Sie sind auf Seite 1von 3

PER UNIT QUESTIONS

1. A balanced Y connected voltage source with Eab = 480 0o Volts is applied to a


balanced load with Z = 30 40o. The line impedance between the source and
load is ZL = 1 85o for each phase. Calculate the per-unit and actual current in
phase a of the line using Sbase 3 = 10 kVA and VbaseL-L = 480V.

2. Consider a system with the one line diagram shown in Figure 2. The 3 phase
transformer name plate ratings are listed. The transformer reactances are given in
percent, 10% = 0.1 p.u. the transformer line and load impedance are in actual ohm.
The generator terminal voltage(magnitude) is 13.2 kV(line-to-line). Find the generator
current, the transmissions current, the load current, the load voltage and the power
delivered to the load.
VB1

VB2

VB3

Figure 2

3. Consider the same basic system as in Q2, but with these changes. The generator
voltage and load impedance are not specified. Instead, we are given the following
information. The voltage (magnitude) at the load is 63 kV ad the 3 load power is 5.0
MW at a pf of 0.9 lagging. Find the load current, the generator voltage and the
generator power.

Figure 3

4. Prepare a per phase schematic of the system shown in Figure 4 below and show all
impedances in pu on a 100 MVA, 132 kV base in the transmission line circuit. The
necessary data for this problem are as follow :

G1 = 50 MVA, 122.2 kV,

X = 0.15 PU

G2 = 20 MVA, 13.8 kV,

X = 0.15 PU

T1 = 80 MVA, 12.2 / 161 kV,

X = 0.10 PU

T2 = 40 MVA, 13.8 / 161 kV,

X =0.10 PU

Load = 50 MVA, 0.8 PF lagging, (operating at 154 kV)

Determine the Pu impendence of the load for the following cases:


a) Load modeled as a series combination of resistance and inductance.
b) Load modeled as a parallel combination of resistance and inductance.
40 MVA

80 MVA
12.2 / 161 kV
50 MVA

161 / 13.8 kV

40 + j 160

T2

T1

12.2 kV

20 MVA
13.8 kV

20 + j80

20 + j80

Load

Figure 4

5. Consider the simple power system network shown in Figure 5. The ratings of each
component are given in the Table 6.61.

Table 6.61
Generator

300 MVA

20 kV

X = 0.2

T1

350 MVA

20 / 230 kV

X = 0.1

T2

3 x 1

100 MVA

127 / 13.2 kV

X = 0.1

M1

200 MVA

13.2 kV

X = 0.2

M2

100 MVA

13.2 kV

X = 0.2

Length = 64 Km (40 miles), series reactants = 0.5 / Km

Choose the generators rating as the base rating in the circuit and draw an impedance diagram
for all the reactants in per unit system.

13.2 KV

VB1

VB2
k

T1

VB2
l

VB3
T2

M1
n

G
13.2 KV
300 MVA
20KV

M2
350 MVA
20 / 230KV

100 MVA
127 / 13.2 KV
Per phase

Figure 5

6. If both M1 and M2 motors in Q5 need supply powers of 100MW and 50MW at


13.2kV and 0.8 lagging power factors, find the voltage at the generator.
PM1 = 100 MW, cos = 0.8 lagging
PM2 = 50 MW, cos = 0.8 lagging

Das könnte Ihnen auch gefallen