Standby Power (3D)

Standby Power ratings apply to installations served by a reliable utility source. The standby ratings are
applicable to varying loads for the duration of a power outage. Quoted ratings are in accordance with ISO 3046
and represent maximum power.
Typical applications: industrial and manufacturing plants, residential areas, healthcare and hospitals, airports

Cooling

kWm

kVA1)

kWe1)

6R 1600 G70F

274

300

240

A2A

Download

6R 1600 G80F

301

330

264

A2A

Download

8V 1600 G70F

358

400

320

A2A

Download

8V 1600 G80F

394

440

352

A2A

Download

10V 1600 G70F

448

500

400

A2A

Download

10V 1600 G80F

493

550

440

A2A

Download

12V 1600 G70F

576

650

520

A2A

Download

12V 1600 G80F

634

715

572

A2A

Download

12V 2000 G25

635

715

572

A2A

Download

12V 2000 G25

635

715

572

W2A

Download

12V 2000 G76F

732

825

660

A2A

Download

12V 2000 G65

765

860

688

A2A

Download

12V 2000 G65

765

860

688

W2A

Download

12V 2000 G86F

887

1000

800

A2A

Download

16V 2000 G25

890

1000

800

A2A

Download

16V 2000 G25

890

1000

800

W2A

Download

16V 2000 G65

975

1100

880

A2A

Download

16V 2000 G65

975

1100

880

W2A

Download

16V 2000 G76F

979

1110

888

A2A

Download

18V 2000 G65

1100

1250

1000

A2A

Download

16V 2000 G86F

1100

1250

1000

A2A

Download

Engine model

variant2)

Spec Sheets

13-08-2015 14:11

Diesel engines for standby applications - 50 Hz: MTU Online

2 of 4

http://www.mtu-online.com/mtu/products/engine-program/diesel-engin...

Cooling

kWm

kVA1)

kWe1)

18V 2000 G65

1100

1250

1000

W2A

Download

18V 2000 G76F

1235

1400

1120

A2A

Download

12V 4000 G23

1575

1800

1440

W2A

Download

12V 4000 G63

1750

2000

1600

W2A

Download

16V 4000 G23

1965

2250

1800

W2A

Download

16V 4000 G63

2185

2500

2000

W2A

Download

20V 4000 G23

2420

2800

2240

W2A

Download

20V 4000 G63

2670

3100

2480

W2A

Download

20V 4000 G63L

2850

3300

2640

W2A

Download

Engine model

variant2)

Spec Sheets

Standby Power with overload (3E)

Standby Power with Overload ratings apply to installations served by a reliable utility source. The standby
ratings are applicable to varying loads for the duration of a power outage. Quoted ratings are in accordance with
ISO 3046 and are capable of 10% overload.
Typical applications: industrial and manufacturing plants, residential areas, healthcare and hospitals, airports

Cooling

kWm

kVA1)

kWe1)

12V 4000 G23

1420

1600

1280

W2A

Download

12V 4000 G63

1575

1800

1440

W2A

Download

16V 4000 G23

1798

2100

1680

W2A

Download

16V 4000 G63

1965

2250

1800

W2A

Download

20V 4000 G23

2200

2500

2000

W2A

Download

20V 4000 G63

2420

2800

2240

W2A

Download

20V 4000 G63L

2590

3000

2400

W2A

Download

Engine model

variant2)

Spec Sheets

Data Center Continuous Power (3F)

Data Center Continuous Power ratings apply to data center installations where a reliable utility power is available
and comply with Uptime Institute Tier III and IV requirements. At constant or varying load, the number of
generator set operating hours is unlimited. Quoted ratings are in accordance with ISO 3046 and are capable of
10% overload.
Typical applications: data centers

Engine model

12V 4000 G23

kWm

kVA1)

kWe1)

1420

1600

1280

Cooling
variant2)
W2A

Spec Sheets

Download

13-08-2015 14:11

Diesel engines for standby applications - 50 Hz: MTU Online

3 of 4

http://www.mtu-online.com/mtu/products/engine-program/diesel-engin...

Cooling

kWm

kVA1)

kWe1)

12V 4000 G63

1575

1800

1440

W2A

Download

16V 4000 G23

1798

2100

1680

W2A

Download

16V 4000 G63

1965

2250

1800

W2A

Download

20V 4000 G23

2200

2500

2000

W2A

Download

20V 4000 G63

2420

2800

2240

W2A

Download

20V 4000 G63L

2590

3000

2400

W2A

Download

Engine model

variant2)

Spec Sheets

Mission Critical Power (3H)

Mission Critical Power ratings apply to installations served by a reliable utility source. The ratings are applicable
to varying loads for the duration of a power outage. Quoted ratings are in accordance with ISO 3046 and are
capable of 10% overload.
Typical applications: public and governmental buildings / infrastructure, hospitals, storm avoidance programs

Cooling

kWm

kVA1)

kWe1)

12V 4000 G23

1420

1600

1280

W2A

Download

12V 4000 G63

1575

1800

1440

W2A

Download

16V 4000 G23

1798

2100

1680

W2A

Download

16V 4000 G63

1965

2250

1800

W2A

Download

20V 4000 G23

2200

2500

2000

W2A

Download

20V 4000 G63

2420

2800

2240

W2A

Download

20V 4000 G63L

2590

3000

2400

W2A

Download

Engine model

variant2)

Spec Sheets

NPP Standby Power (3C)

NPP Standby Power ratings apply to installations in thermal power stations. At constant or varying load, the
number of generator set operating hours is unlimited. Quoted ratings are in accordance with ISO 3046 and are
capable of 10% overload. Products are qualified in accordance with IEEE and / or KTA requirements.
Typical applications: nuclear thermal power plants or nuclear research facilities

Cooling

kWm

kVA1)

kWe1)

12V 4000 E63(3), (4)

1560

1800

1440

W2A

16V 4000 E63(3), (4)

2080

2400

1920

W2A

20V 4000 E63(4)

2600

3000

2400

W2A

12V 956 TB34(3)

3900

4400

3520

W2A

16V 956 TB34(3)

5200

5820

4656

W2A

Engine model

variant2)

13-08-2015 14:11

Diesel engines for standby applications - 50 Hz: MTU Online

4 of 4

Engine model

20V 956 TB34

http://www.mtu-online.com/mtu/products/engine-program/diesel-engin...

kWm

kVA1)

kWe1)

6500

7275

5820

Cooling
variant2)
W2A

1) The quoted typical kVA / kWe ratings are based on typical generator efficiencies.

The kVA figures are calculated with a 0.8 power factor.


Typical deductions for fan drive power and generator efficiency is applied for calculation and serves
as guideline only.
2) A2A: Air-to-air charge air cooling / W2A: Water-to-air charge air cooling