Beruflich Dokumente
Kultur Dokumente
The 2002 National Electrical Code (NEC) has an added notation that can be confusing. The
notation is a Fine Print Note (FPN) to 240.85 of the NEC that reads, "Proper application of
molded-case circuit breakers on 3-phase systems, other than solidly grounded WYE, particularly
on corner-grounded delta systems, considers the individual pole interrupting capability." A FPN is
non-mandatory information according to 90.5 of the NEC. This document will explore its meaning.
There was considerable controversy among the NEC Panel about whether such a statement will
be helpful to users. While there is no reason for special attention for the generally applied
distribution systems, there can be a reason for care in applying MCCBs in the corner-grounded
delta system.
Solidly-grounded WYE
For the solidly grounded WYE system, either a L-N or a L-G fault would be detected and
interrupted by a single pole. The L-N and L-G voltages are both phase voltages as opposed to
being a L-L voltage. For a 480 V L-L system, the phase voltage is 277 V. For a 208 V system, the
phase voltage is 120 V. The individual poles of a 3-phase MCCB are effectively tested at the full
current value of the interrupting rating and at phase voltage when they interrupt the 3-phase short
circuit in the high available fault test of UL 489. This combination of parameters occurs for the first
pole to clear. Without exception, MCCBs used in these systems are fully capable of interrupting
any short circuit condition up to the value of the interrupting rating.
Corner-grounded delta
Now look at the corner grounded delta system. A L-G fault would be detected and interrupted by
the single pole of a MCCB. However, in this case the voltage is full L-L voltage. It is 480 V in a
480 V system or 208 V in a 208 V system. This voltage exceeds the phase voltage seen by the
individual pole in the 3-phase test at the interrupting rating. In UL 489 testing, there is a single
pole test at full L-L voltage. While it is at the highest voltage rating of the MCCB, it is at a limited
test current that may be below the current that could flow in a L-G fault on this system. 2-pole
MCCBs specifically intended for use in these systems are marked 1-3 as indicated in NEC
240-85. In both cases, 2-pole or 3-pole, it would be well for the engineer designing a corner
grounded system to verify that the tested current is not lower than the current that can flow in a
fault or to select a MCCB rated for application on the corner grounded system.
Impedance-grounded WYE
Next look at the impedance grounded WYE system. A L-N fault would be covered by test, the
same as it is for the solidly grounded WYE system. With respect to a L-G fault, the impedance
would limit such a fault to a very low level of several amperes. Therefore, a MCCB is well rated
and tested to interrupt a fault seen by an individual pole. However, if multiple, simultaneous faults
are considered, there is a condition that may deserve attention. A L-G fault on one phase on the
load side of the MCCB plus a simultaneous L-G fault on a different phase on the supply side of
the MCCB would result in the condition shown in figure 4. In this case, full L-L voltage appears
across the pole. The probability of such a condition becoming a problem for interruption by the
MCCB is very low considering:
Note: Circuit breakers can react very rapidly to these types of arcing faults to clear the circuit. As
the arcing fault current is increasing through one pole the fault will most likely propagate to the
other phases due to ionized gases. At the same time as the pole under fault trips, it is causing all
poles of the circuit breaker to open simultaneously due to common trip. This circuit breaker
feature will invariably allow the circuit breaker to clear the fault successfully while limiting the
arcing current to levels well below the circuit breakers interrupting capability.
In addition to these points, NEC 250.36 limits the application of impedance grounded systems
and requires ground detection systems to support early repair of the first fault thereby reducing
the potential for occurrence of a second simultaneous fault. MCCBs can be safely applied in
these systems. Depending on the specific protection needs and the anticipated maintenance of
the facility, the design engineer may wish to verify the single pole test values against the system.
Here, the straight voltage rating expressed as 600, 480 or 240 V should be used. The slash
voltage ratings such as 600Y/346 and 480Y/277 are not intended for impedance grounded
systems.
Systems such as the impedance grounded WYE system are utilized primarily in the process
industries specifically to avoid having manufacturing processes interrupted by the occurrence of a
single ground fault. To gain the value of the system, facilities using them must detect and repair
any ground fault within a short time of its occurrence. The occurrence of a second ground fault
anywhere in the system on a different phase will cause overcurrent devices to open and result in
an outage.
The three systems addressed above represent all but a small percentage of installations. In
addition is the ungrounded delta system, the analysis of which is the same as for the impedance
grounded WYE system from the MCCB standpoint. There is also the center-point grounded delta
system used in residential and commercial applications, which is comprehensively covered by
testing.