Beruflich Dokumente
Kultur Dokumente
#090 11/06
INSTRUCTION MANUAL
PACKAGE CHILLER
PACKAGE CHILLER
INSTRUCTION MANUAL
for D1 Series
1 - 10 Tons
Air-Cooled Package Chillers
COVERING
INSTALLATION
OPERATION
MAINTENANCE
TABLE OF CONTENTS
1.0
GENERAL
1.1
Unit location
1.2
Efficiency
1.3
Safety
1.4
Clean air act
1.5
Miscellaneous
1.6
Components
7
8
8
8
9
9
10
2.0
INSTALLATION
2.1
General
2.2
Unit location
2.3
To and from process connections
2.4
Manual fill port
2.5
Electrical connection
11
12
12
12
13
13
3.0
OPERATIONS
3.1
General
3.2
Start up/operations procedure
3.3
Instrument/operation
3.4
Shut down procedure
17
18
19
23
28
4.0
TROUBLESHOOTING
4.1
Unit will not start
4.2
Compressor hums but will not start
4.3
Shuts off on high pressure control
4.4
Shuts off on low pressure control
4.5
Compressor shuts off on internal overload
4.6
Low or now process pressure or water flow
4.7
Cooling capacity inadequate
4.8
Sensor
4.9
Pumps
4.10
Crankcase heater
4.11
M1 Chiller Instrument
29
30
30
30
31
31
31
32
32
32
33
33
5.0
MAINTENANCE
5.1
Warranty service procedure
5.2
Periodic preventative maintenance
5.3
Special maintenance
5.5
Pump seal service
5.6
Checking the refrigerant charge
5.7
Proper cleaning procedure for brazed plate evaporators
35
36
36
37
38
41
42
6.0
COMPONENTS
6.1
Water system
6.2
Refrigeration system
45
46
46
Page: 4
7.0
APPENDIX
7.1
Operations with fluid temperatures below 48F
and/or ambient temperatures below 35f
7.2
Inhibited propylene glycol
7.3
Water quality control
7.4
Sensor current vs temperature
7.5
Pressure-temperature chart for R-22 refrigerant
7.6
Chiller capacity and derate chart
7.7
Air-Cooled Schematic
49
50
51
51
52
53
54
55
Page: 5
Page: 6
1.0
GENERAL
1.1
1.2
1.3
1.4
1.5
1.6
UNIT LOCATION
EFFICIENCY
SAFETY
CLEAN AIR ACT
MISCELLANEOUS
COMPONENTS
Page: 7
1.1
1.2
UNIT LOCATION
A.
The chiller is designed for outdoor or indoor use. For most efficient
operation, locate the chiller in a clean and well ventilated
environment.
B.
C.
D.
E.
F.
EFFICIENCY
A.
1.3
SAFETY
A.
B.
Page: 8
C.
1.4
1.5
B.
C.
MISCELLANEOUS
A.
B.
C.
Page: 9
1.6
COMPONENTS
Air-cooled condenser
Compressor (not visible)
Reservoir
Liquid Receiver
Electrical Cabinet
Evaporator
Coolant Pump
Refrigerant Limits
Page: 10
2.0
INSTALLATION
2.1
2.2
2.3
2.4
2.5
GENERAL
UNIT LOCATION
TO AND FROM PROCESS CONNECTIONS
MANUAL FILL PORT
ELECTRICAL CONNECTION
Page: 11
2.1
2.2
2.3
GENERAL
A.
B.
UNIT LOCATION
A.
B.
Air flow is generated by the motor driven fan located inside the
condensing unit. Air flow is from the outside of the chiller, through
the condenser and exhausted through the top of the unit.
C.
A free air space of at least four (4) feet is required at the condenser
intake and six (6) feet at the condenser discharge to allow for
proper air flow.
D.
B.
C.
D.
Page: 12
Manual Fill :
From Process :
Connect to Water Out
port on process manifold
To Process :
Connect to Water In port
on process manifold
2.3
2.4
Use the Manual Fill port to fill the units reservoir and the process.
1.
Connect the units manual fill port to the plants city water
source.
2.
3.
ELECTRICAL CONNECTION
A.
Page: 13
B.
C.
D.
The units supplied control circuit is 110 volt, 1 phase, 60 cycle. The
control circuit is supplied by the factory installed transformer. An
inline control circuit fuse is provided.
E.
GENERAL
F.
1.
2.
3.
4.
2.
Page: 14
Transformer
Power Entry
Electrical Cabinet
Control Instrument
Electrical Cabinet
Page: 15
Page: 16
3.0
OPERATIONS
3.1
3.2
3.3
3.4
GENERAL
START UP/OPERATIONS PROCEDURE
INSTRUMENT/OPERATION
SHUT DOWN
Page: 17
3.1
GENERAL
A.
B.
C.
3.3
3.4
Page: 18
3.2
B.
SYSTEM FILL
1.
2.
3.
b.
Page: 19
d.
Toggle the
illuminated ON/OFF
SWITCH (figure
3.2C). This will
quickly cycle the
pump motor on
and then off.
On/Off switch
2.
Figure 3.2C
e.
f.
Page: 20
C.
b.
c.
2.
3.
The operator must determine and set proper water flow rate
for the most efficient and trouble free operation.
a.
b.
b.
Page: 21
4.
b.
5.
If an excessive flow
situation is
encountered and the
motor overload
circuit has tripped,
the operator must
manually reset the
overload relay
(figure 3.2E) before
operations can
continue.
Figure 3.2E
This is done by
opening the electrical panel cover, identifying the
reset lever on the overload relay, and pushing the
reset lever in until the overloads are reset
(evidenced by a clicking sound as the overloads
reset).
b.
c.
d.
Page: 22
f.
g.
h.
3.3
Figure 3.2G
INSTRUMENT/OPERATION
A.
GENERAL
1.
2.
3.
Figure 3.3A
Page: 23
Figure 3.3C
Instrument display
B.
Figure 3.3B
INSTRUMENT START-UP
1.
2.
Page: 24
3.
Precautions:
The chiller control is programmed from the factory with a
setpoint range of 48 to 90F. To operate below 48F or if
the ambient conditions where the chiller is installed will
reach temperature below 35F, the addition of inhibited
propylene glycol is required.
If a setpoint of 48F or less is required, then additional
modification of the limit switch setting is also required.
Diligent monitoring of the water/glycol solution is mandatory
to prevent freezing of the evaporator. Freezing may cause
the evaporator to rupture allowing water and freon to mix
which will cause major damage to the refrigeration system.
Operating above 70F requires the addition of a refrigerant
crankcase pressure regulating (CPR) valve. The CPR valve
is necessary to prevent overloading of the compressor and
to reduce return gas temperatures that cool the compressor
windings which can cause premature failure.
Contact your local refrigeration contractor or the factory for
further information about the proper use of inhibited
propylene glycol and modification of limit switches.
4.
B.
INSTRUMENT OPERATION
1.
2.
3.
4.
Page: 25
C.
INSTRUMENT CONTROLS
1.
2.
3.
Figure 3.3D
Setpoint Lock Out Jumper
Page: 26
D.
4.
5.
STATUS LIGHTS
1.
2.
3.
E.
TEMPERATURE DISPLAY
1.
2.
Page: 27
F.
3.4
PRESSURE GAUGES
1.
2.
3.
.
SHUT DOWN/DISCONNECT SEQUENCE
A.
PRECAUTIONS/WARNINGS
1.
B.
2.
b.
b.
c.
b.
c.
Page: 28
4.0
TROUBLESHOOTING
4.1
4.2
4.3
4.4
4.5
4.6
4.7
4.8
4.9
4.10
4.11
Page: 29
4.1
4.2
4.3
B.
C.
D.
B.
C.
D.
Air-cooled units:
1.
2.
B.
C.
Page: 30
D.
4.4
The low pressure switch will automatically resets when the pressure
rises above the cut-in pressure. If this does not occur contact the
Advantage service department for instructions.
The low pressure switch is set to cut-out at 58 psi and cut-in at 63
psi. If a low pressure condition exists for more than five seconds the
compressor will stop and a L-P fault will appear in the display
window.
After the refrigerant pressure rises above the cut-in pressure, a
three minute time delay will occur before the compressor restarts.
This will protect the evaporator and compressor from damage
should a problem occur in the refrigeration system or if the chiller is
operated under circumstances which could cause damage to the
refrigeration system.
A.
Air-cooled units:
Head pressure too low. Low pressure flooding control not
operating properly. Have unit diagnosed by a refrigerant
serviceman.
B.
C.
D.
2.
3.
4.
Page: 31
4.5
4.6
4.7
4.8
B.
Pump. Check pump for correct rotation. Check pump suction for
restriction. Replace motor if defective.
C.
D.
Fuses and wiring. Have electrician check the fuses and wiring.
B.
C.
D.
E.
SENSOR
The sensor is a solid state temperature transducer which converts
temperature input to proportional current output. To quickly test for a
defective probe, switch connections between the defective probe
and a probe known to be working properly. A defective sensor will
display a --- in the display window on the instrument control.
4.9
PUMPS
A.
Page: 32
much flow can overload the motor and cause the overload circuit to
open and stop the pump.
4.10
4.11
B.
C.
Check the amp draw and if overloaded, partially close the from
process line valve until the amp draw drops to the proper level.
CRANKCASE HEATER
A.
B.
M1 CHILLER INSTRUMENT
A.
The display is used for all normal set ups, diagnostics, temperature
readout, and operational information. Note: the display is not field
repairable. It can be easily removed and replaced if required.
B.
Page: 33
Page: 34
5.0
MAINTENANCE
5.1
5.2
5.3
5.4
5.5
5.6
Page: 35
5.1
5.2
B.
C.
D.
Lubricate all motors. Note that some motors are supplied with
sealed bearings.
B.
C.
D.
E.
Clean condenser fins of dust and dirt (air cooled models only).
F.
G.
H.
Page: 36
5.3
I.
J.
Clean unit.
SPECIAL MAINTENANCE
A.
2.
3.
Addition of refrigerant.
4.
5.
6.
7.
8.
Page: 37
5.4
B.
C.
Rotating Member
Tension Spring
Figure 5.5A
The operator should follow this procedure to replace the pump seal:
1.
2.
3.
4.
5.
Pump motor
Figure 5.5B
Pump motor
Figure 5.5C
Page: 38
7.
8.
9.
10.
Figure 5.5D
Impeller
Figure 5.5E
Motor shaft
Figure 5.5F
Typical impeller
Figure 5.5G
Page: 39
11.
12.
13.
14.
15.
16.
E.
Seal components
Figure 5.5H
Stationary member
Figure 5.5I
Stationary member
Figure 5.5J
Seal members
Figure 5.5K
17.
18.
19.
Page: 40
5.5
B.
Figure 5.6A
1.
2.
3.
4.
Page: 41
5.6
B.
C.
2.
3.
4.
5.
Page: 42
6.
FREON OUT
FREON IN
Page: 43
Page: 44
6.0
COMPONENTS
6.1
6.2
WATER SYSTEM
REFRIGERATION SYSTEM
Page: 45
6.1
WATER SYSTEM
A.
6.2
REFRIGERATION SYSTEM
A.
B.
C.
D.
E.
Typical pump
Figure 6.1A
Typical compressor
Figure 6.2A
Typical filter-drier
Figure 6.2B
Figure 6.2C
Page: 46
G.
Figure 6.2D
H.
I.
J.
K.
Page: 47
Page: 48
7.0
APPENDIX
7.1
7.2
7.3
7.4
7.5
7.6
7.7
Page: 49
7.1
B.
C.
OPERATING
TEMPERATURE
D.
ANTI-FREEZE MIXTURE
GLYCOL
WATER
30F - 47F
30%
70%
20F - 29F
40%
60%
OPERATING
TEMPERATURE
LOW
CUT-IN
LOW
CUT-OUT
48F - 70F
63 #
58 #
20F - 47F
45 #
30 #
Figure 8.1A
Figure 8.1B
AMBIENT
TEMPERATURE
GLYCOL
WATER
above 35F
0%
100%
20F - 34F
30%
70%
0F - 19F
40%
60%
below 0F
50%
50%
Figure 8.1C
Page: 50
7.2
B.
7.3
Lack of, as well as, improper water treatment can damage the
chilling unit. The services of a competent water treatment specialist
should be obtained and their recommendations followed. It is the
equipment owners responsibility to prevent damage from foreign
material or inadequate water treatment.
B.
The two main things to consider for water treatment in chillers are
corrosion and organism growth. Proper chemical treatment can
control PH levels and algae growth. An alternative to chemical
treatment is the addition of 20% inhibited propylene glycol to the
water. This will help prevent organism growth and coat the heat
transfer surfaces with corrosion inhibitor.
Page: 51
7.4
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
243.86
249.43
255.00
260.57
266.14
271.71
277.27
282.84
288.41
293.98
299.55
305.12
310.69
316.26
321.82
327.39
332.96
338.53
344.10
349.67
355.24
360.80
366.37
371.64
377.51
383.08
388.65
394.22
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
Formula:
1 u A = (556.8627 x 10 x F) = (255 x 10)
F = (1 u A - 255 x 10) + (556.8627 x 10)
Battery
9 volt
Microammeter
White wire
Black wire
Page: 52
7.5
SATURATED TEMPERATURE
FREON PRESSURE
40F
68
45F
76
50F
84
55F
93
60F
100
65F
112
70F
122
75F
132
80F
144
85F
156
90F
168
95F
182
100F
196
Page: 53
7.6
Standard chiller rating is at 50F. For all other temperature settings, output
tonnage is altered as follows:
OUTPUT FULL
TEMPERATURE AVAILABLE %
F CAPACITY
60
105%
50
100%
45
90%
40
80%
35
70%
30
60%
25
50%
20
40%
15
30%
*
10
22%
*
5
15%
*
0
9%
*
-5
5%
*
NOTES:
If operation of the chiller at less than 48F is required, an inhibited propylene glycol solution
is required.
Consult factory for chiller operation below 20F.
Ambient conditions affect air cooled chiller operation and capacity. Standard rating is at 95F
entering air temperature. For ambient air conditions greater than 95F, chiller derating will
occur. For ambient of 95-105F, select the next larger capacity chiller. For ambient over
105F, consult factory.
* These ranges require special options.
Page: 54
SERVICE
VALVE
FILTER-DRIER
LIQUID LINE
RECEIVER
COMPRESSOR
(may be Scroll Hermetic or Recip)
LIQUID LINE
SOLENOID VALVE
REFRIGERANT
SIGHT GLASS
HOT GAS
BYPASS VALVE
EXPANSION VALVE
COOLANT PUMP
TO PROCESS
SENSOR PROBE
TO PROCESS
PORT CONNECTION
FROM PROCESS
PORT CONNECTION
TO PROCESS
PRESSURE GAUGE
FROM PROCESS
TEMPERATURE SENSOR
EVAPORATOR
RESERVOIR TANK
SUCTION LINE
PRESSURE GAUGE
7.7
LOW PRESSURE
SAFETY SWITCH
Page: 55
Page: 56
END
2005 ADVANTAGE ENGINEERING, INC.
RE 1 12/06