Beruflich Dokumente
Kultur Dokumente
Learning Objectives
Here is what you will be able to do when you complete each objective:
1. Describe the purpose and function of standard hot water heating system
accessories.
2. Explain how the location of the hot water circulating pump and the expansion
tank are determined.
3. Describe the cleaning, filling, starting, routine operation, and troubleshooting
of hot water heating systems.
4. Apply a hot water heating system troubleshooting guide.
1
HVAC 6017
INTRODUCTION
This module will cover the major accessories of a hot water heating system.
Accessories such as radiators, convectors, and other heating units used in hot
water heating systems are basically the same in design as those used in steam
heating systems. See Module 027-41-54-02 for a description of these units.
ACCESSORIES
Diverter Fittings
Special diverter fittings are required in the one-pipe hot water systems to ensure
an adequate flow of water through each convector.
Fig. 1 illustrates the operation of one type of diverter fitting or tee which is
installed in the return connection of each radiator or convector. This diverter
makes use of a venturi section which reduces the pressure in the return connection
and thus induces a flow of water through the radiator or convector.
Figure 1
Diverter Fitting (Return Type)
Diverter fittings are also used in the supply line to the heating unit when higher
output of the unit is required or when the distance from the unit to the supply
main is quite far.
The supply fitting works the opposite way of the return fitting. It restricts the
flow of the water in the supply main and so forces part of the water into the
supply line to the convector. Fig. 2 illustrates how and where supply and return
type diverter fittings are used.
2
HVAC 6017
Figure 2
Diverter Fitting Applications
Air Vents
The removal of air from a hot water heating system is vitally important for the
proper operation of the system. Air collects in the high spots of piping and
heating units and forms air pockets which restrict or even block the flow of the
water, resulting in insufficient heating. It also can be responsible for noisy
operation of the heating system.
When a hot water system is filled for the first time, much care must be taken to
vent all the air out of the system. This is normally done at the high points of the
system where the air tends to collect, such as the upper parts of the risers and in
radiators and convectors. At start-up, the system should be air-free except for the
air trapped in the expansion tank.
3
HVAC 6017
Cold water, however, always contains a certain amount of dissolved air that is
freed when the water is heated. Air is also absorbed by the cooler water in the
expansion tank during operation. This air will enter the system with the water
that flows from the tank when the temperature of the water in the system drops,
and it is then freed when the temperature is raised again. Therefore, air removal
will be necessary during the warm-up period and during regular operation of the
heating system.
In older systems venting was done manually by opening small petcocks, Fig. 3, on
radiators and convectors, and larger vent valves on the risers.
Figure 3
Petcock
On newer systems automatic air vents are used. Fig. 4 shows a float-operated air
vent commonly installed on the highest part of mains and risers (see Figs. 5 and 6
in Module 027-41-54-03). As long as water is present in the vent body, the float
will hold the vent valve shut. When air collects, the float will drop, thus opening
the vent valve.
Figure 4
Float Type Air Vent
4
HVAC 6017
Fig. 5 shows an automatic vent used on radiators and convectors. The vent uses
composition discs which are hygroscopic (they readily absorb water). As long as
water is in contact with the discs, they will swell or expand and seal off the vent
opening. Any air trapped at the vent will dry the discs and cause them to contract,
thus opening the vent port. The vent can also be manually opened by turning the
cap about 3/4 turn so that the discs do not pack together any longer.
Figure 5
Automatic Air Vent
Air Separators
The air liberated by heating the water should not be allowed to travel to the
various parts of the heating system. Instead, this air should be trapped and either
directed to the expansion tank or vented to the atmosphere.
Two methods are used to remove this air from the water. The first method allows
the air to leave the boiler with the heated water. The air being lighter than water
will generally tend to travel along the upper portion of a horizontal pipe. An air
separator is installed in the first horizontal stretch of the supply piping after the
water leaves the boiler.
A cutaway view of one type of air separator is shown in Fig. 6. This separator
contains a baffle which causes the air bubbles to rise and accumulate in the upper
part of the housing. The bubbles then pass upwards to the expansion tank, which
is directly connected to the separator, where they help to maintain the air cushion,
Fig. 7, or they are vented to atmosphere via an air vent.
5
HVAC 6017
Figure 6
Air Separator
(Courtesy of Dunham-Bush)
Figure 7
Air Separation in Supply Main
In the second method the hot water leaves the boiler through a dip tube extending
several centimetres below the top of the boiler. This prevents the air that collects
at the top of the boiler from leaving with the water. Instead, it passes up to the
expansion tank which is either directly connected to the top of the boiler, Fig. 8,
or to a special fitting which combines the hot water outlet and tank connection, as
is illustrated in Fig. 9.
6
HVAC 6017
Figure 8
Air Separation in Boilers
Figure 9
Airtrol Boiler Fitting
Flow Control Valves
Flow control valves are necessary in each circuit of a multi-zone system to
prevent continued circulation of hot water after the circulator has been stopped by
the zone control. Continued circulation can be caused either by the circulation of
the water in the other circuits connected to the same supply and return mains or
by natural convection currents set up by the temperature difference of the water in
various parts of the circuit (gravity circulation). This may cause overheating of a
zone.
7
HVAC 6017
A cutaway view of a typical flow control valve is shown in Fig. 10. It is basically
a lift type check valve. When the circulator is running, the disc rises to open the
valve; when the circulator stops, the disc closes tightly to prevent gravity flow.
The valve is also equipped with an external adjusting knob or handle by which it
is possible to hold the valve in the open or the closed position if required.
Figure 10
Flow Control Valve
8
HVAC 6017
Circulating Pumps
The pumps used to provide forced circulation in hot water heating systems are of
the electrically driven centrifugal type, usually of single stage design. They must
be capable of operating quietly and reliably for long periods of time without
shutdown.
In small installations, the type known as the in-line circulator is favoured. It is
a low head pump which is installed in and supported by the system piping. It is
driven by an electric motor by means of a flexible coupling, or pump and motor
are close-coupled. In larger systems, pump and motor are usually base-mounted
and connected by a flexible coupling.
Expansion Tanks
A hot water heating system must be equipped with an expansion tank. The
reasons for the use of this tank are the following:
1. When the water in the boiler and system heats up, it expands and, to
prevent excessive pressure buildup due to this expansion, the excess water
is stored in the expansion tank.
2. When water in the boiler and system cools down, it shrinks. In order to
keep the system properly filled, the excess water stored in the tank is
returned to the system so that no makeup water is required except for a
minimal amount to replace water lost due to leakage or blowoff.
3. Since the amount of makeup water can be kept to a minimum, the amount
of water treatment chemicals required to maintain the proper concentration
for protection of the boiler and system can also be kept to a minimum.
The modern hot water system is equipped with a closed expansion tank. A
cushion of air is trapped in the tank and is compressed when water enters the tank
due to a temperature rise in the system. This results in an increase in the system
air pressure and the water pressure.
9
HVAC 6017
BG4_fig11.gif
Figure 11
Diaphragm Type Expansion Tank
Before the heating system is filled, the tank is charged with air up to the pressure
normally maintained by the automatic fill valve so that when the system is
completely filled, no water has entered the expansion tank yet.
10
HVAC 6017
When the system is brought up to temperature, the tank receives the expanded
volume of water and the diaphragm simply flexes against the air cushion.
When an expansion tank contains a flexible diaphragm, air separated from the
water in an air separator or from the top of the boiler cannot be directed to the
expansion tank. Instead, it has to be vented directly to atmosphere by means of an
automatic float vent as is shown in Fig. 11.
Large heating systems often are equipped with expansion tanks which, instead of
having an air cushion above the water, use nitrogen gas as a cushion. Nitrogen,
an inert gas, is less soluble in water than air and does not cause corrosion. A
nitrogen-filled pressure cylinder, connected to the top of the expansion tank via a
pressure reducing valve, will then maintain a pressurized gas cushion in the tank.
11
HVAC 6017
BG4_fig12.gif
Figure 12
Multistory Building Heating by Converters
(Courtesy of Taco Inc.)
A converter arrangement for a hot water heating system is shown in Fig. 13. The
system, apart from the converter, is similar to the conventional hot water system
requiring an expansion tank, relief valve, fill valve, etc.
Referring to Fig. 13, steam from the boiler is fed to the converter and is regulated
by control valve G which senses the temperature of the hot water leaving the
converter. As the steam gives its heat to the water, it condenses, passes through
the steam trap, and is led back to the boiler via the condensate return system. The
circulator C, controlled by thermostat H, draws the water from the converter and
forces it through the heating system and back through the converter again for
reheating.
12
HVAC 6017
Figure 13
Steam-Hot Water Converter System
(Courtesy of Dunham-Bush)
Figure 14
Basic Hot Water System
When the pump is started, it develops a pressure differential (the pump head)
between suction and discharge, and the pressure throughout the system changes,
thus it is not uniform anymore. The pressure in the expansion tank, however, will
not change, assuming that the temperature of the water remains constant so that
no change in volume due to expansion or contraction occurs.
The reason that the pressure in the tank does not change is fairly simple. Any
pressure increase in the tank would compress the air and reduce its volume. The
space vacated by the air would have to be filled by water from the system.
However, since this is a closed system without the means to receive more water,
no water can move from the system into the tank because that would create an
empty space in the system, which is impossible.
A reduction in tank pressure is also impossible because that would result in an
increased air volume and part of the water in the tank would have to be forced
into the system, which is already completely filled. In other words, the pressure
in the expansion tank remains at a constant value. Thus no pressure change takes
place when the pump is started.
Since the pressure at the point where the expansion tank is connected to the
system is practically the same as that in the tank, this point is called the point of
no pressure change.
Since it is desirable that the pressure of the boiler in a hot water system is not
affected by the operation of the circulating pump, the expansion tank, and thus the
point of no pressure change, is nearly always located at or near the boiler. Note
that the boiler is not indicated in Figs. 14 and 15 for clearness sake.
14
HVAC 6017
Figure 15(a)
Main of Closed Hot Water System
Fig. 15(b) illustrates the same system but now the pump is running. It is assumed
that the pressure differential between suction and discharge of the pump is 55 kPa
(8 psig). Since the expansion tank is located on the suction side of the pump and
this is the point of no pressure change, the suction pressure of the pump will
remain 124 kPa (18 psig). However, the pressure on the discharge side is now
boosted by 55 kPa to 179 kPa (26 psig). This 55 kPa pressure is required to force
the water through, and to overcome the friction of, the system. The pressure at
various points in the main will become progressively lower, until it reaches 124
kPa on the suction side again.
15
HVAC 6017
Figure 15(b)
Fig. 15(c) illustrates the same system as Fig. 15(b) except that the expansion tank
is now connected to the discharge side of the pump and this point becomes the
point of no pressure change. The pressure here remains 124 kPa. The pressure
differential developed by the pump now appears as a negative pressure and the
suction pressure of the pump will be reduced by 55 kPa to 69 kPa (10 psig).
Again this pressure differential is required to move the water through the system
and to overcome friction. The pressure at various points in the main will now
become progressively lower until it reaches 69 kPa on the suction side of the
pump.
Figure 15(c)
16
HVAC 6017
Fig. 15(d) illustrates the same system as Fig. 15(c), but in this diagram the pump
develops a pressure differential of 207 kPa (30 psig) when running. Since the
expansion tank is connected at the discharge side of the pump, the pressure
differential developed by the pump appears as a negative pressure. Under these
conditions part of the system will be at a pressure above, and the remainder of the
system at a pressure below atmospheric pressure. The lowest pressure will occur
at the suction side of the pump where it is reduced from 124 kPa (18 psig) to a
negative pressure of 124 kPa - 207 kPa = -83 kPa (-12 psig).
Figure 15(d)
Severe operating problems would occur in this system. Should the temperature of
the water at the pump suction be over 57C (135F), vapor bubbles would form
which cause cavitation in the pump. Also, since part of the system operates at
below atmospheric pressure, air may be sucked into the system creating additional
problems.
It was discussed earlier that normally the expansion tank is either directly
connected to the boiler or to the hot water supply line near the boiler. This places
the boiler at the point of no pressure change, therefore, boiler pressure is not
affected by the location of the circulating pump as long as the circulating pump is
not between the boiler and the expansion tank.
17
HVAC 6017
A minimum pressure of 83 kPa (12 psi) indicated on the boiler pressure gage
(8.5 m or 28 feet of water on the altitude gage) should be maintained on all hot
water heating systems of smaller buildings, such as residences and single-story
commercial buildings where the boiler and circulator are usually located on the
lowest level. Any drop in pressure below this value will cause the pressure
reducing valve in the water supply line to open and to feed water into the system
until pressure has returned to normal.
The circulator in smaller systems normally produces only a slight pressure
differential and, even when it is placed in the return line, a pressure of 83 kPa (12
psi) will assure that sufficient positive pressure is maintained at the highest points
in the system.
There is no specific reading for the pressure or altitude gage on boilers in large
hot water systems. These readings differ considerably depending on the location
of the boiler, which may be placed in the basement, penthouse, or any floor inbetween. The pump, which usually develops quite a high pressure differential, is
generally installed in the supply line, thus it draws water from the boiler, and the
pressure throughout the system is increased during operation.
As a general rule, the minimum reading on the altitude gage of a boiler in a large
hot water system can be determined by taking the distance from the top of the
boiler to the highest point in the system and adding 1.2 m (4 ft). For example, if
the highest point of the heating system is 19.8 m (65 ft) above the top of the
boiler, the altitude gage on the boiler should indicate at least 21 m (69 ft) of water
head. Considering that 1 m of water head is equivalent to a pressure of 9.81 kPa,
a pressure gage on the boiler should indicate at least 21 x 9.81 = 206 kPa. For a
pressure gage indicating in psi, the minimum reading would be
69 x 0.433 = 30 psi.
When boiler and circulator are placed on the top floor, as is common in large
high-rise buildings, the value of the water head given above may have to be
increased in order to supply sufficient suction head for the circulator to prevent
cavitation or vapor binding. Always make sure that the pressure is high enough to
give the pump the required net positive suction head (NPSH).
The pressure reducing valve (automatic fill valve) on the system should be set to
maintain adequate pressure in the system.
18
HVAC 6017
19
HVAC 6017
A clean hot water system should never be drained except for an emergency or the
necessary servicing of equipment which may be needed after years of operation.
Antifreeze solutions in systems should be tested from year to year as
recommended by the manufacturers of the antifreeze used.
2. Admit water to the system with the automatic fill valve set to supply
adequate pressure to the highest point of the system.
3. Vent each radiator and convector unit and all the high points of the
system.
4. When the system is completely filled and vented, check the altitude gage
on the boiler. Readjust the automatic fill valve if necessary to obtain the
proper pressure in the system.
5. Check the water level in the expansion tank. The water should just be
showing in the bottom of the gage glass.
6. Switch on the power supply to the boiler and circulator and start up the
boiler.
7. Warm up the boiler, and circulate the water through the entire system.
Any air bubbles clinging to the inside walls of piping and the boiler will
be removed and either vented or directed into the expansion tank. Air
dissolved in the cold water will also be freed and removed.
8. Check the entire system over for proper operation. Any irregularities or
leaks should be corrected.
9. When the boiler temperature reaches the maximum setting, shut off the
burner, stop the circulator, and vent all parts of the system once again.
10. Set the controls to commence normal operation.
20
HVAC 6017
USE OF ANTIFREEZE
When the heating system is exposed to freezing temperatures, an antifreeze
solution may be used instead of water. If this is the case, the following points
should be regarded:
1. Make sure the antifreeze used is not corrosive to the piping and other parts
of the system. Many manufacturers of antifreeze solutions include a
corrosion inhibitor in their products.
2. Since antifreeze will expand more than water, a larger expansion tank will
be required.
3. Antifreeze has a greater density than water, therefore, more power will be
required for the circulating pump.
4. Since antifreeze will not carry as much heat as water it must be kept at a
higher temperature.
5. Before using antifreeze in an old system, make sure the system has been
thoroughly flushed out and cleaned by circulating a solution of trisodium
phosphate through the system for 3 or 4 hours. Use
1 kg/500 L of water (1 lb/50 Imp. gal).
6. Antifreeze mixtures are harmful if swallowed and must be kept out of
reach of children.
Circulating Pump
Check the operation of the pump regularly. If equipped with a stuffing box, make
sure it does not drip excessively. Lubricate the pump and motor according to
manufacturers recommendation.
Expansion Tank
Check the level regularly to make sure that the air cushion is maintained. If the
tank becomes waterlogged, recharge it with air.
22
HVAC 6017
TROUBLESHOOTING GUIDE
HOT WATER HEATING SYSTEMS
COMPLAINT: Insufficient heat throughout building
TROUBLE
POSSIBLE CAUSE
CORRECTION
Boiler water
Temperature
too low.
1.
a) Check power supply to boiler
and various control circuits
b) Raise setting of temperature
operating control and/or
outdoor reset control Replace
controls if defective
c) Repair or replace fuel valve
d) Find reason for flame failure,
correct trouble
2.
3.
a) Clean nozzle
b) Remove any obstruction from
air supply openings or ducts
c) Adjust dampers to give
required amount of air
d) Adjust belt tension
e) Reduce air supply by
adjusting dampers
4. Shut boiler down and inspect
heating surface on fire and
water side. Clean when
necessary. To prevent
reoccurrence a) improve
water treatment and b) check
combustion.
23
HVAC 6017
TROUBLE
POSSIBLE CAUSE
CORRECTION
Main supply
Header temperature
too low
1. See above
1.
a) Check power supply to pump
and controls. It may have
been switched off by mistake.
If breaker tripped, electrical
trouble in motor or
mechanical trouble in pump
should be suspected.
b) Check setting of controls. If
defective replace.
Insufficient
circulation
2. Clean screen
POSSIBLE CAUSE
CORRECTION
Supply water
temperature
too low
1. See above
24
HVAC 6017
TROUBLE
POSSIBLE CAUSE
CORRECTION
Insufficient
circulation
POSSIBLE CAUSE
CORRECTION
Insufficient
circulation
3. As above
5. Replace thermostat
25
HVAC 6017
TROUBLE
POSSIBLE CAUSE
CORRECTION
1.
a) Check power supply to fan.
Check 3 speed switch
b) Clean or replace filter
c) Check operation of damper
control
b) filter plugged
c) dampers misadjusted
3. Adjust dampers
5. Shorten curtains
POSSIBLE CAUSE
CORRECTION
Noisy circulator
1. Faulty bearings
2. Impeller unbalanced
3. Cavitation in pump
a) suction restricted
3.
a) Check that size of pump
suction complies with that
recommended for the pump
b) Raise system pressure
c) Lower water temperature
Piping
Convectors
2. Casing vibrates
Renew bearings
26
HVAC 6017