BASIS OF DESIGN
-ELECTRICAL SYSTEM

JAZAN INTEGRATED GASIFICATION COMBINED CYCLE


(JIGCC) PROJECT

DISCIPLINE
ENGINEER
_______________
DATE _________
PROJECT
ENGINEER
_______________

PACKAGE NO. 06, SEA WATER SYSTEM

DATE _________
CERTIFIED
_______________
DATE _________
CONSTRUCTION
AGENCY
_______________
DATE _________
OPERATIONS
_______________

REVISION CERTIFICATION

DATE: __________

-----------------------------CONTROL NUMBER
BY: ____________

THIS INDICATES THAT REV. NO. ______


OF THIS DOCUMENT IS COVERED,
FOR ALL APPROVAL / CERTIFICATION
REQUIREMENTS, BY DOCUMENT
COMPLETION CERTIFICATE
(DCC) NO. ___________

EDSD VERIFICATION

DATE _________

00

28/01/16

Issue for Review

MXX

YL

CW

A00

28/09/14

Issue for Review

ZSY

YL

CW

Rev

Date

Description

Prep

Chk

App

Proj

SAPMT

CHEC Revision History (to be removed after IFP issue)

BASIS OF DESIGN
ELECTRICAL SYSTEM

DWG. TYPE

DOC

PACKAGE NO. 06, SEA WATER SYSTEM


JAZAN

SAUDI ARABIA

PLANT

INDEX

DOC.

SHT.

REV.

A61

VE-383332

1
of
51

00

JOB ORDER NO. 10-01525-0006

THIS DOCUMENT AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN WHOLE OR PART SHALL BE MADE WITHOUT THE PRIOR WRITTEN CONSENT OF THE OWNER.

CERT

PMT

OPRNS

SAUDI ARABIAN OIL COMPANY

CERT

1.DOCUMENT PURPOSE ..................................................................................11

ENGG

TABLE OF CONTENTS

1.1 Scope .................................................................................................11

DESCRIPTION

1.2 Definitions...........................................................................................11
2

STANDARD&REFERENCE SAUDI ARAMCO STANDARDS / MATERIAL


SYSTEM SPECIFICATIONS .......................................................................13

JO/EWO

2.1 Conflicts and Deviations ....................................................................18


2.2 References .........................................................................................18

DATE

2.3 Language ...........................................................................................19

REV NO.

3.SCOPE .............................................................................................................20
4 FACILITIES DESCRIPTION .............................................................................22

DISCIPLINE
ENGINEER
_______________

4.1 Cooling Water Inlet Canal ..................................................................22

DATE _________

4.2 Cooling Water Inlet Structures ...........................................................22

PROJECT
ENGINEER
_______________

4.3 Inlet Pumping Station .........................................................................22

DATE _________

4.4 Intake Channel ...................................................................................22

CERTIFIED

4.5 In-Plant Lagoon ..................................................................................22

_______________
DATE _________

4.6 Bypass Channel .................................................................................22

CONSTRUCTION
AGENCY
_______________

4.7 Collection Basin & Discharge Channel ..............................................22

DATE _________

4.8 Basin, Overflow Channel & Submarine Outfall Pipes .......................23

OPERATIONS
_______________

REVISION CERTIFICATION

DATE: __________

-----------------------------CONTROL NUMBER
BY: ____________

THIS INDICATES THAT REV. NO. ______


OF THIS DOCUMENT IS COVERED,
FOR ALL APPROVAL / CERTIFICATION
REQUIREMENTS, BY DOCUMENT
COMPLETION CERTIFICATE
(DCC) NO. ___________

EDSD VERIFICATION

DATE _________

5 ELECTRICAL POWER DISTRIBUTION ..........................................................24


6 SUBSTATION BUILDINGS ..............................................................................30
7 ELECTRICAL EQUIPMENT .............................................................................32
7.1 13.8kV Switchgears ...........................................................................32
7.2 480V Switchgear ................................................................................32

BASIS OF DESIGN
ELECTRICAL SYSTEM

DWG. TYPE

DOC

PACKAGE NO. 06, SEA WATER SYSTEM


JAZAN

SAUDI ARABIA

PLANT

INDEX

DOC.

SHT.

REV.

A61

VE-383332

2
of
51

00

JOB ORDER NO. 10-01525-0006

THIS DOCUMENT AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN WHOLE OR PART SHALL BE MADE WITHOUT THE PRIOR WRITTEN CONSENT OF THE OWNER.

PMT

OPRNS

SAUDI ARABIAN OIL COMPANY

7.4 Low Voltage Panelboards ..................................................................34

ENGG

7.5 Transformers ......................................................................................34

DESCRIPTION

8 PROTECTION AND METERING .....................................................................36


9 AC&UPS SYSTEM ...........................................................................................37
10 DC SYSTEM ...................................................................................................38

JO/EWO

11 MOTORS ........................................................................................................39

DATE

12 CABLING AND WIRING .................................................................................40

REV NO.

13 LIGHTING AND RECEPTACLES ..................................................................43


14 GROUNDING .................................................................................................46

DISCIPLINE
ENGINEER
_______________

15 SYSTEM STUDIES ........................................................................................48


16 POWER SYSTEM AUTOMATION .................................................................50

DATE _________
PROJECT
ENGINEER
_______________

17 ELECTRICAL INTERFACES .........................................................................51

DATE _________
CERTIFIED
_______________
DATE _________
CONSTRUCTION
AGENCY
_______________
DATE _________
OPERATIONS
_______________

-----------------------------CONTROL NUMBER
BY: ____________

DATE: __________

EDSD VERIFICATION
REVISION CERTIFICATION

THIS INDICATES THAT REV. NO. ______


OF THIS DOCUMENT IS COVERED,
FOR ALL APPROVAL / CERTIFICATION
REQUIREMENTS, BY DOCUMENT
COMPLETION CERTIFICATE
(DCC) NO. ___________

DATE _________

BASIS OF DESIGN
ELECTRICAL SYSTEM

DWG. TYPE

DOC

PACKAGE NO. 06, SEA WATER SYSTEM


JAZAN

SAUDI ARABIA

PLANT

INDEX

DOC.

SHT.

REV.

A61

VE-383332

3
of
51

00

JOB ORDER NO. 10-01525-0006

THIS DOCUMENT AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN WHOLE OR PART SHALL BE MADE WITHOUT THE PRIOR WRITTEN CONSENT OF THE OWNER.

PMT

7.3 480V Motor Control Centers ..............................................................33

CERT

OPRNS

SAUDI ARABIAN OIL COMPANY

REV NO.

DATE

JO/EWO

DESCRIPTION

AC

DISCIPLINE
ENGINEER
_______________

Alternating Current

AFD

Adjustable Frequency Drive

AGR

Acid gas Removal Unit

AOC

Aramco Overseas Company

ASU

Air Separation Unit

BEDD

Basic Engineering Design Data

BFW

Boiler Feed Water Pump

BLD

Buildings

DATE _________
PROJECT
ENGINEER
_______________
DATE _________
CERTIFIED
_______________
DATE _________

CADD

Computer Aided Design & Drafting

CONSTRUCTION
AGENCY
_______________
DATE _________

CCB

Combined Cycle Block

CCR

Central Control Room

CCW

Closed Cooling Water System

CGT

Combustion Gas Turbine Generator

OPERATIONS
_______________

-----------------------------CONTROL NUMBER
BY: ____________

DATE: __________

EDSD VERIFICATION
REVISION CERTIFICATION

THIS INDICATES THAT REV. NO. ______


OF THIS DOCUMENT IS COVERED,
FOR ALL APPROVAL / CERTIFICATION
REQUIREMENTS, BY DOCUMENT
COMPLETION CERTIFICATE
(DCC) NO. ___________

DATE _________

BASIS OF DESIGN
ELECTRICAL SYSTEM

DWG. TYPE

DOC

PACKAGE NO. 06, SEA WATER SYSTEM


JAZAN

SAUDI ARABIA

PLANT

INDEX

DOC.

SHT.

REV.

A61

VE-383332

4
of
51

00

JOB ORDER NO. 10-01525-0006

THIS DOCUMENT AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN WHOLE OR PART SHALL BE MADE WITHOUT THE PRIOR WRITTEN CONSENT OF THE OWNER.

PMT

The following acronyms and abbreviations are used in this document:

ENGG

List of Acronyms & Abbreviations

CERT

OPRNS

SAUDI ARABIAN OIL COMPANY

Communication Systems

ENGG

Current Transformer

DC

Direct Current

DCS

Distributed Control Systems

EAS

Engineering Automation System

ESD

Emergency Shutdown System

ETAP

Electrical Transient Analyzer Program

FEED

Front End Engineering & Development

GAC

Generator Auxiliary Cabin

GEC

Generator Excitation Cabin

GFU

Gasification Unit

GIS

Gas Insulated Switchgear

HOC

Houston Operating Center

REV NO.

DATE

JO/EWO

CT

DESCRIPTION

CERT

COM

DISCIPLINE
ENGINEER
_______________
DATE _________
PROJECT
ENGINEER
_______________
DATE _________
CERTIFIED
_______________
DATE _________
CONSTRUCTION
AGENCY
_______________
DATE _________
OPERATIONS
_______________

-----------------------------CONTROL NUMBER
BY: ____________

DATE: __________

EDSD VERIFICATION
REVISION CERTIFICATION

THIS INDICATES THAT REV. NO. ______


OF THIS DOCUMENT IS COVERED,
FOR ALL APPROVAL / CERTIFICATION
REQUIREMENTS, BY DOCUMENT
COMPLETION CERTIFICATE
(DCC) NO. ___________

DATE _________

HP

BASIS OF DESIGN
ELECTRICAL SYSTEM

High Pressure

DWG. TYPE

DOC

PACKAGE NO. 06, SEA WATER SYSTEM


JAZAN

SAUDI ARABIA

PLANT

INDEX

DOC.

SHT.

REV.

A61

VE-383332

5
of
51

00

JOB ORDER NO. 10-01525-0006

THIS DOCUMENT AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN WHOLE OR PART SHALL BE MADE WITHOUT THE PRIOR WRITTEN CONSENT OF THE OWNER.

PMT

OPRNS

SAUDI ARABIAN OIL COMPANY

ENGG

HRC

Hazard Risk Category

HVAC

HVN

High Voltage Neutral

IED

Intelligent Electronic Device

IPR

Main and interconnecting Pipe Racks

IRP

Interface Relay Panel

ISF

Industrial Support Facility

JZR

Jazan Refinery

KSM

Knowledge Skill Matrix

LAN

Local Area Network

REV NO.

DATE

JO/EWO

Heating, Ventilation, Air Conditioning

DISCIPLINE
ENGINEER
_______________
DATE _________
PROJECT
ENGINEER
_______________
DATE _________
CERTIFIED
_______________
DATE _________
CONSTRUCTION
AGENCY
_______________
DATE _________
OPERATIONS

LP

_______________

Low Pressure

-----------------------------CONTROL NUMBER
BY: ____________

DATE: __________

EDSD VERIFICATION
REVISION CERTIFICATION

THIS INDICATES THAT REV. NO. ______


OF THIS DOCUMENT IS COVERED,
FOR ALL APPROVAL / CERTIFICATION
REQUIREMENTS, BY DOCUMENT
COMPLETION CERTIFICATE
(DCC) NO. ___________

DATE _________

LRC

Locked Rotor Current

LSTK

Lump sum Turn Key

BASIS OF DESIGN
ELECTRICAL SYSTEM

DWG. TYPE

DOC

PACKAGE NO. 06, SEA WATER SYSTEM


JAZAN

SAUDI ARABIA

PLANT

INDEX

DOC.

SHT.

REV.

A61

VE-383332

6
of
51

00

JOB ORDER NO. 10-01525-0006

THIS DOCUMENT AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN WHOLE OR PART SHALL BE MADE WITHOUT THE PRIOR WRITTEN CONSENT OF THE OWNER.

Hydrogen Production Unit

CERT

HPU

DESCRIPTION

PMT

OPRNS

SAUDI ARABIAN OIL COMPANY

Low Voltage

ENGG

Millions Barrels per Calendar Day

MBOD

Millions Barrels per Operating Day

MCC

Motor Control Centre

MEC

Monterrey Execution Centre

MMS

Machine Monitoring System

MOV

Motor Operated Valves

REV NO.

DATE

JO/EWO

MBCD

DESCRIPTION

CERT

LV

DISCIPLINE
ENGINEER
_______________
DATE _________

MP

Medium Pressure

OA

Operating Area

PROJECT
ENGINEER
_______________
DATE _________
CERTIFIED
_______________
DATE _________
CONSTRUCTION
AGENCY
_______________

OAS

Operator Automation System

OME

Operating, Maintenance & Engineering

ONAF

Oil Natural Forced Air Cooled

ONAN

Oil Natural Air Natural Cooled

DATE _________
OPERATIONS
_______________

-----------------------------CONTROL NUMBER
BY: ____________

DATE: __________

EDSD VERIFICATION
REVISION CERTIFICATION

THIS INDICATES THAT REV. NO. ______


OF THIS DOCUMENT IS COVERED,
FOR ALL APPROVAL / CERTIFICATION
REQUIREMENTS, BY DOCUMENT
COMPLETION CERTIFICATE
(DCC) NO. ___________

DATE _________

OOK

BASIS OF DESIGN
ELECTRICAL SYSTEM

Out of Kingdom

DWG. TYPE

DOC

PACKAGE NO. 06, SEA WATER SYSTEM


JAZAN

SAUDI ARABIA

PLANT

INDEX

DOC.

SHT.

REV.

A61

VE-383332

7
of
51

00

JOB ORDER NO. 10-01525-0006

THIS DOCUMENT AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN WHOLE OR PART SHALL BE MADE WITHOUT THE PRIOR WRITTEN CONSENT OF THE OWNER.

PMT

OPRNS

SAUDI ARABIAN OIL COMPANY

Optical Fiber Ground Wire

ENGG

Off sites pipe Lines & Pipe Racks

OSE

On-Stream Efficiency

P&ID

Piping & Instrumentation Diagram

PCC

Power Control Center

PDI

Electrical Power Distribution and Interconnection

PDS

Plant Design System

REV NO.

DATE

JO/EWO

OPR

DESCRIPTION

CERT

OPGW

DISCIPLINE
ENGINEER
_______________
DATE _________

PEECC

Packaged Electrical Electronic Control Center

PROJECT
ENGINEER
_______________

PF

DATE _________

Power Factor

CERTIFIED
_______________
DATE _________
CONSTRUCTION
AGENCY
_______________

PGB

Power Generation Block

PIB

ProcessInterfaceBuilding

PPE

Personnel Protective Equipment

PSA

Power System Automation

RTU

Remote Telemetry Unit

DATE _________
OPERATIONS
_______________

-----------------------------CONTROL NUMBER
BY: ____________

DATE: __________

EDSD VERIFICATION
REVISION CERTIFICATION

THIS INDICATES THAT REV. NO. ______


OF THIS DOCUMENT IS COVERED,
FOR ALL APPROVAL / CERTIFICATION
REQUIREMENTS, BY DOCUMENT
COMPLETION CERTIFICATE
(DCC) NO. ___________

DATE _________

BASIS OF DESIGN
ELECTRICAL SYSTEM

DWG. TYPE

DOC

PACKAGE NO. 06, SEA WATER SYSTEM


JAZAN

SAUDI ARABIA

PLANT

INDEX

DOC.

SHT.

REV.

A61

VE-383332

8
of
51

00

JOB ORDER NO. 10-01525-0006

THIS DOCUMENT AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN WHOLE OR PART SHALL BE MADE WITHOUT THE PRIOR WRITTEN CONSENT OF THE OWNER.

PMT

OPRNS

SAUDI ARABIAN OIL COMPANY

Saudi Aramco Engineering Procedures

Saudi Aramco Engineering Standards

ENGG

SAMSS

Saudi Aramco Material System Specification

SCADA

Supervisory Control and Data Acquisition

SEC

Saudi Electricity Company

SFC

Static Frequency Converter

REV NO.

DATE

JO/EWO

SAES

DESCRIPTION

CERT

SAEP

SS

DISCIPLINE
ENGINEER
_______________
DATE _________

Substation

SSD

Safety and Security Directives

STG

Steam Turbine Generator

STM

Steam, BFW and Condensate System

SWA

Sea Water Area

SWA

Sour Water Stripper

TNK

Tank Form

UPS

Uninterruptible Power supply

PROJECT
ENGINEER
_______________
DATE _________
CERTIFIED
_______________
DATE _________
CONSTRUCTION
AGENCY
_______________
DATE _________
OPERATIONS
_______________

-----------------------------CONTROL NUMBER
BY: ____________

DATE: __________

EDSD VERIFICATION
REVISION CERTIFICATION

THIS INDICATES THAT REV. NO. ______


OF THIS DOCUMENT IS COVERED,
FOR ALL APPROVAL / CERTIFICATION
REQUIREMENTS, BY DOCUMENT
COMPLETION CERTIFICATE
(DCC) NO. ___________

DATE _________

BASIS OF DESIGN
ELECTRICAL SYSTEM

DWG. TYPE

DOC

PACKAGE NO. 06, SEA WATER SYSTEM


JAZAN

SAUDI ARABIA

PLANT

INDEX

DOC.

SHT.

REV.

A61

VE-383332

9
of
51

00

JOB ORDER NO. 10-01525-0006

THIS DOCUMENT AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN WHOLE OR PART SHALL BE MADE WITHOUT THE PRIOR WRITTEN CONSENT OF THE OWNER.

PMT

OPRNS

SAUDI ARABIAN OIL COMPANY

ENGG

VSD

Variable Speed Drive

WAN

Wide Area Network

WTS

Water Treatment Systems

WWT

Waste Water Treatment

JO/EWO
DATE
REV NO.
DISCIPLINE
ENGINEER
_______________
DATE _________
PROJECT
ENGINEER
_______________
DATE _________
CERTIFIED
_______________
DATE _________
CONSTRUCTION
AGENCY
_______________
DATE _________
OPERATIONS
_______________

-----------------------------CONTROL NUMBER
BY: ____________

DATE: __________

EDSD VERIFICATION
REVISION CERTIFICATION

THIS INDICATES THAT REV. NO. ______


OF THIS DOCUMENT IS COVERED,
FOR ALL APPROVAL / CERTIFICATION
REQUIREMENTS, BY DOCUMENT
COMPLETION CERTIFICATE
(DCC) NO. ___________

DATE _________

BASIS OF DESIGN
ELECTRICAL SYSTEM

DWG. TYPE

DOC

PACKAGE NO. 06, SEA WATER SYSTEM


JAZAN

SAUDI ARABIA

PLANT

INDEX

DOC.

SHT.

REV.

A61

VE-383332

10
of
51

00

JOB ORDER NO. 10-01525-0006

THIS DOCUMENT AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN WHOLE OR PART SHALL BE MADE WITHOUT THE PRIOR WRITTEN CONSENT OF THE OWNER.

Virtual Local Area Network

CERT

VLAN

DESCRIPTION

PMT

OPRNS

SAUDI ARABIAN OIL COMPANY

CERT

1.DOCUMENT PURPOSE

ENGG

This design basis describes the minimum requirements for the design,
drawings, fabrication, testing and installation of Electrical System.
1.1 Scope

DESCRIPTION

This document applies to the supply and installation of the electrical systems
and equipment used in the Sea Water Unit of the Integrated Gasification
Combined Cycle (IGCC) Project in Jazan, Saudi Arabia.

JO/EWO

1.2 Definitions

COMPANY

Means Saudi Arabian Oil Company, Saudi


Aramco and Companies affiliated thereto,
including but not limited to Aramco Overseas
Company (AOC) and/or Aramco Services
Company (ASC).

CONTRACTOR

Means the organization that has a contractual


arrangement or a prospective contractual
arrangement with the COMPANY to perform
Design, Engineering, Procurement and
Construction services under this project
proposal.

SUBCONTRACTOR(S)

Means an organization or organizations


contracted by and wholly responsible to
CONTRACTOR for executing a specific part of
the WORK.

VENDOR

Means an organization that has a contractual


arrangement with CONTRACTOR or a
prospective contractual arrangement with
CONTRACTOR to supply equipment, materials
and/or services including documentation.

WORK

Means all the work and services to be


performed by CONTRACTOR under a
contractual arrangement with the COMPANY.

MUST

Defines a mandatory contractual or legal


requirement or action.

REV NO.

DATE

The following definitions apply to this document:

DISCIPLINE
ENGINEER
_______________
DATE _________
PROJECT
ENGINEER
_______________
DATE _________
CERTIFIED
_______________
DATE _________
CONSTRUCTION
AGENCY
_______________
DATE _________
OPERATIONS
_______________

-----------------------------CONTROL NUMBER
BY: ____________

DATE: __________

EDSD VERIFICATION
REVISION CERTIFICATION

THIS INDICATES THAT REV. NO. ______


OF THIS DOCUMENT IS COVERED,
FOR ALL APPROVAL / CERTIFICATION
REQUIREMENTS, BY DOCUMENT
COMPLETION CERTIFICATE
(DCC) NO. ___________

DATE _________

BASIS OF DESIGN
ELECTRICAL SYSTEM

DWG. TYPE

DOC

PACKAGE NO. 06, SEA WATER SYSTEM


JAZAN

SAUDI ARABIA

PLANT

INDEX

DOC.

SHT.

REV.

A61

VE-383332

11
of
51

00

JOB ORDER NO. 10-01525-0006

THIS DOCUMENT AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN WHOLE OR PART SHALL BE MADE WITHOUT THE PRIOR WRITTEN CONSENT OF THE OWNER.

PMT

OPRNS

SAUDI ARABIAN OIL COMPANY

Defines a mandatory contractual requirement or


action.

SHOULD

Defines a desirable or recommended outcome


or action;

WILL

Defines an intended outcome or action.

MAY

Defines freedom of choice.

DESCRIPTION
JO/EWO
DATE
REV NO.
DISCIPLINE
ENGINEER
_______________
DATE _________
PROJECT
ENGINEER
_______________
DATE _________
CERTIFIED
_______________
DATE _________
CONSTRUCTION
AGENCY
_______________
DATE _________
OPERATIONS
_______________

-----------------------------CONTROL NUMBER
BY: ____________

DATE: __________

EDSD VERIFICATION
REVISION CERTIFICATION

THIS INDICATES THAT REV. NO. ______


OF THIS DOCUMENT IS COVERED,
FOR ALL APPROVAL / CERTIFICATION
REQUIREMENTS, BY DOCUMENT
COMPLETION CERTIFICATE
(DCC) NO. ___________

DATE _________

BASIS OF DESIGN
ELECTRICAL SYSTEM

DWG. TYPE

DOC

PACKAGE NO. 06, SEA WATER SYSTEM


JAZAN

SAUDI ARABIA

PLANT

INDEX

DOC.

SHT.

REV.

A61

VE-383332

12
of
51

00

JOB ORDER NO. 10-01525-0006

THIS DOCUMENT AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN WHOLE OR PART SHALL BE MADE WITHOUT THE PRIOR WRITTEN CONSENT OF THE OWNER.

SHALL

ENGG

CERT

PMT

OPRNS

SAUDI ARABIAN OIL COMPANY

CERT

2 STANDARD&REFERENCE SAUDI ARAMCO STANDARDS /


MATERIAL SYSTEM SPECIFICATIONS

ENGG

This project shall be designed and implemented in accordance with the latest
revision of applicable Saudi Aramco Standards.

DESCRIPTION

For special equipment not covered by Saudi Aramco Standards, industry


standards and manufacturer's recommendations for installation will be
followed. However, COMPANY agreement is required before accepting nonSaudi Aramco (industry or manufacturer) standards.

REV NO.

DATE

JO/EWO

The following Saudi Aramco Engineering Standards, as a minimum, are


applicable to this document including the standard installation drawings
referenced therein. CONTRACTOR shall verify and finalize the full list of
applicable standards during detailed engineering.

DISCIPLINE
ENGINEER
_______________
DATE _________

A00-A-DOC-VE722623

Project Design Data

A00-P-DOC-VE721940

Power System Automation Philosophy

A00-A-FPP-VA722020

Overall JIGCC Plot Plan

A00-P-E1L-VA721950

Overall IGCC One Line Diagram

A61-P-E1L-VA746200

SLDG of Genral Power System

A61-P-E1L-VA746199

Switchgear legend & Symbol Sheet

14-SAMSS-531

Material System Specification - Power Transformers

PROJECT
ENGINEER
_______________
DATE _________
CERTIFIED
_______________
DATE _________
CONSTRUCTION
AGENCY
_______________
DATE _________
OPERATIONS
_______________

-----------------------------CONTROL NUMBER
BY: ____________

DATE: __________

EDSD VERIFICATION
REVISION CERTIFICATION

THIS INDICATES THAT REV. NO. ______


OF THIS DOCUMENT IS COVERED,
FOR ALL APPROVAL / CERTIFICATION
REQUIREMENTS, BY DOCUMENT
COMPLETION CERTIFICATE
(DCC) NO. ___________

DATE _________

BASIS OF DESIGN
ELECTRICAL SYSTEM

DWG. TYPE

DOC

PACKAGE NO. 06, SEA WATER SYSTEM


JAZAN

SAUDI ARABIA

PLANT

INDEX

DOC.

SHT.

REV.

A61

VE-383332

13
of
51

00

JOB ORDER NO. 10-01525-0006

THIS DOCUMENT AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN WHOLE OR PART SHALL BE MADE WITHOUT THE PRIOR WRITTEN CONSENT OF THE OWNER.

PMT

OPRNS

SAUDI ARABIAN OIL COMPANY

Material System Specification - Three-Phase Dry type


Transformers

14-SAMSS-536

Material System Specification - Pad Mounted, Three


Phase Distribution Transformers

15-SAMSS-502

Material System Specification Medium Voltage Power


cables 5kV through 35kV

16-SAMSS-502

Material System Specification Metal Enclosed, Metal


Clad Indoor Low Voltage Switchgear Assemblies

16-SAMSS-503

Material System Specification Indoor Control gear


Low voltage

16-SAMSS-504

Material System Specification Indoor Metal-Clad


switchgear: 1 to 38kV

16-SAMSS-506

Material System Specification Indoor Control gear


High Voltage

16-SAMSS-507

Material System Specification High Voltage Motor


Controller-Outdoor

16-SAMSS-512

Material System Specification -Out door SwitchrackLow Voltage

16-SAMSS-513

Material System Specification Power System


Automation Components

REV NO.

DATE

JO/EWO

DESCRIPTION

ENGG

CERT

14-SAMSS-533

DISCIPLINE
ENGINEER
_______________
DATE _________
PROJECT
ENGINEER
_______________
DATE _________
CERTIFIED
_______________
DATE _________
CONSTRUCTION
AGENCY
_______________
DATE _________
OPERATIONS
_______________

-----------------------------CONTROL NUMBER
BY: ____________

DATE: __________

EDSD VERIFICATION
REVISION CERTIFICATION

THIS INDICATES THAT REV. NO. ______


OF THIS DOCUMENT IS COVERED,
FOR ALL APPROVAL / CERTIFICATION
REQUIREMENTS, BY DOCUMENT
COMPLETION CERTIFICATE
(DCC) NO. ___________

DATE _________

BASIS OF DESIGN
ELECTRICAL SYSTEM

DWG. TYPE

DOC

PACKAGE NO. 06, SEA WATER SYSTEM


JAZAN

SAUDI ARABIA

PLANT

INDEX

DOC.

SHT.

REV.

A61

VE-383332

14
of
51

00

JOB ORDER NO. 10-01525-0006

THIS DOCUMENT AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN WHOLE OR PART SHALL BE MADE WITHOUT THE PRIOR WRITTEN CONSENT OF THE OWNER.

PMT

OPRNS

SAUDI ARABIAN OIL COMPANY

Material System Specification - Control and Protective


Relay panel Indoor

16-SAMSS-517

Material System Specification - AFD system 1kV and


above

16-SAMSS-518

Material System Specification Low Voltage Panel


Boards

16-SAMSS-520

Material System Specification Cable Bus

16-SAMSS-521

Material System Specification Indoor Automatic


Transfer Switch

16-SAMSS-523

Material System Specification-Metal Enclosed Isolated


Phase Bus- Indoor and outdoor

17-SAMSS-004

Material System Specification Conventional


Transformer/Rectifier for Cathodic Protection

17-SAMSS-005

Material System Specification Cathodic Protection


Phase Controlled rectifier

17-SAMSS-006

Material System Specification Galvanic Anodes for


Cathodic Protection

17-SAMSS-007

Material System Specification Impressed Current


Anodes for Cathodic Protection

17-SAMSS-008

Material System Specification Junction Boxes for

REV NO.

DATE

JO/EWO

DESCRIPTION

ENGG

CERT

16-SAMSS-514

DISCIPLINE
ENGINEER
_______________
DATE _________
PROJECT
ENGINEER
_______________
DATE _________
CERTIFIED
_______________
DATE _________
CONSTRUCTION
AGENCY
_______________
DATE _________
OPERATIONS
_______________

-----------------------------CONTROL NUMBER
BY: ____________

DATE: __________

EDSD VERIFICATION
REVISION CERTIFICATION

THIS INDICATES THAT REV. NO. ______


OF THIS DOCUMENT IS COVERED,
FOR ALL APPROVAL / CERTIFICATION
REQUIREMENTS, BY DOCUMENT
COMPLETION CERTIFICATE
(DCC) NO. ___________

DATE _________

BASIS OF DESIGN
ELECTRICAL SYSTEM

DWG. TYPE

DOC

PACKAGE NO. 06, SEA WATER SYSTEM


JAZAN

SAUDI ARABIA

PLANT

INDEX

DOC.

SHT.

REV.

A61

VE-383332

15
of
51

00

JOB ORDER NO. 10-01525-0006

THIS DOCUMENT AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN WHOLE OR PART SHALL BE MADE WITHOUT THE PRIOR WRITTEN CONSENT OF THE OWNER.

PMT

OPRNS

SAUDI ARABIAN OIL COMPANY

17-SAMSS-502

Material System Specification Form Wound Induction


Motors 500HP and Above

17-SAMSS-503

Material System Specification Severe Duty Totally


Enclosed Squirrel Cage Induction Motors to 500HP

17-SAMSS-511

Material System Specification Stationary Storage


Batteries

17-SAMSS-514

Material System Specification - Battery Rectifier /


Charger

17-SAMSS-515

Material System Specification Auxiliary Electrical


Systems for skid mounted equipment

17-SAMSS-516

Material System Specification Un-Interruptible Power


Supply System

17-SAMSS-518

Material System Specification Diesel Generator Sets

17-SAMSS-520

Material System Specification Form Wound Brushless


Synchronous motors

SAES-O-207

Engineering Standard Power Supply for Security


System

SAES-O-204

Engineering Standard Security Lighting

SAES-P-100

Engineering Standard - Basic Power System Design

REV NO.

DATE

JO/EWO

DESCRIPTION

ENGG

CERT

Cathodic Protection

DISCIPLINE
ENGINEER
_______________
DATE _________
PROJECT
ENGINEER
_______________
DATE _________
CERTIFIED
_______________
DATE _________
CONSTRUCTION
AGENCY
_______________
DATE _________
OPERATIONS
_______________

REVISION CERTIFICATION

DATE: __________

-----------------------------CONTROL NUMBER
BY: ____________

THIS INDICATES THAT REV. NO. ______


OF THIS DOCUMENT IS COVERED,
FOR ALL APPROVAL / CERTIFICATION
REQUIREMENTS, BY DOCUMENT
COMPLETION CERTIFICATE
(DCC) NO. ___________

EDSD VERIFICATION

DATE _________

BASIS OF DESIGN
ELECTRICAL SYSTEM

DWG. TYPE

DOC

PACKAGE NO. 06, SEA WATER SYSTEM


JAZAN

SAUDI ARABIA

PLANT

INDEX

DOC.

SHT.

REV.

A61

VE-383332

16
of
51

00

JOB ORDER NO. 10-01525-0006

THIS DOCUMENT AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN WHOLE OR PART SHALL BE MADE WITHOUT THE PRIOR WRITTEN CONSENT OF THE OWNER.

PMT

OPRNS

SAUDI ARABIAN OIL COMPANY

SAES-P-101

Engineering Standard - Regulated Vendors list for


Electrical Equipment

SAES-P-103

Engineering Standard - UPS and DC systems

SAES-P-104

Engineering Standard -Wiring Methods and Materials

SAES-P-107

Engineering Standard - Overhead Distribution Systems

SAES-P-111

Engineering Standard - Grounding

SAES-P-113

Engineering Standard - Motors and Generators

SAES-P-114

Engineering Standard - Power System and Equipment


Protection

SAES-P-116

Engineering StandardSwitchgear and Control


Equipment

SAES-P-119

Engineering Standard Onshore Substations

SAES-P-121

Engineering Standard Transformers and Reactors

SAES-P-123

Engineering Standard Lighting

SAES-P-126

Engineering Standard Power System Automation

REV NO.

DATE

JO/EWO

DESCRIPTION

ENGG

CERT

Criteria

DISCIPLINE
ENGINEER
_______________
DATE _________
PROJECT
ENGINEER
_______________
DATE _________
CERTIFIED
_______________
DATE _________
CONSTRUCTION
AGENCY
_______________
DATE _________
OPERATIONS
_______________

-----------------------------CONTROL NUMBER
BY: ____________

DATE: __________

EDSD VERIFICATION
REVISION CERTIFICATION

THIS INDICATES THAT REV. NO. ______


OF THIS DOCUMENT IS COVERED,
FOR ALL APPROVAL / CERTIFICATION
REQUIREMENTS, BY DOCUMENT
COMPLETION CERTIFICATE
(DCC) NO. ___________

DATE _________

BASIS OF DESIGN
ELECTRICAL SYSTEM

DWG. TYPE

DOC

PACKAGE NO. 06, SEA WATER SYSTEM


JAZAN

SAUDI ARABIA

PLANT

INDEX

DOC.

SHT.

REV.

A61

VE-383332

17
of
51

00

JOB ORDER NO. 10-01525-0006

THIS DOCUMENT AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN WHOLE OR PART SHALL BE MADE WITHOUT THE PRIOR WRITTEN CONSENT OF THE OWNER.

PMT

OPRNS

SAUDI ARABIAN OIL COMPANY

Engineering Standard Cathodic Protection of Buried


Pipelines

SAES-X-500

Engineering Standard Cathodic Protection of Vessels


and Tanks Internals

SAES-X-600

Engineering Standard Cathodic Protection of Plant


Facilities

SAES-J-902

Engineering Standard Electrical Systems for


Instrumentation

SAES-B-014

Safety requirements for Plant and Operations Support


Buildings

REV NO.

DATE

JO/EWO

DESCRIPTION

ENGG

CERT

SAES-X-400

DISCIPLINE
ENGINEER
_______________
DATE _________

2.1 Conflicts and Deviations

PROJECT
ENGINEER
_______________

Any inconsistency, conflict or disagreement between the requirements


specified in this document, Saudi Aramco Standards, industry standards
and/or manufacturers standards, shall be brought to the attention of
COMPANY for resolution.

DATE _________
CERTIFIED
_______________

Saudi Aramco standards shall represent the minimum requirements to be met


by the project. Any deviation from Mandatory Saudi Aramco Engineering
Requirements (MSAER) shall require written approval by COMPANY.

DATE _________
CONSTRUCTION
AGENCY
_______________
DATE _________

2.2 References

OPERATIONS
_______________

This document shall be read in conjunction with the following related project
documents:

REVISION CERTIFICATION

DATE: __________

-----------------------------CONTROL NUMBER
BY: ____________

THIS INDICATES THAT REV. NO. ______


OF THIS DOCUMENT IS COVERED,
FOR ALL APPROVAL / CERTIFICATION
REQUIREMENTS, BY DOCUMENT
COMPLETION CERTIFICATE
(DCC) NO. ___________

EDSD VERIFICATION

DATE _________

A00-A-FPP-VA-722020

Jazan IGCCOverall Plot Plan

A00-A-DOC-VE-72223

Jazan IGCC Design Data

A00-A-DOC-VE-722624

Jazan IGCC Equipment & Building Numbering

BASIS OF DESIGN
ELECTRICAL SYSTEM

DWG. TYPE

DOC

PACKAGE NO. 06, SEA WATER SYSTEM


JAZAN

SAUDI ARABIA

PLANT

INDEX

DOC.

SHT.

REV.

A61

VE-383332

18
of
51

00

JOB ORDER NO. 10-01525-0006

THIS DOCUMENT AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN WHOLE OR PART SHALL BE MADE WITHOUT THE PRIOR WRITTEN CONSENT OF THE OWNER.

PMT

OPRNS

SAUDI ARABIAN OIL COMPANY

SWA Equipment List (G-IGC-6)

CERT

A95-A-DOC-VE-541008

Onshore Geotechnical Report

A61-A-PID-VA-728820

SWA Fire Water System Inlet & Outfall P&ID

DESCRIPTION

A61-B-FPS-VA-722745
A61-P-E1L-VA-383359

JO/EWO

A61-S-GAP-VA-745070

SWA Fire Protection Equipment Plan (4 sheets)


SWA SLDG of Genral Power System
SWA Inlet Apron & Canal GA Plan

Also refer to other applicable P&IDs, line lists, and equipment lists.

DATE

2.3 Language

REV NO.

All documentation shall be in the English language and use the English
(International) dictionary. Language usage disputes shall be resolved by
reference to the Oxford English Dictionary.

DISCIPLINE
ENGINEER
_______________

Equipment warning labels and instruction labels shall be in the English and
Arabic languages.

DATE _________
PROJECT
ENGINEER
_______________
DATE _________
CERTIFIED
_______________
DATE _________
CONSTRUCTION
AGENCY
_______________
DATE _________
OPERATIONS
_______________

-----------------------------CONTROL NUMBER
BY: ____________

DATE: __________

EDSD VERIFICATION
REVISION CERTIFICATION

THIS INDICATES THAT REV. NO. ______


OF THIS DOCUMENT IS COVERED,
FOR ALL APPROVAL / CERTIFICATION
REQUIREMENTS, BY DOCUMENT
COMPLETION CERTIFICATE
(DCC) NO. ___________

DATE _________

BASIS OF DESIGN
ELECTRICAL SYSTEM

DWG. TYPE

DOC

PACKAGE NO. 06, SEA WATER SYSTEM


JAZAN

SAUDI ARABIA

PLANT

INDEX

DOC.

SHT.

REV.

A61

VE-383332

19
of
51

00

JOB ORDER NO. 10-01525-0006

THIS DOCUMENT AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN WHOLE OR PART SHALL BE MADE WITHOUT THE PRIOR WRITTEN CONSENT OF THE OWNER.

PMT

A00-A-DOC-VE-745698

ENGG

OPRNS

SAUDI ARABIAN OIL COMPANY

CERT

3.SCOPE

DESCRIPTION

ENGG

The Electrical scope of work for the Sea Water Contract includes the detail
design of the electrical systems in support of the Lump Sum Turn Key (LSTK)
contract. All work shall be in accordance with Saudi Aramco Engineering
Standards and Procedures as identified in this document as well as all the
related documents issued as part of the ITB package.

JO/EWO

3.1 Substations SS-161, all power distribution system and control equipment
downstream of the 132kV incoming cables, including, but not limited to, stepdown power transformers, 13.8kV and 480V switchgears and motor control
centers, panel boards, neutral grounding resistors, power, control, and fiber
optic cables etc.

DATE

3.2 All power and control cabling required for electrical loads within the geographic
limits of the Sea Water Areas.

REV NO.

3.4 Adjustable Speed Drives (ASD) as required and specified by process if needed.

DISCIPLINE
ENGINEER
_______________
DATE _________
PROJECT
ENGINEER
_______________

3.5 Essential power distribution system, including unit step-down transformers,


transformer secondary circuit breaker, Automatic Transfer Switch and Motor
Control Center.
3.6 UPS systems
3.7 DC Batteries and battery charger systems.

DATE _________
CERTIFIED
_______________
DATE _________
CONSTRUCTION
AGENCY
_______________
DATE _________
OPERATIONS

3.8 Design of the Power System Automation will be as per Section 16 of this
document.
3.9 All interior and exterior lighting systems within the geographic boundary of the
contract including area, street, and roadway lighting.
3.10 Equipment & system grounding systems.
3.11 Power system studies and data.

_______________

-----------------------------CONTROL NUMBER
BY: ____________

DATE: __________

EDSD VERIFICATION
REVISION CERTIFICATION

THIS INDICATES THAT REV. NO. ______


OF THIS DOCUMENT IS COVERED,
FOR ALL APPROVAL / CERTIFICATION
REQUIREMENTS, BY DOCUMENT
COMPLETION CERTIFICATE
(DCC) NO. ___________

DATE _________

3.12 Protection relay configuration and setting. Setting will be based on the system
study based on the purchased equipment and coordinated with Power System
Contractor (IGC-4).
3.13 Electric Heat Tracing Systems (where identified on the P&IDs)
3.14 Interface and co-ordination with other EPC Contractors during engineering as
per project interface procedures, diagrams and register. This shall include but
not be limited to:

BASIS OF DESIGN
ELECTRICAL SYSTEM

DWG. TYPE

DOC

PACKAGE NO. 06, SEA WATER SYSTEM


JAZAN

SAUDI ARABIA

PLANT

INDEX

DOC.

SHT.

REV.

A61

VE-383332

20
of
51

00

JOB ORDER NO. 10-01525-0006

THIS DOCUMENT AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN WHOLE OR PART SHALL BE MADE WITHOUT THE PRIOR WRITTEN CONSENT OF THE OWNER.

PMT

OPRNS

SAUDI ARABIAN OIL COMPANY

IGC-004 for the normal and essential power supply

CERT

IGC-004 for Power System Automation

ENGG

EPC-14 for power feed to beach valve shelter

DESCRIPTION

3.15 The Sea Water contract package is comprised of the following major areas
which are identified as the Sea Water System (Unit A61) of the Jazan IGCC
facility. Refer to drawing A61-A-FPP-VA-722037
Cooling Water Inlet Canal

JO/EWO

Cooling Water Inlet Structure

DATE

Inlet Pumping Station (including Substation SS-161)

REV NO.

Intake Channel
In-Plant Lagoon
Bypass Channel

DISCIPLINE
ENGINEER
_______________

Collection Basin

DATE _________

Discharge Channel

PROJECT
ENGINEER
_______________

Submarine Outfall

DATE _________
CERTIFIED
_______________
DATE _________
CONSTRUCTION
AGENCY
_______________
DATE _________
OPERATIONS
_______________

-----------------------------CONTROL NUMBER
BY: ____________

DATE: __________

EDSD VERIFICATION
REVISION CERTIFICATION

THIS INDICATES THAT REV. NO. ______


OF THIS DOCUMENT IS COVERED,
FOR ALL APPROVAL / CERTIFICATION
REQUIREMENTS, BY DOCUMENT
COMPLETION CERTIFICATE
(DCC) NO. ___________

DATE _________

BASIS OF DESIGN
ELECTRICAL SYSTEM

DWG. TYPE

DOC

PACKAGE NO. 06, SEA WATER SYSTEM


JAZAN

SAUDI ARABIA

PLANT

INDEX

DOC.

SHT.

REV.

A61

VE-383332

21
of
51

00

JOB ORDER NO. 10-01525-0006

THIS DOCUMENT AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN WHOLE OR PART SHALL BE MADE WITHOUT THE PRIOR WRITTEN CONSENT OF THE OWNER.

PMT

OPRNS

SAUDI ARABIAN OIL COMPANY

DESCRIPTION

The Cooling Water Inlet Canal is an excavated, sheet pile lined, open waterway
directing the gravity and tidal flow of seawater from the Red Sea to the Cooling
Water Inlet Structure. Other than area and roadway lighting and water condition
instrumentation there are no other electrical loads currently identified for the
Cooling Water Inlet Canal.

JO/EWO

4.2 Cooling Water Inlet Structures

DATE

The Cooling Water Inlet Structures are concrete intake structures housing the
inlet trash screens, drum screens, water quality measurement, chemical dosing
and associated maintenance equipment.

REV NO.

4.3 Inlet Pumping Station


The Inlet Pumping Station is a concrete intake and pumping structure housing
twelve vertical lift pumps and associated maintenance and service equipment
which are used to lift the treated seawater from sea level to the flow level of the
Intake Channel. This area also contains the electro-chlorination building and
Substation SS-161.

DISCIPLINE
ENGINEER
_______________
DATE _________
PROJECT
ENGINEER
_______________

4.4 Intake Channel

DATE _________

The Intake Channel is a concrete lined, open waterway directing the gravity flow
of treated seawater from the Inlet Pumping Structure to the In-Plant Lagoon.
Other than area and roadway lighting and water condition instrumentation there
are no other electrical loads currently identified for the Intake Channel.

CERTIFIED
_______________
DATE _________
CONSTRUCTION
AGENCY
_______________

4.5 In-Plant Lagoon

DATE _________

The In-Plant Lagoon is a concrete lined, open sea water reservoir which serves
as the source of cooling water for the IGCC facility.

OPERATIONS
_______________

-----------------------------CONTROL NUMBER
BY: ____________

4.6 Bypass Channel

DATE: __________

EDSD VERIFICATION
REVISION CERTIFICATION

THIS INDICATES THAT REV. NO. ______


OF THIS DOCUMENT IS COVERED,
FOR ALL APPROVAL / CERTIFICATION
REQUIREMENTS, BY DOCUMENT
COMPLETION CERTIFICATE
(DCC) NO. ___________

DATE _________

The Bypass Channel is a concrete lined, open waterway directing the gravity
flow of excess seawater from the Inlet Pumping Structure directly to the
Discharge Channel. Other than area lighting there are no other electrical loads
currently identified for the Bypass Channel.
4.7 Collection Basin & Discharge Channel

BASIS OF DESIGN
ELECTRICAL SYSTEM

DWG. TYPE

DOC

PACKAGE NO. 06, SEA WATER SYSTEM


JAZAN

SAUDI ARABIA

PLANT

INDEX

DOC.

SHT.

REV.

A61

VE-383332

22
of
51

00

JOB ORDER NO. 10-01525-0006

THIS DOCUMENT AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN WHOLE OR PART SHALL BE MADE WITHOUT THE PRIOR WRITTEN CONSENT OF THE OWNER.

PMT

4.1 Cooling Water Inlet Canal

ENGG

4 FACILITIES DESCRIPTION

CERT

OPRNS

SAUDI ARABIAN OIL COMPANY

ENGG

CERT

The Collection Basin & Discharge Channel are a concrete lined, open
waterways directing the gravity return flow of seawater from the IGCC facility to
the Outfall Pipes. Other than roadway and area lighting and water condition
instrumentation there are no other electrical loads currently identified for the
Collection Basin & Discharge Channel.

DESCRIPTION

4.8 Basin, Overflow Channel & Submarine Outfall Pipes

REV NO.

DATE

JO/EWO

The Outfall Pipes returning seawater into Submarine pipes for discharge into
the Red Sea.

DISCIPLINE
ENGINEER
_______________
DATE _________
PROJECT
ENGINEER
_______________
DATE _________
CERTIFIED
_______________
DATE _________
CONSTRUCTION
AGENCY
_______________
DATE _________
OPERATIONS
_______________

-----------------------------CONTROL NUMBER
BY: ____________

DATE: __________

EDSD VERIFICATION
REVISION CERTIFICATION

THIS INDICATES THAT REV. NO. ______


OF THIS DOCUMENT IS COVERED,
FOR ALL APPROVAL / CERTIFICATION
REQUIREMENTS, BY DOCUMENT
COMPLETION CERTIFICATE
(DCC) NO. ___________

DATE _________

BASIS OF DESIGN
ELECTRICAL SYSTEM

DWG. TYPE

DOC

PACKAGE NO. 06, SEA WATER SYSTEM


JAZAN

SAUDI ARABIA

PLANT

INDEX

DOC.

SHT.

REV.

A61

VE-383332

23
of
51

00

JOB ORDER NO. 10-01525-0006

THIS DOCUMENT AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN WHOLE OR PART SHALL BE MADE WITHOUT THE PRIOR WRITTEN CONSENT OF THE OWNER.

PMT

OPRNS

SAUDI ARABIAN OIL COMPANY

DESCRIPTION

5.2 Normal electric power for the Inlet Areas shall be received at Substation SS-161
via two redundant 132kV underground cables from the Main IGCC Distribution
Substation SS-229.

JO/EWO

5.3 Essential power to Substation SS-161 shall be supplied from IGCC substation
SS-329 at 13.8kV via underground cable to the substation essential transformer
A61-329-XFR(T)-301.

REV NO.

DATE

5.4 Supply, Installation, termination, testing, and commissioning of the normal and
essential power, control, and fiber optic signalling cables shall be by the IGCC
lead power distribution contractor (IGC-4). The design and construction of cable
trench within project boundary of IGC-006 will be done by the Seawater LSTK
contractor (IGC-6).

DISCIPLINE
ENGINEER
_______________
DATE _________
PROJECT
ENGINEER
_______________
DATE _________
CERTIFIED
_______________
DATE _________
CONSTRUCTION
AGENCY
_______________
DATE _________
OPERATIONS
_______________

-----------------------------CONTROL NUMBER
BY: ____________

DATE: __________

EDSD VERIFICATION
REVISION CERTIFICATION

THIS INDICATES THAT REV. NO. ______


OF THIS DOCUMENT IS COVERED,
FOR ALL APPROVAL / CERTIFICATION
REQUIREMENTS, BY DOCUMENT
COMPLETION CERTIFICATE
(DCC) NO. ___________

DATE _________

5.5 The essential power in SS-161 will feed an essential MCC via a step down
transformer or a power panel via MCC, a secondary circuit breaker and an
automatic transfer switch.
5.7 The normal position of the automatic transfer switch will be on essential power.
The position can be changed manually to "B" (backup) for maintenance of the
step down transformer or change to back up automatically in case of loss of
power from essential bus and DG's not starting.
5.8 Depending on the start-up time of the diesel generators and availability of power
(to be determined later by IGCC lead power distribution contractor, IGC-4), a
time delay will be incorporated in the automatic operation of the Automatic
Transfer Switch. The change-over time of diesel generator shall be immediately
after max 15 Sec to be loaded at 50% of its rated name plat capacity.
5.9 The essential bus in SS-329 will be powered from the normal power in addition
to power from the 4 diesel generators, 5 MW each. The switchgear will operate
under normal power during the routine operating conditions and will
automatically switch over to generator power during power outage or distress
conditions.
5.10.The back-up power to the essential MCC in substation SS-161 will be provided
by the normal power 480 V switchgear; in case of loss of essential power (DG
failure) or failure of the essential power step down transformer, the power will
automatically switch to back-up power. Refer to the one line diagrams for details.

BASIS OF DESIGN
ELECTRICAL SYSTEM

DWG. TYPE

DOC

PACKAGE NO. 06, SEA WATER SYSTEM


JAZAN

SAUDI ARABIA

PLANT

INDEX

DOC.

SHT.

REV.

A61

VE-383332

24
of
51

00

JOB ORDER NO. 10-01525-0006

THIS DOCUMENT AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN WHOLE OR PART SHALL BE MADE WITHOUT THE PRIOR WRITTEN CONSENT OF THE OWNER.

PMT

5.1 For details of the JIGCC electrical system refer to Overall One Line Diagram
A00-P-E1L-VA-721950. For the electrical distribution for the Sea Water System
refer to A61-P-E1L-VA-746200.

ENGG

5 ELECTRICAL POWER DISTRIBUTION

CERT

OPRNS

SAUDI ARABIAN OIL COMPANY

ENGG

5.12 A list of all the essential loads will be included in the electrical load list.

DESCRIPTION

5.13 Only secondary selective switchgear shall be used to feed critical loads. The
process loads and especially process critical loads shall be connected to
different MCCs or power sources. There shall be no single point of failure in
the power distribution design.

REV NO.

DATE

JO/EWO

5.14 All Interrupting devices shall be fully rated for the short circuit duty. Low voltage
AC distribution equipment shall be protected by circuit breakers; fuses are not
allowed. Molded case circuit breakers with integral current limiting fuses are
permitted and fuses are permitted for protection of circuits fed from UPS
systems.

DISCIPLINE
ENGINEER
_______________
DATE _________
PROJECT
ENGINEER
_______________
DATE _________
CERTIFIED
_______________
DATE _________
CONSTRUCTION
AGENCY
_______________

5.15 During motor starting, allowable voltage variation at motor terminal is -15% of
motor nominal voltage. Higher voltage variation (-20% or more) during starting
of large medium voltage motors may be allowed on an individual case basis
with specific approval from ARAMCO. Refer to section 6 of SAES-P-100 for
voltage range. Due consideration shall be given to individual load
characteristics and overall system voltage profile during such approvals.
5.16 The voltage variation is 5% as design basis for normal operation. However,
under exceptional circumstances the maximum over-voltage limit of + 10%
voltage shall not be exceeded for more than 30 minutes.
5.17 All cables, substations and equipment numbering system shall follow Aramco
standard SAES-A-202 and document A00-A-DOC-VE-722624 Revision D2.
Electrical equipment installation in the substation yards shall comply with the
requirements of Section 7 of SAES-P-119.

DATE _________
OPERATIONS
_______________

-----------------------------CONTROL NUMBER
BY: ____________

DATE: __________

EDSD VERIFICATION
REVISION CERTIFICATION

THIS INDICATES THAT REV. NO. ______


OF THIS DOCUMENT IS COVERED,
FOR ALL APPROVAL / CERTIFICATION
REQUIREMENTS, BY DOCUMENT
COMPLETION CERTIFICATE
(DCC) NO. ___________

DATE _________

BASIS OF DESIGN
ELECTRICAL SYSTEM

DWG. TYPE

DOC

PACKAGE NO. 06, SEA WATER SYSTEM


JAZAN

SAUDI ARABIA

PLANT

INDEX

DOC.

SHT.

REV.

A61

VE-383332

25
of
51

00

JOB ORDER NO. 10-01525-0006

THIS DOCUMENT AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN WHOLE OR PART SHALL BE MADE WITHOUT THE PRIOR WRITTEN CONSENT OF THE OWNER.

OPRNS
PMT

5.11 The essential power is part of the black start power for starting the CTGs in the
first power block and it is not intended to provide essential power to any process
loads.

CERT

SAUDI ARABIAN OIL COMPANY

CERT

5.18.The equipment shall be designed for operation at the voltages listed below:

ENGG

Equipment /
Service

Nominal
Voltage

DESCRIPTION

General lighting and


receptacles

Nameplate
Voltage

400 V/230 V, 3-Ph

and 230 V, 1- Ph

400 V/230V, 3-Ph,

JO/EWO

Essential lighting

DATE

and 230 V, 1-ph

REV NO.

Instrument and
telecommunication users

120 V, 1-Ph

Space heaters 1kW and


smaller

230 V, 1-Ph

Space heater larger than 1kW

400 V/230V, 3-Ph/1Ph

230 V, 1-Ph

DISCIPLINE
ENGINEER
_______________
DATE _________

400 V,
3-Ph/1-Ph

PROJECT
ENGINEER
_______________
DATE _________

Process heaters (incl. lube oil)

480 V, 3-Ph

HVAC

480 V , 3-Ph

CERTIFIED
_______________
DATE _________
CONSTRUCTION
AGENCY
_______________

AC UPS Input:

DATE _________

Greater than 10 kVA

480, 3-Ph, 3W+G

OPERATIONS

Less than or Equal to 10 kVA

480, 3-Ph, 3W+G

_______________

REVISION CERTIFICATION

AC UPS Output:

DATE: __________

-----------------------------CONTROL NUMBER
BY: ____________

THIS INDICATES THAT REV. NO. ______


OF THIS DOCUMENT IS COVERED,
FOR ALL APPROVAL / CERTIFICATION
REQUIREMENTS, BY DOCUMENT
COMPLETION CERTIFICATE
(DCC) NO. ___________

EDSD VERIFICATION

DATE _________

Less than or Equal to 10 kVA

120 VAC, 1Ph


OR
230 VAC,1Ph,60 HZ

Greater than 10 kVA

BASIS OF DESIGN
ELECTRICAL SYSTEM

208/120 VAC,3Ph, 4W+G 60

DWG. TYPE

DOC

PACKAGE NO. 06, SEA WATER SYSTEM


JAZAN

SAUDI ARABIA

PLANT

INDEX

DOC.

SHT.

REV.

A61

VE-383332

26
of
51

00

JOB ORDER NO. 10-01525-0006

THIS DOCUMENT AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN WHOLE OR PART SHALL BE MADE WITHOUT THE PRIOR WRITTEN CONSENT OF THE OWNER.

PMT

OPRNS

SAUDI ARABIAN OIL COMPANY

-----------------------------CONTROL NUMBER
BY: ____________

REV NO.

DATE

JO/EWO

DESCRIPTION

ENGG

CERT

PMT

HZ

Switchgear close & trip and


control power

BASIS OF DESIGN

ELECTRICAL SYSTEM

JAZAN

125 VDC

DWG. TYPE

PACKAGE NO. 06, SEA WATER SYSTEM

DOC

SAUDI ARABIA

DISCIPLINE
ENGINEER
_______________

DATE _________

PROJECT
ENGINEER
_______________

DATE _________

_______________
CERTIFIED

DATE _________

CONSTRUCTION
AGENCY
_______________

DATE _________

_______________
OPERATIONS

DATE _________

JOB ORDER NO. 10-01525-0006

PLANT

INDEX

DOC.

SHT.

REV.

A61

VE-383332

27
of
51

00

OPRNS

THIS DOCUMENT AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN WHOLE OR PART SHALL BE MADE WITHOUT THE PRIOR WRITTEN CONSENT OF THE OWNER.

DATE: __________

EDSD VERIFICATION

REVISION CERTIFICATION

THIS INDICATES THAT REV. NO. ______


OF THIS DOCUMENT IS COVERED,
FOR ALL APPROVAL / CERTIFICATION
REQUIREMENTS, BY DOCUMENT
COMPLETION CERTIFICATE
(DCC) NO. ___________

SAUDI ARABIAN OIL COMPANY

Nominal
System
Voe

Motor
Nameplate
Voltage

Ph

KW (hp)

Type

Notes

120

115

UP TO
0.25 (0.34)

208

200

UP TO
0.25 (0.34)

240

230

UP TO
0.25 (0.34)

208

200

0.18 (0.25)
to 3.7 (5)

Induction

1,2

240

230

0.18 (0.25)
to 7.5 (10)

Induction

480

460

0.18 (0.25)
to 185
(250)

Induction

4,160

4,000

185 (250)
to 3000
(4000)

Induction

4,160

4,000

370 (500)
to 3000
(4000)

Synchronous

3,4

6,900

6,600

750 (1000)
to 6000

Induction,

REV NO.

DATE

JO/EWO

DESCRIPTION

ENGG

CERT

5.19. Motors shall be selected in accordance with Table 1 of SAES-P-113 shown


below.

DISCIPLINE
ENGINEER
_______________
DATE _________
PROJECT
ENGINEER
_______________
DATE _________
CERTIFIED
_______________
DATE _________
CONSTRUCTION
AGENCY
_______________
DATE _________
OPERATIONS
_______________

-----------------------------CONTROL NUMBER
BY: ____________

DATE: __________

EDSD VERIFICATION
REVISION CERTIFICATION

THIS INDICATES THAT REV. NO. ______


OF THIS DOCUMENT IS COVERED,
FOR ALL APPROVAL / CERTIFICATION
REQUIREMENTS, BY DOCUMENT
COMPLETION CERTIFICATE
(DCC) NO. ___________

DATE _________

BASIS OF DESIGN
ELECTRICAL SYSTEM

DWG. TYPE

DOC

PACKAGE NO. 06, SEA WATER SYSTEM


JAZAN

SAUDI ARABIA

PLANT

INDEX

DOC.

SHT.

REV.

A61

VE-383332

28
of
51

00

JOB ORDER NO. 10-01525-0006

THIS DOCUMENT AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN WHOLE OR PART SHALL BE MADE WITHOUT THE PRIOR WRITTEN CONSENT OF THE OWNER.

PMT

OPRNS

SAUDI ARABIAN OIL COMPANY

Synchronous

13,200

750 (1000)
to 10500
(14000)

Induction,
Synchronous

13,800

13,200

above
10500
(14000)

Synchronous

For description of the notes, refer to SAES-P-113

REV NO.

DATE

5.20 Cathodic protection will be provided for all underground metal piping, and tank
bases, vessels and equipment in accordance with SAES-X-400, SAES-X-500
and SAES-X-600.
5.21 Heat Tracing shall be provided where required for process purposes.

DISCIPLINE
ENGINEER
_______________

5.22 Ground mat as per SAES-P-111 standard will be provided for substation SS161.

DATE _________
PROJECT
ENGINEER
_______________
DATE _________
CERTIFIED
_______________
DATE _________
CONSTRUCTION
AGENCY
_______________
DATE _________
OPERATIONS
_______________

-----------------------------CONTROL NUMBER
BY: ____________

DATE: __________

EDSD VERIFICATION
REVISION CERTIFICATION

THIS INDICATES THAT REV. NO. ______


OF THIS DOCUMENT IS COVERED,
FOR ALL APPROVAL / CERTIFICATION
REQUIREMENTS, BY DOCUMENT
COMPLETION CERTIFICATE
(DCC) NO. ___________

DATE _________

BASIS OF DESIGN
ELECTRICAL SYSTEM

DWG. TYPE

DOC

PACKAGE NO. 06, SEA WATER SYSTEM


JAZAN

SAUDI ARABIA

PLANT

INDEX

DOC.

SHT.

REV.

A61

VE-383332

29
of
51

00

JOB ORDER NO. 10-01525-0006

THIS DOCUMENT AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN WHOLE OR PART SHALL BE MADE WITHOUT THE PRIOR WRITTEN CONSENT OF THE OWNER.

DESCRIPTION
JO/EWO

(8000)

13,800

ENGG

CERT

PMT

OPRNS

SAUDI ARABIAN OIL COMPANY

DESCRIPTION

6.2 Substation buildings shall have separate rooms for switchgears, batteries, and
HVAC equipment.

JO/EWO

6.3 Substations shall not be located in hazardous areas and will be located away
from the security fence per Saudi Aramco engineering standards.
6.4 No substation doors shall exit into the transformer yard.

REV NO.

DATE

6.5 When the cable bus or cable enters the substation through walls, the entry shall
be with the use of cable transit rated for the application in compliance with
NFPA 251 and classified per UL 1479.

DISCIPLINE
ENGINEER
_______________
DATE _________
PROJECT
ENGINEER
_______________
DATE _________
CERTIFIED
_______________
DATE _________
CONSTRUCTION
AGENCY
_______________
DATE _________
OPERATIONS

6.6 Substation fence shall comply with SAES-M-006 and the signs on the fence
shall be as per standard drawing AB-036319 mounted on fence at intervals not
to exceed six (6) meters.
6.7 Battery rooms will be provided with redundant ventilation fans in accordance
with SAES-B-014. Audible and visual alarms will be installed outside the battery
room entrance to annunciate a failure in ventilation for immediate action in
accordance with SAES-P-103.
6.8 Each battery room shall have a storage cabinet equipped with safety equipment
required per SAES-P-103 paragraph 6.9 and accessories as required by
paragraph 15 of 17-SAMSS-511.
6.9 Battery disconnect switches shall be installed in the battery room (see paragraph
6.3.4 of SAES-P-103). Battery disconnect switches shall not be located directly
above the batteries and shall have a minimum horizontal separation of 1.5
meters from the nearest cell.

_______________

REVISION CERTIFICATION

DATE: __________

-----------------------------CONTROL NUMBER
BY: ____________

THIS INDICATES THAT REV. NO. ______


OF THIS DOCUMENT IS COVERED,
FOR ALL APPROVAL / CERTIFICATION
REQUIREMENTS, BY DOCUMENT
COMPLETION CERTIFICATE
(DCC) NO. ___________

EDSD VERIFICATION

DATE _________

6.10 Battery rooms shall be provided with enclosed and gasketed (vapor tight)
corrosion resistant lighting fixtures.Lighting fixtures in the battery rooms shall be
installed at least 300 mm below the finished ceiling.
6.11 Fire detection and alarm systems will be designed and installed in accordance
with SAES-B-014.
6.12 Each substation building shall be provided with Annunciation/Monitoring panel
that complies with the requirements of 34-SAMSS-815 and section 5.5 of

BASIS OF DESIGN
ELECTRICAL SYSTEM

DWG. TYPE

DOC

PACKAGE NO. 06, SEA WATER SYSTEM


JAZAN

SAUDI ARABIA

PLANT

INDEX

DOC.

SHT.

REV.

A61

VE-383332

30
of
51

00

JOB ORDER NO. 10-01525-0006

THIS DOCUMENT AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN WHOLE OR PART SHALL BE MADE WITHOUT THE PRIOR WRITTEN CONSENT OF THE OWNER.

PMT

6.1 The substation and the substation buildings shall comply with ARAMCO
Standards SAES-P-119 and SAES-M-100. Requirements of Standards SAESM-100, SAES-B-055, and SAES-B-014 shall also be considered in the
substation building design.

ENGG

6 SUBSTATION BUILDINGS

CERT

OPRNS

SAUDI ARABIAN OIL COMPANY

CERT

SAES-P-119, and installed in the substation. The panel shall be located as near
the main entrance door as practicable.

ENGG

6.13 The annunciator circuits shall be designed to fail safe. As a minimum the status
conditions to be displayed shall follow section 5.5.3 of SAES-P-119.

DESCRIPTION

6.14 Interiors of floor mounted UPS and battery chargers and other digital cabinets
containing power supplies shall be monitored by an addressable high sensitivity
air sampling or point type smoke detection as per the requirements of SAES-B014 section 7.6.

JO/EWO

6.15 Fire detection and alarm system for In-Plant buildings and substations shall
include a listed interior and external local audible alarm and listed external
visual beacon. The visual beacons shall be visible from the patrolling road side.

REV NO.

DATE

6.16 HVAC for substation buildings will be provided in accordance with SAES-K001,SAES-K-002, and SAES-K-100. Substation HVAC shall provide a sufficient
positive pressure to prevent the ingress of dust and sand. Buildings or HVAC air
intake shall not be taken from electrically classified areas. Redundant and
independent HVAC units shall be provided for each substation.

DISCIPLINE
ENGINEER
_______________
DATE _________
PROJECT
ENGINEER
_______________
DATE _________
CERTIFIED
_______________
DATE _________
CONSTRUCTION
AGENCY
_______________
DATE _________

6.17 The HVAC control panel shall be located in the HVAC mechanical room.
6.18 Each HVAC outdoor condensing unit shall have a disconnect switch installed
within sight of the equipment.
6.19 The following general maintenance considerations shall be applicable for
design of the electrical substations and systems for operation and start up.
Supplier for each piece of equipment shall provide details of specific
maintenance requirements for each supplied item and this shall form an
essential part of the Supplier's Scope of Supply. The equipment shall be
located with sufficient spacing to permit access to all components for normal
maintenance work and complete removal if required. The layout of the facilities
shall permit adequate maintenance access to all mechanical and control
components of the unit.

OPERATIONS
_______________

-----------------------------CONTROL NUMBER
BY: ____________

DATE: __________

EDSD VERIFICATION
REVISION CERTIFICATION

THIS INDICATES THAT REV. NO. ______


OF THIS DOCUMENT IS COVERED,
FOR ALL APPROVAL / CERTIFICATION
REQUIREMENTS, BY DOCUMENT
COMPLETION CERTIFICATE
(DCC) NO. ___________

DATE _________

6.20 Each substation shall have remote racking units for each MV/HV switchgear
assembly as required by 16-SAMSS-504 paragraph 20.4.
6.21 Each substation shall have a cabinet for storage of operating and special tools.
Two fire blankets and a basket type splint stretcher shall be located in the same
cabinet.

BASIS OF DESIGN
ELECTRICAL SYSTEM

DWG. TYPE

DOC

PACKAGE NO. 06, SEA WATER SYSTEM


JAZAN

SAUDI ARABIA

PLANT

INDEX

DOC.

SHT.

REV.

A61

VE-383332

31
of
51

00

JOB ORDER NO. 10-01525-0006

THIS DOCUMENT AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN WHOLE OR PART SHALL BE MADE WITHOUT THE PRIOR WRITTEN CONSENT OF THE OWNER.

PMT

OPRNS

SAUDI ARABIAN OIL COMPANY

DESCRIPTION

7.1.1 13.8 kV switchgears will be in accordance with the requirements detailed in


specification 16-SAMSS-504. The13.8 kV switchgears shall be of metal clad
design, single bus with dual transformer incomers and a normally open bus tie
vacuum circuit breakers of the same type and rating.

JO/EWO

7.1.2 The 13.8 kV Switchgears shall be comprised of individual vertical sections


sharing a common main circuit horizontal bus and common ground bus.

DATE

7.1.3 Normal operation will be with both incomers closed and the bus tie circuit
breaker open per section 6.4 of Aramco Standard SAES-P-116. Pad locking
facilities shall be provided per Section 14 of 16-SAMSS-504.

REV NO.

7.1.4 Contactors shall not be used as switching assemblies in switchgear.

DISCIPLINE
ENGINEER
_______________
DATE _________

7.1.5 The rating of the switchgear shall not be dependent on the forced air system.
The main switchgear bus bar and the switchgear ground bus bar shall have
the same ampacity rating throughout its length. The main switchgear bus bar
shall be insulated for full phase to phase voltage rating. Mating surfaces within
the main circuit shall be silver plated.

PROJECT
ENGINEER
_______________

7.1.6 The spare and space requirement shall be as per Aramco specification.

DATE _________

7.1.7 Space heaters shall not be installed within the switchgear enclosure.

CERTIFIED
_______________
DATE _________
CONSTRUCTION
AGENCY
_______________

7.1.8 Incoming breakers and bus tie breaker shall have individual vertical section.
For the incoming breakers the upper section can be used to house VTs.
7.1.9 A secondary selective transfer scheme will be included in the switchgear
design for the incomers and bus section circuit breakers.

DATE _________

7.1.10 The switchgear shall interface with PSA system.

OPERATIONS
_______________

7.1.11 Cable entry will be from top.

-----------------------------CONTROL NUMBER
BY: ____________

DATE: __________

EDSD VERIFICATION
REVISION CERTIFICATION

THIS INDICATES THAT REV. NO. ______


OF THIS DOCUMENT IS COVERED,
FOR ALL APPROVAL / CERTIFICATION
REQUIREMENTS, BY DOCUMENT
COMPLETION CERTIFICATE
(DCC) NO. ___________

DATE _________

7.1.12 Control voltage for all tripping and closing circuits, protective relaying and
metering shall be 125 VDC.
7.2 480V Switchgear
7.2.1 Low Voltage (480 V) switchgears will be in accordance with the requirements
detailed in specifications 16-SAMSS-502.

BASIS OF DESIGN
ELECTRICAL SYSTEM

DWG. TYPE

DOC

PACKAGE NO. 06, SEA WATER SYSTEM


JAZAN

SAUDI ARABIA

PLANT

INDEX

DOC.

SHT.

REV.

A61

VE-383332

32
of
51

00

JOB ORDER NO. 10-01525-0006

THIS DOCUMENT AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN WHOLE OR PART SHALL BE MADE WITHOUT THE PRIOR WRITTEN CONSENT OF THE OWNER.

PMT

7.1 13.8kV Switchgears

ENGG

7 ELECTRICAL EQUIPMENT

CERT

OPRNS

SAUDI ARABIAN OIL COMPANY

ENGG

CERT

7.2.2 The switchgear shall comprise of air insulated, metal enclosed design with
main transformer incomers, bus tie and feeder circuit-breakers. The
switchgear shall interface with Power System Automation and Power
Management System.

DESCRIPTION

7.2.3 A secondary selective transfer scheme will be included in the switchgear for
incomers and tie breaker.
7.2.4 Normal operation will be with both incomer circuit breakers closed and the bus
tie circuit breaker open per section 6.4 of Aramco Standard SAES-P-116.

JO/EWO

7.2.5 Bus tie breaker shall be in a separate vertical section (one high arrangement).
7.2.6 The 480 V switchgears shall feed separate Motor Control Centers.

DATE

7.2.7 The spare and space requirement shall be as per Aramco specification.

REV NO.

7.2.8 Neutral buses shall not be installed.


7.2.9 Space heaters shall not be installed within the switchgear assembly.

DISCIPLINE
ENGINEER
_______________
DATE _________
PROJECT
ENGINEER
_______________
DATE _________
CERTIFIED
_______________
DATE _________
CONSTRUCTION
AGENCY
_______________
DATE _________
OPERATIONS
_______________

7.2.10 Cable entry will be from the top.


7.3 480V Motor Control Centers
7.3.1 The MCC shall be of the metal enclosed type and shall be comprised of
individual vertical sections sharing a common main circuit horizontal bus and a
common ground bus.
7.3.2 The 480 V motor control centers shall be in accordance with the requirements
detailed in specification 16-SAMSS-503.
7.3.3 The480 V MCC shall be comprised of individual vertical sections containing
switching assemblies. The vertical sections shall share a common main circuit
horizontal bus, common ground bus and a common integrated horizontal and
vertical wire-way system except for the main MCC disconnect or and fixed
mounted switching assemblies.

-----------------------------CONTROL NUMBER
BY: ____________

DATE: __________

EDSD VERIFICATION
REVISION CERTIFICATION

THIS INDICATES THAT REV. NO. ______


OF THIS DOCUMENT IS COVERED,
FOR ALL APPROVAL / CERTIFICATION
REQUIREMENTS, BY DOCUMENT
COMPLETION CERTIFICATE
(DCC) NO. ___________

DATE _________

7.3.4 All switching assemblies in 480 V MCC shall be withdrawable except switching
assemblies containing a main circuit breaker rated greater than 225 A can be
fixed mounted.
7.3.5 The main circuit bus systems of Motor Control Center and switchgear shall not
be connected together.
7.3.6 Motor starters shall have isolation and start/stop facilities at the starter. They

BASIS OF DESIGN
ELECTRICAL SYSTEM

DWG. TYPE

DOC

PACKAGE NO. 06, SEA WATER SYSTEM


JAZAN

SAUDI ARABIA

PLANT

INDEX

DOC.

SHT.

REV.

A61

VE-383332

33
of
51

00

JOB ORDER NO. 10-01525-0006

THIS DOCUMENT AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN WHOLE OR PART SHALL BE MADE WITHOUT THE PRIOR WRITTEN CONSENT OF THE OWNER.

PMT

OPRNS

SAUDI ARABIAN OIL COMPANY

shall also have start/stop facilities and indicating lights local to the motor.

ENGG

CERT

7.3.7 Starters associated with process loads shall have stop / start / permissive
facilities from the DCS. These signals will be hard wired between the DCS
interposing panel and the relevant starter. The motor starters shall be
conventional type.

DESCRIPTION

7.3.8 Motors will be streamed so that two motors of the same duty, one running and
one standby will be fed from different buses or MCC.

JO/EWO

7.3.9 Load diversification will be maintained to ensure that removal of a MCC from
service does not adversely affect the operation of the plant.
7.3.10 Control voltage will be 120VAC.

DATE

7.3.11 Cable entry will be from the top.

REV NO.

7.3.14 Distribution/lighting panel boards or distribution/lighting transformers shall not


be installed within the 480 V Motor Control Center.

DISCIPLINE
ENGINEER
_______________
DATE _________
PROJECT
ENGINEER
_______________
DATE _________
CERTIFIED
_______________

7.4 Low Voltage Panelboards


7.4.1 Low voltage panel boards will be in accordance with the requirements detailed
in material specification, 16-SAMSS-518.
7.4.2 Outdoor panel boards installed in the classified area shall comply with section
5.7 of 16-SAMSS-518.
7.4.3 The minimum continuous rating of the panel board shall be 100 amperes and
a minimum interrupting rating of 10kA RMS.

DATE _________
CONSTRUCTION
AGENCY
_______________
DATE _________

7.4.4 The breakers shall have minimum trip rating of 20A.


7.4.5 Breakers operating at greater than 240V shall be equipped with pad lockable
Lock-off devices.

OPERATIONS
_______________

7.4.6 Tandem, twin or half size breakers shall not be used.

DATE _________
-----------------------------CONTROL NUMBER
BY: ____________

DATE: __________

EDSD VERIFICATION
REVISION CERTIFICATION

THIS INDICATES THAT REV. NO. ______


OF THIS DOCUMENT IS COVERED,
FOR ALL APPROVAL / CERTIFICATION
REQUIREMENTS, BY DOCUMENT
COMPLETION CERTIFICATE
(DCC) NO. ___________

7.5 Transformers
7.5.1 Oil filled transformers shall be in accordance with Material System
Specification 14-SAMSS-531.
7.5.2 If specified, high voltage winding taps for de-energized operation shall be
provided with 2.5% and 5.0% above and 2.5% and 5.0% below the rated
voltage.

BASIS OF DESIGN
ELECTRICAL SYSTEM

DWG. TYPE

DOC

PACKAGE NO. 06, SEA WATER SYSTEM


JAZAN

SAUDI ARABIA

PLANT

INDEX

DOC.

SHT.

REV.

A61

VE-383332

34
of
51

00

JOB ORDER NO. 10-01525-0006

THIS DOCUMENT AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN WHOLE OR PART SHALL BE MADE WITHOUT THE PRIOR WRITTEN CONSENT OF THE OWNER.

PMT

OPRNS

SAUDI ARABIAN OIL COMPANY

ENGG

CERT

7.5.3 When transformers are specified to be furnished with load tap changers (LTC),
it will be on the high voltage winding and provide approximately +/- 10%
automatic adjustment of the low voltage winding voltage, in approximately
5/8% steps with 16 steps above and below the rated voltage.

DESCRIPTION

7.5.4 Transformer will be sized to allow the largest motor to start without the voltage
limits on switchgear, motor terminals and other consumers being exceeded as
per SAES-P-100.
7.5.5 The impedances for transformers shall follow the guidelines of Material
System Specification 14-SAMSS-531, Tables 1 and 2.

JO/EWO

7.5.6 Connections between Transformer secondary and switchgear will be by Cable


Bus as shown on the single line diagrams.

REV NO.

DATE

7.5.7 Transformer Neutral Resistors will be in accordance with IEEE 32, freestanding, sheet steel enclosed of the stainless-steel grid type, short time rated
for 10 seconds.

DISCIPLINE
ENGINEER
_______________
DATE _________
PROJECT
ENGINEER
_______________
DATE _________
CERTIFIED
_______________
DATE _________
CONSTRUCTION
AGENCY
_______________
DATE _________
OPERATIONS
_______________

7.5.8 No oil containment is required for transformers containing 2500 liters of oil or
less. For all others the oil containment is required and it shall follow the
requirements of section 7.3 of SAES-P-119.
7.5.9 Transformer clearances and fire barriers shall follow the requirements of
section 7.2 of SAES-P-119.
7.5.10 Cables feeding the primary side of transformers at all primary voltages of
13.8 kV will be routed underground in transformer pit area. However, 132 kV
cables, shall run direct underground in their entire length. Conduits will be
installed through the transformer oil containment bund and transformer
foundation in such a manner that the oil containment does not leak.
7.5.11 The conduits shall have sufficient bending radius to accommodate the
bending radius of the transformer primary cables. These conduits shall line up
with the transformer primary connections to allow for straight cable line up with
the primary terminals. The size of the conduit and use of long radius 90
degrees elbows shall facilitate installation and pulling of the cables.

-----------------------------CONTROL NUMBER
BY: ____________

DATE: __________

EDSD VERIFICATION
REVISION CERTIFICATION

THIS INDICATES THAT REV. NO. ______


OF THIS DOCUMENT IS COVERED,
FOR ALL APPROVAL / CERTIFICATION
REQUIREMENTS, BY DOCUMENT
COMPLETION CERTIFICATE
(DCC) NO. ___________

DATE _________

7.5.12 Each transformer will be equipped with valve and standard adaptor flange to
interface with future condition monitoring system by others.

BASIS OF DESIGN
ELECTRICAL SYSTEM

DWG. TYPE

DOC

PACKAGE NO. 06, SEA WATER SYSTEM


JAZAN

SAUDI ARABIA

PLANT

INDEX

DOC.

SHT.

REV.

A61

VE-383332

35
of
51

00

JOB ORDER NO. 10-01525-0006

THIS DOCUMENT AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN WHOLE OR PART SHALL BE MADE WITHOUT THE PRIOR WRITTEN CONSENT OF THE OWNER.

PMT

OPRNS

SAUDI ARABIAN OIL COMPANY

DESCRIPTION

8.2 Relay coordination must cover both relay settings and relay configuration,
including Automatic Transfer Schemes and Emergency Transfer Schemes.

JO/EWO

8.5 Remote backup protection will be provided to protect against relay or breaker
failures. Upstream backup protection shall coordinate with downstream
protection over the range of minimum to maximum fault currents.

REV NO.

8.4 Protection zones shall overlap, where feasible, to ensure complete protection at
the zone boundaries.

DATE

8.3 Protection relays must be microprocessor-based type, as per applicable SAMSS.


Protection relays shall be compatible with the Power Management System and
Power System Automation.

DISCIPLINE
ENGINEER
_______________
DATE _________

8.6 The protection schemes for each voltage level shall follow the schemes given in
the project protection and metering drawings. Interlocking and Inter-tripping will
be shown on the Project Protection and Metering drawings.
8.7 All micro processor based protective relays shall comply with IEC 61850.

PROJECT
ENGINEER
_______________
DATE _________
CERTIFIED
_______________
DATE _________
CONSTRUCTION
AGENCY
_______________
DATE _________
OPERATIONS
_______________

-----------------------------CONTROL NUMBER
BY: ____________

DATE: __________

EDSD VERIFICATION
REVISION CERTIFICATION

THIS INDICATES THAT REV. NO. ______


OF THIS DOCUMENT IS COVERED,
FOR ALL APPROVAL / CERTIFICATION
REQUIREMENTS, BY DOCUMENT
COMPLETION CERTIFICATE
(DCC) NO. ___________

DATE _________

BASIS OF DESIGN
ELECTRICAL SYSTEM

DWG. TYPE

DOC

PACKAGE NO. 06, SEA WATER SYSTEM


JAZAN

SAUDI ARABIA

PLANT

INDEX

DOC.

SHT.

REV.

A61

VE-383332

36
of
51

00

JOB ORDER NO. 10-01525-0006

THIS DOCUMENT AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN WHOLE OR PART SHALL BE MADE WITHOUT THE PRIOR WRITTEN CONSENT OF THE OWNER.

PMT

8.1 Protection requirements and types of relays shall generally be in accordance


with the requirements detailed in SAES-P-114, 16-SAMSS-502 thru 506 & 513.

ENGG

8 PROTECTION AND METERING

CERT

OPRNS

SAUDI ARABIAN OIL COMPANY

DESCRIPTION

9.2 Four sets of AC Uninterruptible Power Supply (UPS) system will be installed in
substation SS-161 to serve the critical loads, the four UPS(s) are listed as follows:

JO/EWO

a) A dual standalone UPS system (refer to attached drawing: A61-P-SCM-VA746229_001), 120/208V, 3 phases, 4 wires, 40kVA, 0.5 hours, with vented
(flooded) lead acid (Lead-Calcium) type batteries installed in battery room, and
two separate power distribution panels, mainly supplying the PCS system.

REV NO.

DATE

b) A redundant UPS system (refer to SAES-P-103, Attachment 4, Figure 2), 120V,


1 phase, 5kVA, 0.5 hours, with Valve Regulated (sealed) Lead-Acid (VRLA) type
batteries, and intergrated power distribution panel, mainly supplying the
instruments.

DISCIPLINE
ENGINEER
_______________
DATE _________
PROJECT
ENGINEER
_______________
DATE _________
CERTIFIED

c) A redundant UPS system (refer to SAES-P-103, Attachment 4, Figure 2), 120V,


1 phase, 6kVA, 4 hours, with Valve Regulated (sealed) Lead-Acid (VRLA) type
batteries, and intergrated power distribution panel, mainly supplying the In-plant
communication (IPCS) system and process CCTV system.
d) A redundant UPS system (refer to SAES-P-103, Attachment 4, Figure 2), 230V,
1 phase, 3kVA, 0.5 hours, with Valve Regulated (sealed) Lead-Acid (VRLA) type
batteries, and intergrated power distribution panel, mainly supplying the Data
Network system and Access Control system.

_______________
DATE _________
CONSTRUCTION
AGENCY
_______________
DATE _________

9.4 Each battery bank will be sized for 50% of the total back up time at 100% load.
The UPS voltages shall follow the voltage requirements of Section 5.
9.5 Smoke detection systems shall be installed for UPS and Battery Chargers in
accordance with SAES-B-014.

OPERATIONS
_______________

-----------------------------CONTROL NUMBER
BY: ____________

DATE: __________

EDSD VERIFICATION
REVISION CERTIFICATION

THIS INDICATES THAT REV. NO. ______


OF THIS DOCUMENT IS COVERED,
FOR ALL APPROVAL / CERTIFICATION
REQUIREMENTS, BY DOCUMENT
COMPLETION CERTIFICATE
(DCC) NO. ___________

DATE _________

9.6 Per section 6.3.2.a of SAES-P-103, an interlock between the air handling unit
and high rate charging switch shall be provided, such that failure of the air
handling unit shall cause the high rate charging of batteries to stop.
9.7 Per section 6.3.2.b of SAES-P-103, the ventilation system shall be 100%
redundant. Only direct drive exhaust fans shall be used. An interlock with the
ventilation system shall be provided to stop the high-rate battery charging if the
exhaust fan stops.

BASIS OF DESIGN
ELECTRICAL SYSTEM

DWG. TYPE

DOC

PACKAGE NO. 06, SEA WATER SYSTEM


JAZAN

SAUDI ARABIA

PLANT

INDEX

DOC.

SHT.

REV.

A61

VE-383332

37
of
51

00

JOB ORDER NO. 10-01525-0006

THIS DOCUMENT AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN WHOLE OR PART SHALL BE MADE WITHOUT THE PRIOR WRITTEN CONSENT OF THE OWNER.

PMT

9.1 The AC UPS systems shall be provided in accordance with SAES-P-103, 17SAMSS-516 and 17-SAMSS-511.

ENGG

9 AC&UPS SYSTEM

CERT

OPRNS

SAUDI ARABIAN OIL COMPANY

DESCRIPTION

10.2 Direct Current (DC) secure supply systems will be provided for the 13.8 kV
and 480 V Switchgear protective relay power, tripping and closing circuits. If
required, each substations Fire & Gas and PSA systems will also be fed from
substation DC UPS 125 VDC system.

JO/EWO

10.5 The batteries will be vented lead acid type, and to be located in the substation
battery room. The battery will be sized to give a life expectancy of 20 years.
The batteries shall support the connected load for a period of two hours in
substations SS-161.

REV NO.

10.4 The system shall comprise of two 100% chargers and two 50% batteries (per
Clause 5.3.7 of SAEP-P-103) and one common distribution panel.

DATE

10.3 The nominal output voltage will be 125 VDC.

DISCIPLINE
ENGINEER
_______________
DATE _________
PROJECT
ENGINEER
_______________

10.6 Working space of at least 1 meter shall be provided in front of each battery rack
or enclosure.
10.7 Per section 6.3.2.a of SAES-P-103, an interlock between the air handling unit
and high rate charging switch shall be provided, such that failure of the air
handling unit shall cause the high rate charging of batteries to stop.

DATE _________
CERTIFIED
_______________
DATE _________
CONSTRUCTION
AGENCY
_______________

10.8 Per section 6.3.2.b of SAES-P-103, the ventilation system shall be 100%
redundant. Only direct drive exhaust fans shall be used. An interlock with the
ventillation system shall be provided to stop the high-rate battery charging if
the exhaust fan stops.
10.9 The power supply to both chargers will be from essential source in SS-161.

DATE _________

10.10 Return air-conditioning ducts from battery rooms shall be prohibited.


OPERATIONS
_______________

-----------------------------CONTROL NUMBER
BY: ____________

10.11 Battery monitoring system shall be provided as shown on the AC and DC


UPS systems one line diagrams.

DATE: __________

EDSD VERIFICATION
REVISION CERTIFICATION

THIS INDICATES THAT REV. NO. ______


OF THIS DOCUMENT IS COVERED,
FOR ALL APPROVAL / CERTIFICATION
REQUIREMENTS, BY DOCUMENT
COMPLETION CERTIFICATE
(DCC) NO. ___________

DATE _________

BASIS OF DESIGN
ELECTRICAL SYSTEM

DWG. TYPE

DOC

PACKAGE NO. 06, SEA WATER SYSTEM


JAZAN

SAUDI ARABIA

PLANT

INDEX

DOC.

SHT.

REV.

A61

VE-383332

38
of
51

00

JOB ORDER NO. 10-01525-0006

THIS DOCUMENT AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN WHOLE OR PART SHALL BE MADE WITHOUT THE PRIOR WRITTEN CONSENT OF THE OWNER.

PMT

10.1 The 125V DC system shall conform to the requirements of SAES-P-103, 17SAMSS-511 and 17-SAMSS-514.

ENGG

10 DC SYSTEM

CERT

OPRNS

SAUDI ARABIAN OIL COMPANY

CERT

11.1 Motors will be in accordance with SAES-P-113 and 16-SAMSS-502 / 503 / 520.

ENGG

11.2 All motors except AFD system motors designated on electrical load lists will be
suitable for direct on line starting.
11.3 It will be verified that any power cables which have been oversized due to
ampacity or voltage drop issues can be terminated at both ends without the
need for splice boxes either at the field end or the MCC. Splice boxes shall not
be specified without ARAMCO approval.

REV NO.

DATE

JO/EWO

11.4 All motors rated 75kW (100HP) and above shall be equipped with space
heaters. Motor space heaters shall be powered from contactors installed in a
free standing space heater cabinet. The control for each space heater
contactor shall be from a 24VAC source originating from the space heater
cabinet through an auxiliary contact of the motor starter.
11.5 Motor starting studies shall be performed as per the requirements of section
7.5.3 of SAES-P-100.

DISCIPLINE
ENGINEER
_______________
DATE _________
PROJECT
ENGINEER
_______________
DATE _________
CERTIFIED
_______________
DATE _________
CONSTRUCTION
AGENCY
_______________
DATE _________
OPERATIONS
_______________

11.6 Motor voltages shall be selected in accordance with Table 1 of SAES-P-113


shown in Section 5.
11.7 Generally, motors will be automatically controlled, and each motor shall have a
local control station at the motor and at the motor starter comprising of a startstop push button, Manual-Off-Auto selector switch and start/stop indicator
lamps. The method of control to be provided will be as defined on the P&ID
drawings.
11.8 Motors that are automatically controlled from the DCS will be connected to the
DCS via interposing relay and hard wired connections.
11.9 Interposing Relay Panels will be located in the substations. Signals on the
instrument side of the interposing relays will be 24VDC, powered from the
Control and Instrument systems. The electrical side of the interposing relays
will be 125V AC.

-----------------------------CONTROL NUMBER
BY: ____________

DATE: __________

EDSD VERIFICATION
REVISION CERTIFICATION

THIS INDICATES THAT REV. NO. ______


OF THIS DOCUMENT IS COVERED,
FOR ALL APPROVAL / CERTIFICATION
REQUIREMENTS, BY DOCUMENT
COMPLETION CERTIFICATE
(DCC) NO. ___________

DATE _________

11.10 Controls shall include, but not be limited to, motor start, stop, status, fault and
motor in manual selection (available to run) to the DCS control system. For
individual control and indication requirements P&ID drawings will be referred
to. Motors which do not have the local control station adjacent to the motor
shall, in addition, have a hard wired emergency stop button provided
adjacent to the drive, connected directly to the motor control circuit.

BASIS OF DESIGN
ELECTRICAL SYSTEM

DWG. TYPE

DOC

PACKAGE NO. 06, SEA WATER SYSTEM


JAZAN

SAUDI ARABIA

PLANT

INDEX

DOC.

SHT.

REV.

A61

VE-383332

39
of
51

00

JOB ORDER NO. 10-01525-0006

THIS DOCUMENT AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN WHOLE OR PART SHALL BE MADE WITHOUT THE PRIOR WRITTEN CONSENT OF THE OWNER.

PMT

11 MOTORS

DESCRIPTION

OPRNS

SAUDI ARABIAN OIL COMPANY

12.2 All cable and wire conductor sizes will be metric (mm2).

DESCRIPTION

12.3 All threaded cable fittings, including terminators (glands) for metric size cables,
shall have tapered (NPT) threads in accordance with ANSI/ASME B1.20.1.

JO/EWO

12.4 The selection and sizing of cables will be in accordance with ARAMCO
standards. Where a cable is installed by more than one method e.g.
underground and above ground, the cable will be rated for the worst case
condition for any portion of installation greater than 3 meters.

REV NO.

DATE

12.5 All power and control cables in non hazardous and Zone 2 hazardous process
and utilities areas installed on metal tray will be unarmored.
12.6 All power and control cables in Zone 1 hazardous classified areas, where
required, will be armored.

DISCIPLINE
ENGINEER
_______________
DATE _________
PROJECT
ENGINEER
_______________

12.7 All power and control cables installed underground will be armored per
paragraph 5.13 of SAES-P-104. Un-armored cable will be used for cable tray
and conduit systems installations. However, as per exception clause of
paragraph 5.13 of SAES-P-104, if the cable run has transition from direct
burial to cable tray, then the cable will be armored for the entire length.

DATE _________
CERTIFIED
_______________

12.8 All cables will be of consistent construction for the entire length of the cable.
Transition joints are not allowed except for extremely long runs where the
joints cannot be avoided, in agreement with Company.

DATE _________
CONSTRUCTION
AGENCY
_______________
DATE _________

12.9 Cable armoring for single core cables, where required, will be aluminum wire.
The armor will be adequately terminated using proprietary glands and will be
grounded at both ends. The cable will be rated to accommodate circulating
currents.

OPERATIONS
_______________

-----------------------------CONTROL NUMBER
BY: ____________

DATE: __________

EDSD VERIFICATION
REVISION CERTIFICATION

THIS INDICATES THAT REV. NO. ______


OF THIS DOCUMENT IS COVERED,
FOR ALL APPROVAL / CERTIFICATION
REQUIREMENTS, BY DOCUMENT
COMPLETION CERTIFICATE
(DCC) NO. ___________

DATE _________

12.10 Non-magnetic gland plates will be used for the termination of single core
cables.
12.11 The inter-tripping, protection, and signaling for the main cable runs will be by
fiber optic cables and installed with the main power cable runs by the main
power distribution contractor.
12.12 Underground cable burial depth shall be according to table 2 of SAES-P-104.
12.13 Where any portion of an underground cable is located in areas where liquid

BASIS OF DESIGN
ELECTRICAL SYSTEM

DWG. TYPE

DOC

PACKAGE NO. 06, SEA WATER SYSTEM


JAZAN

SAUDI ARABIA

PLANT

INDEX

DOC.

SHT.

REV.

A61

VE-383332

40
of
51

00

JOB ORDER NO. 10-01525-0006

THIS DOCUMENT AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN WHOLE OR PART SHALL BE MADE WITHOUT THE PRIOR WRITTEN CONSENT OF THE OWNER.

PMT

12.1 All cables will be sized, manufactured and tested in accordance with SAES-P104 and 15-SAMSS-502.

ENGG

12 CABLING AND WIRING

CERT

OPRNS

SAUDI ARABIAN OIL COMPANY

CERT

hydrocarbons or liquid solvents are handled, the cable will be provided with a
lead sheath and single galvanized steel wire armor for multi-core cables and
aluminum wire armor for single core cables.

DESCRIPTION

ENGG

12.14 In general, cables will be installed aboveground in ladder type cable tray
covered with ventilated covers. Flanged type covers shall be secured with
heavy duty wrap around stainless steel band. Cable trays that run vertically in
outdoor areas shall have covers on both sides. The bands shall be installed
every meter and minimum of 6 per cover.

JO/EWO

12.15 Underground routing will be minimized. Where required, cables shall run in
duct bank for road crossings. Duct bank design shall be per section 10.4 of
SAES-P-104.

REV NO.

DATE

12.16 In general, cable entrances into all electrical gear will be by top entry. Cable
entry into instrumentation cabinets will be bottom entry through raised floor.

DISCIPLINE
ENGINEER
_______________
DATE _________
PROJECT
ENGINEER
_______________
DATE _________
CERTIFIED
_______________

12.17 In general cable entrances into buildings shall utilize factory made cable
transits. Cable entrances into substations will be distributed using entries
along the whole length of the substation wall to minimize layering and long
internal runs of cable tray. They shall, as far as practicable, be adjacent to
their associated equipment in the substations.
12.18 When cables or cable buses enter the substations through walls, the entry
shall be with the use of factory made transit systems rated for the application
in compliance with NFPA 251 and classified per UL-1479. Cable trays will be
constructed and cables installed on the trays in compliance with the
installation and safety requirements of NEMA VE1 Cable Tray System and
NEMA VE2 Cable Tray Installation Guidelines or according to manufacturers
recommendations.

DATE _________
CONSTRUCTION
AGENCY
_______________

12.19 Cables installed in vertical runs will be fixed using cable cleats such that the
weight of the cable is supported.

DATE _________
OPERATIONS
_______________

-----------------------------CONTROL NUMBER
BY: ____________

DATE: __________

EDSD VERIFICATION
REVISION CERTIFICATION

THIS INDICATES THAT REV. NO. ______


OF THIS DOCUMENT IS COVERED,
FOR ALL APPROVAL / CERTIFICATION
REQUIREMENTS, BY DOCUMENT
COMPLETION CERTIFICATE
(DCC) NO. ___________

DATE _________

12.20 Power and Control cables will be segregated from instrument, signal and
communication cables in accordance with the relevant COMPANY standards.
Power and Control cables will be segregated from Instrument, signal and
communication cables in accordance with code requirements. In general cable
separation shall follow the guidelines of Section 14 of SAES-P-104.
12.21 Cabling associated with critical safety systems passing through fire hazardous
zones will be fire proofed in accordance with SAES-B-006. The fireproofing
shall meet UL1709 fire test procedure for twenty (20) minutes while
maintaining electrical continuity. Cable Trays and/or other supports for such
cables in fire hazardous zones will be made of stainless steel, or otherwise fire
proofed.

BASIS OF DESIGN
ELECTRICAL SYSTEM

DWG. TYPE

DOC

PACKAGE NO. 06, SEA WATER SYSTEM


JAZAN

SAUDI ARABIA

PLANT

INDEX

DOC.

SHT.

REV.

A61

VE-383332

41
of
51

00

JOB ORDER NO. 10-01525-0006

THIS DOCUMENT AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN WHOLE OR PART SHALL BE MADE WITHOUT THE PRIOR WRITTEN CONSENT OF THE OWNER.

PMT

OPRNS

SAUDI ARABIAN OIL COMPANY

ENGG

CERT

12.22 Cable bus will be used for connection of the LV side of transformers to the
switchgear as shown on the single line diagrams and shall be in accordance
with 16-SAMSS-520. Cable bus entry through the walls of the substations
shall be by factory made transitions.

REV NO.

DATE

JO/EWO

DESCRIPTION

12.23 Conduct material of all cables and cablebus should be copper.

DISCIPLINE
ENGINEER
_______________
DATE _________
PROJECT
ENGINEER
_______________
DATE _________
CERTIFIED
_______________
DATE _________
CONSTRUCTION
AGENCY
_______________
DATE _________
OPERATIONS
_______________

-----------------------------CONTROL NUMBER
BY: ____________

DATE: __________

EDSD VERIFICATION
REVISION CERTIFICATION

THIS INDICATES THAT REV. NO. ______


OF THIS DOCUMENT IS COVERED,
FOR ALL APPROVAL / CERTIFICATION
REQUIREMENTS, BY DOCUMENT
COMPLETION CERTIFICATE
(DCC) NO. ___________

DATE _________

BASIS OF DESIGN
ELECTRICAL SYSTEM

DWG. TYPE

DOC

PACKAGE NO. 06, SEA WATER SYSTEM


JAZAN

SAUDI ARABIA

PLANT

INDEX

DOC.

SHT.

REV.

A61

VE-383332

42
of
51

00

JOB ORDER NO. 10-01525-0006

THIS DOCUMENT AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN WHOLE OR PART SHALL BE MADE WITHOUT THE PRIOR WRITTEN CONSENT OF THE OWNER.

PMT

OPRNS

SAUDI ARABIAN OIL COMPANY

DESCRIPTION

13.2 Lighting power distribution will be at 400V/230V, 3 phase, 3 or 4 wire, and 60


Hz system as specified in SAES-P-100, Paragraph 6.1.3.

JO/EWO

13.3 Building lighting design shall not rely solely on the technical specifications for
this project in order to achieve a suitable overall lighting scheme. Special
attention will be given to the architectural and ergonomic requirements for
lighting in certain special applications, as indicated below.

REV NO.

DATE

13.4 Detail lighting design and selection of light fixtures fittings will be carried out
and approved by Company prior to implementation. The following design
criteria will be carefully considered in the building lighting design:

Control of reflection and glare on monitors

Purpose of the room (e.g. presentations)

DATE _________

Frequency of use (24 hour shift cycles in CCB)

PROJECT
ENGINEER
_______________

Daylight attributes

Provision for future modifications

Maintenance

Local operator control

Contrast modifications

Energy efficient fittings

DISCIPLINE
ENGINEER
_______________

DATE _________
CERTIFIED
_______________
DATE _________
CONSTRUCTION
AGENCY
_______________
DATE _________
OPERATIONS
_______________

-----------------------------CONTROL NUMBER
BY: ____________

DATE: __________

EDSD VERIFICATION
REVISION CERTIFICATION

THIS INDICATES THAT REV. NO. ______


OF THIS DOCUMENT IS COVERED,
FOR ALL APPROVAL / CERTIFICATION
REQUIREMENTS, BY DOCUMENT
COMPLETION CERTIFICATE
(DCC) NO. ___________

DATE _________

13.5 Substation Building will be illuminated with trough type fluorescent fixtures
which shall have a wrap around type cover or egg crate type grille.
13.6 Battery rooms shall use enclosed and gasketed (vapor tight) lighting fixtures
suitable for the environment where they are installed as per paragraphs 4.2.6
and 4.2.7 of SAES-P-123.
13.7 Lighting circuits inside substation will be fed from different power source or

BASIS OF DESIGN
ELECTRICAL SYSTEM

DWG. TYPE

DOC

PACKAGE NO. 06, SEA WATER SYSTEM


JAZAN

SAUDI ARABIA

PLANT

INDEX

DOC.

SHT.

REV.

A61

VE-383332

43
of
51

00

JOB ORDER NO. 10-01525-0006

THIS DOCUMENT AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN WHOLE OR PART SHALL BE MADE WITHOUT THE PRIOR WRITTEN CONSENT OF THE OWNER.

PMT

13.1 Lighting design, installation, fixture selection and illumination lux levels shall
comply with SAES-P-123. All fixtures will be suitably certified for the area in
which they are installed.

ENGG

13 LIGHTING AND RECEPTACLES

CERT

OPRNS

SAUDI ARABIAN OIL COMPANY

ENGG

CERT

buses to ensure normal lighting is available during any single outage. A


minimum of 30% of all the luminaries will be connected to essential power
distribution system to allow for safe short time working and organized
evacuation. Where in a substation Emergency MCC is not available,
emergency lighting will be provided by utilizing luminaries with battery backup.
The Emergency luminaries back up time shall be 90 minutes.

DESCRIPTION

13.8 Plant Area, task lighting and street lighting will be in accordance with SAES-P123.

JO/EWO

13.9 Control of the area lighting will be accomplished by photocell with Hand-OffAuto override switches. The area lighting will be operated on a 400/230V, 3
phase, 4 wire 60Hz electrical distribution system, supplied from panel boards
in the adjacent process area Substation.

REV NO.

DATE

13.10 Outdoors, general area lighting will be provided by high intensity, high
pressure sodium floodlights mounted on structures and / or poles.

DISCIPLINE
ENGINEER
_______________
DATE _________
PROJECT
ENGINEER
_______________
DATE _________
CERTIFIED
_______________
DATE _________
CONSTRUCTION
AGENCY
_______________
DATE _________
OPERATIONS
_______________

-----------------------------CONTROL NUMBER
BY: ____________

DATE: __________

EDSD VERIFICATION
REVISION CERTIFICATION

THIS INDICATES THAT REV. NO. ______


OF THIS DOCUMENT IS COVERED,
FOR ALL APPROVAL / CERTIFICATION
REQUIREMENTS, BY DOCUMENT
COMPLETION CERTIFICATE
(DCC) NO. ___________

DATE _________

13.11 Task lighting will be provided for areas not illuminated sufficiently by the area
lighting. Sufficient plant area/task lighting connected to EDS (emergency
distribution system) will be provided at emergency and critical equipment /
areas for the safe plant shutdown in case of emergency.
13.12 All light fixtures in the process area shall be rated for classified area Class I
division 2, flame proof for consistency.
13.14 Buildings and areas that are to be used by personnel to follow planned
operating and shutdown procedures and to allow safe egress will be provided
by emergency distribution system after loss of the normal power source.
Substations and other buildings shall also be provided with reflective arrows to
show exit direction during lighting failure. Non-essential buildings will have
battery backed up luminaries to allow safe egress.
13.15 Minimum of 30% essential lighting will be provided in all Substation buildings
and PIBs. Emergency lighting will be provided along evacuation routes,
assembly areas and in the Process Plant areas. Normal and emergency task
lighting of at least 200 lux (20fc) will be provided in Plant areas to illuminate
equipment required for use in emergencies including, but not limited to,
emergency telephones, shutdown and emergency isolation stations, fire water
pump areas, central foam concentrate mixing areas, fire control panels and
stand-by generators.
13.16 Substation and other buildings shall be provided with battery back up exit
lights to indicate exit direction during lighting failure.
13.17 Power supply to all outdoor lighting system/fixtures will be switched on/off

BASIS OF DESIGN
ELECTRICAL SYSTEM

DWG. TYPE

DOC

PACKAGE NO. 06, SEA WATER SYSTEM


JAZAN

SAUDI ARABIA

PLANT

INDEX

DOC.

SHT.

REV.

A61

VE-383332

44
of
51

00

JOB ORDER NO. 10-01525-0006

THIS DOCUMENT AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN WHOLE OR PART SHALL BE MADE WITHOUT THE PRIOR WRITTEN CONSENT OF THE OWNER.

PMT

OPRNS

SAUDI ARABIAN OIL COMPANY

CERT

through electro-magnetic contactors to facilitate switching off of all outdoor


lighting from a central location.

ENGG

13.18 All outdoor lights will be connected to the central blackout switch located in
the CCR as per ARAMCO standard SAES-O-113 and SAES-P-123.

DESCRIPTION

13.19 Single phase 230 Volts, 20A receptacles will be located in plant areas so that
any point in the working area can be reached with a 25m (82 feet) extension
cord. The receptacles in the process areas will be of a construction suitable for
classified area class I division 2.

JO/EWO

13.20 Indoor type receptacles will be installed inside office and buildings in
accordance with ARAMCO guidelines.

REV NO.

DATE

13.21 Welding receptacles will be 480 Volt, 40 kW rated, three phase, 4 wire, 3 pole
plus ground. The receptacles will be of a construction suitable for the area
where it is to be installed. Receptacles will be located throughout the open
areas so that any part of the process areas can be reached with a 30m lead.

DISCIPLINE
ENGINEER
_______________
DATE _________
PROJECT
ENGINEER
_______________
DATE _________
CERTIFIED
_______________
DATE _________
CONSTRUCTION
AGENCY
_______________
DATE _________
OPERATIONS
_______________

-----------------------------CONTROL NUMBER
BY: ____________

DATE: __________

EDSD VERIFICATION
REVISION CERTIFICATION

THIS INDICATES THAT REV. NO. ______


OF THIS DOCUMENT IS COVERED,
FOR ALL APPROVAL / CERTIFICATION
REQUIREMENTS, BY DOCUMENT
COMPLETION CERTIFICATE
(DCC) NO. ___________

DATE _________

BASIS OF DESIGN
ELECTRICAL SYSTEM

DWG. TYPE

DOC

PACKAGE NO. 06, SEA WATER SYSTEM


JAZAN

SAUDI ARABIA

PLANT

INDEX

DOC.

SHT.

REV.

A61

VE-383332

45
of
51

00

JOB ORDER NO. 10-01525-0006

THIS DOCUMENT AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN WHOLE OR PART SHALL BE MADE WITHOUT THE PRIOR WRITTEN CONSENT OF THE OWNER.

PMT

OPRNS

SAUDI ARABIAN OIL COMPANY

DESCRIPTION

14.2 Conductors used as grid conductors, grounding electrode conductors,


equipment grounding conductors or bonding conductors in grounding systems
shall be soft or annealed copper and have PVC insulation. The insulation shall
be green jacket or green jacket with yellow stripes.

JO/EWO

14.3 Grid conductors and grounding electrode conductors used for substation grids
shall not be insulated. If conductors are larger than 35mm2 then they shall be
stranded according to SA standards.

REV NO.

DATE

14.4 The electrical grounding system for the entire installation will be based on an
underground earth grid system for each unit area. All equipment and
structures in each unit area will be connected to the area grid. Each area grid
will be connected to adjacent area grid via a test well to prevent any
equipotential difference in the grounding system across the site.

DISCIPLINE
ENGINEER
_______________
DATE _________
PROJECT
ENGINEER
_______________
DATE _________
CERTIFIED
_______________
DATE _________
CONSTRUCTION
AGENCY
_______________
DATE _________

14.5 The grounding grid conductor size, laying depth, length of each rod etc. will be
as shown on grounding drawing for the sea water project.
14.6 All grounding connections to ground grids, structures, electrical/mechanical
equipment, etc., will be performed as per installation detail drawings.
14.7 The 13.8 kV system will be low resistance grounded via neutral grounding
resistors connected to local dedicated ground electrodes and test wells which
have a solid connection to the plant main ground grid.
14.8 The 480 V and 400/230 Volts electrical system neutrals at each source of
supply will be solidly grounded by means of dedicated ground electrodes and
test well which have a solid connection to the plant main ground grid. Ground
loop impedances shall effect circuit disconnection in a time not exceeding 0.5
second under solid ground fault conditions.

OPERATIONS
_______________

-----------------------------CONTROL NUMBER
BY: ____________

DATE: __________

EDSD VERIFICATION
REVISION CERTIFICATION

THIS INDICATES THAT REV. NO. ______


OF THIS DOCUMENT IS COVERED,
FOR ALL APPROVAL / CERTIFICATION
REQUIREMENTS, BY DOCUMENT
COMPLETION CERTIFICATE
(DCC) NO. ___________

DATE _________

14.9 For the grounding of electrical systems, equipment, and structures, each
installation or building shall have one common ground grid connected to at
least two groups of ground electrodes.
14.10 The ground resistance of made electrodes used for system grounding shall
not exceed five (5) ohms per paragraphs 8.2.1 and 8.3.1 of SAES-P-111
14.11 Static grounding and bonding of all electrical equipment and structures shall
ensure that no equipotential difference exists in the grounding system.

BASIS OF DESIGN
ELECTRICAL SYSTEM

DWG. TYPE

DOC

PACKAGE NO. 06, SEA WATER SYSTEM


JAZAN

SAUDI ARABIA

PLANT

INDEX

DOC.

SHT.

REV.

A61

VE-383332

46
of
51

00

JOB ORDER NO. 10-01525-0006

THIS DOCUMENT AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN WHOLE OR PART SHALL BE MADE WITHOUT THE PRIOR WRITTEN CONSENT OF THE OWNER.

PMT

14.1 In general, substation and plant grounding shall comply with the requirements
of SAES-P-111.

ENGG

14 GROUNDING

CERT

OPRNS

SAUDI ARABIAN OIL COMPANY

14.13 Lightning protection systems will be installed in accordance with SAES-P-111

DESCRIPTION

ENGG

14.14 To facilitate low impedance lightning discharge path to ground, ground


electrodes will be located near the base of elevated structures requiring
lightning protection. The electrodes will be connected to the structure as well
as the lightning conductor, and will be interconnected with the existing main
ground grid to ensure that no equipotential difference exists.

REV NO.

DATE

JO/EWO

14.15 Special attention will be paid to the requirement for the instrument system
grounding for computers and control systems. Computer systems and
instrumentation should be grounded per supplier requirements and tied to
plant ground at one point as required per NEC and meet the requirement of
SAES-J-902

DISCIPLINE
ENGINEER
_______________
DATE _________
PROJECT
ENGINEER
_______________
DATE _________
CERTIFIED
_______________
DATE _________
CONSTRUCTION
AGENCY
_______________
DATE _________
OPERATIONS
_______________

-----------------------------CONTROL NUMBER
BY: ____________

DATE: __________

EDSD VERIFICATION
REVISION CERTIFICATION

THIS INDICATES THAT REV. NO. ______


OF THIS DOCUMENT IS COVERED,
FOR ALL APPROVAL / CERTIFICATION
REQUIREMENTS, BY DOCUMENT
COMPLETION CERTIFICATE
(DCC) NO. ___________

DATE _________

BASIS OF DESIGN
ELECTRICAL SYSTEM

DWG. TYPE

DOC

PACKAGE NO. 06, SEA WATER SYSTEM


JAZAN

SAUDI ARABIA

PLANT

INDEX

DOC.

SHT.

REV.

A61

VE-383332

47
of
51

00

JOB ORDER NO. 10-01525-0006

THIS DOCUMENT AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN WHOLE OR PART SHALL BE MADE WITHOUT THE PRIOR WRITTEN CONSENT OF THE OWNER.

PMT

14.12 For equipment grounding refer to section 9.0 of SAES-P-111.

CERT

OPRNS

SAUDI ARABIAN OIL COMPANY

REV NO.

DATE

JO/EWO

DESCRIPTION

15.2 The following studies shall be performed during detail design phase:

Starting the largest in-plant motor during the normal and contingency
operation.

Load flow studies

In-Plant maximum short circuit for equipment design

Grounding study

Normal and contingency operation SC current for relay coordination

Final over-current coordination, equipment protection, & relay setting


study

Final arc-flash study

DISCIPLINE
ENGINEER
_______________
DATE _________
PROJECT
ENGINEER
_______________
DATE _________
CERTIFIED

15.3 The design shall include confirmation of equipment sizes and ratings of all
electrical system components such as cable sizing, relay coordination, motor
starting, battery sizing, etc. by performing required system studies and
calculations.

_______________
DATE _________
CONSTRUCTION
AGENCY
_______________
DATE _________
OPERATIONS

15.4 The data for the sea water design shall be shared and coordinated with the
power distribution contractor.
15.5 The PSA network fiber optic cabling will be done by the communications
contractor and according to the drawings produced by the power system
automation contractor.

_______________

-----------------------------CONTROL NUMBER
BY: ____________

DATE: __________

EDSD VERIFICATION
REVISION CERTIFICATION

THIS INDICATES THAT REV. NO. ______


OF THIS DOCUMENT IS COVERED,
FOR ALL APPROVAL / CERTIFICATION
REQUIREMENTS, BY DOCUMENT
COMPLETION CERTIFICATE
(DCC) NO. ___________

DATE _________

15.6 A stand-alone, comprehensive, automation system comprised of


microprocessor-based systems, associated software, and required peripherals
for centralized monitoring and controlling an electrical generation, transmission
and distribution power network for the entire IGCC facility shall be provided.
15.7 This Power System Automation (PSA) shall provide the functionality as defined
in the Saudi Aramco standard, SAES-P-126, and as supplemented by Saudi
Aramco specification, 16-SAMSS-513, Power System Automation Philosophy
- A00-P-DOC-VE-721940, Power System Automation Block Diagram A00-P-

BASIS OF DESIGN
ELECTRICAL SYSTEM

DWG. TYPE

DOC

PACKAGE NO. 06, SEA WATER SYSTEM


JAZAN

SAUDI ARABIA

PLANT

INDEX

DOC.

SHT.

REV.

A61

VE-383332

48
of
51

00

JOB ORDER NO. 10-01525-0006

THIS DOCUMENT AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN WHOLE OR PART SHALL BE MADE WITHOUT THE PRIOR WRITTEN CONSENT OF THE OWNER.

PMT

15.1 Power System studies will be performed during project detail design phase as
per SAES-P-100, using the ETAP software Version 11.1.1

ENGG

15 SYSTEM STUDIES

CERT

OPRNS

SAUDI ARABIAN OIL COMPANY

CERT

SCH-VE-744360 (7 Sheets), Power System Automation Scope of Work A00P-DOC-VE-721995, and Power System Automation I/O List A00-P-DOC-VE744363.

DESCRIPTION

ENGG

15.8 The PSA shall interface with electrical equipment and IEDs to provide
supervisory control, comprehensive acquisition of operational and nonoperational data, time synchronization and engineering access to the IEDs.
15.9 The PSA shall be designed with redundancy as per SAES-P-126 requirements.
No single failure of a PSA component shall result in loss of communication or
any function of PSA.

REV NO.

DATE

JO/EWO

15.10 The PSA local area network topology shall be parallel redundant or bus ring
or a combination of both topologies to provide a fault tolerant architecture. The
PSA LAN shall be stand alone and isolated from all other network traffic.

DISCIPLINE
ENGINEER
_______________
DATE _________
PROJECT
ENGINEER
_______________

15.11 An Operator Automation System shall be provided in individual substations for


monitoring and control of the substation electrical equipment. Redundant,
centralized OAS shall be provided in the CCR for overall monitoring and
control of the entire electrical system network (by others). An Engineering
Automation System shall be provided in the CCR for system configuration,
network and security management and engineering access to the IEDs.
15.12 The PSA shall interface with the DCS for the exchange of electrical system
data as defined in project drawings and documents.

DATE _________
CERTIFIED
_______________
DATE _________
CONSTRUCTION
AGENCY
_______________
DATE _________
OPERATIONS
_______________

-----------------------------CONTROL NUMBER
BY: ____________

DATE: __________

EDSD VERIFICATION
REVISION CERTIFICATION

THIS INDICATES THAT REV. NO. ______


OF THIS DOCUMENT IS COVERED,
FOR ALL APPROVAL / CERTIFICATION
REQUIREMENTS, BY DOCUMENT
COMPLETION CERTIFICATE
(DCC) NO. ___________

DATE _________

BASIS OF DESIGN
ELECTRICAL SYSTEM

DWG. TYPE

DOC

PACKAGE NO. 06, SEA WATER SYSTEM


JAZAN

SAUDI ARABIA

PLANT

INDEX

DOC.

SHT.

REV.

A61

VE-383332

49
of
51

00

JOB ORDER NO. 10-01525-0006

THIS DOCUMENT AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN WHOLE OR PART SHALL BE MADE WITHOUT THE PRIOR WRITTEN CONSENT OF THE OWNER.

PMT

OPRNS

SAUDI ARABIAN OIL COMPANY

DESCRIPTION

16.2 A stand-alone, comprehensive, automation system comprised of


microprocessor-based systems, associated software, and required peripherals
for centralized monitoring and controlling an electrical generation, transmission
and distribution power network for the entire IGCC facility shall be provided.

REV NO.

DATE

JO/EWO

16.3 This Power System Automation (PSA), including Power Management System
(PMS) and SCADA sub-systems, shall provide the functionality as defined in
the Saudi Aramco standard, SAES-P-126, and as supplemented by Saudi
Aramco specification, 16-SAMSS-513, Power System Automation Philosophy
- A00-P-DOC-VE-721940, Power System Automation Block Diagram A00-PSCH-VE-744360 (7 Sheets), Power System Automation Scope of Work A00P-DOC-VE-721995, and Power System Automation I/O List A00-P-DOC-VE744363.

DISCIPLINE
ENGINEER
_______________
DATE _________
PROJECT
ENGINEER
_______________
DATE _________

16.4 The PSA shall interface with electrical equipment and IEDs to provide
supervisory control, comprehensive acquisition of operational and nonoperational data, time synchronization and engineering access to the IEDs.
16.5 PSA shall be designed with redundancy as per SAES-P-126 requirements. No
single failure of a PSA component shall result in loss of communication or any
function of PSA.

CERTIFIED
_______________
DATE _________
CONSTRUCTION
AGENCY
_______________
DATE _________
OPERATIONS
_______________

-----------------------------CONTROL NUMBER
BY: ____________

DATE: __________

EDSD VERIFICATION
REVISION CERTIFICATION

THIS INDICATES THAT REV. NO. ______


OF THIS DOCUMENT IS COVERED,
FOR ALL APPROVAL / CERTIFICATION
REQUIREMENTS, BY DOCUMENT
COMPLETION CERTIFICATE
(DCC) NO. ___________

DATE _________

16.6 The PSA local area network topology shall be parallel redundant or bus ring or
a combination of both topologies to provide a fault tolerant architecture. The
PSA LAN shall be stand alone and isolated from all other network traffic.
16.7 An Operator Automation System shall be provided in individual substations for
monitoring and control of the substation electrical equipment. Redundant,
centralized OAS shall be provided in the CCR for overall monitoring and
control of the entire electrical system network (by others). An Engineering
Automation System shall be provided in the CCR for system configuration,
network and security management and engineering access to the IEDs.
16.8 The PSA shall interface with the DCS for the exchange of electrical system
data as defined in project drawings and documents.

BASIS OF DESIGN
ELECTRICAL SYSTEM

DWG. TYPE

DOC

PACKAGE NO. 06, SEA WATER SYSTEM


JAZAN

SAUDI ARABIA

PLANT

INDEX

DOC.

SHT.

REV.

A61

VE-383332

50
of
51

00

JOB ORDER NO. 10-01525-0006

THIS DOCUMENT AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN WHOLE OR PART SHALL BE MADE WITHOUT THE PRIOR WRITTEN CONSENT OF THE OWNER.

PMT

16.1 The PSA network fiber optic cabling will be done by the communications
contractor and according to the drawings produced by the power system
automation contractor.

ENGG

16 POWER SYSTEM AUTOMATION

CERT

OPRNS

SAUDI ARABIAN OIL COMPANY

CERT

17 ELECTRICAL INTERFACES

ENGG

All electrical interface points between sea water unit and other EPC
contractors shall be identified in the Interface document.

DESCRIPTION

17.1 All cable tray, grounding, and trenching interface points shall be at the area
boundaries between different EPC contractors. EPC contractors are
responsible for coordination with the neighboring EPC contractor.

JO/EWO

17.2 The interface point for all main power distribution cables will be the cable
connection point at the primary of the main substation transformers. The main
power distribution cables are defined as cables connecting the 132 kV IGCC
GIS switchgear to the process area main substation transformer primaries, etc.

REV NO.

DATE

17.3 The interface point for all the control, signaling, and protection cables related to
the main power distribution shall be at the switchgears. These cables shall run
with the main power cables per the standards. The main power distribution
EPC contractor is responsible for coordinating this effort.

DISCIPLINE
ENGINEER
_______________
DATE _________

17.4 The main power distribution contractor is responsible for the purchase,
installation, termination, and testing of the main power and their associated
control, signaling, and protection cables. Cable raceway, trays, trenches,
supports, etc shall be by each area EPC contractor within their boundaries.

PROJECT
ENGINEER
_______________
DATE _________
CERTIFIED
_______________
DATE _________
CONSTRUCTION
AGENCY
_______________
DATE _________
OPERATIONS
_______________

-----------------------------CONTROL NUMBER
BY: ____________

DATE: __________

EDSD VERIFICATION
REVISION CERTIFICATION

THIS INDICATES THAT REV. NO. ______


OF THIS DOCUMENT IS COVERED,
FOR ALL APPROVAL / CERTIFICATION
REQUIREMENTS, BY DOCUMENT
COMPLETION CERTIFICATE
(DCC) NO. ___________

DATE _________

BASIS OF DESIGN
ELECTRICAL SYSTEM

DWG. TYPE

DOC

PACKAGE NO. 06, SEA WATER SYSTEM


JAZAN

SAUDI ARABIA

PLANT

INDEX

DOC.

SHT.

REV.

A61

VE-383332

51
of
51

00

JOB ORDER NO. 10-01525-0006

THIS DOCUMENT AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN WHOLE OR PART SHALL BE MADE WITHOUT THE PRIOR WRITTEN CONSENT OF THE OWNER.

PMT

OPRNS

SAUDI ARABIAN OIL COMPANY

Das könnte Ihnen auch gefallen