Beruflich Dokumente
Kultur Dokumente
Ceilings
Infiltration
Windows
Doors
Each of these component loads is added up, to arrive at a total block load for a zone in a
house. Loads are always measured in British Thermal Units per Hour (BTUH). 12,000 BTUH =
one air conditioning (or heating) ton of load. If windows lose 6400 BTUH and the ceiling loses
5600 BTUH, together they lose one ton of heat at design temperatures. BTUH is an Acronym
used frequently. All Acronyms are defined on the last page of this course. Add in the other loss
components for the total load to that zone, such as shown below. The simplified Excel
spreadsheet we use automatically totals these component loads. One does not need Excel
knowledge to run this easy program. Sample Totals:
Heating BTUH
Cooling BTUH
21,661
14,820
Although heat enters and leaves a building in three ways: Conduction, Convection and
Radiation, the focus is on Conduction, with Heat in BTUH
= Area x Temperature Difference
Thermal Resistance (also known as Insulation R values)
Heat Transfer by Convection, such as physical air escaping through cracks is converted to
an infiltration BTUH for use with the Conduction calculations. Radiation from the sun is also
accommodated in the window fenestration worksheets, and is not a concern. The American
Society of Heating Refrigeration and Air-conditioning Engineers (ASHRAE) publish the
www.SunCam.com
Page 2 of 38
Page 3 of 38
Instead of just replacing an old air conditioner or heat pump with a similar tonnage size,
this analysis results in equipment that is more accurately sized for its rated heating and cooling
capacity. The bottom line for these spreadsheet additive loads is to achieve design heating and
cooling loads that can be used to select proper heating and cooling capacity equipment.
Even if equipment is not replaced, analyzing an existing house can give the owner the
knowledge to save in certain areas. Perhaps window coverings and solar shading will save
significant air conditioning load in summer, with accurate BTUH (BTU per hour) as measured.
Perhaps ducts that are not well insulated in a hot attic can be shown quantitatively to justify
blowing more insulation around them. Infiltration losses for a leaky home can be expressed as a
percentage of the total heating or cooling bill to show the benefits of caulking.
This course will start with an overview of how to use the downloaded Manual J ae
spreadsheet. Header information, finding the nearest climate city and entering the designer name
and address are reviewed.
www.SunCam.com
Page 4 of 38
Next we discuss how to use building plans, elevations and insulation details needed for
measuring net areas that must be input into the program. One may measure these on the job, or
use accurate plans if available. Discussion of each of the 16 load components such as windows,
doors, and walls, etc. will follow (16 = 11 Sensible Loads + 5 Latent Loads). Results and
examples will be reviewed, and typical heating and cooling equipment capacity tonnage will be
selected based on total combined loads (the block load) determined to be imposed on the
equipment. Please open your Manual J ae program and explore it in overview first. If you print
it out, it will appear like the one in the photograph above between the two Manual J text books.
We will examine its features next. The completed sheet appears on the last pages of this course.
Special thanks to ACCA for providing this useful tool for free.
They have offices on the third floor of this beautiful Arlington, VA high rise office building.
Please visit www.ACCA.org and consider joining as a member.
www.SunCam.com
Page 5 of 38
Read
Me
J1
Form
Summary
Glass
Schedule
Doors
Glass
Walls
Ceilings
Floors
Help
Notes
What
to do
next
Insert
Work
sheet
Click on the third bottom Tab for the very important J1 Form.
Connecticut
Waterbury
70
HTD
68
75
@ Outdoor (Summer) 1% db
85
CTD
10
50%
Grains Difference
29
Daily Range
Elevation
850
ACF
Latitude
41
Medium
0.978
Block Load
Not Applicable
ESPN residence
Connecticut
Bristol
70
HTD
66
75
@ Outdoor (Summer) 1% db
87
CTD
12
50%
Grains Difference
36
Daily Range
www.SunCam.com
Page 7 of 38
Medium
www.SunCam.com
Page 8 of 38
41
Elevation
850
ACF
Continuing with the Header, Latitude is important for the directional angle, with which
the sun shines on the windows. The Altitude Correction Factor (ACF) is automatically
calculated for pressure differences above sea level. Waterbury at Elevation 850 above sea level
corrects by 1.0 - 0.978 = 2.2%. Not a concern here, but significant for Denver, CO. Latitude is
shown for verification that the City is correct. The last clarification for the Header is that dry
bulb temperatures are recorded by thermometer bulbs that are in the shade, dry and uncovered.
Note that the Header table stays fixed as one scrolls through the heat loss and gain
components below, as addressed next.
Because Glass Windows are very important and fenestration is complicated, with
multiple sub work sheets, this course skips to Doors for the introduction of how to enter door
data into the worksheet and thus into form J1.
www.SunCam.com
Page 9 of 38
0.978
U-Value
U-Value
0.350
Notes
Door Glass
* Ignore door glass if the glass area is less than 51 percent of the door area.
* Classify as a French door (under the "Glass" tab if the glass area exceeds
50 percent of the door area.
The form starts like this above, but evolves as you save information into your template
version to save time on future projects.
Table 4A refers to the Manual J and Manual J ae Table with printed information on
insulation values for opaque panels including doors without a majority of glass. Construction
Number 11 Wood and Metal Doors refers to specific doors with known R or its reciprocal U
value U = 1/R. R is for (thermal) Resistance and U is for (thermal) Conductance of panels.
In the software is one example, 11N, Metal, Polystyrene Core, with a U-Value of 0.350 =
R 2.9. The manual lists 9 wood doors and 8 metal doors ranging from U = 0.26 to 0.54 for wood
and 0.17 to 0.60 for metal. If one knows the R value of the door from the manufacturer, or
online research, enter its description and U-Value on the top line. If an existing house shows no
easy sign of this data, choose a description and U-Value consistent with what can be observed.
Perhaps it is a Fiberglas Core at 0.60 or Fiberglas Core with Storm Door at 0.36. For our
example, because it is unknown, from best visual, non-destructive testing inspection, select a
solid core wood door at U = 0.40, i.e. R = 2.5. From the Floor Plan, there is one door to the
garage, one to the basement plus the front door, with all three of the same construction. The
direction they face: North, South, East or West does not matter. Be careful not to spend too
much time focusing on R value for doors, which have only a small percentage of the wall, ceiling
and floor square footage.
www.SunCam.com
Page 10 of 38
U-Value
0.400
Exit the Door Worksheet, by hitting the J1 tab at the bottom left. There is no need to
save each worksheet. But do save your entire spreadsheet as you exit the program.
______________________________________________________________________________
On the J1 form, line 7a, the yellow drop down tab transfers the Door worksheet
description just typed in Solid core wood doors R = 2.5, as the construction detail, which the
Client will see in simple terms without unnecessary Table references from the unavailable
Manual J. Typing in the R = 2.5 also gives the Client/Reviewer the important information on the
door insulation characteristic in the one page final printout.
Wood &
Metal
Doors
Heating
Cooling
Construction Detail
HTM
HTM
27.20
Note that the program immediately assigns Heating - Heat Transfer Multiplier (HTM) as
27.20 BTUH/square foot and Cooling HTM @8.40 because Climate Data previously entered
gives Delta T, and because U values are known too, from the door worksheet. The total BTUH
will be known once the square footage for the doors is input.
Use the best floor plan available, sometimes in the Local Tax Assessors office, because
they measure square feet and prepare a plan for property tax. For this SUNCAM course we will
use a rough AutoCAD drawing showing important features with extraneous information that will
be typical. From the plan below, there is one door to the garage and one to the basement each
with rough opening 3 x 6.9= 21 square feet, and the front door is 5 x 6.9 = 35 square feet.
Overall dimensions not easily seen in the image below are: 32 wide by 50.5 long, with
floor area = 1616 36 in northeast corner + breakfast nook = 20 = 1600 square feet. The plan
does not show window heights that would have to be measured. Use the copy of this plan
repeated on the last page of this course, for reference throughout.
www.SunCam.com
Page 11 of 38
8.40
The sliding glass door will be figured in the glass window calculations. Doors if any to
the second floor would not be considered because the second floor is conditioned too, whether
that floor is insulated against the first floor or not. On the J1 form, enter 21 + 21+ 35 = 77 sq.
feet of total door Net Area in the white cell.
7 Wood &
Metal
Doors
Heating
Cooling
Net
Heating
Cooling
Net
HTM
HTM
Area
BTUH
BTUH
Area
27.20
8.40
77
2094
647
The small font sizes above are necessary to fit the entire line on this page. Use control & scroll
or other zooming tools to read such small print that should match numbers on your separate
Manual J ae spreadsheet.
This provides all the information the program needs to now determine BTUH Heating
Loss of 2094 and Cooling Gain of 647 for the Doors Component.
One tip is to use the floor plan as a handwritten worksheet to write total areas in the
margins so that the one drawing contains area measurements if they must be checked.
Doors: 21+21+35 =77.
www.SunCam.com
Page 12 of 38
77
Heating
U-Value
NE/NW
Cooling HTM
E/W
SE/SW
Construction Number; Glass Type; Number of Panes; Type of Sash; Type of Frame
1C-cm, Clear, Single Pane / Storm, Operable, Metal no Break
Construction Number; Glass Type; Number of Panes; Type of Sash
8Bc-4, Flat Clear, Double Pane, Wood
U-Value
0.870
U-Value
0.940
It is important for the engineer to figure the closest reasonable insulative value for the
window fenestration assemblies. For triple pane, average U = 0.50 (0.18 best to 0.72 worst). For
an unknown double pane, with operable window or sliding glass door, average U = 0.65 (0.49 to
0.87). Types of frames that might provide a short circuit for heat transmission should have
higher U and lower R values. Single pane can be 1.27, so there is quite a range for unknown
properties. If the manual is unavailable, try an internet search if the manufacturer is known.
Default U values for single pane = 0.98, double pane = 0.56, triple pane = 0.42.
Low-e (emissivity) glass has a metal-oxide coating on a glazing face. For northern
climates it is on the inside of a double pane window at the Argon gas enclosure, to keep the heat
in. Down south, the coating is on the outer layer to keep the heat out by reducing solar radiation.
If unknown except that low-e is properly applied, reduce the U value.
For double pane with low-e in our example, use a U = 0.45.
The table below in the Glass worksheet gives the Heat Transfer Multiplier (HTM) based
on window direction. This affects cooling load only and not heating loss calculations.
Obviously there is more cooling load from the radiant sun on windows facing east or west than
north, or even directly south, and the HTM accounts for it.
Glass Type; Number of Panes; Type of Internal Shade; Rounded CTD
Double Pane; Clear; Horiz. Blinds @ 45 Deg; 15
www.SunCam.com
N
13
NE/NW
30
E/W
43
SE/SW
37
Page 13 of 38
S
21
Table 2A/3A -- Construction Numbers 1 through 7 & 10 -- Vertical Glass Heat Loss
Enter Construction Number, Glass Type, # Panes, Sash Type, Frame Type, Shading
Unknown brand, double pane low-e, with shading blinds. R=2.2
N
9
NE/NW
24
Cooling HTM
E/W
SE/SW
35
30
S
16
We would raise them all if U= 1.0 single pane and CTD = 15, (not 10) to: N21, 41, 56, 49
S30. If a neighboring building or large trees provide shading, reduce the HTM from that
direction (but do not cut the trees). Be sure to enter reasonable if not exact HTMs. There is no
difference between East and West windows in the Program, (although peak temperature should
occur during the afternoon, when the sun shines through West facing windows.)
For unknown double pane windows, keeping the program defaults is prudent without
Table 3A adjustments available, or interpolate off these values above, as shown. Do not confuse
vertical window HTMs or CTDs with skylight values that can be ten times higher as shown in
the following pages. For more information refer to the National Fenestration Rating Council
(NFRC). This example as in most cases is for one type of glass throughout the zone. If some
have storm windows and some do not, add each type in on the lines provided.
With the vertical glass characteristics complete on the Glass worksheet, we work next on
the Glass Sched (ule) worksheet before transferring all data to the J 1 form.
Glass Schedule
VERTICAL GLASS
X (Ft.)
Heating
Table 2A Construction Numbers and Details
that Apply to this Load Estimate
Top of
Opening to
Overhang
Y (Ft)
Adjustment for
Projected Window
or French Door
Clg
HTM
Adjustment
#1
None
None
#2
None
None
#3
None
None
Direction
Glass
Faces
Height of
opening
H (Ft)
Overhang
Distance
X (Ft)
#4
None
None
#5
None
None
#6
None
None
#7
None
None
#8
None
None
#9
None
None
#10
None
None
#11
None
None
#12
None
None
The Glass schedule allows adjustment to sunshine entering a window because of the
shading roof overhang above, per the diagram. In our example on the first floor of a two story
www.SunCam.com
Page 14 of 38
Y (FT.)
H (Ft.)
Direction
Glass
Faces
Height of
opening
H (Ft)
Overhang
Distance
X (Ft)
Top of
Opening to
Overhang
Y (Ft)
Adjustment for
Projected Window
or French Door
Clg
HTM
Adjustment
#1
5.00
2.00
10.00
None
None
#2
E/W
5.00
2.00
10.00
None
None
J1 Form.
Opening J1 shows us the window information from the schedule has been automatically
transferred to the blue Output From Formula cells.
6A Windows
& Glass
Glass
Heating
Direction
Construction Detail
HTM
HTM
30.60
16.00
E/W
30.60
35.00
Doors
The Construction Detail is as was typed in. Heating and Cooling HTMs were figured,
and the form awaits input of how many square feet of window and glass doors there are in each
direction. These areas are added up from the floor plan and elevation plan or window schedule
or field measurement.
The South window 5 h x 3 wide has area = 15. There are six East or West windows @
15sf = 90. Kitchen 4h x 5w = 20 and slider = 41sf. Total = 151 sq. ft. Enter in white cells.
Heating
Cooling
Net
BTUH
BTUH
Area
459
240
15
4621
5285
151
Note that 15 sq. ft. of South facing glass yields 240 Cooling BTUH = 16 HTM x 15 sq. ft.
The East West facing glass yields 5285 BTUH = 35 HTM x 151 sq. ft. or about twice the
load per square foot. There was no HTM adjustment for roof overhang shading 10 above as
www.SunCam.com
Cooling
Page 15 of 38
6B Skylights
Skylights similarly are input first on the Glass worksheet, and then on the Glass Sched for
transfer to J1. From Glass:
Table 2A/3A -- Construction Numbers 8 & 9 -- Skylight Heat Loss
Enter Construction Number, Glass Type, # Panes, Sash Type
Heating
U-Value
NE/NW
Cooling HTM
E/W
SE/SW
Note how much higher the HTMs are for Skylights than glass in the example.
Glass Type; Number of Panes; Tilt Angle; Rounded CTD
Double Pane, Clear, 30 Deg; 15
N
142
NE/NW
156
E/W
167
SE/SW
162
S
150
These given values are for a 30 degree sloped roof as average. If steeper at 6o degrees, N
= 101. If horizontal, N = 148 as do all directions. For single pane, 142 increases to 166. For
triple pane it decreases to 128. So interpolations can be used if Table 3C is unavailable, or if
exact skylight construction is unknown.
There are no skylights in the first floor example, (but for illustrative purposes we can
pretend there is to see how it is input.) Copy and paste the description for the Double Pane
Clear, 30 Degree: 15CTD and Cooling HTM values into the table above. Enter U = 0.90.
Table 2A/3A -- Construction Numbers 8 & 9 -- Skylight Heat Loss
Enter Construction Number, Glass Type, # Panes, Sash Type
Double Pane, Clear, 30 Deg; 15
Heating
U-Value
0.90
N
142
NE/NW
156
Cooling HTM
E/W
SE/SW
167
162
S
150
Direction
Glass
Faces
#1
#2
We use the yellow drop down arrow to select the skylight, which we will say faces North.
SKYLIGHTS
#
#1
Heating
Table 2A Construction Numbers and Details
that Apply to this Load Estimate
Double Pane, Clear, 30 Deg; 15
Direction
Glass
Faces
N
Page 16 of 38
6B Skylights
Heating
Cooling
Construction Detail
HTM
HTM
61.20
142
Cooling
Net
BTUH
BTUH
Area
1420
10
U-Value
Group
U-Value
PTDH
Shaded
Wall
No
No
Partitions
Table 4A -- Constructions 12 & 13 -- Partitions
Construction Number; Wall Type; Board R-Value; Cavity R-Value, Finish
PTDC
Below Grade
Table 4A -- Construction Number 15 -- Below Grade Walls
Construction Number; Wall Type; Board R-Value; Cavity R-Value, Floor Depth
U-Value
The first floor plan example will involve Above Grade walls, some Partition wall to the
unconditioned basement, and some Below Grade wall area adjacent to the basement stairs.
Wall examples require U-Value. The Group Listing is for cooling reference issue only,
not heating. Doors, Ceilings and Floors do not have a Group number. If Table 4A is
unavailable, use Group I for R-13 2 x 4 walls or Group J for R-19 2 x 6 walls.
www.SunCam.com
Page 17 of 38
U-Value
Group
0.053
0.053
J
J
Shaded
Wall
No
Yes
The building perimeter measures 165 on the outside. Inside space is 9 clear with
assumed uninsulated second floor not needed. Assume properly insulated rim joist below the first
floor. Use average height = 9.5 x 140 = 1330 sq. ft. Subtract out window and front door areas =
1330 - (166 + 35) = 1129 sq. ft. net above grade area. And garage wall = 25 x 9.5 = 238 sq. ft.
- 21 door = 217 sq. ft.
Heating
Cooling
Net
Heating
Cooling
Net
Construction Detail
HTM
HTM
Area
BTUH
BTUH
Area
3.58
0.34
1129
4038
380
1129
2 x 6 R -19
3.60
0.04
217
782
217
Partition Wall
The 2 x 4 wall to the basement loses and gains heat, but not at the same rate as to the
outside air at design condition. See the wall on the right side of the picture below. The Partition
Temperature Difference for Heating (PTDH) is input at 70 55 (near furnace) = 15F. The
PTDC is perhaps also like the outside air temperature without solar gain = 85-75 = 10F.
www.SunCam.com
Page 18 of 38
U-Value
PTDH
PTDC
0.077
15
10
Area along the stairs is 8 x 8.5 high = 68 sq. ft. - 21sq. ft door = 47 sq. ft. input on J1.
Construction Detail
Partition Walls
Heating
Cooling
Net
Heating
Cooling
Net
HTM
HTM
Area
BTUH
BTUH
Area
1.16
0.77
41
47
Heating and Cooling loads are lower than if the HTMs were set to outside air at 2F.
www.SunCam.com
Page 19 of 38
32
41
U-Value
The temperature input box to the right is greyed out. There is no opportunity to input the
temperature of the ground at say 50F versus the indoor heating temperature at 70F. The
program and a Manual J and J ae design example use Delta T or HTM = 68F, figuring heat
eventually transfers to the air above the frost! To overcome this deficiency, a high U-value must
be used. It would appear to be a program improvement to treat Below Grade walls like Partition
walls and allow PTDH input. Result:
Table 4A -- Construction Number 15 -- Below Grade Walls
Construction Number; Wall Type; Board R-Value; Cavity R-Value, Floor Depth
Concrete, rigid board and sheetrock R-12
U-Value
0.083
For 2 ft. + below grade wall area = (5.33 x 3.5) + (5.5 x 6/2) = 35 sq. ft., Net Area along
left side of stairs, input to Form J.
Heating
Cooling
Net
Heating
Cooling
Net
Construction Detail
HTM
HTM
Area
BTUH
BTUH
Area
5.64
35
198
Note that there is no air conditioning load from heat gain from a below grade wall. (OK)
But the heat loss based on outside air, not ground temperature is improper, at Heating HTM =
5.64 x 35 sq. ft. = 198 BTUH. The 5.64 = 68F / 12. 68F = 70F - 2F. 2F is air, not ground
temperature.
For a small area like this, it is not a concern, but for a finished basement, it is significant.
If HTM was 70F inside temperature - 50F outside ground temperature = 20,
HTM = 20/R12 = 1.67 x 35 sq. ft. = 58 BTUH or 58/198 = 29% of the computed load.
This 71% reduction is significant for accuracy. Ascertaining that a house is losing as
much heat through its above grade walls (exposed to wind and cold) as it is through its below
grade walls, is an issue being discussed with ACCA and pursued to make the Manual J program
better. For oversized fossil fuel heating systems, it has not been a concern, but for heat pump
www.SunCam.com
Page 20 of 38
35
10. Ceilings
The Ceilings worksheet also uses outside air temperature for Heating Temperature
Difference. An attic with floor insulation will be as cold as the outdoors, and can be much
warmer than the summer high temperatures. Cooling Load Temperature difference needs to be
input.
Table 4A -- Construction Numbers 16, 17 & 18 -- Ceilings
Construction Number; Type of Ceiling; R-Value; Roof Material and Roof Color
U-Value
CLTD
Although the floor plan example we are using has a second floor over the entire 1600 sq.
ft., we will exercise as if there were an unencapsulated attic above. Use R-40 for typical R-30 in
the 2 x 10 ceiling joists, plus blown in insulation to air seal above the Fiberglas, at a cost of say
$350 in materials. If rafters are spray foamed, account for the extra conditioned roof/ceiling area
and volume later.
From Table 4A, for the Waterbury CLTD of 10F, and medium daily range, choose
CLTD = 45F under a vented attic with dark shingles and no radiant barrier.
Table 4A -- Construction Numbers 16, 17 & 18 -- Ceilings
Construction Number; Type of Ceiling; R-Value; Roof Material and Roof Color
2 x 10 joists with R-40 Fiberglas and blown in Insulation
www.SunCam.com
U-Value
CLTD
0.025
45
Page 21 of 38
The J1 form has the 1600 sq. ft. entered for net area.
.
Heating
Cooling
Net
Heating
Cooling
Net
Construction Detail
HTM
HTM
Area
BTUH
BTUH
Area
10 Ceilings
1.70
1.13
1600
2720
1800
Heating BTUH would be 2720 and Cooling BTUH would be 1800. But it will be erased
from our compiled J1 form because it is not really a load. We have a conditioned second floor
above.
11. Floors
Open the tenth bottom tab for the Floors worksheet.
Table 4A -- Floors
Construction Number 19 -- Floor Over Enclosed Unconditioned Crawlspace or Basement
U-Value
PTDH
PTDC
We must input U-Value = R-19 typically, because blowing in more insulation is difficult.
Heating or cooling escaping to the basement where people enter more frequently is preferred to
heating or cooling escaping to the attic, which is seldom used in winter or summer. So insulation
with low UValue and high R-Value is critical in the attic floor or rafters. Humidity in a
basement is not covered in the Floors worksheet discussion.
Partition Temperature Difference for Heating (PTDH) and Cooling PTDC are from table
4A. Assume a cold leaky uninsulated basement, or modify PTDH for actual delta T.
For HTD = 68F, and an R-19 insulation assembly, PTDH = 53F.
For CTD = 10F, and an R-19 insulation assembly, PTDC = 7.9F.
Table 4A -- Floors
Construction Number 19 -- Floor Over Enclosed Unconditioned Crawlspace or Basement
First Floor 2 x 10 joists over unheated basement R-19
U-Value
PTDH
PTDC
0.053
53.0
7.9
Proceeding to the J-1 Form, considered a passive floor because it does not have radiant
floor coils, although it could be an exposed floor as well, we input the Floor Area = 1600 sq. ft.
www.SunCam.com
Page 22 of 38
1600
Heating
Cooling
Net
Heating
Cooling
Net
Construction Detail
HTM
HTM
Area
BTUH
BTUH
Area
11 Passive Floors
2.81
0.42
1600
4494
670
If we were to examine the basement floor slab, the program calculation rightly
understands that no heat is lost or gained from the ground beneath the slab. But for a slab near a
walkout basement, the perimeter in feet of that exposed slab and its insulation value are input, to
correctly ascertain BTUH for heating.
This concludes the straightforward Conduction heat loss and gain building
components. The next component is the very important Infiltration calculation. From ACCA
provided graphics, here are components for heating and cooling.
www.SunCam.com
Page 23 of 38
1600
12. Infiltration
www.SunCam.com
Page 24 of 38
Envelope Leakage
No. of Fireplaces
Average
Fireplaces: After floor area and volume are typed in, use the yellow Number of
Fireplaces dropdown box to show how many fireplaces are in the zone. The chimney riser from
the combustion boiler below the Mudroom on our floor plan might be losing substantial heat in
the 2 building code air gap between masonry and Douglas fir. While historic older buildings
used the masonry for structural support, new building and fire codes specify separation. Poorly
insulated and leaky walls surrounding this chimney can lose much heat, as air travels up this
corridor. It is difficult to retrofit through finished sheetrock with Great Stuff type foam spray or
ordinary caulk, and special high temperature sealant products may be required. When Energy
Auditors search for air leakage in a house, they zero in on attic hatchways and fireplaces.
www.SunCam.com
Page 25 of 38
The official designation between the five categories is based on Air Changes per Hour
(ACH). ASHRAE 62 recommends 0.35 air changes per hour for mechanical ventilation. By
having a simple visual inspection, it is difficult to ascertain ACH. The most common method is
to conduct a Blower Door Test as fully explained in the SUNCAM Energy Audit of an Existing
House Course. One would convert the pressure at -50 Pascals to ACH depending on climate and
number of house stories and other factors.
www.SunCam.com
Page 26 of 38
www.SunCam.com
Page 27 of 38
Heating BTUH
2593
6717
9963
14877
19644
Cooling BTUH
191
381
545
844
1144
8501
545
So there is a seven fold difference in heating loss load between Tight and Loose for this
condition. And the second fireplace contributes 9963 - 8501 = 1462 BTUH.
Knowing that there is blown in insulation and good Tyvek and energy audit caulking
performed, a value of Semi-Tight is used for our example.
12 Infiltration
Envelope Leakage
Semi-Tight
No. of Fireplaces
1600
Heating
Cooling
BTUH
BTUH
15200
6717
As seen in the table above, 6717 BTUH, (over half a ton) is lost in the Semi-Tight 1600
sq. ft. floor plan example.
Cooling losses are not as significant. If the State and City were changed to Florida and
Fort Lauderdale, Heating BTUH would be 2021 and Cooling BTUH would be 585. For
Southern Climates, an insulated attic makes sense. A report that over 3/4 of US houses have air
conditioning must mean that the percentage is even higher in the South. While heat rises (Is it 3
degrees from floor to ceiling stratification, with no other ventilation as some claim?) allowing
conditioned air to escape through the attic is costly. Giant Exhaust fans that suck up cool air
through bad ceilings and attic hatchways are inefficient overall. Indoor Fans can achieve some
comfort, but would not remove humidity as a condensate pan under an air handler would.
Ceiling fans might have benefit in houses without ducts that should be circulating air more
efficiently and comfortably. If Ridge Vents are not working properly, consider gable end
www.SunCam.com
Page 28 of 38
381
Number of Bedrooms
Occupants
Appliance - 0 BTUH
There are two inputs, the number of bedrooms and the appliances generating heat. The number
of occupants equals the number of bedrooms plus one. Although our example is a first floor, we
can enter 1 bedroom to show two occupants there during cooling season, if pertinent. Note that
occupants supply moisture or Latent Heat that is calculated in the Line 21 cells below as well as
Sensible Cooling on Line 13.
Appliances similarly will add air conditioning, Cooling Load but cannot be depended on
to heat in winter. The yellow drop box allows a choice of 0, 1200 or 2400 BTUH. For a kitchen,
with refrigerator and range, the default is 1200 BTUH. Adding dishwasher and lighting
allowance moves load to 2400 BTUH selected. An additional freezer or washer / drier increases
the Sensible Load to 3400, beyond ae capability.
Although Room loads had not been addressed yet, the program will give a message if
Room load is not matched, so enter 2400 for one of the rooms as shown.
Room-->
13 Internal Gains
Number of Bedrooms
Heating
Cooling
Net
BTUH
BTUH
Area
Occupants
BTUH
Heating
Cooling
460
2400
2400
Besides the 460 BTUH Sensible Cooling Load for Occupants, there is also a latent load
of 400 BTUH on Line 21.
Latent load for occupants
400
This completes the Sensible Heating and Cooling Loads for the House:
Heating
Cooling
BTUH
BTUH
23451
14 Sub Totals
10503
The Sensible Heating Load will be the Total Heating load, but Sensible Cooling plus
Latent Cooling will give Total Cooling Load.
www.SunCam.com
Page 29 of 38
Lines 15 to 19 give three more Load Components to be input: Ducts, Ventilation and
Blower Fan. Ducts and Ventilation add to Sensible Heating and Cooling Loads, while Blower
Fan adds to Cooling only. The five Latent Cooling Loads in Line 21 are populated automatically
as required from these and a future Plant input.
R-Value = 6
0.250
Supply
5851
0.272
1
Return
For our example, the top yellow drop box should be changed to:
7D-T&B SA, RA in Closed Crawlspace or Unconditioned Basement
The R value options are: 2, 4, 6 or 8. Good insulation as shown above can be R-8, which
will be used. If attic ducts were encapsulated totally in several inches of blown in insulation,
ducts might be considered part of the conditioned space for very high R values. But there has
been some concern for mold in humid attics with very thick R-50value cellulose.
Leakage Class default is 0.12/0.24. 0.12 cfm/sq. ft. of exposed duct surface on the
supply line and 0.24 cfm/sq. ft. of exposed duct surface on the return line. Systems leakier than
this should be sealed. Verified tighter systems would be assigned 0.06/0.06 or 0.09/0.15. Poor
ductwork can be worse than 0.35/0.70. If no duct blaster testing by auditor, enter the best
subjective estimate. The example will use 0.24/0.47, because first floor ducts are located in an
unheated but (semi-conditioned) always 60F in winter, basement. Attic ductwork was assumed
to be sealed tighter during construction.
www.SunCam.com
Page 30 of 38
2736
Cooling
BTUH
BTUH
R-Value = 8
0.151
Supply
3550
0.091
300
Return
917
100
Note that the Line 21 Cooling Latent Load exceeds the Sensible Load at1983 versus 917.
There is no Ductwork Latent Heating Load.
1983
Manual D discusses ductwork design in detail. The room cells to the right can be used,
and air flow at about 400 cfm per ton is distributed to each room register according to BTUH
load for that room. This is best done with the unabridged version of Manual J.
16. Ventilation
If outdoor air is processed by the heating and cooling equipment within the building,
and possibly within the conditioned space, it pressurizes or depressurizes it, impacting
infiltration. Account for raw outdoor air used for combustion, or fed into the return duct work.
Check appropriate Furnace or Water Heater or both, for informational purposes, neither of which
affect BTUH results. The yellow drop down box allows choice of 25 or 50 cfm. If more through
ae is specified (for example 53cfm), choose that box.
16 Ventilation
Furnace
Water Heater
None
The example house has a heat pump and boiler located in the basement, so a minimal 25
cfm is selected.
16 Ventilation
Line 21
Furnace
Water Heater
25 CFM
Heating
Cooling
BTUH
BTUH
25
1828
482
Note again that Latent Cooling load of 482 BTUH of moist summertime Waterbury
outside air exceeds Sensible Cooling load of 269 BTUH.
www.SunCam.com
Page 31 of 38
269
Lines 17: Winter Humidification Loss, and 18: Hot Water Piping Loss,
as well as 20: AED Excursion and Latent Moisture Migration Gain
are parts of the unabridged Manual J spreadsheet and not on J ae.
Either the Manufacturer of the Cooling equipment has a blower heat discount figured into
its performance data, or not. A typical zone fan will produce 3412 BTU per hour for half an hour
= 1707 BTUH. The fact that it adds heat in winter is not considered. This is the case for our
work plan example, where amperage was measured for the fan at this rate.
19 Blower Heat Gain
Heating
Cooling
BTUH
BTUH
1707
Cooling
BTUH
BTUH
28829
13438
Almost 2 tons of heating capacity is required at 28,829 BTUH, and 13,438 BTUH
Sensible Cooling. But Total Cooling must be determined. Total Cooling = Sensible Cooling +
www.SunCam.com
Page 32 of 38
Cooling
BTUH
BTUH
684
400
Small
Medium
Large
1983
482
3548
400
Small
Medium
Large
100
1983
482
3648
If the house were instead located in Baton Rouge, LA, Total Latent Gain would be 5961
BTUH and a significantly higher percentage (29%) of the Total Cooling of 20,466 BTUH. The
latent heat removal capacity must be checked for equipment specified.
Back to Waterbury, CT where total cooling = 13,438 + 3648 = 17,086, almost a ton and a
half.
Latent percentage is 3648/17,086 = 21%, within the range of most air conditioning
equipment.
The total can be printed out in black and white to fit on a single 8 x 11 sheet, and is
easily saved as a .pdf to send to clients without the Excel detail.
Final Spreadsheet is as follows:
www.SunCam.com
Page 33 of 38
Project
Waterbury
Connecticut
70
HTD
68
75
@ Outdoor (Summer) 1% db
85
CTD
10
50%
Grains Difference
29
Daily Range
Elevation
850
ACF
Latitude
6A Windows
& Glass
41
Medium
0.978
Block Load
Glass
Heating
Cooling
Net
Heating
Cooling
Direction
Construction Detail
HTM
HTM
Area
BTUH
BTUH
30.60
16.00
15
459
240
E/W
30.60
35.00
151
4621
5285
27.20
8.40
77
2094
647
Doors
6B Skylights
Wood &
Metal
Doors
3.58
0.34
1129
4038
380
2 x 6 R -19
3.60
0.04
217
782
1.16
0.77
41
47
32
5.64
35
198
2.81
1600
4494
670
15200
6717
381
c
d
e
Partition Walls
f
g
a
b
10 Ceilings
a
b
c
d
Partition Ceilings
e
11 Passive Floors
0.42
b
Exposed Floors
Basement Floor
Partition Floors
12 Infiltration
g
Envelope Leakage
Semi-Tight
No. of Fireplaces
13 Internal Gains
1600
460
2400
14 Sub Totals
23451
10503
3550
959
R-Value = 8
0.151
0.091
300
Return
100
25
25 CFM
1828
28829
400
Small
Medium
Large
PeterTavino@gmail.com
100
1983
482
3648
13438
684
www.SunCam.com
269
1707
Page 34 of 38
Summary Sheet
The fourth tab on the bottom of the spreadsheet is for the Summary Sheet. There is no
need to figure percentages of components manually. Note that Infiltration at 23.3% is the largest
single heat loss contributor, while Windows and Glass at 41.1% are the largest Heat Gain
contributor.
Total Area
Construction Components
166
HEAT LOSS
5080
HEAT GAIN
17.62%
5525
41.11%
Skylights
77
2094
7.26%
647
4.81%
1346
4820
16.72%
388
2.89%
32
41
Partition Walls
47
0.16%
35
198
0.69%
4494
15.59%
6717
23.30%
0.23%
Ceilings
Partition Ceilings
1600
Passive Floors
4.99%
670
Exposed Floors
Slab Floors
Basement Floors
Partition Floors
Infiltration
Internal Gains
381
2.84%
2860
21.28%
3550
12.31%
959
7.14%
Ventilation
1828
6.34%
269
2.00%
1707
12.70%
28829
100.00%
13438
100.00%
3648
17086
This completes the ACCA J ae analysis. It provides a good design condition estimate for
observing energy patterns and for sizing equipment. Manual S for Residential Equipment
Selection and Manual H for Heat Pump Systems: Principles and Applications should be studied
before specifying equipment. The best use of this new ACCA J ae skill set is for the engineer to
run the heating and cooling loads, and report them to licensed HVAC contractors (and preferably
ACCA Quality Installer Contractors). Ask them to submit a proposal to install equipment that
matches the heating and cooling output that has been calculated. They may use their ACCA J
third party software programs to confirm the Manual J ae totals before proceeding.
For understanding of how the calculated Loads relate to equipment capacities, consult
performance charts, usually found on-line. If an air source heat pump is desired, for the Total
Cooling Load of 17,086 BTUH = 1.42 ton unit, select a 1 ton heat pump. But heating will be
www.SunCam.com
Page 35 of 38
Carrier
Buderus
Logano 115WS
Air source
Oil
CAPACITIES
1.5-5 ton (for one floor as analyzed)
www.SunCam.com
heat only
Page 36 of 38
Buderus
WaterFurnace
7 Series NV036
Gas
Ground Source
heat only
Conclusion
While many professional engineers taking this course might be members of ASHRAE, it
is ACCA that provides this wonderful free tool for residential heat loss and gain calculations.
Using our own homes as first trials allows us to help others who may wish to understand their
systems in these times of costly energy.
Principles mastered in residential construction allow easy transformation to commercial
buildings and the use of the parallel Manual N software. Knowledge is power. I have been
fortunate to have received good experience with residential heat loss and gain calculation work.
I am grateful that SUNCAM allows this accumulated knowledge to be passed on to the 700
engineers who have enjoyed my past courses, and to those of you now completing this one.
List of Acronyms follows on the last page:
www.SunCam.com
Page 37 of 38
Manual J ae Acronyms
ACCA: Air Conditioning Contractors of America
ACF: Altitude Correction Factor
ACH: Air Changes per Hour
Ae: Abridged Edition
AED: Adequate Exposure Diversity
ASHRAE: American Society of Heating
Refrigeration and Air-conditioning Engineers
BTUH: British Thermal Unit per Hour
CFM50: Cubic Feet of air per Minute at -50 Pascals
CLTD: Cooling Load Temperature Difference (F)
CTD: Cooling Temperature Difference (F)
DR: Daily Range (F)
ELA: Envelope Leakage Area (Sq. Inches)
www.SunCam.com
Page 38 of 38