AECS Engineering & Geotechnical Services (P) Ltd.

Deisgn of Contiguous pile system for side D


Sandeep Giri
Analysis of slope retention strucutre for c/o double basement

Sheeting structure design


Input data
Project
Task
Part
Description
Customer
Author
Date

:
:
:
:
:
:

Deisgn of Contiguous pile system for side D


Analysis of slope retention strucutre for c/o double basement
C/O Commercial Building at Plot No. - 41, Phase-III, Okhla Industrial Area, New Delhi.
M/S. Morpho Genesis
Sandeep Giri
26-Feb-16

Settings
India - Standard
Pressure analysis
Active earth pressure calculation :
Passive earth pressure calculation :
Earthquake analysis :
Verification methodology :

Coulomb
Caquot-Kerisel
Mononobe-Okabe
Safety factors (ASD)

Basic soil parameters


No.
1

Name
Silty sand with gravels

Pattern

jef

cef

gsu

[]

[kPa]

[kN/m3]

[kN/m3]

31.00

0.00

17.50

10.00

d
[]
20.00

Soil parameters
Silty sand with gravels
Unit weight :
Stress-state :
Angle of internal friction :
Cohesion of soil :
Angle of friction struc.-soil :
Saturated unit weight :

g = 17.50 kN/m3
effective
jef = 31.00
cef =
0.00 kPa
d = 20.00
gsat = 20.00 kN/m3

Geological profile and assigned soils


No.

Layer
[m]

Assigned soil

Pattern

Silty sand with gravels

1
[GEO5 - Sheeting Design | version 5.2016.7.0 | hardware key 8512 / 1 | AECS Engineering and Geotechnical Services Pvt. Ltd. | Copyright 2015 Fine spol. s r.o. All Rights Reserved |
www.finesoftware.eu]
[Ram Caddsys Pvt Ltd | +91 44 24898532| sales@ramcadds.in| http://www.ramcadds.com]

AECS Engineering & Geotechnical Services (P) Ltd.


Deisgn of Contiguous pile system for side D
Sandeep Giri
Analysis of slope retention strucutre for c/o double basement
Name : Profile and assignment

Stage - analysis : 1 - 0

Geometry of structure
Soil in front of wall is excavated to a depth of 10.00 m.
Inserted props
No.
1
2

New Depth Length Spacing Inclination


prop z [m] l [m]
b [m]
a []
Yes
5.00 18.00
3.20
0.00
Yes
1.00 18.00
3.20
0.00

Terrain profile
Terrain behind the structure is flat.
Water influence
Ground water table is located below the structure.

2
[GEO5 - Sheeting Design | version 5.2016.7.0 | hardware key 8512 / 1 | AECS Engineering and Geotechnical Services Pvt. Ltd. | Copyright 2015 Fine spol. s r.o. All Rights Reserved |
www.finesoftware.eu]
[Ram Caddsys Pvt Ltd | +91 44 24898532| sales@ramcadds.in| http://www.ramcadds.com]

AECS Engineering & Geotechnical Services (P) Ltd.


Deisgn of Contiguous pile system for side D
Sandeep Giri
Analysis of slope retention strucutre for c/o double basement
Input surface surcharges
No.
1
No.
1

Surcharge
new
change
Yes

Action
permanent

Mag.1
[kN/m2]
30.00

Mag.2
[kN/m2]

Ord.x
x [m]

Length
l [m]

Depth
z [m]
on terrain

Name
Nominal Suecharge

Name : Surcharge

Stage - analysis : 1 - 0

Settings of the stage of construction


Design situation : permanent

Verification No. 1
Design of anchored sheeting wall hinged at heel
Coeff. of reduction of passive pressure = 1.00
A minimum dimensioning pressure was considered when computing the active pressure.
3
[GEO5 - Sheeting Design | version 5.2016.7.0 | hardware key 8512 / 1 | AECS Engineering and Geotechnical Services Pvt. Ltd. | Copyright 2015 Fine spol. s r.o. All Rights Reserved |
www.finesoftware.eu]
[Ram Caddsys Pvt Ltd | +91 44 24898532| sales@ramcadds.in| http://www.ramcadds.com]

AECS Engineering & Geotechnical Services (P) Ltd.


Deisgn of Contiguous pile system for side D
Sandeep Giri
Analysis of slope retention strucutre for c/o double basement
Computed depth of the zero-value point u = 0.59 m
Max. value of shear force
Max. value of moment
Required depth of structure in soil
Overall length of structure

= 153.02 kN/m
= 157.49 kNm/m
=
1.90 m
= 11.90 m

Prop forces
No.
1
2

Depth
z [m]
5.00
1.00

Prop force
[kN]
773.91
33.18

Distribution of pressure and internal forces along the structure


Depth
[m]

Total Pressure
[kPa]
0.00
1.00
1.00
1.67
2.33
3.00
3.67
4.33
5.00
5.00
5.71
6.43
7.14
7.86
8.57
9.29
10.00
10.63
11.27
11.90

Shear Force
[kN/m]
8.07
12.78
12.78
15.92
19.05
22.19
25.33
28.47
31.61
31.61
34.97
38.33
41.70
45.06
48.42
51.78
55.15
-3.97
-63.08
-122.20

Moment
[kNm/m]
0.00
-10.42
-0.06
-9.62
-21.28
-35.03
-50.87
-68.80
-88.83
153.02
129.24
103.06
74.47
43.49
10.10
-25.68
-63.87
-80.11
-58.84
0.00

0.00
4.82
4.82
7.93
18.11
36.77
65.28
105.06
157.49
157.49
56.54
-26.57
-90.11
-132.38
-151.67
-146.25
-114.40
-66.74
-20.67
0.00

4
[GEO5 - Sheeting Design | version 5.2016.7.0 | hardware key 8512 / 1 | AECS Engineering and Geotechnical Services Pvt. Ltd. | Copyright 2015 Fine spol. s r.o. All Rights Reserved |
www.finesoftware.eu]
[Ram Caddsys Pvt Ltd | +91 44 24898532| sales@ramcadds.in| http://www.ramcadds.com]

AECS Engineering & Geotechnical Services (P) Ltd.


Deisgn of Contiguous pile system for side D
Sandeep Giri
Analysis of slope retention strucutre for c/o double basement
Stage - analysis : 1 - 1

200.00 -200.00
[kNm/m]
-150.00

1.31

0.59

10.00
773.91kN

33.18kN

Geometry of structure
Length of structure = 11.90 m
Depth in soil = 1.90 m

150.00
[kPa]

-151.67

-200.00

Bending moment
Max. M = 157.49 kNm/m

157.49

-88.83

-80.11

-10.42 -0.06

Shear force
Max. Q = 153.02 kN/m

153.02

200.00
[kN/m]

Name : Analysis

5
[GEO5 - Sheeting Design | version 5.2016.7.0 | hardware key 8512 / 1 | AECS Engineering and Geotechnical Services Pvt. Ltd. | Copyright 2015 Fine spol. s r.o. All Rights Reserved |
www.finesoftware.eu]