Binary inputs
Construction
The NA016 protection relay case is suitable for ush or rack
mounting.
Protective functions
50/51
50N/51N
Phase overcurrent
Earth fault
52
TCS
50
51
50N
51N
Control functions
METERING
- I L1...I L3, I E,....
- Data logger
COMMUNICATION
- RS232
- Modbus RS485
Communication
Measuring inputs
Three phase current inputs and one residual current input, with
nominal currents independently selectable at 1 A or 5 A through
DIP-switches.
Firmware updating
The use of ash memory units allows on-site rmware updating.
Output relays
Four output relays are available (two changeover contacts);
each relay may be individually programmed as normal state
(normally energized or de-energized) and reset mode (manual
or automatic).
A programmable timer is provided for each relay (minimum pulse
width). The user may program the function of each relay in accordance with a matrix (tripping matrix) structure.
Self diagnostics
All hardware and software functions are repeatedly checked
and any anomalies reported via display messages, communication interfaces, LEDs and output relays.
Anomalies may refer to:
Hw faults (auxiliary power supply, output relay coil interruptions, ...).
Sw faults (boot and run time tests for data base, EEPROM
memory checksum failure, data BUS,...).
Metering
Data storage
Several useful data are stored into a non volatile memory.
Sequence of Event Recorder
The event recorder runs continuously capturing in circular
mode the last one hundred events upon trigger of binary input/output.
Sequence of Fault Recorder
The fault recorder runs continuously capturing in circular
mode the last twenty faults upon trigger of binary input/output
and/or element pickup (start-trip).
Settings recording
Following some setting changes the last ten changes are recorded in circular mode (Data Logger CEI 0-16)
Trip counters
ThySetter
SPECIF IC AT IONS
INPUT CIRCUITS
GENERAL
Mechanical data
Mounting:
Mass (ush mounting case)
ush, rack
2.0 kg
Insulation tests
Reference standards
High voltage test 50Hz
Impulse voltage withstand (1.2/50 s)
Insulation resistance
EN 60255-5
2 kV 60 s
5 kV
>100 M
EN 61000-4-29
EN 60255-22-1
EN 60255-22-2
EN 60255-22-4
EN 60255-22-6
EN 60255-4-3
EN 61000-4-5
EN 61000-4-8
EN 61000-4-12
EN 61000-4-12
EN 61000-4-16
1 kV-2.5 kV
8 kV
4 kV
10 V
10 V/m
2 kV
1 kA/m
2.5 kV
2 kV
10 V
Reference standards
EN 61000-6-4 (ex EN 50081-2)
Conducted emission 0.15...30 MHz
Class A
Radiated emission 30...1000 MHz
Class A
Climatic tests
IEC 60068-x, ENEL R CLI 01, CEI 50
Mechanical tests
Reference standards
Safety requirements
Reference standards
Pollution degree
Reference voltage
Overvoltage
Pulse voltage
Reference standards
Protection degree:
Front side
Rear side, connection terminals
EN 61010-1
3
250 V
III
5 kV
EN 60529
IP52
IP20
Environmental conditions
Ambient temperature
Storage temperature
Relative humidity
Atmospheric pressure
-25...+70 C
-40...+85 C
10...95 %
70...110 kPa
Certifications
Product standard for measuring relays
CE conformity
EMC Directive
Low Voltage Directive
Type tests
EN 50263
2004/108/EC
2006/95/EC
IEC 60255-6
COMMUNICATION INTERFACES
Local PC RS232
RS485 port
Protocol
24...230 Vac/dc
19...265 Vac / 19...300 Vdc
6 W (9 VA)
Binary inputs
Quantity
Type
Max permissible voltage
Max consumption, energized
3
dry inputs
19...265 Vac/19...300 Vdc
3 mA
OUTPUT CIRCUITS
Emission
Reference standards
LEDs
Quantity
ON/fail (green)
Start (yellow)
Trip (red)
Trip I>, I>>, I>>> (red)
Trip IE>, IE>> (red)
52a - CB position (red)
52b - CB position (red)
TCS - Trip Circuit Supervision (red)
8
1
1
1
1
1
1
1
1
GENERAL SETTINGS
Rated values
Phase CT nominal primary current (Inp)
Residual CT nominal primary current (IEnp)
Reading
1 A...1000 A
1 A...1000 A
Direct / Relative
19200 bps
1200...57600 bps
ModBus RTU/IEC 60870-5-103
0.01...0.50 s
FUNCTIONS
Phase overcurrent - 50/51
I> Element
I> Curve type (I>Curve)
50/51 First threshold inverse time (I>inv)
I>inv Operating time (t >inv)
IEC/BS A, B, C
0.100...2.50 In
0.02...60.0 s
I>> Element
50/51 Second threshold denite time (I>> def )
I>> def Operating time (t >> def )
I>> Reset time delay (t >> RES)
0.100...20.0 In
0.03...10.00 s
0.00...1.00 s
I>>> Element
Denite time
50/51 Third threshold denite time (I>>> def )
I>>>def Operating time (t >>> def )
I>>> Reset time delay (t >>> RES)
0.100...20.0 In
0.03...10.00 s
0.00...1.00 s
0.005...5.00 IEn
0.03...180 s
0.00...1.00 s
IE>> Element
Denite time
50N/51N Second threshold denite time (IE>>def) 0.005...5.00 IEn
IE>>def within CLP (IECLP>>def )
0.02...10.00 IEn
IE>>def Operating time (t E>> def )
0.03...10.00 s
IE>> Reset time delay (t E>> RES)
0.00...1.00 s
Circuit Breaker
BF diagnostic
Trip Circuit Supervision (74TCS)
On/Off
On/Off
METERING
Measured parameters
Fundamental RMS phase currents
Fundamental RMS residual current
I L1, I L 2 , I L 3
IE
Circuit Breaker
Position
Trip Circuit Supervision 74TCS
IN1 - 52b state
IN2 - 52a state
IN3 - TCS state
Counters
Fault Recorder
Number of events
Recording mode
Trigger:
Output relays activation (OFF-ON transition)
External trigger (binary inputs)
Element pickup (OFF-ON transition)
Data recorded:
Event counter (resettable by ThySetter)
Fundamental RMS phase currents
Fundamental RMS residual current
Event cause
Binary inputs state
Output relays state
Event cause info (operating phase)
Time stamp
Settings recording
Number of setting changes
Recording mode
Data recorded:
Setting counter
Setting data
Time stamp
20
circular
K1...K4
IN1, IN2, IN3
Start/Trip
0...10 9
I L1, I L 2 , I L 3
IE
start, trip
IN1, IN2, IN3
K1...K4
L1, L2, L3
Date and time
10
circular
0...109
description and parameter
Date and time
COMTRADE
2 [1]
circular
16 per power frequency cycle
0...63 T [2]
IN1, IN2, IN3
K1...K4
Start, Trip
ThySetter
Start I>, I>>, ...Trip I>...
i L1
i L2
i L3
iE
K1
Event storage
Sequence of Event Recorder (SER)
Number of events
100
Recording mode
circular
Trigger:
K1...K4
Output relays switching
IN1, IN2, IN3
Binary inputs switching
Setting changes
Data recorded:
0...10 9
Event counter (resettable by ThySetter)
Event cause
binary input/output relay/setting changes
Time stamp
Date and time
+UAUX
DG
52a
52b
52a
52b
-UAUX
NA016
P2
IL1
C4
C5
IL2
C6
IL3
C7
S1
S2
C8
OUTPUT RELAYS
P2
C2
C3
CURRENT INPUTS
S1
S2
P1
K1
C1
P1
IE
K2
K3
K4
A2
A1 TRIP
A3 +UAUX
A4
A6
A5
A9
A8
A7
A11
A12
A10
A13
A14 IN1
CB
supervision
A15
-UAUX
A16 IN2
A17
+UAUX
Trip Circuit
Supervision (TCS)
A18 IN3
A19
A20
UAUX
A+ 3
B2 E1
A21
A22
RS485
RS232
FRONT PANEL
120
DIMENSIONS
FRONT VIEW
REAR VIEW
101
107
D1
A1
A2
C1
C2
A3
A4
A5
RX
A6
TX
A7
ON
START
TRIP
149
171
177
A8
C3
F1
F2
F3
F4
F5
C4
A9
B1
A10
A11
B2
B3
A12
A13
A14
B4
B5
C5
C6
B6
B7
B8
A15
A16
A17
A18
A19
A20
C7
C8
A21
A22
E1
SIDE VIEW
30
161
154
75
IDENTIFICATION DATA
In 5A 1A
5A
IEn 5A 1A
5A
UAUX 24-230 Vac/dc
1
2
3
4
5
LEDs
ON e Diagnostic
50-51
50N-51N
CB OPEN
CB CLOSED
TCS
Start
Trip
NA016#5M00