixed device
Front or horizontal rear
40
45
50
55
NS1600b N/H
1600
1600
1600
1600
1500
1450
1400
1600
1600
1600
1600
1600
1550
1500
NS2000 N/H
2000
2000
2000
2000
1900
1800
1700
2000
2000
2000
2000
2000
1900
1800
NS2500 N/H
2500
2500
2500
2500
2500
2500
2500
2500
2500
2500
2500
2500
2500
2500
NS3200 N/H
3200
3200
3200
3180
3080
2970
2860
(1) For a circuit breaker mounted in horizontal position, the derating to be applied is equivalent to that of a front or horizontal rear connected circuit breaker.
(2) Ti: temperature around the circuit breaker and its connections.
162
Compact
Schneider Electric
Compact NSC100N
3/4 poles
NSC100N
NSC100NA
Rat. (A)
16
20
25
32
40
50
63
70
80
100
100
Fixed device
Additional modules
R/pole
15
11.2
8
5.4
3.7
2.8
2
2
1.4
1
0.6
P/pole
4
4.5
5
5.5
6
7
8
10
9
10
6
Compact NS100 to 250 equipped with TM-D and TM-G trip units
Fixed device
3/4 poles
NS100N/H/L 16
25
32
40
50
63
80
100
NS160N/H/L 80
100
125
160
NS250N/H/L 125
160
200
250
11.42
6.42
3.94
3.42
1.64
2.17
1.37
0.88
1.26
0.77
0.69
0.55
0.61
0.46
0.39
0.3
Additional modules
P/pole
Vigi
Vigi
With-
2.92
4.01
4.03
5.47
4.11
8.61
8.77
8.8
8.06
7.7
10.78
13.95
9.45
11.78
15.4
18.75
(N, L3)
0
0
0.06
0.10
0.15
0.3
0.4
0.7
0.4
0.7
1.1
1.8
1.1
1.8
2.8
4.4
(L1, L2)
0
0
0.03
0.05
0.08
0.15
0.2
0.35
0.2
0.35
0.55
0.9
0.55
0.9
1.4
2.2
drawable module
0
0
0.1
0
0.15
0.1
0.2
0.1
0.3
0.1
0.4
0.1
0.6
0.1
1
0.2
0.6
0.1
1
0.2
1.6
0.3
2.6
0.5
1.6
0.3
2.6
0.5
4
0.8
6.3
1.3
Ammeter Transfo.
module
0
0
0.1
0.1
0.1
0.1
0.1
0.2
0.1
0.2
0.3
0.5
0.3
0.5
0.8
1.3
NS80H
1.5
2.5
6.3
12.5
25
50
80
NS100N/H/L 2.5
6.3
12.5
25
50
100
NS160N/H/L 150
NS250N/H/L 220
NS400H/L
320
NS630H/L
500
93.3
89.6
75.6
12.8
2.24
1.04
0.94
148.42
99.02
4.05
1.66
0.67
0.52
0.38
0.3
0.12
0.1
P/pole
0.21
0.56
3
2
1.4
2.6
6.02
0.93
3.93
0.63
1.04
1.66
5.2
8.55
14.52
12.29
25
Additional modules
Vigi
Vigi
(N, L3)
With-
0
0
0
0
0.2
0.7
1.35
2.9
3.2
13.99
0
0
0
0
0.1
0.35
0.68
1.45
1.6
7
0
0
0
0.1
0.3
1
2.6
4.89
6.14
15
Ammeter Transfo.
0
0
0
0
0.1
0.2
0.45
0.97
1.54
3.75
0
0
0
0
0.1
0.2
0.45
0.97
1.54
3.75
NS160N/H
163
Rat. (A)
16
20
30
40
50
63
80
100
125
160
Compact
R/pole
11.3
6.3
2.9
2.9
1.4
1.4
1.25
0.76
0.63
0.48
P/pole
2.89
2.52
2.61
4.64
3.5
5.56
8
7.6
9.84
12.29
Schneider Electric
Installation
recommendations
P/pole
Additional modules
Vigi
Vigi
With-
Ammeter Transfo.
Compact NSA160
Fixed device
3/4 poles
NSA160
NSA125NA
NSA160NA
15
8
5.4
3.7
2.8
2
1.4
1
0.8
0.6
0.7
0.6
P/pole
4
5
5.5
6
7
8
9
10
12.5
15.4
11
15.4
Additional modules
Vigi
Vigi
(N, L3)
0.06
0.16
0.26
0.4
0.63
1
1.6
2.5
3.9
6.4
(L1, L2)
0.06
0.16
0.26
0.4
0.63
1
1.6
2.5
3.9
6.4
Fixed device
Dissipated power
Input/output resistance
NS630b N/H/L
NS800 N/H/L
NS1000 N/H/L
NS1250 N/H
NS1600 N/H
30/45
45/60
65/100
130
220
0.026/0.039
0.026/0.039
0.026/0.039
0.026
0.026
Version
Withdrawable device
Dissipated power
Input/output resistance
NS630 N/H/L
NS800 N/H/L
NS1000 N/H/L
NS1250 N/H
NS1600 N/H
55/115
90/120
150/230
250
460
0.05
0.05
0.05
0.036
0.036
Fixed device
Dissipated power
Input/output resistance
NS1600b N/H
NS2000 N/H
NS2500 N/H
NS3200 N/H
250
250
300
680
0.019
0.013
0.008
0.008
164
Compact
Schneider Electric
Compact NS
Dimensions, volumes
Presentation
Functions and characteristics
Installation recommendations
1
11
143
Compact NB
Compact NS80H-MA
Compact NSC100
Compact NSA160
Compact NS100 to 630 (fixed version)
Vigicompact NS100 to 630 (fixed version)
Compact NS100 to 630
(plug-in and withdrawable versions)
Vigicompact NS100 to 630
(plug-in and withdrawable versions)
Compact NS100 to 250
(single-pole and two-pole versions)
Visu function for Compact NS100 to 630
(combination with Interpact INV)
Motor-mechanism module for Compact NS100 to 630
Rotary handle for Compact NS100 to 630
Indication and measurement modules
for Compact NS100 to 630
Front accessories for Compact NS100 to 630
Compact NS630b to 1600 (fixed version)
166
168
170
171
172
174
176
178
180
182
184
186
188
190
192
Dimensions
Mountings
Front-panel cutouts
Rotary handle
192
193
194
195
196
196
197
198
Dimensions
198
200
External modules
200
Accessories
204
Connection
Electrical diagrams
Additional characteristics
Catalogue numbers
165
Compact NS
205
221
251
267
Schneider Electric
Compact NB
Dimensions, volumes
E58736A
E58522A
H1
H3
H5
H
H2
H4
(d)
(c)
Y
P1
P2
P3
L
L1
E43682A
K1
K
E58739A
U (e)
G1
G1
T G
Door cutout
(B, C)
E62279A
E62277A
E62278A
E62276A
Cutout (A)
C1
B/C
C1
C
Y
R2
R3
Y
R
R1
C1
C
P4
P5
Z
Dimensions (mm)
Type
C
NB50N
27
NB100F/N 27
C1
54
54
G
G1 H
H1 H2
55.5 111 65
130 ??
66
132 77.5 155 ??
H3
??
??
H4
??
??
166
H5
??
??
K
K1
12.5 25
15
30
L
L1
37.5 75
45
90
Compact NS
P1
68
68
P2
72
72
P3
90
90
P4
70
70
P5
74
74
R
R1
12.5 25
12.5 25
R2 R3
30.5 61
43.5 87
T
6
6
U (e)
i32
i32
Schneider Electric
E58737A
H1
H3
H5
H7
X
T
H2
H4
K1
K
E58740A
E43683A
E58738A
H6
G1
G1
(a)
(b)
(c)
Y
L
P1
P2
P3
L1
Door cutout
E62282A
E62283A
(B, C)
E62281A
E62280A
Cutout (A)
C1
Y
R
R2
R1
C3
C2
C2
B/C
C3
R3
P4
P5
Z
E62308A
E62307A
E62306A
With escutcheon
C5
C7
C6
C4
Y
Y
R6
R7
R4
R5
P5
Z
Dimensions (mm)
Type
NB250N
NB400/600N
C
C1
29
76
41.5 116
C2
C3
54
108
92.5 184
C4
C5
43
104
56.5 146
Type
NB250N
NB400/600N
P1
P2
81
86
95.5 110
P3
111
168
P5
88
112
P4
83
117
C6
C7
34
86
46.5 126
R
R1
14.5 29
31.5 63
G
G1
62.5 125
100 200
R2
R3
54
108
71.5 143
167
H
H1
80.5 161
127.5 255
R4
R5
29
58
46.5 93
R6
43
63
Compact NS
H2
H3
94
188
142.5 285
H4
H5
160.5 321
240 480
R7
86
126
U (e)
i32
i32
T
6
6
H6
H7
178.5 357
237 474
K
K1
17.5 35
22.5 45
L
L1
52.5 105
70
140
Schneider Electric
Compact NS80H-MA
Dimensions, volumes
Dimensions
Mounting
On rails
103
30
E21876
30
15
E21873
E21874
E21875
On backplate
15
32
120
X
60
100
100
48,5
206
48,5
(a)
64,5
70
80
84
100
45
90
Front-panel cutouts
E21884
Cutout C
E21883
Cutout B
E21882
E21881
Cutout A
60,5
26
B/C
71
81
68,5
30
30
Y
14,5
68,5
46
29
92
168
Compact NS
Schneider Electric
E21887
7,5
65,5
60
E21886
E21885
E21888
Front-panel cutout
ON
I
4,2
28,5
60
68,5
tripped
30
O
OFF
47,5
82,5
112
45
80
90
43
85
86
E21890
E21889
75
37,5
45
7,5
E21891
7,5
50
60
4,2
75
4,2
37,5
4,2
60
Y
Z
36
72
mini 175
L ( maxi 590 )
E21894
E21892
E21893
120
69,2
7,5
4,2 120
X
X
60
45,8
1 to 3 maxi
Y
116 2
100
Y
51,7
E22046
100
Note.
Door cutout dimensions are given for a device position in the
enclosure where u 100 + (h x 5) with respect to the door
hinge.
169
Compact NS
Schneider Electric
Compact NSC100
Dimensions, volumes
Dimensions
Compact NSC100
E43400
4 poles
E43399
E43398
3 poles
103
120
X
60
(a)
(a)
206
90
15
70
80
84
100
Y
45
45
90
120
Vigicompact NSC
E43402
E43401
4 poles
E43403
3 poles
101,2
103
120
(a)
(a)
X
60
90
206
70
80
84
100
15
45
75
210
240
E31295
E43404
83
E31296
50
60
75
37,5
4,2
60
Y
Z
72
36
mini 122
maxi 147
Note.
Centre line X indicates the centre of the mounting r ail.
170
Compact NS
Schneider Electric
Compact NSA160
Dimensions
Compact NSA160
4 poles
E21896
E21895
E21897
3 poles
98,5
120
X
X
64,5
45
206
90
(a)
15
(a)
72,5
82,5
89,5
102,5
Y
45
45
90
120
Vigicompact NSA160
3 poles
4 poles
E21902
E21901
E21903
101,2
98,5
120
X
64,5
45
206
90
(a)
15
(a)
72,5
82,5
89,5
102,5
45
75
210
240
Dimensions
75
E31296
37,5
E31294
45
83
50
60
X
X
75
37,5
4,2
60
Y
Z
72
36
mini 122
maxi 147
Note.
Centre line X indicates the centre of the mounting r ail.
171
Compact NS
Schneider Electric
Dimensions, volumes
Dimensions
E21503
4 poles
E21502
E21504
2 poles or 3 poles
H1
H3
H5
H7
X
H
H2
H4
H6
(a)
(b)
(c)
P1
P2
P4
L1
Y
L
L2
Mounting
K1
4 poles
K1
K1
E21508
E21507
On backplate
2 poles or 3 poles
K1
K1
K2
G1
G5
X
G
K1
G4
T4 (d)
4 poles
K1
K
U (e)
G1
E21512
E21511
On rails
2 poles or 3 poles
K2
K
X
G
E49738
G49
X
G48
G47
Z
172
Compact NS
Schneider Electric
Front-panel cutouts
Cutout C
C1
E21604
E21603
Cutout B
E21601
E21600
B/C
R1
E21602
E21608
E21609
With escutcheon
C3
C2
Y
R2
R4(3P)
R5(4P)
P5
P6
C2
C3
C7
X C21
C20
C6
Y
R6
R7
P6
Y
R12
R13
Dimensions (mm)
Type
NS100/160/250N/H/L
NS400/630N/H/L
C
29
41.5
C1
76
116
C2
54
92.5
C3
108
184
C6
43
56.5
C7
104
146
C20
34
46.5
C21
86
126
G
62.5
100
G1
125
200
G4
70
113.5
Type
NS100/160/250N/H/L
NS400/630N/H/L
G5
140
227
G47
95
G48
75
G49
13.5
G50
23
G51
17.5
H
80.5
127.5
H1
161
255
H2
94
142.5
H3
188
285
H4
160.5
240
Type
NS100/160/250N/H/L
NS400/630N/H/L
H5
321
480
H6
178.5
237
H7
357
474
K
17.5
22.5
K1
35
45
K2
70
90
L
52.5
70
L1
105
140
L2
140
185
P1
81
95.5
P2
86
110
P6
88
112
R
14.5
31.5
R1
29
63
R2
54
71.5
R4
108
143
R5
143
188
R6
29
46.5
R7
58
93
R12
43
63
Type
P4
P5
NS100/160/250N/H/L
111(1)
83
NS400/630N/H/L
168
107
(1) : P4 = 126 mm for Compact NS250N/H/L.
E22046
Type
R13
T
T4
U(e)
NS100/160/250N/H/L
86
6
22
32
NS400/630N/H/L
126
6
32
32
(e) U 20 mm if automatic auxiliary connectors are used (NS100 to 250).
Nota :
Door cutout dimensions are given for a device position in the
enclosure where u100 + (h x 5) with respect to the door
hinge.
173
Compact NS
Schneider Electric
Dimensions, volumes
Dimensions
E21514
4 poles
E21513
E21515
2 poles or 3 poles
(a)
(b)
(c)
Y
P1
P2
P4
L1
L
L2
Mounting
On backplate
2 poles or 3 poles
K1
K1
E21519
E21518
K1
4 poles
K1
K
G9
G1
G7
K1 K1
K2
K
X
G
G8
G6
T
T4 (d)
U (e)
G7
4 poles
K1
K
E21521
E21520
On rails
2 poles or 3 poles
K2
K
G1
X
X
G
G6
T
174
Compact NS
Schneider Electric
Front-panel cutouts
Fixed or plug-in circuit breaker
Cutout B
E21796
E21605
E21795
Cutout A
R1
R
C1
C3
C4
C2
C5
R28
Y
R28
R26
P5
P6
R26
R2
R4 (3P)
R5 (4P)
With escutcheons
E21610
E21800
R7
R6
C7
X
C6
C18
C19
Y
R27
R11
P6
Z
Dimensions (mm)
Type
NS100/160/250N/H/L
NS400/630N/H/L
C
29
41.5
C1
76
116
C2
130
192
C3
184
276
Type
H8
H9
H10 H11
NS100/160/250N/H/L
155.5 236
169
263
NS400/630N/H/L
227.5 355
242.5 385
(1) P4 = 126 mm for Compact NS250N/H/L.
C4
C5
86
37
147.5 37
C6
43
56.5
C7
104
146
C18
71
132
C19
68
68
C20
34
46.5
C21
86
126
G
62.5
100
G1
125
200
G6
G7
137.5 200
200
300
G8
G9
145
215
213.5 327
H12 H13
235.5 396
340
580
H14 H15
253.5 432
337
574
K
17.5
22.5
K1
35
45
K2
70
90
L
52.5
70
L1
105
140
L2
140
185
P1
81
95.5
P2
86
110
P4
P5
111(1) 83
168
107
R11
58
58
R12
43
63
R13
86
126
R26
14.5
32
R27
29
47
T
6
6
T4
22
32
U(e)
32
32
R7
58
93
E22046
Type
P6
R
R1
R2
R4
R5
R6
NS100/160/250N/H/L
88
14.5 29
54
108
143
29
NS400/630N/H/L
112
31.5 29
71.5 143
188
46.5
(e) U 20 mm if automatic auxiliary connectors are used (NS100 to 250).
Note.
Door cutout dimensions are given for a device position in the
enclosure where u100 + (h x 5) with respect to the door
hinge.
175
Compact NS
Schneider Electric
Dimensions, volumes
Dimensions
Plug-in base
N
2 poles or 3 poles
Z
4 poles
(*)
K1
K1
E21523
E21522
E21524
K1
H17
G11
H16
G10
(*)
P7
P8
P9
P4
Chassis
2 poles or 3 poles
4 poles
E21585
E21584
E21586
L2
L1
H19
X
H18
(*)
(*)
Z
P7
P8
P9
P2
P4
Y
L6
L7
L8
P12
L6
L9
L10
Mounting
Through panel M (plug-in base)
K1
2P, 3P
4P
K2
K
X
G12
Y
K5
K5
4P
K21
K20
Y
K11
K12
K7
X
G12
G10
K6
K11
K13
K22
K20
E21534
E21533
G13
G11
G10
K
E21588
E21526
E21525
G13
G11
K2
4P
K
E21587
G21
G20
Y
176
Compact NS
Schneider Electric
E21590
E21589
K2
K
G15
X
G14
4P
K K
K2
K K
E21593
T6
4P
K1
K K
K2
E21592
G15
G18
G16
G15
X
G14
G17
K1
G19
G14
Y
K1
K1 K1
Y
K1
T5
K1
Y
K1
K1 K1
Y
K1
Front-panel cutouts
Plug-in base
E21619
E21591
K1
K K
E21594
C11
C17
P44
Z
Y
R8
R9
Dimensions (mm)
Type
NS100/160/250N/H/L
NS400/630N/H/L
C11
103
155
C17
42.5
56
G10
95
150
Type
NS100/160/250N/H/L
NS400/630N/H/L
G25
380
567
G26 G27
208
416
318.5 637
Type
NS100/160/250N/H/L
NS400/630N/H/L
K21
70
100
K22
105
145
G14
77.5
125
G15
155
250
G16
66
101
G17
132
202
G18
82
126
G19
164
252
G20
37.5
75
G21
75
150
G22 G23
111
222
170.5 341
G24
190
283.5
H16 H17
102.5 205
157.5 315
H18 H19
103.5 210
140
280
K
17.5
22.5
K1
35
45
K2
70
90
K5
54.5
71.5
K6
109
143
K7
144
188
K11
74
91.5
K12
148
183
K13
183
228
K20
35
50
L1
105
140
L6
92.5
110
L7
185
220
L8
216
250
L9
220
265
L10
251
295
P2
86
110
P4
P7
111(1) 27
168
27
P8
45
45
P9
75
100
P10
64
86
P12
32
32
Type
P44 R8
R9
U(2)
T
T5
NS100/160/250N/H/L
123
74
148
32 6
24
NS400/630N/H/L
147
90
180
32 6
33
(1) P4 = 126 mm for Compact NS250N/H/L
(2) U 20 mm if automatic auxiliary connectors are used (NS100 to 250).
T6
30
33
L
52.5
70
G11
190
300
G12
87
137
L2
140
185
177
G13
174
274
Compact NS
Schneider Electric
Dimensions, volumes
Dimensions
Plug-in base
K1
(*)
K1
K1
E21536
4 poles
E21535
E21537
2 poles or 3 poles
H17
G11
G10
H16
(*)
P7
P8
P9
L1
L2
P4
Chassis
See withdrawable Compact, page XXX.
Mounting
E21587
E21526
E21525
K1
K
4P
K2
K
G13
G11
Y
K5
K21
K20
G20
Y
K11
K13
K22
K20
G21
Y
K11
4P
E21534
E21533
Y
K12
K7
X
G12
K5
K6
G13
G10
K2
X
G12
G10
K1
K
G11
4P
E21588
178
Compact NS
Schneider Electric
Front-panel cutouts
Chassis with protection collar and escutcheons
R9
R8
E21623
E21813
Plug-in base
See fixed Compact, page XXX.
C11
C17
C16
C13
Y
R33
P44
Z
R34
Dimensions (mm)
Type
NS100/160/250N/H/L
NS400/630N/H/L
C11
103
155
C13
84
84
C16
55
116.5
C17
42.5
56
G10
95
150
G11
190
300
G12
87
137
G13
174
274
G20
37.5
75
G21
75
150
H16
102.5
157.5
Type
NS100/160/250N/H/L
NS400/630N/H/L
H17
205
315
K
17.5
22.5
K1
35
45
K2
70
90
K5
54.5
71.5
K6
109
143
K7
144
188
K11
74
91.5
K12
148
183
K13
183
228
K20
35
50
L
52.5
70
L1
105
140
L2
140
185
P4
111(1)
168
P7
27
27
P8
45
45
P9
75
100
P44
123
147
R8
74
90
Type
K21
K22
NS100/160/250N/H/L
70
105
NS400/630N/H/L
100
145
(1) P4 = 126 mm for Compact NS250N/H/L.
U(2)
32
32
E22046
Type
R9
R33
R34
T
NS100/160/250N/H/L
148
74
148
6
NS400/630N/H/L
180
91.5
148
6
(2) U 20 mm if automatic auxiliary connectors are used (NS100 to 250).
Note.
Door cutout dimensions are given for a device position in the
enclosure where u100 + (h x 5) with respect to the door
hinge.
179
Compact NS
Schneider Electric
Dimensions, volumes
Dimensions
2 poles
H1
H3
E29215
E29214
E29213
1 pole
H7
X
X
H
H2
H6
(a)
(b)
Y
L3
L3
L5
P1
P2
P4
L4
Mounting
On backplate
E21506
2 poles
E29216
1 pole
K1
K
K1
K
G5
G1
G4
T
T4 (c)
On rails
2 poles
U (d)
K1
K
G1
E21510
E29217
1 pole
X
G T
180
Compact NS
Schneider Electric
C1
E21604
E29218
E21601
E21600
Front-panel cutout
B/C
R2
R4(1P)
R5(2P)
R1
C3
C2
P5
P6
X
C2
C3
E21608
E21609
With escutcheon
C7
X
C6
Y
R6
R7
P6
Z
Dimensions (mm)
Type
NS100/160/250
C
29
C1
76
C2
54
C3
108
C6
43
C7
104
G
62.5
G1
125
G4
70
G5
140
H
80.5
Type
NS100/160/250
H1
161
H2
94
H3
188
H4
160.5
H6
178.5
H7
357
K
17.5
K1
35
L3
17.5
L4
70
L5
35
Type
NS100/160/250
P1
81
P2
86
P4
111
P5
83
P6
88
R
14.5
R1
29
R2
19
R4
38
R5
73
R6
29
U(d)
32
E22046
Type
R7
T
T4
NS100/160/250
58
6
22
(d) U 20 mm if automatic auxiliary connectors are used
Note.
Door cutout dimensions are given for a device position in the
enclosure where u100 + (h x 5) with respect to the door
hinge.
181
Compact NS
Schneider Electric
Visu function
for Compact NS100 to 630
(combination with Interpact INV)
Dimensions, volumes
Fixed Compact NS100 to 250 with Visu function Interpact INV100 to 250
3 poles
E62427
510
474
4 poles
E62429
140
E62428
(a)
314 for front
connection.
316.5 for rear
connection.
322.5 with
connectors.
(b)
80.5 for front
connection.
83 for rear
connection.
89 with connectors.
138
131
96
86
52,5
35
35
35
140
52,5
35
35
35
215
215
(a)
277,5
X
X
93,7
277,5
X
(b)
178,5 160,5
Y
52,5
52,5
105
140
Mounting on rails
4 poles
E62431
3 poles
E62430
70
35
7 6
35
9 6
17,5
100
70
17,5
100
50
50
22,3
22,3
157,5
157,5
125
125
62,5
62,5
132
E62433A
E62432A
Front-panel cutout
86
65,5
84
17,5
115,5
X
76
29
14,5
29
182
Compact NS
Schneider Electric
E62434
110
522,5
717,5
(a)
X
142,5
(b)
240
4 poles
185
E62436
160,4
120
(a)
492.5 for front
connection
493.5 for rear
connection
512.5 with right-angle
terminal extensions
536.5 with edgewise
terminal extensions
532.5 with spreaders
525 with 2-cable
connectors.
(b)
127.5 for front
connection
128.5 for rear
connection
147.5 with right-angle
terminal extensions
171.5 with edgewise
terminal extensions
167.5 with spreaders
160 with 2-cable
connectors.
E62435
3 poles
162
70
45
45
185
70
45
45
45
45
241
241
341
341
70
Z
70
140
185
Mounting on rails
4 poles
E62438
E62437
3 poles
90
45
7 6
90
45
7 6
22,5
22,5
75
75
150
241
33
241
33
200
150
200
100
100
E62440
E62439
Front-panel cutout
110
172
86
127
22,5
177,5
116
41,5
Y
Z
31,5
63
183
Compact NS
Schneider Electric
Dimensions, volumes
Dimensions
4 poles
E21597
E21598
E21599
3 poles
H22
X
H20
H21
H23
Y
L
L2
L12
L11
L1
P33
P32
Z
Front-panel cutouts
R9
R8
E21621
E21612
E21614
E21813
C23
C11
C17
C22
Y
R14
R15
C16
C13
P45
P45
R33
R34
E22046
Note.
Door cutout dimensions are given for a device position in the
enclosure where u100 + (h x 5) with respect to the door
hinge.
184
Compact NS
Schneider Electric
Dimensions (mm)
Type
NS100/160/250N/H/L
NS400/630N/H/L
C11
103
155
C13
84
84
C16
56
116.5
C17
42.5
56
C22
29
41.5
C23
76
126
H20
62.5
100
H21
97
152
H22
45.5
83
H23
73
123
L
52.5
70
L1
105
140
Type
NS100/160/250N/H/L
NS400/630N/H/L
L2
140
185
L11
91
123
L12
45.5
61.5
P32
178
250
P33
143
215
P45
145
217
R8
74
90
R9
148
180
R14
48.5
64.5
R15
97
129
R33
74
91.5
R34
148
148
185
Compact NS
Schneider Electric
Rotary handle
for Compact NS100 to 630
Dimensions, volumes
E21625
E21627
3 poles
E21626
L12
60
H23
X
60
H24
DD
H20
60
(a) sans se
(b) avec se
(c) avec se
DD
60
X
O
L15
P34
P35 (a)
Z
L2
L
L11
L1
P36 (b)
P37 (c)
Front-panel cutouts
Fixed or plug-in circuit breaker
E21615
E21613
E21805
Vigicompact
E21614
Compact
C23
C23
C22
C4
C22
Y
R14
R15
P43
Z
C5
Y
Z
P43
R28
R26
R14
R15
E21620
E21622
E21813
Vigicompact
E21618
Compact
C11
R9
R8
C17
C11
C17
C16
C13
P44
Z
Y
Y
R8
R33
P44
Z
R9
An escutcheon is mandatory
R34
186
Compact NS
Schneider Electric
E21632
L8
E21634
E21633
L7
L12
H24 H10
X
G38
H9
1 to 3 maxi
P422
G39
Y
K14
K15
E21628
E21629
L14
L13
E21630
L12
10
60
I
H24 H26
H25
60
Y
P38
E21631
Front-panel cutout
45
L12
T7
H24
X
T6
G36
G37
Dimensions (mm)
Type
NS100/160/250N/H/L
NS400/630N/H/L
C4
C5
86
37
147,5 37
C11
103
155
C13
84
84
C16 C17
55
42,5
116,5 56
C22
29
41,5
C23
76
126
G36
36
36
G37
72
72
G38
41
51
G39
100
145
H9
60
83
H10
120
160
H20
28
40
H23
73
123
H24
9
24,5
Type
NS100/160/250N/H/L
NS400/630N/H/L
H25
37,5
37,5
H26
75
75
K14
50
72,5
K15
100
145
L
52,5
70
L1
105
140
L2
140
185
L7
69
85
L8
120
160
L11
91
123
L12
9,25
5
L13
37,5
37,5
L14
75
75
L15
55
66,5
P34
121
145
P35
155
179
P36
156
180
Type
NS100/160/250N/H/L
NS400/630N/H/L
P37
164
188
P43
89
112
P44
123
147
R1
29
29
R8
74
90
R9
148
180
R14
48,5
64,5
R15
97
129
R26
14,5
32
R33
74
91,5
R34 T6 T7
148
4,2
50
148
4,2
50
187
Compact NS
Schneider Electric
Indication
and measurement modules
for Compact NS100 to 630
Dimensions, volumes
Dimensions
Circuit breaker with current-transformer module
E21516
E21517
X
H9 H11 H13 H15
P1
P2
P47
P1
P2
P4
Mounting
4 poles
K1
E21519
E21518
On backplate
2 poles or 3 poles
K1
K1
K1
G7
K1 K1
K2
K
G9
G1
X
G
G8
G6
T
T4 (d)
U (e)
G7
4 poles
K1
K
E21521
E21520
On rails
2 poles or 3 poles
K2
K
G1
X
X
G
G6
T
188
Compact NS
Schneider Electric
Front-panel cutout
Circuit breaker with ammeter module and voltage-presence indicator
E21673
E21674
T8
C30
C1
C
C28
C27
T8
E21677
E21678
Y
R
R1
R16
R17
P6
C30
C23
C22
C28
C27
Y
R16
R17
R14
R15
P43
Z
Dimensions (mm)
Type
NS100/160/250N/H/L
NS400/630N/H/L
C
28
41.5
C1
76
116
C22
28
41.5
Type
NS100/160/250N/H/L
NS400/630N/H/L
H11
263
385
H12 H13
235.5 396
340
580
Type
NS100/160/250N/H/L
NS400/630N/H/L
R14
48.5
64.5
R15
97
129
R16
46.5
64.5
C23
76
126
C27
56.5
56.5
C28 C29
124
30
185.5 30
C30
78.5
122
G
62.5
100
G1
125
200
G6
G7
137.5 200
200
300
G8
G9
145
215
213.5 327
H8
H9
155.5 236
227.5 355
H10
169
242.5
H14 H15
253.5 432
337
574
K
17.5
22.5
K1
35
45
K2
70
90
P1
81
95.5
P2
86
110
P4
P6
111(1) 88
168
112
P43
89
112
P48
128
154
R1
29
63
R17
93
93
T4
22
32
U(2)
32
32
T
6
6
P47
137
162
R
14.5
31.5
189
Compact NS
Schneider Electric
Front accessories
for Compact NS100 to 630
Dimensions, volumes
Protection collar
E21637
E21635
E21636
.
.
E21640
E21638
52,4
91
53
35
E21653
E21654
E21655
Toggle cover
M8
D3
A3
Front-panel escutcheons
E21643
E21641
E21642
For toggle
M3
M2
A1
D1
D2
E21646
E21645
E21644
64
79
3,5
69
190
Compact NS
6,5
Schneider Electric
Front-panel escutcheons
E21647
E21649
E21648
M6
M7
A2
D1
D2
E21650
E21652
E21651
93,5
80,5
157
3,5
6,5
Dimensions (mm)
Type
NS100/160/250N/H/L
NS400/630N/H/L
A
91
123
A1
69
102
A2
157
189
A3
94
35
D
35
134
191
D1
3.5
3.5
D2
6.5
6.5
D3
40
60
Compact NS
M
73
123
M2
115
155
M3
102
142
M6
114
164
M7
101
151
M8
94
134
Schneider Electric
Dimensions,
volumes
Manual control
E47973A
E47972B
Front connection
(1)
163,5
327
254
508
200
100
107,5
99,5 (3P)
169,5 (4P)
205
99,5
E47914A
Rear connection
105 (3P)
175 (4P)
105
188
94
E47913A
123
105
234
113
92,5
117
210
123
35
107,5
70
140,5
146,5
14
205
Electrical control
E47897A
105
188
94
E47896A
123
105
210
234
200
117
100
123
F : Datum
107,5
35
169,5
70
99,5 (3P)
169,5 (4P)
175,5
F
192
Compact NS
99,5
Note.
Dimensions for front and rear
connection on electrically
operated devices are
identical to those for
manually operated devices.
Schneider Electric
Mounting
Front connection
On rails
On backplate
E47898A
4 6,5
E47899A
4 6,5
200
100
100
99,5 (3P)
169,5 (4P)
99,5 (3P)
169,5 (4P)
200
99,5
99,5
Rear connection
On backplate or rails
3P
4P
4 6,5
6 6,5
Y
E47970A
E47969A
106
106
44
44
234
44
106
234
44
106 117
117
35
35
70
70
70
100
100
270
200
Note.
Mounting parameters for electrically operated devices are identical to those for manually
operated devices.
X and Y are the symmetry planes for a 3-pole device
Z is the back plane of the device.
193
Compact NS
Schneider Electric
Dimensions,
volumes
124 mini
(1) (2)
Door cutout
A
150
(2)
E59201B
(A)
(B)
(C)
E47901A
E59368
Toggle control
194 mini
194 mini
201 (1)
216 (1)
266 (2)
100,5 (1)
108 (1)
133 (2)
90,5 (1)
107,5
194 (1)
244 (2)
140,5
146,5
97 (1)
122 (2)
181 (1)
E59200A
194 mini
Y
119 (1)
144 (2)
95,5 (1)
108 (2)
35,5 (1)
60,5 (2)
71 (1)
121 (2)
Electrical control
(A)
150 mini
(1) (2)
E47901A
E59369
Door cutout
A
194 mini (3P)
264 mini (4P)
194 mini
216 (1)
266 (2)
108 (1)
133 (2)
107,5
194 (1)
244 (2)
169,5
175,5
97 (1)
122 (2)
194
Compact NS
Schneider Electric
Rotary handle
(A)
(B)
(D)
180 mini
(2)
60
E47955A
E47954
195
R80
24
60
25
107,5
154,5
160,5
189,5
229,5
194 mini
E47956A
B
E47957
E47901A
Door cutout
A
194 mini
194 mini
201 (1)
216 (1)
266 (2)
201 (1)
100,5 (1)
100,5 (1)
108 (1)
133 (2)
194 (1)
244 (2)
90,5 (1)
90,5 (1)
97 (1)
122 (2)
130 (1)
181 (1)
Door cutout
E47960A
E47959A
E47958A
Y
60
51
R100
25,5
X
60
212,5
24
24
5
25
25
25,5
605,5 maxi
F
F : Datum
51
Note.
X and Y are the symmetry planes for a 3-pole device
Z is the back plane of the device.
195
Compact NS
51
Schneider Electric
Dimensions,
volumes
Dimensions
Electrical control
210
mini
E59370B
E47943B
210
mini
127,5 (3P)
197,5 (4P)
E47944A
Manual control
160,5
188
94
Y
70 (*)
46 (*)
199
X
45,5
69
5
123
60 mini
90 (3P)
160 (4P)
60 mini
F
90
Mounting
Vertical on uprights or backplate
E47937A
E47945
E47175B
4 6,5
6 6,5
X
25
24
150
50
25 100
100
216
231
F
90 (3P)
160 (4P)
90
109 (3P)
179 (4P)
109
Cutouts
170 mini (3P)
240 mini (4P)
E47177B
Door cutout
230 mini
259 (1)
303 (2)
234
117
109 (1)
130,8 (2)
161 (1)
183 (2)
102,5 (3P)
172,5 (4P)
102,5
259 (1)
307 (2)
Note.
X and Y are the symmetry planes for a 3-pole device.
196
Compact NS
Schneider Electric
Rotary handle
Direct rotary handle
Dimensions
210
mini
E47963A
E47962A
Y
136 (*)
60
R80
X
93
60
24
60 mini
25
E47964B
Door cutout
170 mini (3P)
240 mini (4P)
230 mini
259 (1)
303 (2)
X
109 (1)
130,8 (2)
259 (1)
307 (2)
161 (1)
183 (2)
Door cutout
E47966A
R200
51
E47967A
E47965A
E47966A
Y
60
25,5
24
60
509 maxi
51
24
5
25
25
25
25,5
51
Note.
X and Y are the symmetry planes for a 3-pole device
197
Compact NS
Schneider Electric
Dimensions,
volumes
Dimensions
145 mini
Y
E59440A
E59439
(A)
(B)
(C)
165
105
330
150
210
75
20
162
40
169
131
338
180 (3P)
195 (3P) 295 (4P)
310 (4P)
210 (3P)
325 (4P)
160,5
166,5
242
390
180
195
210
E59456A
Mounting on rails
Y
4 12
150
75
195 (3P)
310 (4P)
F : Datum
195
Note.
X and Y are the symmetry planes for a 3-pole device
198
Compact NS
Schneider Electric
Door cutout
A
Y
E59729A
E59457B
216
201
100,5
108
166
173
332
346
E59458A
119
95,9
73
146
Note.
X and Y are the symmetry planes for a 3-pole device
199
Compact NS
Schneider Electric
Dimensions,
volumes
E47684A
E47683A
1
8
3,5
Only one wire per terminal.
60
L4
L3
AD 22
t
Inpu C
24VD
ut
Outp C
24VD
0A
2 6
60
73
+
G2
112
E47691A
G1
75
L4
L3
t
Inpu C
24VD
ut
Outp C
24VD
0A
AD 22
+
G2
G1
E47692A
60
2 6
60
H4
H3
24V
BAT
t
Inpu C
24VD
73
ut
Outp C
24VD H1
112
75
E47693A
H2
H4
H3
24V
BAT
t
Inpu C
24VD
ut
Outp C
24VD H1
H2
200
Compact NS
Schneider Electric
MN delay unit
E47694A
57
1
4 5
81
S
3 6
0.5
10 12
73,5
73
E47695A
66
42
1.5
3
MN
r de R
UV
dateu
Retardelay for
Time
MN
UVR
30 V
100/1C
AC/D
2 4,2
4 5
72
S
3 6
0.5
30 V
100/1C
AC/D
1.5
3
MN
r de R
UV
dateu
Retardelay for
Time
MN
UVR
10 12
46
E47686A
E47685A
ModBus
90
us
modb
CCM
Fault
Com.
58
CE
CD
CT
ss
Addre
.
sync
Disjoncteur
Rseau
shield
B B
A A
B B
A A
Breaker
Network
++
45
54
E47687A
E58561
External sensor
200
90
130
45
F
MDG
45
76
150
58
201
Compact NS
106
Schneider Electric
Dimensions,
volumes
E47699
4 14
GND VN VC
H1
H2
35 76
X2 X1 SG2 SG1
177
208
E47701
8 14
H1
H2
SG1
SG2
X1
X2
GND
VN
VC
44
174
44 127
44
295
E47696
Installation
400/1600 (NS630b to NS1600)
202
Compact NS
Schneider Electric
E47703A
E47704B
4 9
2
M1 M
115
M3
197
215
M1 M2 M3
70
280
362
380
E47717A
E47718B
8 9
146
2
M1 M
242
160
260
M3
M1 M2 M3
70
456
470
552
570
Busbars
Sensor
Weight (kg)
I i 1600 A
I i 3200 A
280 x 115
14
470 x 160
18
Busbars path
470 x 160 window
Busbars spaced 115 mm centre-to-centr
E47708
E47707
M1 M2 M3
M1 M2 M3
2 bars 50 x 10
E67971
E67970
4 bars 100 x 5
M1 M2 M3
M1 M2 M3
2 bars 100 x 5
4 bars 125 x 5
203
Compact NS
Schneider Electric
Dimensions,
volumes
Escutcheon
NS630b to 1600 (fixed control)
C
(C)
E59885A
E59891A
A
(A)
E59886A
275
154
27
27
27
131
27
253
E59892A
E59887A
313
X
27
27
13
27
317
204
Compact NS
Schneider Electric
Compact NS
Connection
Presentation
Functions and characteristics
Installation recommendations
Dimensions, volumes
1
11
143
165
206
208
Bars
Cables with lugs and bare cables
212
215
216
Bars
Cables with lugs
216
218
219
Electrical diagrams
Additional characteristics
Catalogue numbers
205
Compact NS
210
212
221
251
267
Schneider Electric
Compact NS80H-MA,
NSC100N and NSA160
Connection
E21877
E21878
Compact NS80H-MA
97
48,5
Y
29,2 29,2
32
Z
Compact NSC100N
34,5
30
E43406
E43405
30
48,5
X
48,5
34,5
45
83
90
Z
30
30
30
30
E21900
30
E62454
E21898
Compact NSA160
44
44
X
53
53
45
90
34,5
45
34,5
120
83
Z
206
Compact NS
Schneider Electric
30
60,8
30
4 poles
30
30
E43407
E62455
Bottom connection
3 poles
30
30
30
60,8
30
30
30
30
incoming
incoming
outgoing
outgoing
30
60,8
30
incoming
4 poles
30
30
30
E43408
E62456
Top connection
3 poles
outgoing
30
30
60,8
30
incoming
30
30
30
outgoing
207
Compact NS
Schneider Electric
Compact, Vigicompact
NS100 to 630 (fixed version)
Connection
P21
P13
E21747
E21748
Connection dimensions
G4
X
G5
G19
Y
Z
K1
K1
K1
Front connection
Terminals
NS100/160/250
E21554
10,5
E21750
NS400/630
Z
E35578
14
70
113,5
Connectors
NS100/160/250
E21751
E21553
E21752
NS400/630
Z
19
Z
46,5
14
70
113,5
113,5
X
X
Rear connection
NS400/630
10
8,6
E21756
E21755
E21561
NS100/160/250
20
15
13
23,2
13
18
14
30
70
43 short RC
88 long RC
50 short RC
115 long RC
X
Z
113,5
Z
208
Compact NS
Schneider Electric
NS100/160/250
4
E21556
E21563
37,5
39,5 (b)
41 Z
E35577
20,5
70
70
E35580
Z
X
30
E21754
NS400/630
E21758
NS400/630
8
61
View F
58
42
Z
34
8
113,5
113,5
X
E21557
E21565
E21558
Spreader
K10
K8
K8
K8
K9
K8
K8
G27
X
G26
E21566
70
X
41
64,5
66,5 (b)
Dimensions (mm)
Type
NS100/160/250N/H/L
NS400/630N/H/L
G4
70
113.5
G5
140
227
G19
215
327
G26
30
39
52,5
G27
41
54
67,5
K1
35
45
K8
45
52.5
70
K9
159
187.5
240
K10
114
135
170
P13
P21
19.5(1)
26
44
Note.
For dimensions of conductors, see pages 00 to 00
209
Compact NS
Schneider Electric
Connection
K1
E21569
E21570
K1
Front connection
Terminals
NS400/630
With spreaders
E21939
E21571
NS100/160/250
Mounting on backplate or on rails (1)
(*)
E21572
P21
42
P21
Z
G32
G31
195,5
210,5
G32
G31
Connectors
NS400/630
With spreaders
94
E21941
NS100/160/250
Mounting on backplate or on rails (1)
(*)
68
Z
E21580
E21581
P28
Z
G31
G32
202
G34
210
Compact NS
Schneider Electric
E21583
Connectors
NS100/160/250
Mounting through backplate or on rails
E21942
(*)
NS400/630
109
83
P29
P30
E21582
G32
G34
66
94
Rear connection
E21574
E21573
P22
P23
G35
P24
P25
G33
E21577
Mounting on backplate
Right-angle extensions (mounted down and out)
P26
P27
E21576
(*)
G33
X
E21579
(*)
P26
P27
E
G35
Dimensions (mm)
Type
NS100/160/250N/H/L
NS400N/H/L
NS630N/H/L
E
4
6
6
G31
108.5
171
181
G32
100
156.5
166.5
G33
63.5
104
104
G34
110
211
G35
80.5
129
129
K1
35
45
45
P21
19
26
26
Compact NS
P22
75.5
114.5
124.5
P23
67
100
110
P24
49
82
92
P25
57.5
96.5
104.5
P26
75.5
108.5
108.5
Connection
E47905A
E47904A
70
70
70
E47918A
15
123
67,5
N
44
E47201B
X
67,5
Y
25
9,5 12,5
123
60
15
12,5
31
2 11
E47908A
E47919A
E47907A
43,5
70
70
15
View A
97
E47205B
97
60
12,5
9,5
12,5
31
44
25
2 11
View A detail
70
163,5
129
70
70
30
E47911B
E47916A
E47910A
Front connection
Y
View A
163,5
16,5
E47971A
Top terminal
129
44
9,5
25
15
2 vis M10
15
Bottom terminal
2 vis M10
25
44
15
15
9,5
View A detail
Note.
Recommended connection screws: M10 class 8.8
Tightening torque: 50 Nm with contact washer
212
Compact NS
Schneider Electric
E47922A
E47920A
E47921A
70
25
25
196
181
15
Y
View A
E47923A
X
181
196
95
95
70
95
70
70
12,5
31,5
12,5
15
Y
View A
98
95
E47926A
E47924A
E47925A
70
70
123
15
15
82,5
52,5
Y
E47927A
123
83
95
95
70
95
70
70
12,5
12,5
Spreader detail
25
38,5
13,5
25
13,5
15
5 11
13,5
38,5
=
13,5
=
30
30
82 52
15
77
25
30
82 52
15
5 11
82 52
15
5 11
5 11
25
25
52
38,5
25
30
82 52
77
77
77
38,5
E47234A
25
25
52
52
52
View A detail
F : Datum
Note.
X and Y are the symmetry planes for a 3-pole device.
213
Compact NS
Schneider Electric
Connection
Bars
E47930A
E47929A
70
70
70
15
View A
200
430
200
E47218A
E47928A
25
89
= =
12,5
21 (1)
101
15
21
3 11
10
62,5
15
20
View A detail
Note.
(1) two mounting possibilities for vertical-connection adapters
(pitch 21 mm).
Recommended connection screws: M10 class 8.8
Tightening torque: 50 Nm with contact washer
214
Compact NS
Schneider Electric
E47932A
E47931A
15
E47933A
70
70
View A
250
200
Y
15
530
E47230A
200
250
184
17
50
50
50
50
80
5 13
5 11
View A detail
15
10
150
F
70
E59204A
E59202A
E59203A
70
199
206,5
N
398
413
199
206,5
E59205A
4 21,5
26 63
26
54
16,5
35
61
215
Compact NS
Schneider Electric
Connection
Bars
E47181A
E47948A
E47179A
70
70
70
15
67,5
228
N
E47201B
67,5
114
44
25
9,5 12,5
15
267,5
60
F
12,5
2 11
70
E47940A
E47182A
70
15
49
97
E47184A
View A
X
N
E47205B
97
267,5
60
12,5
9,5
12,5
F
44
25
2 11
View A detail
15
12,5
70
E47187A
E47941A
70
View A
70
171
N
X
Top terminal
9,5
12,5
Bottom terminal
44
140
235
336
25
37,9
9,5
2 11
E47188B
E47185A
Front connection
26
83
131
52
26
2 11
25
37,9
9,5
100
44
9,5
View A detail
Note.
Recommended connection screws: M10 class 8.8
Tightening torque: 50 Nm with contact washer
216
Compact NS
Schneider Electric
E47225A
E47952A
E47223A
95
70
View A
70
238
223
Y
E47226A
X
207
95
95
70
192
95
70
70
View A
12,5
12,5
250
F
Spreader detail
25
38,5
13,5
25
13,5
15
5 11
13,5
38,5
=
13,5
=
30
30
82 52
15
77
25
30
82 52
15
5 11
82 52
15
5 11
5 11
25
25
52
38,5
25
30
82 52
77
77
77
38,5
E47234A
25
25
52
52
52
View A detail
217
Compact NS
Schneider Electric
Connection
70
70
View A
15
50
E47229A
E47227A
E47953A
15
71
292
21
171
184
583
E47230A
17
140
21
261
50
50
50
50
80
5 13
71
15
5 11
View A detail
50
15
193,5
F
F : Datum
Note.
X and Y are the symmetry planes for a 3-pole device.
Tightening torque: 50 Nm with contact washer
X and Y are the symmetry planes for a 3-pole device
218
Compact NS
Schneider Electric
165
150
E59459A
115
115
E59461A
E59460
115
View A
OFF
150
13
E59462B
OFF
25
76
= =
165
=
=
3 11
View A detail
20
15
E59738A
E59737
E59736A
115
80
115
80
80
230
142,5
Vue A
OFF
142,5
230
4 11
E59735
OFF
25
60 100
25
25
25
20
40
20
12,5
45
20
15
25 25
60
80
View A detail
E59740
230
115
115
E59741A
E59739A
115
142,5
Z
230
E59735
142,5
25
60 100
25
25
20
25
45
40
60
Note.
Recommended connection screws: M10 class 8.8
Tightening torque: 50 Nm with contact washer
View A
4 11
OFF
OFF
20
12,5
20
15
25 25
80
View A detail
219
Compact NS
Schneider Electric
220
Compact
Schneider Electric
Electrical diagrams
Compact NS
Presentation
Functions and characteristics
Installation recommendations
Dimensions, volumes
Connection
221
1
11
143
165
205
222
Indication contacts
Early-make contacts
222
223
Compact NSA160
224
Indication contacts
224
226
Indication contacts
Motor mechanism (automatic reset)
Motor mechanism (local reset)
Early-make contacts
Motor protection - Trip unit STR22/43ME
226
228
232
234
236
240
240
242
244
244
246
Additional characteristics
Catalogue numbers
251
267
Compact
248
Schneider Electric
Compact NSC100
Compact NS80H-MA
Indication contacts
Electrical diagrams
The diagram is shown with circuits deenergised, all devices open, connected and
charged and relays in the normal position.
With OF1 and CAF1/CAF2
C1
92
94 12
12
RD
WH
14
14
E43822
E43821
D1
VT
YE
OF1
CAO1
OF1
CAF2
CAF1
trip unit
MN (1)
SD
11
11
GY
91
RD
D4 C2
WH
MX
CN1
- CN 1 +
- CN 2
CN2
E43824
With MX
E43823
With MN
CN1
- CN 1 +
CN2
F1
- CN 2
F1
tripping order
tripping order
H1
H1
D1
92
C1
94
92
94
trip unit
trip unit
MX
MN
SD
SD
D4
C2
91
Symbols
Q
Compact NS
SD
trip indication contact
OF
ON / OFF indication contact
MN
undervoltage release
MX
shunt release
CAO early-break contact of rotary handle
CAF early-make contact of rotary handle
XI
terminal block for CAF wiring (must be ordered)
F1
breaker for the protection of MN/MX
H1
lamp signalling tripped position
91
222
Compact NS
Schneider Electric
Early-make contacts
Following tripping due to an electrical fault,
reset must be carried out locally and
manually.
With MN
CN1
- CN1 +
CN2
- CN2
tripping
unit
(1)
X1
RD
BL
WH
RD
D1
WH
WH
E43831
WH
D1 C1
CAF1
CAF2
trip unit
BL
MN
D4
D4
With MN + SD
CN1
- CN1 +
CN2
- CN2
trippinng
order
(1)
X1
D1 C1
RD
BK
WH
BL
94
WH
92
RD
GN
WH
E43830
D1
RD
GN
WH
92
94
CAF1
CAF2
trip unit
MN
SD
91
BL
BL
D4
D4
91
223
Compact NS
Schneider Electric
Compact NSA160
Indication contacts
Electrical diagrams
With OF1
D1
C1
92
94 12
14
E62467
The diagram is shown with circuits deenergised, all devices open, connected and
charged and relays in the normal position.
OF1
CAO1
trip unit
MN (1)
MX
D4 C2
SD
91
11
Symbols
Compact NS
Q
SD
trip indication contact
OF
ON / OFF indication contact
MN
undervoltage release
MX
shunt release
CAO early-break contact of rotary handle
CAF early-make contact of rotary handle
XI
terminal block for CAF wiring (must be ordered)
F1
breaker for the protection of MN/MX
H1
lamp signalling tripped position
Colour code for auxiliary wiring
red
RD
GN
green
BK
black
BL
blue
WH
white
224
Compact NS
Schneider Electric
E43823
With MN
CN1
- CN 1 +
CN2
- CN 2
F1
tripping order
H1
D1
92
94
trip unit
MN
SD
D4
91
E43824
With MX
CN1
- CN 1 +
CN2
- CN 2
F1
tripping order
H1
C1
92
94
trip unit
MX
SD
C2
225
Compact NS
91
Schneider Electric
Electrical diagrams
The diagram is shown with circuits deenergised, all devices open, connected and
charged and relays in the normal position.
D1 C1
82
VT
GN
24
14 22
94 12
92
YE
14 22
24 72
74 82
VT
84
OF2
OF1
YE
84
RD
94 12
RD
YE
GN
CE
92
VT
D1 C1
354
WH
RD
WH
VT
GY
GY
VT
E18916
CAF1
CAF2
CAO1
trip unit
MN (1)
(2)
SDE
MX SD
Id
SDV
91
71
81
BK
GY
GY
BL
21
11
BK
C2
OR
D4
CD
91
11
81
21
RD
WH
C2
GY
D4
351
YE
YE
311
VT
GY
GY
92
VT
GN (3)
24 72
74 82
WH
A2
B2
84
A2
A4
B4
BL
84
OR
24
14 22
94 12
YE
VT
14 22
RD
D1 C1
94 12
RD
CE
92
YE
D1 C1
354
WH
GN
E18917
VT
A4
B4
OF2
OF
MT
trip unit
MN (1)
(2)
SDE
MX SD
BK (3)
Id
71
81
A1
GN
21
BK
11
GY
91
GY
C2
OR
BL
D4
BK
SDV
L1
CD
D4
351
C2
91
A1
21
11
L1
YE
YE
311
11
91
12
92
14
21
94
81
71
A1
22
82
72
L1
24
74
84
E43817
Symbols
Compact NS100 to 250
Q
SD
trip indication contact
SDE fault indication contact
SDV earth-fault indication contact
OF
ON / OFF indication contact
MN
undervoltage release
MX
shunt release
MT
motor-mechanism module
CAO early-break contact of rotary handle
CAF early-make contact of rotary handle
CE
connected-position carriage switch
CD
disconnected-position carriage switch
Colour code for auxiliary wiring
RD
red
GN
green
BK
black
VT
violet
YE
yellow
GY
grey
BL
blue
OR
orange
WH
white
B4
24
A4
22
A2
21
74
72
71
84
82
L1
81
A1
D4
14
94
C2
12
92
D1
C1
11
91
C1
C2
D4
A2
A4
B4
Fixed part
(front view looking into base)
226
Compact NS
Schneider Electric
OF1
OF2
84
RD
GN
92 94 12 14 22 24 32
D1 C1
82
34
VT
VT
YE
24 32
14 22
VT
YE
RD
YE
92 94 12
GN
GN
OR
BK
CE
WH
Z11 e+ T1 D1 C1
VT
RD
YE
WH
VT
VT
GY
GY
E22042
34 72 74 82
84
OF3
CAF1
CAF2
CAO1
SDE
(2)
MX SD
Id
21
31
71
GY
GY
11
GY
C2
BK
OR
91
BL
C2
e- T2 D4
RD
BL
WH
SDV
D4
81
CD
91
11
81
31
RD
WH
21
GY
Z12
351
YE
YE
311
92 94 12 14 22 24 32
D1 C1
OF1
OR
WH
GN (4)
34 72 74 82
BL
A2 A4 B4
84
RD
YE
34
VT
24 32
VT
14 22
YE
RD
94 12
VT
92
GN
GN
OR
BK
CE
WH
Z11 e+ T1 D1 C1
YE
VT
VT
GY
GY
E22043
B2 A2 A4
84
B4
OF3
OF2
MT
SDE
(2)
MX SD
BK (4)
Id
A1
BK
81
GN
71
GY
C2
31
21
11
GY
e- T2 D4
BK
OR
91
BL
C2
GY
D4
RD
BL
WH
SDV
L1
CD
351
Z12
91
11
A1
31
21
L1
YE
YE
311
11
91
12
14
92
94
21
81
A1
22
82
L1
24
84
31
71
Z11
32
72
e+
34
E43817
Symbols
Compact NS100 to 250
Q
SD
trip indication contact
SDE fault indication contact
SDV earth-fault indication contact
OF
ON / OFF indication contact
MN
undervoltage release
MX
shunt release
MT
motor-mechanism module
CAO early-break contact of rotary handle
CAF early-make contact of rotary handle
CE
connected-position carriage switch
CD
disconnected-position carriage switch
Colour code for auxiliary wiring
RD
red
GN
green
BK
black
VT
violet
YE
yellow
GY
grey
BL
blue
OR
orange
WH
white
74
T2
24
_
e
_
e
T1
22
e+
Z12
21
Z11
B4
D1
C1
C2
D4
A2
A4
B4
Fixed part
(front view looking into base)
Z12 T1 R1 T2 R2
34
A4
32
A2
31
74
72
71
84
82
81
D4
14
94
L1
C2
12
92
A1
D1
C1
11
91
227
Compact NS
Schneider Electric
The diagram is shown with circuits deenergised, all devices open, connected and
charged and relays in the normal position.
Electrical diagrams
- CN1 +
CN1
CN2
- CN2
F1
H2
H1
82
WH
RD
WH
D1
GN (1)
84
B2
OR
A2
D1
A2
A4
B4
BL
tripping
order
(2)
A4
B4
Q
MT
trip unit
SDE
MN
81
D4
A1
GN
D4
BK
BL
BK (1)
A1
L1
L1
E43826
- CN1 +
CN2
- CN2
F1
H1
O
H2
82
B2
A2
A4
B4
BL
OR
GN (1)
84
WH
RD
A2
A4
B4
MT
trip unit
SDE
81
A1
A1
GN
BK (1)
BK
Symbols
Compact NS100 to 630
Q
SDE fault indication contact
MT
motor-mechanism module
F1
breaker for protection of motor-mechanism module circuits
H1
lamp signalling an electrical fault
H2
lamp signalling motor mechanism in manual position
F
closing order
O
opening order
orders must not be simultaneous
(must be > 150 ms)
Colour code for auxiliary wiring
red
RD
GN
green
BK
black
BL
blue
OR
orange
WH
white
L1
L1
228
Compact NS
Schneider Electric
E43827
CN1
CN2
- CN2
F1
H1
O
H2
82
B2
A2
A4
B4
BL
GN (1)
84
OR
WH
RD
A2
A4
B4
MT
trip unit
SDE
81
BK
A1
GN
BK (1)
A1
L1
L1
E43839
Controlled by relay
locked by
tripping
order
locked by
tripping
order
B2
A2
A4
B2
B4
A2
A4
B4
MT
MT
82
82
81
Without auxiliary
Controlled by switch
81
E43840
E43841
Controlled by relay
B2
A2
A4
B4
B2
MT
82
A2
A4
B4
MT
81
82
229
Compact NS
81
Schneider Electric
The diagram is shown with circuits deenergised, all devices open, connected and
charged and relays in the normal position.
Electrical diagrams
- CN1 +
CN1
CN2
- CN2
F1
O
H2
tripping
order
(3)
84
84
BL
(1)
82
OR
WH
RD
D1
A2 A4 B4
WH
D1
B2 A2 A4
B4
Q
MT
trip unit
(2)
SDE
MN
BK
BL
A1
GN
81
D4
A1
D4
L1
L1
E43835
CN1
CN2
- CN2
F1
O
H2
tripping
order
(3)
(1)
82
84
B2
OR
WH
WH
RD
C1
A2
A4
B4
A4
B4
230
MT
trip unit
(2)
SDE
C2
Compact NS
81
A1
A1
GN
C2
BK
MX
OR
A2
BL
84
C1
L1
L1
Schneider Electric
E43836
- CN1 +
- CN2
CN2
F1
H2
(1)
82
84
B2
A4
OR
WH
RD
A2
A2
B4
BL
84
A4
B4
Q
MT
trip unit
SDE
A1
GN
81
BK
(2)
A1
L1
L1
E43915
Controlled by relay
A2
A4
R
locked by
tripping
order
locked by
tripping
order
B2
A2
A4
B4
B2
MT
B4
MT
81
81
Without auxiliary
Controlled by switch
E43916
E43917
Controlled by relay
A2
A4
B2
A2
A4
B2
B4
B4
MT
MT
81
81
231
Compact NS
Schneider Electric
The diagram is shown with circuits deenergised, all devices open, connected and
charged and relays in the normal position.
Electrical diagrams
- CN1 +
CN1
CN2
- CN2
F1
H1
H2
WH
RD
WH
D1
82
84
BL
A2 A4 B4
84
D1
OR
tripping
order
B2 A2 A4
B4
Q
MT
trip unit
SDE
(2)
MN
BL
A1
GN
81
D4
BK
(1)
A1
D4
L1
L1
E43919
CN1
CN2
- CN2
F1
H1
WH
RD
D1
82
84
BL
A2 A4 B4
84
D1
WH
H2
OR
tripping
order
B2 A2 A4
B4
Q
MT
trip unit
MX
SDE
(2)
D4
232
Compact NS
81
A1
A1
GN
BL
D4
BK
(1)
L1
L1
Schneider Electric
E43920
- CN1 +
CN2
- CN2
F1
H1
H2
84
BL
WH
RD
82
OR
A2 A4 B4
84
B2 A2 A4
B4
Q
MT
trip unit
SDE
(2)
A1
A1
GN
81
BK
(1)
L1
L1
E43844
E43845
With MN/MX
locked by
tripping
order
locked by
tripping
order
B2
A2
A4
B2
B4
A2
A4
B4
MT
MT
81
81
Without auxiliary
Controlled by switch
E43913
E43912
Controlled by relay
B2
A2
A4
B4
B2
MT
A2
A4
B4
MT
81
81
233
Compact NS
Schneider Electric
Electrical diagrams
With MN
E43831
CN1
- CN1 +
CN2
- CN2
tripping
order
(1)
X1
RD
BL
WH
RD
D1
WH
WH
WH
The diagram is shown with circuits deenergised, all devices open, connected and
charged and relays in the normal position.
D1 C1
CAF1
CAF2
trip unit
BL
MN
D4
D4
Symbols
Q
Compact NS
SD
trip indication contact
MN
undervoltage release
CAF early-make contact of rotary handle
XI
terminal block for CAF wiring
(must be ordered)
Colour code for auxiliary wiring
red
RD
GN
green
BK
black
BL
blue
WH
white
234
Compact NS
Schneider Electric
E43830
With MN + SD
CN1
- CN1 +
CN2
- CN2
trippinng
order
(1)
X1
D1 C1
RD
BK
WH
BL
94
WH
92
RD
GN
WH
D1
RD
GN
WH
92
94
CAF1
CAF2
trip unit
MN
SD
91
BL
BL
D4
D4
91
235
Compact NS
Schneider Electric
Electrical diagrams
The diagram is shown with circuits deenergised, all devices open, connected and
charged and relays in the normal position.
E28434
Thermal-fault indication
CN1
- CN1 +
CN2
- CN2
F1
D1
WH
BP1
13
97
KA1
14
43
KA1
44
trip unit
SDTAM
BL
98
D4
A1
KAI
X1
H1
A2
X2
Symbols
Q
F1
SDTAM
BP1
KA1
236
Compact NS
Schneider Electric
E28435
Automatic operation
overload
SDTAM
I
O
I
O
BP1
H1
Q
tr
I
O
I
O
I
O
IQ
tr
overload (long-time) protection tripping time
overload
current greater than Ir (long-time tripping threshold)
IQ
closing order for circuit breaker Q
Note.
For a short-circuit or earth fault, only circuit breaker Q opens.
The above automatic control sequence is not run.
Legend
c O: OFF (circuit open)
c I: ON (circuit closed)
c
: either ON or OFF
237
Compact NS
Schneider Electric
Electrical diagrams
The diagram is shown with circuits deenergised, all devices open, connected and
charged and relays in the normal position.
E43828
- CN1 +
CN2
- CN2
F1
WH
D1
97
21
42
Q
BP1
KA1
22
KA1
44
trip unit
SDTAM
(1)
BL
98
D4
E1
A1
A1
KA1
KM1
KM1
A2
KA2
X1
H1
A2
X2
E2
Symbols
Q
F1
SDTAM
BP1
KA1
238
Compact NS
Schneider Electric
E28437
Automatic operation
I
overload
tr
SDTAM
O
I
BP1
O
I
H1
O
I
KM1
O
I
Legend
c O: OFF (circuit open)
c I: ON (circuit closed)
c
: either ON or OFF
E43829
- CN1 +
CN2
- CN2
F1
D1
BP1
D4
E4
RHK
12 11 14
22 21 24
(1)
A1
X1
H1
KM1
A2
X2
239
Compact NS
Schneider Electric
Electrical diagrams
The diagram is shown with circuits deenergised, all devices open, connected and
charged and relays in the normal position.
Control unit
Z5
A4
C2
MN
BPF
B4
BPO
D2
Z5
Z4
Z3
Z2
Z1
AT
A2
Z4
Z1
downstream cb
Z5
Z4
L3
Z3
upstream cb
L2
Z2
L1
Z1
Z3
power
Remote operation
Z2
Power
motor-mechanism
module
MX
Micrologic
(basic) A
Control unit
E1-E6 communication
A1
C1
Remote operation
D1
F2+
T4/F1
T3
X2
T2
X1
24 V DC
MN
or
MX
undervoltage release
shunt release
SG2
SG1
T1/M3
M2
M1
E59040B
E59041A
or
CN1
- 440/480 V
9 11
R
A4
A2
B4
A1
CN2
240
Compact NS
- 440/480 V
Schneider Electric
E59296A
Indication contacts
MN/MX
512
F1 F2
M1M2 M3
Z1 Z2 Z3 Z4 Z5
T1 T2 T3 T4
OF1
D1/C1
D2/C2
514
522
524
532
open
534
94
542
closed
544
fault
92
84
82
fault
14
22
24
32
34
12
closed
open
E6 E5 E4 E3 E2 E1
OF2
OF3
SD
531
Indication contacts
SDE
CAF2/CAF1
early-make contact
(rotary handle)
CAO2 / CAO1
E59044A
indication contacts
91 92 94
541
511
81
82
521
532
542
512
522
534
544
514
524
84
SDE
SD
31 32 34
CAO1
21 22 24
511
CAO2
521
CAF1
531
CAF2
541
SD
81
11
SDE
91
OF1
21
OF2
31
OF3
11 12 14
E6 E5 E4 E3 E2 E1
MN/MX
F1 F2
M1M2 M3
Z1 Z2 Z3 Z4 Z5
T1 T2 T3 T4
D1/C1
D2/C2
early-break contact
(rotary handle)
81
31
21
11
82
32
22
12
84
34
24
14
B4 A4 A2 A1
241
Compact NS
Schneider Electric
Electrical diagrams
The diagram is shown with circuits deenergised, all devices open, connected and
charged and relays in the normal position.
Z5
A4
C2
Q
MN
BPF
B4
BPO
D2
Z5
Z4
Z3
Z2
Z1
AT
A2
Z4
Z3
Z1
downstream cb
Z5
L3
Z4
upstream cb
L2
Z3
L1
Z2
Z1
E59730A
power
Remote operation
E59037B
Control unit
Z2
Power
motor-mechanism
module
MX
Micrologic
Com UC1
UC2
E5 E6 Z5 M1 M2 M3
A1
24 V DC
Control unit
Terminal-block marking
C1
D1
F2+
T4/F1
T3
X2
T2
X1
SG2
SG1
T1/M3
M2
M1
or
Remote operation
UC3
MN / MX
F2+
D2
MT2
C2
MT1
A4
A2
E3 E4 Z3 Z4 T3 T4
E1 E2 Z1 Z2 T1 T2
(basic) A
F1
D1
Control unit
C1
A1
Remote operation
MN
or
MX
undervoltage release
shunt release
B4
CN1
- 440/480 V
9 11
R
A4
A2
B4
motor-mechanism
module
A1
CN2
242
Compact NS
- 440/480 V
Schneider Electric
E47074A
912
914
314
312
324
322
334
332
CT1
Indication contacts
CE1
911
CE2
311
CE3
CD1
821
511
521
531
541
91
81
11
21
31
814
CAO1
CD2
CAF2 CAF1
812
824
822
512
514
524
532
522
CAO2
CAF1
Test
321
CAF2
connected
disconnected
open
534
542
SD
SDE
closed
544
94
92
fault
331
OF1
84
82
12
14
22
OF2
fault
811
OF3
closed
24
32
34
open
E46134A
E47075A
Carriage switches
E59295A
Indication contacts
Carriage switches
SDE
SD
CAO2 CAO1
OF3
OF2
OF1
CD2
CD1
CE3
CE2
CE1
CT1
544
534
84
94
524
514
34
24
14
824
814
334
324
314
914
542
532
82
92
522
512
32
22
12
822
812
332
322
312
912
541
531
81
91
521
511
31
21
11
821
811
331
321
311
911
Indication contacts
Carriage switches
CD2 : disconnected CE3 : connected CT1 : test
CD1 position
CE2 position
position
CE1
indication contacts
SDE
SD
CAF2/CAF1
early-make contact
(rotary handle)
CAO2 / CAO1
early-break contact
(rotary handle)
Legend
Connected
(only one wire per connection point)
243
Compact NS
Schneider Electric
Electrical diagrams
E59303
L2
914
manual
operation
L3
Z5
Z4
Z3
Z2
912 812
314
SDE
OF
SD
SDE
911
811
CT
device
communication
module
Micrologic
CD
CE
CE
Digipact
COM craddle
BB
BB
B' A' B A
E6
E5
E4
E3
E2
E1
F2+
T4/F1
T3
T2
T1/M3
311
CD
CT
+
+
(2)
CCP 303
M2
811
911
Modbus
COM craddle
shield
311
B'
A'
B
A
M1
312
closing order
OF
Z1
812
opening order
BB
BB
CCP 303
5
4
H1 H2
Modbus
junction
block
CJB306
BAT
module
(1)
H3 H4
(2)
E1 E2 E3 E4
+
A B
+
/
/
E3 / E4
E5 / E6
L3 L4
110/240 V AC
24/125 V DC
blue
white
yellow
brown
red
AD
module
black
G1 G2
Digipact
junction
block
E5 E6
A' B'
Modbus
BB BB + Digipact
twisted pair
twisted pair
24 V
0V
0V
24 VDC
1A
communication
power supply
24 V
24 VDC
DC 150
None of the control-unit protection functions require an auxiliary source. However, the 24 V DC external power supply (AD module) is
required for certain operating configurations as indicated in the table below.
Circuit breaker
Fonction protection
Display function
Circuit-breaker status indications and control
communications bus
Closed
Open
no
no (3)
no
no
yes
no
The communications bus requires its own 24 V DC power source (E1, E2). This source is not
the same as the 24 V DC external power-supply module (F1-, F2+).
If the 24 V DC external power supply (AD module) is used, the maximum cable length between
the 24 V DC external power supply (G1, G2) and the Micrologic control unit (F1-, F2+) is ten
metres.
The BAT battery module, mounted in series upstream of the AD module, ensures an
uninterrupted supply of power if the AD module power supply fails.
244
Compact NS
Schneider Electric
CDM303 + CSD309
E47976
d < 1 km
DMB300
2
3
4
CCP303
switchboard
display unit
1
0
24 V
0V
Modbus
junction
block
CJB 306
24 VDC
1A
power circuit
breaker
Communicating switchboard
E59304
Software
PC running
PC running
Micrologic utilities
SMS
Micrologic utilities
SMS
PLC
PLC
TCP/IP
Communication
interface
RS 232C
Ethernet
RS 485
RS 485
Bus Modbus
communication
Bus
Data
concentrator
Bus Modbus
DC150
Device
UA150
source
change-ower
SC150
contraf
interface
PM150
measure
Compact
COM Digipact
Compact
COM Modbus
Digipact Bus
PM300
measure
Sepam
Vigilohm
Altivar
Modbus Bus
245
Compact NS
Schneider Electric
Electrical diagrams
Z4
Z5
Z3
F1 /T4
L3
Z2
L2
T3
L1
Z1
Q
I
H2
F2+
T2
M3/T1
M2
Micrologic 6
M1
E59305A
SG1
SG2
X1
X2
H1
GND
Z4
F1 /T4
Z5
Z3
T3
Z1
Z2
Q
I
E59306
H1
246
H2
X1
12 5
1
3
X2
MDGF module
13 14
F2+
T2
M3/T1
M2
M1
Micrologic 6
10 11
9
8
PE
Compact NS
Schneider Electric
Earth-leakage protection
Z4
Z5
Z3
F1 /T4
L3
Z2
L2
Z1
L1
T3
E59307A
Q
I
Micrologic 7
F2+
T2
M3/T1
M2
M1
M1
M2
M3
Neutral protection
c Three pole circuit breaker:
v neutral protection is impossible.
c Four pole circuit breaker:
v Compact equipped with Micrologic A
v the current transformer for external neutral is not
necessary.
E47975B
Z1
Z2
Z3
Z4
Z5
tsd = 0,3
fault 1
Z1
Z2
Z3
Z4
Z5
tsd = 0,2
fault 2
Z1
Z2
Z3
Z4
Z5
downstream
circuit breaker
Z1
Z2
Z3
Z4
Z5
247
Compact NS
Schneider Electric
Electrical diagrams
The diagram is shown with circuits deenergised, all devices open, connected and
charged and relays in the normal position.
Control unit
Z5
Z4
Z1
downstream cb
Z5
Z4
L3
Z3
upstream cb
L2
Z2
L1
Z1
Z3
power
Remote operation
Z2
Power
C2
D2
Z5
Z4
Z3
Z2
Z1
AT
MN
MX
Micrologic
E1-E6 communication
C1
Remote operation
D1
F2+
T4/F1
T3
X2
T2
X1
24 V DC
Control unit
(basic) A
c
SG2
SG1
T1/M3
M2
M1
E59040B
E59463A
or
MN
or
MX
undervoltage release
shunt release
248
Compact NS
Schneider Electric
Terminal-block marking
E59465A
E59464A
Indication contacts
fault
F1 F2
M1M2 M3
Z1 Z2 Z3 Z4 Z5
T1 T2 T3 T4
94
92
84
82
12
fault
14
22
closed
24
32
34
open
E6 E5 E4 E3 E2 E1
MN/MX
OF1
D1/C1
D2/C2
OF2
OF3
SD
21 22 24
31 32 34
91 92 94
SD
91
11
SDE
81
OF1
21
OF2
31
OF3
11 12 14
81
82
84
SDE
Indication contacts
OF3 / OF2 / OF1 :
SDE
SD
249
Compact NS
Schneider Electric
250
Compact NS
Schneider Electric
Compact NS
Additional characteristics
Presentation
Functions and characteristics
Installation recommendations
Dimensions, volumes
Connection
Electrical diagrams
1
11
143
165
205
221
Tripping curves
252
Compact NSC100
Compact NS80H-MA
Compact NSA160
Compact NB100 to 600
Compact NS100 to 250
Compact NS100 to 250 protection of distribution systems
Compact NS100 to 250 motor-starter protection
Compact NS400 to 630 protection of distribution systems
Compact NS400 to 630 motor-starter protection
Compact NS630b to 3200
Reflex tripping
252
253
254
255
256
258
259
260
261
262
263
Current-limiting curves
264
Catalogue numbers
251
Compact NS
267
Schneider Electric
Additional characteristics
Tripping curves
Compact NSC100
E44454
1640 A
10 000
5 000
2 000
1 000
500
200
100
50
20
10
5
t(s)
2
1
16A : Im = 37,5 x In
.5
20A : Im = 30 x In
.2
25A : Im = 24 x In
.1
.05
32A : Im = 19 x In
40A : Im = 15 x In
.02
.01
.005
.002
.001
.5 .7 1
3 4 5 7 10
20 30
50 70 100
200 300
I / Ir
100 A
10 000
5 000
E44456
E44455
5080 A
10 000
5 000
2 000
2 000
1 000
1 000
500
500
200
200
100
100
50
50
20
20
10
10
t(s)
t(s)
2
100A : Im = 12,5 x In
.5
.5
50A : Im = 20 x In
63A : Im = 16 x In
70A : Im = 14,3 x In
80A : Im = 12,5 x In
.2
.1
.05
.2
.1
.05
.02
.01
.02
.01
.005
.005
.002
.001
.5 .7 1
.002
.001
.5 .7 1
3 4 5 7 10
20 30
50 70 100
200 300
I / Ir
3 4 5 7 10
20 30
50 70 100
200 300
I / Ir
252
Compact NS
Schneider Electric
Compact NS80H-MA
MA1.5MA80
E28466
10 000
5 000
2 000
1 000
500
200
100
50
20
10
5
t(s)
2
Im = 614 x In
1
.5
.2
.1
.05
.02
.01
.005
.002
.001
.5 .7 1
3 4 5 7 10
20 30
50 70 100
200 300
I / Ir
253
Compact NS
Schneider Electric
Additional characteristics
Tripping curves
Compact NSA160
5080 A
E30206
E30207
1640 A
10 000
5 000
10 000
5 000
2 000
2 000
1 000
1 000
500
500
200
200
100
100
50
50
20
20
10
10
5
5
t(s)
t(s)
2
1
16A : Im = 37,5 x In
.5
.5
50A : Im = 20 x In
25A : Im = 24 x In
.2
.2
32A : Im = 19 x In
.1
.05
40A : Im = 15 x In
.02
.01
.02
.01
.005
.005
.002
.001
.5 .7 1
.002
.001
.5 .7 1
3 4 5 7 10
20 30
50 70 100
63A : Im = 16 x In
.1
.05
200 300
80A : Im = 12,5 x In
20 30
50 70 100
200 300
I / Ir
I / Ir
125160 A
E30208
100 A
E30209
3 4 5 7 10
10 000
5 000
10 000
5 000
2 000
2 000
1 000
1 000
500
500
200
200
100
100
50
50
20
20
10
10
160A : Im = 7,8 x In
t(s)
t(s)
2
2
100A : Im = 12,5 x In
.5
.5
.2
.2
.1
.05
.1
.05
.02
.01
.02
.01
.005
.005
.002
.001
.5 .7 1
.002
.001
.5 .7 1
3 4 5 7 10
20 30
50 70 100
200 300
I / Ir
125A : Im = 10 x In
3 4 5 7 10
20 30
50 70 100
200 300
I / Ir
254
Compact NS
Schneider Electric
NB100 - 50100 A
10 000
5 000
E58555
E58554
10 000
5 000
160
NB50
2 000
130
2 000
1 000
100
1 000
500
150
100
500
60
200
20
40
60
60
100
50
20
20
10
10
20
40
60
ambiant temperature ( C )
100
50
t(s)
t(s)
2
1
.5
.2
.1
.05
NB50
Inst.
15 A
20 A
30 A
40 A
50 A
11 In
10 In
12 In
11 In
12 In
1
.5
.2
.02
.01
.02
.01
.005
.005
.002
.001
.5 .7 1
.002
.001
.5 .7 1
3 4 5 7 10
20 30
50 70 100
10 In 20%
.1
.05
200 300
I / In
3 4 5 7 10
20 30
50 70 100
200 300
I / In
NB400 / 600
10 000
5 000
E58712
NB250
E58560
200
ambiant temperature ( C )
ambient compensation
current rating ( % )
2 000
10 000
5 000
2 000
120
1 000
ambient compensation
current rating ( % )
120
1 000
100
NB600
100
500
500
80
200
20
40
NB400
80
50
200
ambient temperature ( C )
100
100
50
50
20
20
10
10
20
40
50
60
ambient temperature ( C )
5
t(s)
t(s)
2
1
.5
.5
.2
.2
.1
.05
.1
.05
.02
.01
.005
.002
.001
.5 .7 1
.02
.01
reflex tripping :
t < 10 ms
3 4 5 7 10
20 30
50 70 100
reflex tripping :
t < 10 ms
.005
200 300
.002
.001
.5 .7 1
I = 11 x In
3 4 5 7 10
20 30
50 70 100
200 300
I / In
I / In
255
Compact NS
Schneider Electric
Additional characteristics
Tripping curves
Compact NS100 to 250
Protection of distribution systems
E28452
TM16D / TM16G
10 000
5 000
10 000
5 000
2 000
2 000
1 000
1 000
500
500
200
200
100
100
50
50
20
20
10
10
t(s)
t(s)
2
TM16D : 12 x In
TM25D : 12 x In
.5
.5
.2
.2
TM16G : 4 x In
.1
.05
.02
.01
.02
.01
reflex tripping :
t < 10 ms
.005
.005
.002
.001
.5 .7 1
.002
.001
.5 .7 1
3 4 5 7 10
20 30
50 70 100
TM25G :
3.2 x In
.1
.05
200 300
reflex tripping :
t < 10 ms
3 4 5 7 10
50 70 100
200 300
E28455
E28454
20 30
I / Ir
I / Ir
10 000
5 000
2 000
2 000
1 000
1 000
500
500
200
200
100
100
50
50
20
20
10
10
5
5
t(s)
t(s)
2
TM40D : 12 x In
.5
.5
TM50D : 10 x In
TM32D : 12,5 x In
.2
.2
TM40G :
2 x In
.1
.05
.02
.01
reflex tripping :
t < 10 ms
.005
TM63G :
2 x In
.1
.05
.02
.01
.002
.001
.5 .7 1
TM63D : 8 x In
3 4 5 7 10
20 30
50 70 100
reflex tripping :
t < 10 ms
.005
200 300
.002
.001
.5 .7 1
3 4 5 7 10
20 30
50 70 100
200 300
I / Ir
I / Ir
256
Compact NS
Schneider Electric
E28456
TM80D / TM100D
10 000
5 000
10 000
5 000
2 000
2 000
1 000
1 000
500
500
200
200
100
100
50
50
20
20
10
10
t(s)
TM125D
10 x In
t(s)
2
NS160/250
Im = 12,5 x In
.5
.5
NS100
Im = 8 x In
.2
.2
.1
.05
TM160D
8 x In
.1
.05
.02
.01
.02
.01
reflex tripping:
t < 10 ms
.005
.005
.002
.001
.5 .7 1
.002
.001
.5 .7 1
3 4 5 7 10
20 30
50 70 100
200 300
I / Ir
reflex tripping :
t < 10 ms
3 4 5 7 10
20 30
50 70 100
200 300
I / Ir
E28458
TM200D / TM250D
10 000
5 000
2 000
1 000
500
200
100
50
20
10
5
t(s)
2
Im = 5 10 x In
1
.5
.2
.1
.05
.02
.01
reflex tripping :
t < 10 ms
.005
.002
.001
.5 .7 1
3 4 5 7 10
20 30
50 70 100
200 300
I / Ir
257
Compact NS
Schneider Electric
Tripping curves
Compact NS100 to 250
Protection of distribution systems (cont.)
Additional characteristics
E28459
STR22SE - 40100 A
10 000
5 000
2 000
10 000
5 000
2 000
Ir = 0.41 x In
1 000
1 000
500
500
200
200
100
100
50
50
20
20
10
10
Ir = 0.41 x In
t(s)
t(s)
2
2
Im = 210 x Ir
.5
.2
.2
.1
.05
.1
.05
.02
.01
.02
.01
reflex tripping
t < 10 ms
.005
.002
.001
.5 .7 1
Im = 210 x Ir
.5
reflex tripping
t < 10 ms
.005
I = 11 x In
3 4 5 7 10
20 30
50 70 100
.002
.001
.5 .7 1
200 300
I = 11 x In
3 4 5 7 10
I / Ir
10 000
5 000
200 300
10 000
5 000
2 000
Ir = 0.41 x In
1 000
50 70 100
STR22GE - 160250 A
E28410
E28409
STR22GE - 40100 A
2 000
20 30
I / Ir
1 000
500
500
200
200
100
100
50
50
20
20
10
10
Ir = 0.41 x In
t(s)
t(s)
2
.5
.5
Im = 210 x Ir
.2
.2
Im = 210 x Ir
.1
.05
.1
.05
.02
.01
.02
.01
reflex tripping :
t < 10 ms
.005
.002
.001
.5 .7 1
reflex tripping :
t < 10 ms
.005
I = 11 x In
3 4 5 7 10
20 30
50 70 100
200 300
I / Ir
.002
.001
.5 .7 1
I = 11 x In
3 4 5 7 10
20 30
50 70 100
200 300
I / Ir
258
Compact NS
Schneider Electric
E30212
MA2,5MA100
E28467
10 000
5 000
10 000
5 000
2 000
2 000
1 000
1 000
500
500
200
200
thermal withstand
100
thermal withstand
MA220
MA150
100
50
50
20
20
10
10
t(s)
t(s)
2
2
Im = 6 14 x In
1
.5
.5
.2
.2
.1
.05
.1
.05
.02
.01
.02
.01
reflex tripping :
t < 10 ms
.005
.005
.002
.001
.5 .7 1
.002
.001
.5 .7 1
3 4 5 7 10
20 30
50 70 100
Im = 9 14 x In
200 300
I / Ir
reflex tripping :
t < 10 ms
3 4 5 7 10
20 30
50 70 100
200 300
I / In
STR22ME - 10220 A
10 000
5 000
2 000
Ir
1 000
500
200
100
50
class 10 (IEC 60947-4)
20
10
5
t(s)
2
1
.5
.2
Im = 13 x Ir
.1
.05
.02
.01
reflex tripping :
t < 10 ms
.005
.002
.001
.5 .7 1
I = 15 x In
3 4 5 7 10
20 30
50 70 100
200 300
I / Ir
259
Compact NS
Schneider Electric
Tripping curves
Compact NS400 to 630
Protection of distribution systems
Additional characteristics
10 000
5 000
E28462
E28461
STR23SE / STR23SV
10 000
5 000
2 000
2 000
Ir = 0.41 x In
1 000
Ir = 0.41 x In
1 000
500
500
200
200
100
100
50
50
20
20
10
10
tr = 0.516 s
Ii = 1.511 x In
5
t(s)
t(s)
2
Isd = 210 x Ir
.5
.5
.2
.2
.1
.05
.1
.05
.02
.01
i 2 t OFF
0.3
0.2
0.1
0
.02
.01
reflex tripping
t < 10 ms
.005
.005
.002
.001
.5 .7 1
Isd = 1.510 x Ir
I2t ON
I = 11 x In
3 4 5 7 10
20 30
50 70 100
200 300
.002
.001
.5 .7 1
reflex tripping :
t < 10 ms
3 4 5 7 10
I / Ir
I / Ir
20
5 7 10
20 30
50
I / In
Earth-fault protection
10 000
5 000
2 000
Ig = 0.21 x In
1 000
500
200
100
50
20
10
I2t ON
5
t(s)
2
1
.5
0.4
0.3
.2
.1
.05
0.2
0.1
I2t OFF
.02
.01
.005
.002
.001
.05 .07 .1
.2
.3 .4 .5 .7 1
7 10
20 30
I / In
260
Compact NS
Schneider Electric
E28468
MA320MA500
10 000
5 000
10 000
5 000
2 000
2 000
1 000
1 000
500
500
200
200
thermal withstand
100
100
50
50
20
20
10
10
class 10 A
t(s)
t(s)
2
.5
.5
Isd = 613 x Ir
.2
.2
Im = 9 ... 14 x In
.1
.05
.02
.01
.02
.01
reflex tripping :
t < 10 ms
.005
.002
.001
.5 .7 1
.1
.05
3 4 5 7 10
20 30
50 70 100
reflex tripping
t < 10 ms
.005
.002
.001
.5 .7 1
200 300
Ii = 10,4 x In
3 4 5 7 10
I / In
200 300
10 000
5 000
E38946
E38879
50 70 100
I / Ir
10 000
5 000
2 000
2 000
1 000
1 000
500
500
200
200
100
100
50
20 30
class 20
50
class 10
20
20
10
10
t(s)
t(s)
2
1
.5
.5
Isd = 613 x Ir
Isd = 613 x Ir
.2
.2
.1
.05
.1
.05
.02
.01
.02
.01
reflex tripping
t < 10 ms
.005
.002
.001
.5 .7 1
reflex tripping
t < 10 ms
.005
Ii = 10,4 x In
3 4 5 7 10
20 30
50 70 100
200 300
I / Ir
.002
.001
.5 .7 1
Ii = 10,4 x In
3 4 5 7 10
20 30
50 70 100
200 300
I / Ir
261
Compact NS
Schneider Electric
Tripping curves
Compact NS630b to 3200
Additional characteristics
10 000
5 000
10 000
5 000
E46276
E46350
Micrologic 2.0
Ir = 0,41 x In
2 000
2 000
1 000
1 000
500
500
200
200
100
Ir = 0,41 x In
100
tr = 0,5...24 s
50
50
20
20
10
10
tr = 0,524 s
t(s)
t(s)
2
1
Isd = 1,510 x Ir
Isd = 1,510 x Ir
.5
.5
.2
.2
I2t ON
0,2
.02
.01
.02
.01
.005
.005
.002
.001
.5 .7 1
.002
.001
.5 .7 1
20 30
50 70 100
200 300
0,2
0,1
.1
.05
3 4 5 7 10
0,3
0,3
.1
.05
0,4
0,4
0,1
I t OFF
Ii = 215 x In . OFF
3 4 5 7 10
20
7 10
x Ir
I / Ir
20 30
x In
Ig = AJ x In (1)
1200 A max.
1 000
500
200
100
50
20
10
5
t(s)
I2t ON
2
1
.5
.2
.1
.05
I2t
0.4
0.4
0.3
0.2
0.1
0.3
0.2
0.1
OFF
.02
.01
.005
.002
.001
.05.07 .1
(1)
Ig = In x
.2 .3 .4 .5 .7 1
7 10
I / In
262
200 300
Ig < 400 A
0.3
400 A i Ig i 1200 A 0.2
Ig > 1200 A
500
Compact NS
0.3
0.3
640
0.4
0.4
720
0.5
0.5
800
0.6
0.6
880
0.7
0.7
960
0.8 0.9 1
0.8 0.9 1
1040 1120 1200
Schneider Electric
E28463
Reflex tripping
TM160D...TM250D
STR22SE250
20
NS630
STR22SE160
NS400
NS250
10
TM160D
8
t
(ms) 7
TM16D...TM100D
STR22SE40... 100
NS100-NS160
5
4
3
2
10
20
30
40
60
100
200
kA rms
263
Compact NS
Schneider Electric
E28800
Additional characteristics
Current-limiting curves
Isc
prospective
Isc peak
prospective
current
prospective
Isc
limited Isc
peak
limited
Isc
tc
actual
current
Current-limiting curves
The current-limiting capacity of a circuit breaker is expressed by two curves which
are a function of the prospective short-circuit current (the current which would flow
if no protection devices were installed):
c the actual peak current (limited current),
c thermal stress (A2s), i.e. the energy dissipated by the short-circuit in a conductor
with a resistance of 1 .
Example
What is the real value of a 150 kA rms prospective short-circuit (i.e. 330 kA peak)
limited by an NS250L upstream ?
Answer: 30 kA peak (see next page).
1.5
2.97x104
2.5
8.26x104
4
2.12x105
6
4.76x105
4.10x104
1.39x105
2.92x105
6.56x105
16
3.4x106
1.39x106
4.69x106
1.93x106
25
8.26x106
3.38x106
1.39x107
4.70x106
35
1.62x107
6.64x106
2.23x107
9.23x106
50
3.31x107
1.35x107
4.56x107
1.88x107
10
1.32x106
5.41x105
1.82x106
7.52x105
Example
Is a Cu/PVC cable with a CSA of 10 mm2 adequately protected by an NS160N?
The table above indicates that the permissible stress is 1.32x106 A2s.
All short-circuit currents at the point where an NS160N (Icu = 35 kA) is installed are
limited with a thermal stress less than 6 x 105 A2s (see next page).
Cable protection is therefore ensured up to the limit of the breaking capacity of the
circuit breaker.
264
Compact NS
Schneider Electric
Current-limiting curves
Voltage 380/415 V AC
Voltage 660/690 V AC
200
NS630bH
NS800H
NS1000H
NS1250H
NS1600H
NS630bN
NS800N
NS1000N
NS1250N
NS1600N
100
80
70
60
50
kA peak40
200
NS630bL
NS800L
NS1000L
NS630
NS400
H
N
30
H
N
20
NS250
NS160
NS100
30
TM32...250
20
10
20
NS400
NS630
TC150/250/400
NS100
NS250
TM40100
TM 25
NH
10
8
7
6
5
4
NSA160
NS160
TM16
NS630bH
NS800H
NS1000H
NS1250H
NS1600H
NS630bN
NS800N
NS1000N
NS1250N
NS1600N
NS630bL
NS800L
NS1000L
100
80
70
60
50
kA peak 40
TM25
10
8
7
6
5
4
300
E58559
E58557
300
30 40
60
100
200 300
TM 16
10
20
30 40
60
100
200 300
kA rms
kA rms
Thermal-stress curves
Voltage 380/415 V AC
Voltage 660/690 V AC
10
E58558
E58556
10
5
3
2
NS630bN
NS800N
NS1000N
NS1250N
NS1600N
10
5
3
2
NS630bH
NS800H
NS1000H
NS1250H
NS1600H
10
NS630bN
NS800N
NS1000N
NS1250N
NS1600N
3
2
3
2
7
10
2
As 5
3
2
N
6
10
5
3
2
10
NS1000L
NS630bL
L NS800L
As 5
NS630
3
2
L
NS400
10
L
NS250
NS160
NS100
TM32250
NSA160
TM25
NS630bL
NS800L
NS1000L
NS630
L
H
N
NS250
NS100
TM 40100
3
2
L NS400
TC150/250/400
NS160
TM 25
TM 16
10
10
TM16
3
2
3
2
NS630bH
NS800H
NS1000H
NS1250H
NS1600H
10
20
30 40
60
kA rms
10
20
30 40
60
kA rms
265
Compact NS
Schneider Electric
266
Compact NS
Schneider Electric