Beruflich Dokumente
Kultur Dokumente
Operating Instructions
CyberAir 2
Index 13
Issue 7.08
Contents
1. Safety ...........................................................................................................................5
1.1 Regulations .......................................................................................................................................5
1.2 Marking..............................................................................................................................................5
1.3 Safety instructions .............................................................................................................................6
1.4 Handling refrigerants .........................................................................................................................6
1.5 Safety and environmental requirements ............................................................................................7
2. Description ..................................................................................................................8
2.1 Type code ..........................................................................................................................................8
2.2 Intended use ....................................................................................................................................13
2.3 Design of the A/C unit .....................................................................................................................13
2.4 Basic components/function of refrigerant circuit ..............................................................................14
2.5 Cooling water circuit (G, GCW, GE) ................................................................................................15
2.6 Chilled water circuit (ACW, GCW) ...................................................................................................15
6. Installation .................................................................................................................33
6.1 Positioning .......................................................................................................................................33
6.2 Air side connection (optional) ..........................................................................................................33
6.3 Connection of the piping ..................................................................................................................35
6.3.1 Position of the refrigerant connections (A/ACW units) .............................................................35
6.3.2 Refrigerant Piping.....................................................................................................................36
6.3.2.1 Selection of pressure and liquid line......................................................................................36
6.3.2.2 Routing refrigerant-conducting pipes ....................................................................................41
6.3.2.3 Evacuating refrigeration systems ..........................................................................................43
6.3.2.4 Filling systems with R407C refrigerants ................................................................................45
6.3.3 Water piping .............................................................................................................................47
6.3.4 Condensate drain connection...................................................................................................49
6.4 Electrical connection ......................................................................................................................50
7. Commissioning .........................................................................................................51
E/0708/13/3
8. Maintenance ..............................................................................................................53
8.1 Safety instructions ...........................................................................................................................53
8.2 Maintenance intervals .....................................................................................................................53
8.3 Refrigerant circuit ............................................................................................................................54
8.4 Air circuit ..........................................................................................................................................55
8.5 Water circuit .....................................................................................................................................56
8.6 Unit in general .................................................................................................................................56
8.7 Competences ..................................................................................................................................56
E/0708/13/4
1. Safety
1.1 Regulations
CEE Guide-lines / Standards
- Guide-line for the security of machines (CEE 98/37/EG)
- Low voltage guide-line (CEE 73/23)
- Electromagnetical interference suppression regulation (CEE 89/336)
- Pressure equipment guide-line (CEE 97/23)
Harmonized European standards
EN 378 - T1/T2/T3/T4
Refrigerating systems and heat pumps
EN ISO 12100 - 1/2
Safety of machines
EN 294
Safety of machines
EN 60204-1
Electrical equipment of machines
EN 61000-6-2
Electromagnetic compatibility, Immunity standard
EN 61000-6-4
Emission standard for industrial environment
This cooling unit contains uorinated greenhouse gas covered by the Kyoto protocol.
1.2 Marking
Danger
Attention
Information
E/0708/13/5
- Observe the national regulations of the country where the unit will be installed
- The refrigerant circuit contains refrigerant and refrigerating plant oil, observe professional disposal for maintenance and when setting the unit out of service.
- Cooling water additives have an acidic effect on skin and eyes, wear safety glasses and
safety gloves
- Observe personal protective equipment when working on the refrigerant circuit.
- The unit may only be used to cool air according to the Stulz specication.
E/0708/13/6
It is absolutely essential to comply with the rst aid measures if accidents occur.
Refrigerants containing FCs contribute to the global warming and with this to climate changes. The FCs
must therefore be disposed of in accordance with the regulations, i.e. only by companies specially qualied
under 191 of the water resources management law and licensed as recognised disposal companies
for refrigerants.
Operation:
Repeated inspection:
according to EN 378
The operator is responsible for the execution.
The operator must ensure that all maintenance, inspection and assembly work is carried out by authorised
and qualied specialist staff who have made an in-depth study of the operating instructions.
It is absolutely essential to comply with the procedure for shutting down the system described in the operating instructions. Before maintenance work, the unit must be switched off at the main switch and a warning
sign displayed to prevent unintentional switching-on.
If health problems occur during or after handling uorinated hydrocarbons, a doctor is to be consulted
immediately. The doctor is to be informed that the work involved the use of uorinated hydrocarbons.
In the case of acute effects, the casualty is to be brought into the fresh air as quickly as possible.
The casualty must never to be left unsupervised.
If the casualty is not breathing, initiate mouth-to-mouth resuscitation immediately.
If the casualty is unconscious or very dazed he or she must not be given any liquid.
Splashes of uorinated hydrocarbons in the eyes can be blown out or fanned out by an assistant. Then
rinse with water.
E/0708/13/7
2. Description
2.1 Type code
The type code represents the unit variant of your A/C unit and can be found on the rating plate.
Serial no.
Explanation
A
Unit variants
Product range
Energy index
Airow direction
Output of unit in kW
Number of refrigeration circuits
Cooling system:
A: air-cooled
G: water/glycol-cooled
GE: glycol-cooled + free cooling
D 35 1 A
CW: chilled water cooling (directly)
A,G, GE, ACW, GCW
1, 2
181 ... 1062
D, U - Downow, Upow
S, L - Standard, Low energy
A = CyberAir
Page code
E / 0708 / 13 / 7
Page code:
D - German
E - English
F - French
U - US English
E/0708/13/8
Date of issue
month/year
Index
number
Page
number
Unit variants
The different versions of the CyberAir product range are dened by the energy index, the airow direction,
the unit capacity, the number of refrigerant circuits and the way of cooling system.
The units of the CyberAir product range exist in 5 different cabinet sizes with different width, to which specic
features adhere as far as the heating and humidier equipment is concerned.
Size
A / G / ACW / GCW
Cab. size
Baugre
1 circuit
1-kreisig
181
211
261
291
311
361
401
411
451
531
22-kreisig
circuits
402
452
512
552
612
702
A / G /GE
Cab. size
Baugre
1 circuit
1-kreisig
181
211
261
291
311
361
401
411
451
531
802
862
1062
22-kreisig
circuits
402
452
512
552
612
702
E/0708/13/9
Air ow (D/U)
A distinction is made between downow and upow A/C units in respect of air ow. On downow units the
room air is drawn in to the A/C units from above and passed down into the raised oor void. On upow units
the room air is drawn in from the front side of the A/C unit and passed upwards.
Downow
Upow
room / return air
supply air
E/0708/13/10
A-system
The air-cooled (A) direct expansion (DX)
system uses refrigerant as the heat transfer
medium. Room air re-circulates through the internally mounted CyberAir unit which houses
the evaporator coil, scroll compressor and
refrigeration system. A remotely mounted aircooled condenser is connected, by specialist
installers, to the room unit via a sealed refrigeration circuit such that the absorbed room heat
load can be rejected to atmosphere.
G-system
The glycol/water cooled (G) version utilises the
same refrigeration system as the type-A CyberAir unit and room air re-circulates through an
evaporator coil. However an internally mounted
plate condenser is then used to transfer the
room heat load to a glycol solution. This condenser water acts as a secondary heat transfer
medium, which is then pumped to a remotely
mounted air-cooled drycooler or cooling tower
where the heat is nally rejected to atmosphere.
Generally the condenser water system is in the
form of a ring main connected in parallel to a
number of stand-alone CyberAir units mounted
in the critical space.
GE-system
The room air is drawn through both the free
cooling coil and the evaporator. In summer
operation with high external temperatures,
the evaporator absorbs heat from the room air
and transfers it to the refrigerant. In the plate
condenser a heat exchange between the refrigerant and the water/glycol takes place.
With low outside temperatures the free cooling
coil transfers the heat directly to the water/glycol.
The water/glycol is conveyed to the drycooler by
an external pump and two installed 2-way ball
valves controlled by the C7000. The drycooler
rejects the heat to the outside air. The A/C unit
and the external drycooler are connected with
each other by a sealed water/glycol circuit.
E/0708/13/11
ACW-System
The ACW CyberAir system is a combination of both the A and CW systems
with two cooling coils. The CompTrol
7000 manages the ACW system to allow the air cooled A system to operate
as standby to the CW chilled water
system or vice versa to give added
security and back up to the computer
room.
Both systems may not run simultaneously. This can be prevented by
adjusting a cooling priority at the
C7000.
GCW-System
The GCW CyberAir system is a combination of both the G and CW systems
with two cooling coils. The CompTrol
7000 manages the GCW system to
allow the glycol cooled or condenser
water G system to operate
as standby to the CW chilled water
system or vice versa to give added
security and back up to the computer
room.
Both systems may not run simultaneously. This can be prevented by
adjusting a cooling priority at the
C7000.
E/0708/13/12
electrical box
Receiver
Filter dryer
Expansion
valve
Sightglass
Humidier
(optional)
E/0708/13/13
Dehumidifying circuit
To achieve a dehumidication, the electronic expansion valve is partially closed in the rst step. The reduction
of the refrigerant mass ow makes the evaporation temperature drop, which lets the surface temperature in
a part of the evaporator fall below the dew point of the air. This causes dehumidication.
For a bigger dehumidication, the fan speed is reduced. With a constant cooling capacity, the temperature of
the air which ows through the heat exchanger coil, passes below the dew point. The moisture contained in
the air condenses on the heat exchanger gathers in the condensate pan and is carried away by the drain.
Safety devices
The refrigerant circuit is protected against insufcient operating pressure by a safety pressure limiter
(low-pressure switch). If the operating pressure is fallen below, a warning signal appears on the display
and the unit is put out of operation. A safety pressure cut-out (high-pressure switch) is triggered at
25,2 (36)* bar and switches off the compressor. A warning signal on the display of the controller appears.
A liquid receiver and a safety valve, which releases refrigerant at 28 (40)* bar, are tted on A/ACW-units
as further protection.
HP switch:
releases at:
25,2 (36)* bar
manual reset possible at: 18,0 (29)* bar
Safety valve:
28 (40)* bar
* The values outside of the brackets are valid for the refrigerants R407C and R134a, the values inside the brackets for R410A.
E/0708/13/14
Component protection
Compressor
The compressor is equipped with an internal high pressure protection which opens a bypass in case of high
pressure, so that an internal pressure compensation takes place.
Fan
The EC fan control contains safety elements which protect the fan in case of phase failure, voltage uctuation
and excessive current. If the voltage in one or more phases drops for 5 seconds or longer below 290 V, the
fan is switched off and an airow alarm is generated. In consequence of the alarm the compressor and, if
existant, the reheat and humidier are also switched off.
After the supply voltage return the airow alarm must be manually resetted in order to restart the A/C unit.
In areas with unstable electrical supply networks the option "three phase control" should therefore be chosen.
With this option the A/C unit starts automatically after the return of the supply voltage.
E/0708/13/15
3. Refrigerant circuit
Legend
TCE
PSL
Expansion valve
PZH
Filter drier
PC
Pressure sensor
Sight glass
TIC
Angle valve
TC
Temperature sensor
Stop valve
Pressure relief valve
Schrader valve
E/0708/13/16
Receiver
TCE
Evaporator
EC
Compressor
Fan
PSL
PZH
2 - circuits
Receiver 1
Evaporator 1
TCE
Compressor 1
PSL
PZH
Receiver 2
Evaporator 2
TCE
EC
Compressor 2
Fan
PSL
PZH
E/0708/13/17
TCE
Evaporator
Condenser
EC
Fan
PSL
PZH
Compressor
2 - circuits
Evaporator 1
TCE
Condenser 1
PSL
PZH
Compressor 1
Evaporator 2
TCE
Condenser 2
EC
Fan
PSL
PZH
Compressor 2
E/0708/13/18
Evaporator
TCE
Condenser
EC
M
M
Fan
PC
PSL
PZH
TIC
Compressor
2 - circuits
TCE
Evaporator
Condenser 1
M
M
PC
PSL
PZH
TIC
Compressor 1
Evaporator
TCE
Condenser 2
EC
PC
Fan
Compressor 2
PSL
PZH
E/0708/13/19
CW coil
Evaporator
TCE
EC
Receiver
3-way chilled
water control
valve
Fan
Compressor
PSL
2 - circuits
PZH
CW coil
TCE
Evaporator 1
Receiver 1
PSL
PZH
Compressor 1
Evapora-
TCE
Receiver 2
EC
Fan
Compressor 2
PSL
E/0708/13/20
PZH
3-way chilled
water control
valve
CW coil
Evaporator
TCE
3-way chilled
water control
valve
EC
Fan
Condenser
PSL
PZH
Compressor
2 - circuits
CW coil
TCE
Evaporator 1
3-way chilled
water control
valve
Compressor 1
PSL
Evaporator 2
Condenser 1
PZH
TCE
EC
Fan
Condenser 2
PSL
PZH
Compressor 2
E/0708/13/21
4. Technical data
4.1 Application limits
The STULZ CyberAir units are provided for operation
within the following ranges:
- Room conditions:
Between 18C, 45% R.H. and 27C, 55% R.H.
- Outdoor ambient conditions:
lower limit: -10C, depending on selected option
down to 45C
upper limit: depending on selected condenser
- Voltage:
Standard
400V/3ph/50Hz
20 Pa
50 Pa
DX Units
Return air conditions for evaporator capacity:
Cooling uid (G, GCW):
Cooling uid (GE):
Fluid inlet temperature:
Fluid outlet temperature:
Condensation temperature:
Max. condensation temperature:
CW Units
Return air conditions for cooling capacity:
EWT - Entering water temperature:
LWT - Leaving water temperature:
Cooling uid:
The sound pressure levels are valid at a height of 1m and distance of 2m in front of the unit under free eld
conditions and with nominal data. The values take into account the effects of all installation and design parts
contained in the standard unit. The values for upow units assume an installed discharge duct.
E/0708/13/22
181
211
261
291
311
361
401
411
451
531
18,2
18,2
21,0
21,0
27,2
24,7
29,7
26,2
30,9
30,9
36,2
33,7
40,1
35,2
40,8
37,8
45,1
45,1
53,5
47,8
Verhltnis
sens./total
Ratio sens./total
Komp.-Leistungsaufnahme
Comp. power consumption
kW
Kompressortyp
Compressor type
1 1
EERmax (ASD...A/G)
R407C
DX-Klteleistung
DX-cooling cap. R410A
R410A total
kW
24C/50% r.F.
sensible
sensibel
Verhltnis
sens./total
Ratio sens./total
Komp.-Leistungsaufnahme
Comp. power consumption
kW
Kompressortyp
Compressor type
1 1
EERmax (ASD...A/G)
R410A
DX-Klteleistung
DX-cooling cap. R134a
R134a total
kW
24C/50% r.F.
sensible
sensibel
Ratio
sens./total
Verhltnis
sens./total
0,91
0,88
0,93
0,88
0,92
0,89
3,7
4,2
5,6
6,3
6,3
7,5
8,4
8,4
9,6
11,6
C3
C4
C13
C14
C14
C15
C16
C16
C17
C18
4,14
3,96
3,89
3,76
4,01
3,85
3,89
4,16
3,73
3,72
18,7
18,7
24,7
22,3
27,0
24,7
30,4
26,5
32,0
30,3
36,5
33,8
40,3
35,3
41,2
38,0
46,6
44,1
53,2
47,7
0,90
0,91
0,87
0,95
0,93
0,88
0,92
0,95
0,90
3,9
5,2
5,6
6,4
6,4
7,4
8,5
8,5
9,3
11,0
C21
C23
C24
C25
C25
C26
C27
C27
C28
C30
4,07
3,92
3,86
3,80
4,10
3,92
3,88
4,16
3,95
3,86
17,5
17,5
19,9
19,9
25,3
24,0
26,2
24,9
27,5
27,5
32,5
32,5
37,3
34,1
37,9
37,9
0,95
0,95
0,91
3,3
3,9
5,0
5,3
5,3
6,7
7,7
7,7
C5
C13
C15
C16
C16
C17
C18
C18
4,38
3,98
3,95
3,80
4,10
3,78
3,89
4,16
CW-cooling
CW-Klteleistung
capacity
total
kW
24C/50% r.h.
r.F.
sensible
sensibel
20,3
18,6
23,9
21,7
26,4
23,9
27,5
24,8
34,0
30,8
37,8
34,0
37,8
34,0
42,4
38,0
51,4
45,5
53,7
47,3
Verhltnis
sens./total
Ratio sens./total
0,92
0,91
0,91
0,88
0,91
0,90
0,90
0,90
0,89
0,88
Comp.
Komp.-Leistungsaufnahme
power consumption
kW
Kompressortyp
Compressor
type
1 1
EERmax (ASD...A/G)
R134a
Refrigerant
charge
Fllmenge G,
GCWG, GCW
kg
2,4
2,8
3,2
3,4
3,9
4,1
4,3
4,4
4,6
5,1
Wasservolumenstrom
G
Water ow G
m/h
1,9
2,2
2,8
3,1
3,2
3,7
4,1
4,1
4,7
5,6
dp wasserseitig
water side G G
kPa
13
18
17
20
15
20
24
18
23
25
Wasservolumenstrom
CW
Water
ow CW
m/h
3,5
4,1
4,5
4,7
5,9
6,5
6,5
7,3
8,8
9,2
dp wasserseitig
CW
water side CW
kPa
32
44
53
57
29
36
36
40
59
63
CW-Registerinhalt
CW
coil content
dm
CW - Ventilgre
(3-Wege)
valve size (3-way)
Airow
Luftvolumenstrom
Vent.-Leistungsaufnahme
Fan
power consumption
Max.
ext.stat.
stat.pressure
Druck
Max. ext.
Vent.-Leistungsaufnahme
Fan
power consumption
Max.
ext.stat.
stat.pressure
Druck
Max. ext.
Schalldruckpegel
Sound
pressure level
Vent.-Leistungsaufnahme
Fan
power consumption
3
Baugre
Cabinet size
Upow
Schalldruckpegel
Sound
pressure level
A/G
ACW/GCW
Schalldruckpegel
Sound
pressure level
A/G
Max.
ext.stat.
stat.pressure
Druck
Max. ext.
ACW/GCW
Vent.-Leistungsaufnahme
Fan
power consumption
Downow
Downow
Schalldruckpegel
Sound
pressure level
14,3
18,3
1"
1"
1"
1"
1 1/4"
1 1/4"
m/h
5500
6500
7200
7500
9000
Pa
450
450
440
410
450
330
330
450
450
420
dBA
48,3
51,8
54,0
54,9
56,5
58,7
58,7
51,3
55,4
56,4
kW
0,7
1,1
1,4
1,6
1,4
1,9
1,9
1,4
2,5
2,8
Ventilatoranzahl
Number
of fans
Max. ext.
ext.stat.
stat.pressure
Druck
Max.
9,6
1 1/4"
1 1/4"
1 1/4"
1 1/4"
Pa
450
450
380
320
430
270
270
450
430
370
dBA
49,5
53,1
55,2
56,1
56,8
59,1
59,1
52,5
56,7
57,6
kW
0,8
1,3
1,7
1,9
1,6
2,2
2,2
1,7
3,0
3,4
Pa
450
450
430
380
450
310
310
450
450
420
dBA
49,6
52,9
54,9
55,8
56,9
59,1
59,1
52,5
56,4
57,3
kW
0,8
1,2
1,6
1,8
1,6
2,1
2,1
1,7
2,9
3,2
Pa
450
450
340
290
410
240
240
450
400
340
dBA
50,8
54,1
56,2
57,0
57,4
59,6
59,6
53,7
57,7
58,6
kW
0,9
1,4
1,9
2,2
1,8
2,4
3,1
2,0
3,4
3,8
E/0708/13/23
402
452
512
552
612
702
802
862
1062
DX-cooling
DX-Klteleistung
cap. R407C
R407c total
kW
24C/50% r.h.
r.F.
sensible
sensibel
40,8
37,8
46,4
43,4
53,3
47,7
54,4
54,4
61,3
61,3
70,9
64,8
81,3
74,4
89,5
80,3
104,5
88,9
Verhltnis
sens./total
Ratio
sens./total
0,93
0,94
0,89
0,91
0,92
0,90
0,85
8,4
9,6
11,2
11,2
12,6
15,0
16,8
19,2
23,0
C4
C5
C13
C13
C14
C15
C16
C17
C18
4,16
3,90
3,81
3,83
3,58
3,49
3,91
3,71
3,62
DX-cooling
DX-Klteleistung
cap. R410A
R410A total
kW
24C/50% r.F.
sensible
sensibel
43,0
38,6
49,3
44,5
52,9
47,6
53,8
53,8
61,3
61,3
72,1
65,2
81,4
74,5
90,4
80,7
104,2
88,7
Verhltnis
sens./total
Ratio
sens./total
0,90
0,90
0,90
0,90
0,92
0,89
0,85
9,0
10,4
11,2
11,2
12,8
14,8
17,0
18,6
22,0
Comp.
Komp.-Leistungsaufnahme
power consumption
kW
1 1
Kompressortyp
Compressor
type
EERmax
(ASD...A/G)
max
R407C
Comp.
Komp.-Leistungsaufnahme
power consumption
kW
Kompressortyp
Compressor
type
1 1
EERmax
(ASD...A/G)
max
R410A
DX-cooling
DX-Klteleistung
cap. R134a
R134a total
kW
24C/50% r.F.
sensible
sensibel
Ratio
sens./total
Verhltnis
sens./total
C22
C23
C24
C24
C25
C26
C27
C28
C29
4,13
3,88
3,78
3,79
3,54
3,66
3,88
3,85
3,73
37,9
37,9
43,5
43,5
49,4
46,2
51,1
51,1
54,7
54,7
63,6
63,6
76,4
72,5
0,94
0,95
7,8
8,6
10,2
10,0
10,6
13,2
15,4
C13
C14
C15
C15
C16
C17
C18
4,12
3,99
3,80
3,93
3,62
3,44
3,94
CW-cooling
CW-Klteleistung
capacity
total
kW
24C/50% r.h.
r.F.
sensible
sensibel
40,4
36,8
47,8
43,0
51,4
46,1
57,2
52,0
66,4
59,7
69,9
62,7
77,9
69,7
83,3
74,2
88,7
78,6
Verhltnis
sens./total
Ratio
sens./total
0,91
0,90
0,90
0,91
0,90
0,90
0,90
0,89
0,89
Comp.
Komp.-Leistungsaufnahme
power consumption
kW
Kompressortyp
Compressor
type
1 1
EERmax
(ASD...A/G)
max
R134a
Refrigerant
charge G, GCW
Fllmenge G/GCW
kg
2,2
2,4
3,2
3,5
3,9
4,1
4,3
4,6
5,2
Wasservolumenstrom
G
Water
ow G
m/h
4,2
4,8
5,5
5,7
6,3
7,3
8,4
9,4
11,0
wasserseitig
dp water
side G G
kPa
16
21
27
17
21
28
25
31
42
Wasservolumenstrom
CW
Water
ow CW
m/h
7,0
8,2
8,9
9,9
11,4
12,0
13,4
14,4
15,3
wasserseitig
CW
dp water
side CW
kPa
33
47
54
35
47
53
33
38
43
CW-Registerinhalt
CW
coil content
dm
1 1/4"
1 1/4"
1 1/4"
1 1/2"
1 1/2"
1 1/2"
2"
2"
2"
m/h
11000
13000
14000
16000
18500
19000
21000
22500
24000
Pa
450
450
440
440
220
190
450
390
300
dBA
51,3
54,8
56,4
57,3
60,4
61,0
57,3
58,8
60,2
kW
1,4
2,3
2,8
3,0
4,5
4,9
4,0
4,9
5,9
Ventilgre
(3-Wege)
CW - valve
size (3-way)
Airow
Luftvolumenstrom
Schalldruckpegel
Sound
pressure level
Fan
Vent.-Leistungsaufnahme
power consumption
Max.ext.
ext.stat.
stat.pressure
Druck
Max.
Fan
Vent.-Leistungsaufnahme
power consumption
Max.ext.
ext.stat.
stat.pressure
Druck
Max.
Schalldruckpegel
Sound
pressure level
Fan
Vent.-Leistungsaufnahme
power consumption
Baugre
Cabinet
size3
Upow
Schalldruckpegel
Sound
pressure level
ACW/GCW
Max.ext.
ext.stat.
stat.pressure
Druck
Max.
A/G
Fan
Vent.-Leistungsaufnahme
power consumption
ACW/GCW
Schalldruckpegel
Sound
pressure level
Downow
Downow
Max.ext.
ext.stat.
stat.pressure
Druck
Max.
A/G
Ventilatoranzahl
Number
of fans
18,3
22,9
27,5
Pa
450
450
360
370
130
90
400
310
210
dBA
52,5
56,1
57,6
58,3
61,4
62,0
58,6
60,1
61,5
kW
1,7
2,7
3,4
3,5
5,3
5,7
4,7
5,8
7,0
Pa
450
450
420
420
200
250
450
370
280
dBA
52,5
55,8
57,3
58,1
61,1
61,7
58,3
59,7
61,0
kW
1,7
2,6
3,2
3,3
5,0
5,4
4,5
5,5
6,6
Pa
450
430
340
350
100
50
380
280
180
dBA
53,7
57,1
58,6
59,1
62,2
62,7
59,6
61,0
62,3
kW
2,0
3,1
3,8
3,9
5,9
6,3
5,4
6,5
7,8
For electrical data, heating and humidier equipment see page 30.
The indicated refrigerant charge is valid per refrigerant circuit for R407C, R410A and R134a, for A/ACW units for all sizes it is: 1,0 kg
For the refrigerant R22 the charge is for all sizes and versions: 0,5 kg.
3
For dimensions and weights see page 29.
1
2
E/0708/13/24
181
211
261
291
311
361
401
411
451
531
18,6
18,6
21,6
21,6
27,6
25,5
30,2
27,0
31,3
31,3
36,6
34,4
40,6
36,0
41,7
38,8
46,4
46,4
54,4
49,2
Verhltnis
sens./total
Ratio
sens./total
0,92
0,89
0,94
0,89
0,93
0,90
3,7
4,2
5,6
6,3
6,3
7,5
8,4
8,4
9,7
11,6
C3
C4
C13
C14
C14
C15
C16
C16
C17
C18
4,65
4,50
4,38
4,25
4,41
4,26
4,27
4,44
4,03
4,00
DX-cooling
DX-Klteleistung
cap. R410A
R410A total
kW
24C/50% r.F.
sensibel
sensible
18,9
17,34
25,1
23,2
27,2
25,3
30,8
27,2
31,5
29,54
36,8
34,5
40,5
35,9
41,6
38,8
46,2
46,2
53,9
48,9
Verhltnis
sens./total
Ratio
sens./total
0,92
0,92
0,93
0,88
0,94
0,94
0,89
0,93
0,91
Comp.
Komp.-Leistungsaufnahme
power consumption
kW
Kompressortyp
Compressor
type
1 1
EERmax (ALD...A/G)
R407C
Comp.
Komp.-Leistungsaufnahme
power consumption
kW
1 1
Kompressortyp
Compressor
type
EERmax (ALD...A/G)
R410A
DX-cooling
DX-Klteleistung
cap. R134a
R134a total
kW
24C/50% r.F.
sensibel
sensible
Ratio
sens./total
Verhltnis
sens./total
Comp.
Komp.-Leistungsaufnahme
power consumption
kW
Kompressortyp
Compressor
type
1 1
EERmax (ALD...A/G)
R134a
3,9
5,2
5,6
6,4
6,4
7,4
8,5
8,5
9,3
11,0
C21
C23
C24
C25
C25
C26
C27
C27
C28
C30
4,50
4,33
4,32
4,28
4,38
4,33
4,22
4,38
4,16
4,15
17,7
17,7
20,4
20,4
25,3
25,3
26,2
26,2
27,8
27,8
33,1
33,1
37,8
34,9
38,7
38,7
0,92
3,3
3,8
5,0
5,3
5,3
6,7
7,7
7,7
C5
C13
C15
C16
C16
C17
C18
C18
4,92
4,64
4,44
4,30
4,56
4,24
4,30
4,45
kg
2,9
3,3
3,7
3,9
4,4
4,6
4,8
4,9
5,1
5,6
Wasservolumenstrom
G
Water
ow G
m/h
1,9
2,2
2,8
3,1
3,2
3,7
4,1
4,2
4,7
5,6
wasserseitig
dp water
side G G
kPa
13
18
17
20
15
20
24
18
23
25
Luftvolumenstrom
Airow
m/h
5500
6500
7200
7500
9000
2
RefrigerantGcharge
G2
Fllmenge
Ventilatoranzahl
Number of fans
Downow
Max. externer
external static
statischer
pressure
Druck
Pa
450
450
450
450
450
450
450
450
450
450
Schalldruckpegel
Sound pressure level
dBA
45,9
49,4
51,6
52,5
47,1
49,3
49,3
49,4
53,5
54,5
Vent.-Leistungsaufnahme
Fan
power consumption
kW
0,3
0,6
0,7
0,8
0,8
1,1
1,1
1,0
1,8
2,0
Upow
Max. external
pressure
externer static
statischer
Druck
Pa
450
450
450
450
450
450
450
450
450
450
dBA
46,9
50,1
52,2
53,0
48,7
50,7
50,7
50,6
54,5
55,4
Fan
power consumption
Vent.-Leistungsaufnahme
kW
0,4
0,7
0,9
1,0
1,0
1,3
1,3
1,2
2,1
2,3
Cabinet
size
Baugre
3
For electrical data, heating and humidier equipment see page 30.
2
The indicated refrigerant charge is valid for R407C, R410A and R134a, for A units for all sizes it is: 1,0 kg
For the refrigerant R22 the charge is for all sizes and versions: 0,5 kg.
3
For dimensions and weights see page 29.
4
Data with reduced air ow, details on request.
1
E/0708/13/25
402
452
512
552
612
702
41,7
38,8
47,3
44,6
54,4
49,2
56,1
56,1
63,3
63,3
72,6
68,3
Verhltnis
sens./total
Ratio
sens./total
0,93
0,94
0,90
0,94
8,4
9,6
11,2
11,2
12,6
15,0
C4
C5
C13
C13
C14
C15
Comp.
Komp.-Leistungsaufnahme
power consumption
kW
Kompressortyp
Compressor
type
1 1
4,44
4,22
4,12
4,32
4,11
3,99
DX-cooling
DX-Klteleistung
cap. R410A
R410A total
kW
24C/50% r.F.
sensibel
sensible
EERmax (ALD...A/G)
R407C
43,1
39,4
49,9
45,7
53,9
48,9
54,74
50,94
63,04
59,04
63,3
59,8
Verhltnis
sens./total
Ratio
sens./total
0,91
0,92
0,91
0,93
0,94
0,94
9,0
10,4
11,2
11,2
12,8
12,8
C22
C23
C24
C24
C25
C26
4,31
4,16
4,08
4,21
4,04
3,96
38,7
38,7
44,3
44,3
50,1
47,5
52,5
52,5
56,0
56,0
66,0
66,0
0,95
7,8
8,6
10,0
10,0
10,6
13,4
Comp.
Komp.-Leistungsaufnahme
power consumption
kW
Kompressortyp
Compressor
type
1 1
EERmax (ALD...A/G)
R410A
DX-cooling
DX-Klteleistung
cap. R134a
R134a total
kW
24C/50% r.F.
sensibel
sensible
Verhltnis
sens./total
Ratio
sens./total
Komp.-Leistungsaufnahme
Comp. power consumption
kW
Kompressortyp
Compressor
type
C13
C14
C15
C15
C16
C17
4,40
4,34
4,18
4,45
4,18
3,98
kg
2,7
2,9
3,7
4,0
4,4
4,6
Wasservolumenstrom
G
Water
ow G
m/h
4,2
4,8
5,5
5,7
6,3
7,3
wasserseitig
dp water
side G G
kPa
16
21
27
17
21
28
Luftvolumenstrom
Airow
m/h
11000
13000
14000
16000
18500
19500
1 1
EERmax (ALD...A/G)
R134a
2
RefrigerantGcharge
G2
Fllmenge
Ventilatoranzahl
Number of fans
Downow
Max. externer
external static
statischer
pressure
Druck
Pa
450
450
450
450
450
450
Schalldruckpegel
Sound pressure level
dBA
49,4
52,9
54,5
51,6
54,7
55,8
Vent.-Leistungsaufnahme
Fan
power consumption
kW
1,0
1,6
2,0
1,8
2,8
3,2
Upow
Max. external
pressure
externer static
statischer
Druck
Pa
450
450
450
450
450
450
dBA
50,6
53,9
55,4
52,9
55,8
56,8
Fan
power consumption
Vent.-Leistungsaufnahme
kW
1,2
1,9
2,3
2,2
3,2
3,7
Cabinet
size
Baugre
3
For electrical data, heating and humidier equipment see page 30.
2
The indicated refrigerant charge is valid per refrigerant circuit for R407C, R410A and R134a, for A units for all sizes it is: 1,0 kg
For the refrigerant R22 the charge is for all sizes and versions: 0,5 kg.
3
For dimensions and weights see page 29.
4
Data with reduced air ow, details on request.
1
E/0708/13/26
181
211
261
291
311
361
401
411
451
531
18,6
18,6
21,6
21,6
27,6
25,5
30,2
27,0
31,3
31,3
36,6
34,4
40,6
36,0
41,7
38,8
46,4
46,4
54,4
49,2
0,92
0,89
0,94
0,89
0,93
0,90
3,7
4,2
5,6
6,3
6,3
7,5
8,4
8,4
9,7
11,6
C3
C4
C13
C14
C14
C15
C16
C16
C17
C18
Verhltnis
sens./total
Ratio
sens./total
Comp.
Komp.-Leistungsaufnahme
power consumption
kW
Kompressortyp
Compressor
type
1 1
4,65
4,50
4,38
4,25
4,41
4,26
4,27
4,44
4,03
4,00
DX-cooling
DX-Klteleistung
cap. R410A
R410A total
kW
24C/50% r.F.
sensibel
sensible
EER
R407C
18,94
17,34
25,1
23,2
27,2
25,3
30,8
27,2
31,54
29,54
36,8
34,5
40,5
35,9
41,6
38,8
46,2
46,2
53,9
48,9
Verhltnis
sens./total
Ratio
sens./total
0,92
0,92
0,93
0,88
0,94
0,94
0,89
0,93
0,91
3,9
5,2
5,6
6,4
6,4
7,4
8,5
8,5
9,3
11,0
C21
C23
C24
C25
C25
C26
C27
C27
C28
C30
4,50
4,33
4,32
4,28
4,38
4,33
4,22
4,38
4,16
4,15
17,7
17,7
20,4
20,4
25,3
25,3
26,2
26,2
27,8
27,8
33,1
33,1
37,8
34,9
38,7
38,7
0,92
3,3
3,8
5,0
5,3
5,3
6,7
7,7
7,7
Comp.
Komp.-Leistungsaufnahme
power consumption
kW
Kompressortyp
Compressor
type
1 1
EER
R410A
DX-cooling
DX-Klteleistung
cap. R134a
R134a total
kW
24C/50% r.F.
sensibel
sensible
Ratio
sens./total
Verhltnis
sens./total
Comp.
Komp.-Leistungsaufnahme
power consumption
kW
Kompressortyp
Compressor
type
C5
C13
C15
C16
C16
C17
C18
C18
4,92
4,64
4,44
4,30
4,56
4,24
4,30
4,45
CW-Klteleistung
CW-cooling capacity
total
kW
24C/50% r.F.
r.h.
sensibel
sensible
19,6
18,5
22,5
21,4
26,9
24,8
28,9
26,3
32,2
29,9
36,6
33,5
38,9
35,0
39,0
36,4
46,0
42,9
51,2
46,7
Verhltnis
sens./total
Ratio
sens./total
1 1
EER
R134a
0,94
0,95
0,92
0,91
0,93
0,92
0,90
0,93
0,93
0,91
kg
2,9
3,3
3,7
3,9
4,1
4,4
4,6
4,7
5,1
5,6
Wasservolumenstrom
Water
ow
m/h
4,3
4,9
6,3
7,0
7,2
8,3
9,3
9,4
10,8
12,5
wasserseitig
- Sommer
dp water
side - summer
kPa
59
76
67
82
66
86
107
61
80
105
dp wasserseitig
- Winter
water side - winter
kPa
43
56
45
56
54
71
89
40
52
70
GE-Registerinhalt
GE coil content
dm
Refrigerant
Fllmenge 2charge 2
Ventilgre
(2-Wege)
Valve
size (2-way)
9,6
14,3
18,3
1 1/4"
1 1/4"
1 1/4"
1 1/4"
1 1/2"
1 1/2"
5500
6500
7200
7500
9000
Pa
450
450
450
450
450
450
450
450
450
450
Schalldruckpegel
Sound pressure level
dBA
46,3
49,9
52,0
52,9
48,4
50,5
50,5
50,4
54,5
55,5
Vent.-Leistungsaufnahme
Fan
power consumption
kW
0,4
0,6
0,8
0,9
1,0
1,3
1,3
1,2
2,1
2,3
Pa
450
450
450
450
450
450
450
450
450
450
dBA
47,5
50,7
52,8
53,6
49,9
51,9
51,9
51,7
55,5
56,4
Fan
power consumption
Vent.-Leistungsaufnahme
kW
0,5
0,7
1,0
1,1
1,2
1,5
1,5
1,4
2,4
2,7
Airow
Luftvolumenstrom
m/h
Ventilatoranzahl
Number of fans
1 1/2"
1 1/2"
1 1/2"
1 1/2"
Downow
Max. externer
external static
statischer
pressure
Druck
Upow
Max. external
pressure
externer static
statischer
Druck
Cabinet
size
Baugre
3
For electrical data, heating and humidier equipment see page 30.
The indicated refrigerant charge is valid for R407C, R410A and R134a.
For the refrigerant R22 the charge is for all sizes: 0,5 kg.
3
For dimensions and weights see page 29.
4
Data with reduced air ow, details on request.
1
2
E/0708/13/27
402
452
512
552
612
702
802
862
1062
DX-cooling
DX-Klteleistung
cap. R407C
R407C total
kW
24C/50% r.h.
r.F.
sensible
sensibel
41,7
38,8
47,3
44,6
54,4
49,2
56,1
56,1
63,3
63,3
72,6
68,3
81,3
74,4
89,5
80,3
104,5
88,9
Verhltnis
sens./total
Ratio
sens./total
0,93
0,94
0,90
0,94
0,92
0,90
0,85
8,4
9,6
11,2
11,2
12,6
15,0
16,8
19,2
23,0
Comp.
Komp.-Leistungsaufnahme
power consumption
kW
Kompressortyp
Compressor
type
C4
C5
C13
C13
C14
C15
C16
C17
C18
4,44
4,22
4,12
4,32
4,11
3,99
3,78
3,58
3,48
DX-cooling
DX-Klteleistung
cap. R410A
R410A total
kW
24C/50% r.F.
sensible
sensibel
43,1
39,4
49,9
45,7
53,9
48,9
54,74
50,94
63,04
59,04
63,3
59,8
81,4
74,5
90,4
80,7
104,2
88,7
Verhltnis
sens./total
Ratio
sens./total
0,91
0,92
0,91
0,93
0,94
0,94
0,92
0,89
0,85
9,0
10,4
11,2
11,2
12,8
12,8
17,0
18,6
22,0
C22
C23
C24
C24
C25
C26
C27
C28
C29
4,31
4,16
4,08
4,21
4,04
3,96
3,75
3,70
3,59
38,7
38,7
44,3
44,3
50,1
47,5
52,5
52,5
56,0
56,0
66,0
66,0
76,4
72,5
0,95
0,95
1 1
EER
R407C
Comp.
Komp.-Leistungsaufnahme
power consumption
kW
Kompressortyp
Compressor
type
1 1
EER
R410A
DX-cooling
DX-Klteleistung
cap. R134a
R134a total
kW
24C/50% r.F.
sensible
sensibel
Ratio
sens./total
Verhltnis
sens./total
Comp.
Komp.-Leistungsaufnahme
power consumption
7,8
8,6
10,0
10,0
10,6
13,4
15,4
C13
C14
C15
C15
C16
C17
C18
4,40
4,34
4,18
4,45
4,18
3,98
3,80
CW-cooling
CW-Klteleistung
capacity
total
kW
24C/50% r.h.
r.F.
sensible
sensibel
41,7
38,8
45,4
42,1
51,2
46,7
56,5
52,2
64,3
59,2
71,3
64,3
77,1
69,1
86,5
75,7
95,6
81,7
Verhltnis
sens./total
Ratio
sens./total
0,93
0,93
0,91
0,92
0,92
0,90
0,90
0,88
0,85
kg
2,6
2,9
3,7
3,9
4,4
4,6
4,6
4,6
5,2
Wasservolumenstrom
Water
ow
m/h
9,4
10,8
12,5
13,1
14,6
16,7
18,0
21,0
24,0
wasserseitig
- Sommer
dp water
side - summer
kPa
79
104
101
78
96
125
72
97
126
wasserseitig
- Winter
dp water
side - winter
kPa
70
93
86
72
89
117
83
112
144
GE-Registerinhalt
GE
coil content
dm
kW
1 1
Kompressortyp
Compressor
type
EER
R134a
Refrigerant
Fllmenge charge
2
Ventilgre
(2-Wege)
Valve
size (2-way)
Airow
Luftvolumenstrom
m/h
Ventilatoranzahl
Number
of fans
22,9
27,5
27,5
1 1/2"
1 1/2"
1 1/2"
2"
2"
2"
2"
2"
2"
11000
13000
14000
16000
18500
19500
21000
22500
24000
Downow
Max. external
externer static
statischer
pressure
Druck
Pa
450
450
450
450
450
450
410
320
220
Schalldruckpegel
Sound
pressure level
dBA
50,4
53,9
55,5
52,9
55,9
57,0
58,6
60,1
61,5
Vent.-Leistungsaufnahme
Fan
power consumption
kW
1,2
1,9
2,3
2,2
3,3
3,8
4,7
5,8
7,0
Upow
Max. external
pressure
externer static
statischer
Druck
Pa
450
450
450
450
450
450
280
280
180
Sound
pressure level
Schalldruckpegel
dBA
51,7
54,9
56,4
54,1
57,0
58,1
61,0
61,0
62,3
Fan
power consumption
Vent.-Leistungsaufnahme
kW
1,4
2,2
2,7
2,5
3,8
4,4
6,5
6,5
7,8
Cabinet
size
Baugre
3
For electrical data, heating and humidier equipment see page 30.
2
The indicated refrigerant charge is valid per refrigerant circuit for R407C, R410A and R134a.
For the refrigerant R22 the charge is for all sizes: 0,5 kg.
3
For dimensions and weights see page 29.
4
Data with reduced air ow, details on request.
1
E/0708/13/28
4.8 Dimensions
Cabinet
Baugre
size
1000
1400
1750
2150
2550
Breite
Width
mm
Hhe
Height
mm
1980
Depth
Tiefe
mm
890
4.9 Weights
Standard Units ASD/ASU [kg]
1-circuit
181
211
261
291
311
361
401
411
451
531
D
U
352
343
353
344
373
364
377
368
453
452
453
452
455
454
530
503
532
505
532
505
D
U
355
346
356
347
378
369
383
374
460
459
460
459
461
460
538
511
540
513
541
514
ACW
D
U
372
363
372
363
393
384
396
384
480
479
481
480
482
481
574
547
575
548
576
549
GCW
D
U
377
368
377
368
400
391
403
394
490
489
490
489
491
490
584
557
585
558
586
559
402
452
512
552
612
702
802
862
1062
2-circuits
A
D
U
556
529
556
529
589
562
672
650
680
658
682
660
805
768
807
770
808
771
D
U
563
536
564
537
597
570
691
669
693
671
694
672
823
786
825
788
827
790
ACW
D
U
600
573
600
573
633
606
733
711
740
718
742
720
883
846
884
847
885
848
GCW
D
U
607
580
608
581
641
614
744
722
751
729
754
732
899
862
900
863
905
868
181
211
261
291
311
361
401
411
451
531
D
U
451
450
452
451
468
467
472
471
563
536
563
536
565
538
633
611
635
613
635
613
D
U
458
457
458
457
475
474
479
478
573
546
573
546
574
547
647
625
648
626
649
627
GE
D
U
470
469
470
469
487
486
488
487
584
557
585
558
587
560
661
639
662
640
663
641
402
452
512
552
612
702
802
862
1062
2-circuits
A
D
U
681
659
681
659
714
692
845
808
852
815
854
817
D
U
700
678
700
678
733
711
878
841
880
843
881
844
GE
D
U
714
692
716
694
748
726
886
849
893
856
902
865
914
877
916
879
916
879
E/0708/13/29
6,11
Stages
Stufen
total
Gesamt
Nom.
current[A]
[A]
Nennstrom
L1 - L2 - L3
Compressor
Kompressor FLA [A]* LRA [A]
C3
7,4
65,5
6+6
12
C4
7,6
74
9+6
15
C5
9,5 (7,8)
101
9+9
18
C13
10,9 (9,5)
95
6+6+6
18
C14
12
111
9+6+6
21
C15
14,1 (11,5)
118
9+9+6
24
C16
15,1 (11,7)
118
9+9+9
27
C17
16,3 (14,7)
140
C18
20,3 (16,6)
185
C20
6,7
64
Hum.capacity[kg/h]
Bef.leistung [kg/h]
Nom.
current[A]
[A]
Nennstrom
C21
6,9
64
5,4
3,75
C22
74
8,7
6,0
C23
10,1
101
10
10,8
7,5
C24
10,5
95
15
16,2
11,25
C25
12
111
C26
14
118
C27
16,9
118
C28
18,2
140
C29
21,8
173
Steam humidier
Cabinet
Baugre
size
Humidifying
Befeuchtungsleistung
capacity
kW
Heizleistung
StufeStage
2
Heating
capacity
2
kW
Heizleistung
StufeStage
3
Heating
capacity
3
kW
Max. max.
Gesamtheizleistung
Total
heating capacity kW
5/8/10/15
2/1*
Heizleistung
StufeStage
1
Heating
capacity
1
5/8
kg/h
Max.
Max. n
mgliche
of heating
Heizstufen
stages
3
6/9
6/9
6/9
18
27
*For upow units with cabinet size 1 only one heating stage can be installed.
E/0708/13/30
Cabinet size 2
1400
1000
Cabinet size 3
Cabinet size 4
2150
10
1750
Cabinet size 5
35
Side view
1980
2550
890
E/0708/13/31
5. Transport / Storage
5.1 Delivery of units
Stulz A/C units are mounted on pallets and packed several times in plastic lm. They must always be transported upright on the pallets.
Units of the version A are delivered with 1 kg refrigerant charge.
Units of the version G contain the complete refrigerant charge.
Construction of protective covering
(from inside to outside)
1.
2.
3.
Neopolene cushioning
Shrink lm
Additional board in container shipments
When delivery is accepted, the unit is to be checked against the delivery note for completeness and checked for external damage which is to be recorded on the consignment note
in the presence of the freight forwarder.
The delivery note can be found on the A/C unit when delivered.
The shipment is made ex works, in case of shipment damages, please assert your claim
towards the carrier.
Hidden damage is to be reported in writing within 6 days of delivery.
5.2 Transport
The Stulz A/C units can be moved by lifting devices with ropes, for this the ropes have to be xed at the
pallet, and the upper unit edges have to be protected by wooden laths or metal brackets in such a way that
they could not be caved in.
You can move the unit still packaged on the pallet with a fork lift, if you take care that the centre of gravity is
within the fork surface. Take care that the unit is in an upright position at the transport.
Never move the unit on rollers and never transport it without pallet on a fork lift, for the risk
of distorting the frame.
5.3 Storage
If you put the unit into intermediate storage before the installation, the following measures have to be carried
out to protect the unit from damage and corrosion:
Make sure that the water connections are provided with protective hoods. If the intermediate storage
exceeds 2 months, we recommend lling the pipes with nitrogen.
the temperature at the storage point should not be higher than 42C, and the site should not be exposed
to direct sunlight.
the unit should be stored packaged to avoid the risk of corrosion especially of the condenser ns.
E/0708/13/32
6. Installation
6.1 Positioning
Check that the installation site is appropriated for the unit weight, which you can read in the technical data.
The A/C unit is designed for the inside installation on a level base. The solid base frame contributes signicantly to an even weight distribution. When selecting the installation site take into account the necessary
clearances for the maintenance and the air ow.
1m
0,5m
Maintenance clearance
Air intake area for Downow units and air
outlet area for Upow units without duct
connection
Discharge plenum
width: according to the unit width
depth: according to the unit depth
height: 500 mm
E/0708/13/33
Duct
width: according to the unit width
depth: according to the unit depth
height: 500/800 mm
Unit base
width: unit width minus 40 mm
depth: 865 mm
height: 450 mm
E/0708/13/34
454
Chilled water
piping
144
128
Pipe entrance
area for refrigerant lines
63
43
144
454
98
181
211
261
291
311
361
401
411
451
531
Druckleitung
Pressure
line
16
16
16
22
22
22
22
22
22
22
Flssigkeitsleitung
Liquid
line
10
12
12
16
16
16
16
16
16
16
402
452
512
552
612
702
802
862
1062
Druckleitung
Pressure
line
16
16
16
16
22
22
22
22
22
Flssigkeitsleitung
Liquid
line
12
12
12
12
16
16
16
16
16
The refrigerant connections are located near the compressor and are labelled by the inscriptions "pressure
pipe" and "liquid pipe" respectively "pressure pipe 1" and "pressure pipe 2" etc. for 2-circuit units.
The lines to be connected have to be soldered.
For the connection of the external pipework please note the pipe entrance area shown on top of the page.
E/0708/13/35
Establish the shortest route for pipework from the unit to the condenser. Exceptions only when
unnecessary bends are to be avoided.
Determine the required pipe ttings/specials between the unit and condenser.
With the aid of table No. 1, convert the pressure loss of the individual ttings into equivalent pipe
lengths, look up equivalent pipe lengths for pipe specials and ttings, add these to the real pipe
lengths.
Select the pipe dimensions from diagram No. 1 on the following page corresponding to the calculated overall pipe length and refrigeration output.
Precautions for pressure line, if the condenser is higher than the unit.
-
To ensure oil return in ascending hot gas lines, particularly at part load, the minimum refrigeration
capacity must not fall below the value stated on table 2 of the following page, for the corresponding
pipe size.
An oil separator must be installed in systems with a pipe length above 25 m.
Oil traps (even when an oil separator is installed) are to be installed every 5-6 m (illustr. 3, p. 42).
The horizontal lines must always be routed with a slope towards the condenser.
Table 1: Pressure drop of pipe ttings/specials in metres for equivalent pipe length
Copper
Kupferrohr
pipe
E/0708/13/36
Bogen
Bend
Winkel
Angle
T-Stck
T-piece
Auen --
outside
mm
mm
45
90
180
90
10
0,16
0,20
0,53
0,32
0,20
12
0,21
0,27
0,70
0,42
0,27
15
0,24
0,30
0,76
0,48
0,30
18
0,26
0,36
0,87
0,54
0,36
22
0,27
0,42
0,98
0,61
0,42
28
0,39
0,51
1,20
0,79
0,51
35
0,51
0,70
1,70
1,00
0,70
42
0,64
0,80
1,90
1,20
0,80
R407C
100
22
50
18
30
16
20
12
10
7
10
Liquid lines
depending on the overall pipe
lengths and refrigeration outputs
with a permissible pressure loss
of: 15 kPa
28
70
5
3
10
20
30
50
70
100
Refrigeration output in kW
Outside diameter in mm
100
35
50
30
28
20
22
Further conditions:
tc = 45C
to = 3C
Subcooling: 3K
Superheating: 7K
18
10
16
7
5
12
Pressure lines
depending on the overall pipe
lengths and refrigeration outputs
with a permissible pressure loss
of: 30 kPa
42
70
10
10
20
30
50
70
100
Refrigeration output in kW
Table 2: Selecting the pipe lines
Minimum refrigeration outputs which are required for oil transportation in rising pipes of pressure lines for
R407C at tc (dew point) 48C.
Pipe
diameter
Rohrdurchmesser
mm
15
18
22
28
35
42
Refrig.
capacity
Klteleistung
kW
4,41
5,17
7,14
10,0
16,58
25,9
E/0708/13/37
R410A
100
28
70
Liquid lines
depending on the overall pipe
lengths and refrigeration outputs
with a permissible pressure loss
of: 15 kPa
50
18
16
20
12
10
7
10
22
30
5
3
10
20
30
50
70
100
Refrigeration output in kW
Outside diameter in mm
100
42
70
28
30
20
22
18
10
16
7
5
12
35
50
10
10
20
30
Refrigeration output in kW
Further conditions:
tc = 45C
to = 3C
Subcooling: 3K
Superheating: 7K
E/0708/13/38
50
70
100
Pressure lines
depending on the overall pipe
lengths and refrigeration outputs
with a permissible pressure loss
of: 30 kPa
R134a
100
28
70
50
22
18
30
Liquid lines
depending on the overall
pipe lengths and refrigeration
outputs with a permissible
pressure loss of: 15 kPa
20
16
10
12
10
5
3
10
20
30
50
70
100
Refrigeration output in kW
Outside diameter in mm
54
100
70
35
30
28
20
22
10
18
7
5
16
42
50
Pressure lines
depending on the overall pipe
lengths and refrigeration outputs
with a permissible pressure loss
of: 30 kPa
12
10
5
10
20
30
50
70
100
Refrigeration output in kW
Further conditions:
tc = 45C
to = 3C
Subcooling: 3K
Superheating: 7K
E/0708/13/39
R22
100
22
50
18
30
16
20
12
10
7
10
Liquid lines
depending on the overall pipe
lengths and refrigeration outputs
with a permissible pressure loss
of: 15 kPa
28
70
5
3
10
20
30
50
70
100
Refrigeration output in kW
Outside diameter in mm
54
100
42
70
35
30
28
20
22
10
18
16
7
5
3
12
50
10
5
10
20
30
Refrigeration output in kW
Further conditions:
tc = 45C
to = 3C
Subcooling: 3K
Superheating: 7K
E/0708/13/40
50
70
100
Pressure lines
depending on the overall pipe
lengths and refrigeration outputs
with a permissible pressure loss
of: 30 kPa
Pipe mountings are to be provided at least every 2 m. The pipe mountings are to be insulated against
vibrations. The rst pipe mounting behind the unit and upstream of the condenser should be exible. So
that the pressure lines can expand, the pipe mountings are to be attached at least 1 m from the bend, in
accordance with sketch No. 1, following page.
-
All copper pipes which pass through masonry must be insulated in this area so that the pipes are protected from damage and a certain exibility is retained.
For routing, only copper pipes are to be used which correspond to the national regulations. Sealing caps
or ends added as ux must be meticulously clean and dry and meet the requirements of refrigeration
engineering.
Before commencing with routing the pipelines, one should ensure that the pipes are dry and clean inside,
by checking whether the sealing caps are seated on the pipe ends and by blowing through the pipes with
nitrogen. If the sealing caps are no longer seated on the pipe ends, the pipes must be cleaned with a
clean non fraying cloth and a spiral and then blown through with nitrogen to remove the remaining dirt.
Furthermore it must be ensured that the remaining pipe is always sealed with a plug after cutting off pipe
ends.
Pipes for refrigerant must always be cut to length with a pipe cutter and then brought to the correct inside
diameter by slightly expanding or calibrating.
Sawing refrigerant pipes is not permitted as the swarf cannot be completely removed and
blockages can occur in the control components or the compressor may be irreparably
damaged. The same can also occur as a result of contaminated pipes.
If copper pipes are ared, the taper of the tube aring tool must be coated lightly with refrigerator oil to
prevent a burr occurring on the copper pipe during the aring process which can enter the pipe. According
to EN 378, pipes with a diameter < 9 mm and > 19 mm may not be ared.
Refrigerant-conducting pipes may only be brazed under nitrogen so that no oxidisation occurs on the
inside of the pipes which also contaminates pipelines.
Before the nal connection is brazed, a screwed connection must be released at the appropriate point so
that no pressure occurs in the pipe system.
After brazing, do not forget to retighten the screwed connection which has been released.
Once the pipework installation is nished, it is mandatory that the system is checked for leaks and for pressure resistance. This must be carried out as follows:
-
The system is lled with dry nitrogen up to the maximum nominal pressure.
The system is shut off, the valve in the system is closed and the nitrogen bottle is removed.
Each connection (including screwed connections) is checked for leaks by brushing on a liquid. In parallel
with this check a pressure gauge is connected on which it can again be checked whether the system is
leaking, the pressure on the pressure gauge being checked for a reasonable period according to the size
of the system.
E/0708/13/41
1000
1000
Correct
Mounting the refrigerant
pipes in corners
Sketch 1
Incorrect
Dealing with obstacles
Sketch 2
gas
liquid
Routing pressure lines when
the Condenser is higher
than the compressor.
ca. 5 - 6 m
liquid
max. 5 m
gas
E/0708/13/42
Pressure side
Suction side
8
Refrigerant bottle
9
Pressure
1
measuring
station 2
Vacuum
meter
7
3
4
Explanation of the
evacuation process
with reference to the
numbers overleaf.
Vacuum pump
E/0708/13/43
Process
Values
Operation
1. Preparation
2. Evacuation
70 mbar
3. Breaking vacuum
0,98 bar
4. Waiting time
5 minutes
5. Disposal
Disposal of refrigerant in accordance with the valid country-specic regulations. (e.g. using disposal
station for FC)
6. Repeat 2. - 5.
1x
7. Last evacuation
1-2 mbar
as item 2
8. Completion
9. Filling refrigerant
E/0708/13/44
Systems without refrigerant receiver or sight glass must always be lled according to weight.
Systems with refrigerant receiver should be lled according to weight but can also be lled by checking
the sight glass.
If you use the refrigerant R407C, please note that R407C is a ternary blend. Take care that
you add refrigerant in a liquid state, as the ratio of the refrigerant components changes if
one of the three compounds passes over into the gaseous phase.
Before the system is lled with refrigerant, it must be clean and dry inside. (Refer to evacuation instructions). Then proceed as follows:
The standing refrigerant bottle is connected to the suction side via a pressure gauge station. The weight
is noted shortly before lling. The specied amount of refrigerant is now added when the system is operating. During lling the pressure in the refrigerant bottle will adjust to that of the system. Filling is then no
longer necessary.
This can be seen by the icing up of the bottle or by checking the pressure gauge. The bottle valve must
then be closed until a pressure increase has taken place which is above the suction pressure of the
system. This process can be accelerated if the bottle is wrapped in hot moist towels or it is placed in a
water bath at a maximum temperature of 50C.
Never heat up the refrigerant bottle with a naked ame as there is a risk of explosion.
For R410A, R134a: Refer to the special requirements of the refrigerant manufacturer.
E/0708/13/45
Underlling
A system which is insufciently lled results in the following:
Output reduction due to evaporation temperatures which are too low and triggering of the low pressure switch.
Excessive overheating temperature which can result in compressor damage.
Recommended superheating: 7 - 10 K
Recommended subcooling:
>2K
In A-units of the CyberAir series, in contrast to the precedent Modular Line series, no nonreturn valve is installed upstream the liquid receiver as standard.
Only in case of very long pipework from the condenser to the unit and with low outside temperatures it may
be useful to install a non-return valve near the condenser to prevent a reverse ow of refrigerant to the
condenser when the unit is stopped and to avoid a possible low pressure fault at the unit start. Such a nonreturn valve can be obtained as an option from Stulz. (The C7000 controller provides the feature to adjust
a winter start delay of 0-255 seconds. For this time, the monitoring of the low pressure is inhibited.) A long
refrigerant line from the non-return valve to the receiver provides an additional buffer to cushion a possible
excessive pressure at unfavourable operating conditions.
E/0708/13/46
ethylenglycol
from +5 to -5C
from -5 to -10C
from -10 to -15C
from -15 to -20C
from -20 to -25C
10%
20%
28%
35%
40%
1.50
1.45
1.40
1.35
1.30
1.25
50%
1.20
40%
1.15
30%
1.10
20%
1.05
10%
-10
-8
-6
-4
-2
If any seals are missing, these must only be replaced by glycolresistant rubber seals.
Insulate the water pipes with the insulating material supplied, to prevent the
introduction of ambient air heat as well as possible.
Screw the water pipes of the A/C unit together with the local water pipes of
the dry-cooler or the chiller.
Fill and bleed air from the cooling water circuit by means of the lling connections and the schrader valves for bleeding (see refrigerant diagram).
E/0708/13/47
144
454
63
128
43
454
144
Durchmesser
Diameter
15
30
16
30
22
37
28
46
35
53
42
65
54
82
70
95
181
211
261
291
311
361
401
411
451
531
Leitung
G/GE
pipes
- G/GE
35
35
35
35
35
35
35
42
42
42
Leitung
- CW
CW
pipes
(for (GCW)
GCW)
35
35
35
35
42
42
42
42
42
42
402
452
512
552
612
702
802
862
1062
Leitung
- G/GE
G/GE
pipes
35
35
35
35
35
42
42
42
54
Leitung
- CW
CW
pipes
(for (GCW)
GCW)
42
42
42
54
54
54
54
54
54
E/0708/13/48
98
60
330
Syphon installation
Ensure that there is a sufcient height difference between the fan pan and the upper bow of the syphon or the
highest part of the drain tube, in order to avoid a water column in the drain syphon caused by the pressure
in the suction area of the A/C unit, which prevents the draining of the condensate water
h = p / ( g)
h = -300Pa / (1000kg/m 10m/s)
h = -3 cm
If the height h is smaller than 3 cm with a pressure of 300 Pa in the suction area, a water column
rests in the drain, the water is not transported
and lls the fan pan. This water can be drawn
dropwise in the fan or can drop out of the unit
if the pan is full.
>10 cm
unit limit
Connect the condensate water drains to the local waste water system.
Comply with the regulations of the local water supply authority.
E/0708/13/49
90
61
125
235
536
For use of leakage-current (FI) circuit breakers, EN 50178 5.2.11.2 must be taken into account.
Only type B pulse-current FI circuit breakers are permitted. FI circuit breakers do not provide
protection against bodily harm during operation of the unit or frequency converters.
Make sure that the power supply corresponds to the indications on the rating plate and that the
tolerances according to the "Application limits" are not exceeded.
In addition to this, the asymmetry of phase between the conductors may amount to 2% maximally.
The asymmetry of phase is determined by measuring the voltage difference between the phase
conductors. The average value of the voltage differences may not exceed 8 V.
E/0708/13/50
7. Commissioning
The unit must be installed and connected in accordance
with the chapter on "installation" before initial commissioning.
Make sure that the master switch is off and the unit is de-energized.
Open the electrical compartment door of the unit using the key provided.
Check whether all power switches and control-circuit fuses in the
electrical section of the unit are switched off.
Retighten all screw connections in the electric cabinet.
Verify the smooth function of the contactors.
Electrical
compartment
Power switches
Control-circuit fuses
Master switch
Do not turn the adjustment screw beyond the end of the calibrated scale range, as it may
result in overheating and short-circuit at the consumer or in the destruction of the power
switch.
non-calibrated range
The controller is now supplied with power, so you can use it for adjustments.
Make sure that the heat rejecting system is operating.
A - air-cooled condenser
G, GE - dry cooler
ACW - air-cooled condenser + chiller
GCW - dry cooler + chiller
Switching on
power switch
E/0708/13/51
E/0708/13/52
8. Maintenance
8.1 Safety instructions
All maintenance work is to be carried out under strict compliance with the country-specic accident prevention regulations. In particular we refer to the accident prevention regulations for electrical installations,
refrigerating machines and equipment. Non-compliance with the safety instructions can endanger people
and the environment.
Maintenance work is only to be carried out on the units by authorized and qualied specialist staff.
Procedure instructions
Work on the system must always only be carried out when it is shut down. To do this, the unit must
be switched off at the controller and at the master switch. A DO NOT SWITCH ON warning sign
must be displayed.
Live electrical components are to be switched to de-energized and checked to ensure that they
are in the de-energized state.
Some verications must be effected with the unit in operation (measuring the current, pressures,
temperatures). In such a case the unit must only be switched on at the master switch after all
mechanical connections have been carried out. The unit must be switched off immediately after
the measuring procedure.
Warning notes!
When the master switch is switched on and the controller is stopped the power contactors
are live, even if the components are not operating.
At the fan contactor, dangerous voltages occur. Do not open the unit within the rst 5 minutes after disconnection of all phases. Be sure that the unit is being isolated.
In units with 2 or 3 fans dangerous charges of >50C can occur between AC line terminals
and PE after disconnection.
The electronics housing can get hot.
The fans have an operation delay after the unit is stopped ! (Risk of injury)
Maintenance interval
monthly
Refrigerant circ.
Refrigerant charge
HP/LP switch
Sight glass
Compressor
Expansion valve
Unit in general
Electrics
Mechanics
half-yearly
yearly
x
x
x
x
x
Air circuit
Heat exchanger
Fan
Air lter
Water circuit
Tightness
Condenser
quarterly
x
x
x
x
x
x
E/0708/13/53
E/0708/13/54
Compressor
In the compressor there is an ester oil charge, which does not have to be renewed under normal operation
conditions and holds out for the unit's lifetime. However, it is possible that the ester oil, as it reacts hygroscopically, has taken up humidity of the air after repeated recharging of the refrigerant circuit due to repair
works. The interaction between ester oil and water results in the formation of acid. Owing to a hyperacidity,
corrosive processes take place inside the compressor. In this case the ester oil should be exchanged.
The oil level can be checked by looking at the sight glass of the compressor.
Expansion valve
The refrigerant circuit is equipped with a electronic expansion valve, which controls the superheating in the
evaporator.
The superheating is adjusted to 7 K at the factory and may not be modied. The expansion valve can freeze,
if the humidity in the system is excessive.
Do not thaw by soldering ame, danger of explosion ! Thaw with moist warm cloth. Check
the sight glass.
Do not distort the ns while cleaning, this also increases the air resistance !
Fan
The bearings of the fans are lifetime lubricated and do not need maintenance. Check the operation current.
An increased operation current indicates either a higher air resistance by a clogged pre-lter or a winding
short circuit in the fan motor.
The fans are speed controlled in dependance of the required cooling capacity. You can manually modify the
speed at the controller for test purposes, so as to compare the measured current with the values on the
pages with the technical data or with those of the planning tool.
Air lter
A lter monitor controls the state of the lter. As soon as the pressure loss exceeds an adjustable value, a
lter alarm via the controller is released. The controller can be congured such as to compensate the pressure
loss by a higher fan speed, however you should not wait too long for exchanging the lter. The lters can be
accessed by the front doors, depending on the cabinet size the the number of lter elements varies.
The clogged lter elements can not be cleaned with pressurized air, as the lter structure would be destroyed otherwise. When you re-install the lter elements
after the exchange, take care that the side with the
coloured mark (dirt side) is turned away from the
heat exchanger.
Downow units
Cabinet
Baugre
size
E/0708/13/55
Upow units
Cabinet
Baugre
size
Mechanics
Clean the unit's inside with a vacuum cleaner. Clean pipes simplify the search for leaks. Check the pipes,
the compressor and the condenser for a tight seat. Vibrations of pipes and circuit components can result in
leaks. Check also the insulation of the water piping. Condensing air humidity on cold water pipes means a
loss of cooling capacity.
8.7 Competences
Repairs on the refrigerant circuit
(tightness, lter drier exchange)
Trained electrician
E/0708/13/56
The refrigerant may not be discharged into the atmosphere, but must be returned to the
manufacturer, if it is not reused.
The ester oil in the compressor must also be disposed. As it contains dissolved refrigerant,
it can not be disposed like usual oils, but must be returned to the oil manufacturer.
Disconnect the depressurized refrigerant pipes from the external system (version A/ACW).
If glycol or similar additives had been used, this liquid also has to be collected and disposed
in an appropriate manner and may under no circumstances be introduced in the local waste
water system.
Disconnect the unit from the external water circuit by closing the shut-off valves and drain the water circuit
of the unit (version G/GE/GCW).
Disconnect the depressurized cooling water pipes of the unit from the external system.
Move the unit, as described in the chapter "transport", with a lifting device of sufcient load-carrying capacity.
Dispose of the A/C unit in accordance with the disposal and safety regulations applicable on site. We recommend a recycling company for this. The unit basically contains the raw materials aluminium (heat exchanger),
copper (pipelines, wiring), and iron (condenser, panelling, mounting panel).
E/0708/13/57
10. Options
10.1 Steam humidier
The steam humidier is an optional extra for your A/C unit. It is installed complete and integrated within
the function and method of operation of the A/C unit. Details concerning the connection assignment for the
power supply can be found in the electrical diagrams in the appendix.
We recommend the installation of an Aqua-stop valve in the water supply of the humidier.
In addition to this, the room, in which the A/C unit with the humidier is installed, should
be equipped with a water detection system.
10.1.1 Description
The humidier uses normal mains water for the production of steam. The conductivity of the water should
be within the range of min. 300 to max. 1250 S/cm. The water is converted directly into steam by means
of electrical energy in a steam cylinder with electrode heating. The steam is introduced into the airow via
the steam throttle.
Due to the evaporation the water level in the cylinder falls. The current consumption is reduced, as the
electrodes are then immersed less in the water. With a sinking water level the mineral concentration in the
cylinder increases, as the minerals do not evaporate. The current is kept by the control between two limit
values (IN+10%, IN-5%). When the lower limit value is reached, the inlet valve opens. Now fresh water is
mixed with residual water, which has a high mineral concentration. After several evaporation and lling cycles, the mineral concentration has increased in such a way, that the current reduction due to evaporation
and falling water level takes place quite rapidly. When a certain limit value of current reduction is exceeded,
the drain valve is opened at the moment, when also the lower current limit value is reached, and nally the
cylinder is completely drained.
The lling phase is automatically interrupted if the sensor electrode is contacted due to the high water level
in the steam cylinder. This may happen in the start-up phase with a new steam cylinder.
Cabinet
Baugre
size
Befeuchtungsleistung
Humidifying
capacity
2
5/8
kg/h
5/8/10/15
Steam humidier
E/0708/13/58
Hum.capacity[kg/h]
Bef.leistung [kg/h]
Nom.
Nennstrom
current[A]
[A]
Nennleistung
Nom. power [kW]
[kW]
5,4
3,75
8,7
6,0
10
10,8
7,5
15
16,2
11,25
max. 40
Pressure
Druck
bar
1-8
min
max
8,5
300
1250
*
hydrogen ions
specic conductivity (at 20C)
R, 20C
S/cm
TDS
mg/l
R180
mg/l
total hardness
mg/l CaCO3
100
400
iron + manganese
mg/l Fe + Mn
0,2
chlorides
ppm Cl
30
silica
mg/l SiO2
20
residual chlorine
mg/l Cl
0,2
calcium sulphate
mg/l CaSO4
100
metallic impurities
mg/l
mg/l
* values depending on specic conductivity; in general: TDS 0,93 20; R180 0,65 20
2
not lower than 200% of chlorides content in mg/l of Cl
Water supply
The water connection is made from the cold water mains and is to be equipped with a shut-off valve. It is
recommended to install a lter to retain solid particles of pollution. The humidier can be connected directly
to the mains by a threaded tenon of 3/4" when the water pressure is between 1 and 8 bar. The pipe should
have a diameter of at least 6 mm. If the line pressure is more than 8 bar, the connection must be made via a
pressure reducing valve (set to 4-6 bar). In each case it is to be ensured that the manufactured water pipe
upstream of the connection to the humidier is ushed properly. We recommend only using copper pipes.
The water supply temperature must not exceed 40C.
Do not treat the water with softeners !
This could result in corrosion of the electrodes and in the formation of foam with considerable operational interruptions.
Prevent:
1. the use of well water, process water or water of cooling circuits and generally chemically
or bacteriologically polluted water;
2. the addition of disinfectants or anti-corrosion liquids, as these are very irritating for the
respiratory ducts.
E/0708/13/59
Water drain
The drain is achieved by a plastic hose and is routed out of the unit by means of the openings in the unit
provided for this purpose (see graphic below).
When creating the drain, attention is to be paid to provision for cleaning. As the water drain is depressurized,
we recommend routing the drain hose directly into an open collector funnel to ensure free discharge. The
drainage pipe should be routed to the sewerage system with sufcient gradient (at least 5%) and should be
located approx. 30 cm below the humidier. Attention is to be paid to temperature resistance when plastic
pipes are used. If copper pipe is used, it must be earthed. For the drainage pipe an inside diameter of 32
mm is recommended, however the minimum inside diameter should not be less than 25 mm.
Supply
Drain
lter
10.1.4 Commissioning
As soon as the controller requires the humidier function, the heating current is switched on; after approx.
30 seconds water is fed into the steam cylinder through the inlet valve which opens and fully automatic
operation begins. A condition is the open shut-off valve in the water supply.
IMPORTANT NOTICE:
After the water pipes have been connected, the supply piping must be ushed for approx. 30 minutes,
where the water is directly conducted into the drain, without letting it ow into the steam humidier.
This way residues or substances of the installation process are removed, which otherwise could
block the ll valve and cause foam during the boiling process.
E/0708/13/60
10.1.5 Operation
The steam humidier is controlled and monitored by the controller. No further operating measures are
required for continuous operation.
However, you can always vary the humidier output, by operating the DIP-switches A3/4, which are located
on the humidier
printed circuit board in the electrical section of the A/C unit.
3 4
ON
OFF
ON
75 % humidication capacity
OFF
ON
OFF
ON
OFF
50 % humidication capacity
20 % humidication capacity
manual
drainage
drain valve
ll valve
high level/foam
sensor
conductivity sensor
external TAM
green LED
yellow LED
red LED
immersed electrodes
max. 5A
RS485
g. 1
remote ON/OFF
alarm relay
humidity sensor
OFF
external controller
3 days
OFF
ON
2 days
OFF
ON
OFF
ON
3 days
OFF
ON
7 days
OFF
E/0708/13/61
1 2 3 4
OFF
ON
OFF
1 2 3 4
ON: hour counter and maintenance alarm disabled (only if the DIP-switch B1 is
already ON before switching on the humidier board).
Maintenance warning
After 2000 humidier operating hours a warning is released, which is indicated by a ashing red LED (7
short ashes) and the intermittent activation of the alarm relay (only if no other alarms are active). The alarm
indicates the need for a cylinder maintenance. However, the humidier operation is still possible.
Maintenance alarm
After 3000 operating hours an alarm is released, which is indicated by a ashing red LED (8 short ashes)
and the steady activation of the alarm relay. The alarm indicates the necessary exchange of the steam cylinder. The humidier operation is blocked.
Reset of the hour counter and the alarms
1. Set DIP-switch B1 to ON, after 5 seconds the alarm LED (red) and the operation LED (yellow) lights up
for 3 seconds (the alarms are still active and the hour counter is still in operation).
2. Set DIP-switch B1 to OFF, the hour counter starts from 0, the alarms are cancelled.
The humidier operation is enabled again.
Notice for counting the operating hours
The counting of the operating hours is proportional to the steam production, because the amount of lime
accumulating in the cylinder (as a criterion for the cylinder exchange) depends on the steam production.
Example:
After 100 operating hours with 100% steam production the hour counter has saved 100 hours.
After 100 operating hours with 75% steam production the hour counter has saved 75 hours.
E/0708/13/62
1 2 3 4
ON
OFF
1 2 3 4
ON
OFF
1 2 3 4
ON
OFF
DIP B5-6:
automatic drainage time
ON
time = default
OFF
ON
OFF
ON
frequency = default
7
OFF
ON
OFF
OFF
OFF
ON
ON
OFF
ON
DIP B7-8:
drainage frequency
ON
OFF
Change the default adjustment only after conrmation of the STULZ technical support.
The dip-switches serve to adapt the drain cycle to extreme water conditions beyond the
previously described limit values.
E/0708/13/63
Diagram 1:
steam
< 1%
time
1-19%
time
20-29%
time
90-99%
time
Diagram 2:
steam
< 1%
time
1-19%
time
20-29%
time
90-99%
time
100%
time
The yellow LED stays off when no steam is produced, whereas it stays continuously on at 100% of the
nominal production.
When steam is being produced at a transient production rate while approaching the steady-state production,
the yellow LED is quickly turned on and off to produce 2 Hz-pulse sequences which are related to the actual
steam production as shown in diagram 1.
When the steady-state production is achieved, the yellow LED is slowly turned on and off to produce 0,5
Hz-pulse sequences which are related to the actual steam production as shown in diagram 2.
Each pulse sequence is separated from the following by a 3-second delay, so that the user can count the
pulse number of a sequence and determine, using the diagram, the actual humidication capacity.
E/0708/13/64
10.1.6 Maintenance
Please switch off the A/C unit at the controller and the main isolator before starting work
and put the power circuit breaker F70 in the electrical box to position 0!
The following work and checks can be carried out:
- check steam hoses, condensate hoses, water hoses and other parts of the humidier for external effects
or wear.
- Flush out the water drain.
Manual drainage
By means of a switch on the humidier
board, you can manually drain the
cylinder.
Put the switch into position "DR" to drain
the humidier.
After the drainage the switch must be
reset to position "ON", otherwise no
humidication can take place.
Position "ON"
Position "DR"
Switch off the power supply circuits to the humidier before continuing the work!
The steam cylinder can be unscrewed from the mount after releasing the hose clamp, pulling off the steam
hose and disconnecting the electrical plug on the cylinder.
The new steam cylinder is installed in the reverse sequence. The humidier is re-started in accordance with
the recommendations of the chapter "10.1.4 Commissioning".
E/0708/13/65
In the event of this signal on the controller, please look for the exact cause of the fault on the humidier printed
circuit board in the electrical section of the A/C unit. If an alarm has been raised, the red light-emitting diode
displays a ashing alarm code. The meaning of the alarm codes can be seen in the alarm table 2.
Diagram 3:
no alarm
time
1x ashing
time
2x ashing
time
9x ashing
time
Diagram 4:
no alarm
time
1x ashing
time
2x ashing
time
9x ashing
time
E/0708/13/66
Alarm list
Table 1 - Alarm types
Type
Description
Blocking
CP-card stops
humidier.
Disabling
CP-card stops
humidier.
automatic
manual:
to restart, turn the cp-card off
and then on again.
Note: the distinction between
the automatic and manual
reset is shown in the table
below.
Warning
Red LED
Alarm codes:
each code is displayed in
sequence.
The codes are displayed
even if the alarm causes
have been removed; to stop
displaying them, turn the cpcard off and then on again.
Alarm relay
The relay is normally open or
normally close depending on
DIP A2.
The relay action is cumulative:
contact is closed (opened), if
at least 1 alarm is active.
contact is opened (closed), if:
- all alarm causes have been
removed.
- all alarms have been reset,
either manually or automatically.
Note: each alarm is not assigned to the relay (see table
below)
automatic
Table 2 - Alarms
Type
Alarmrelay
manual active
Remedy
manual active
blocking
1. Download the proper default conguration via HumiSet.
2. If the problem persists, contact the STULZ customer service.
manual active
1. Switch off the unit and clean the conductivity sensor elec- blocking
trodes;
2. If the problem persists, change the source of supply water or
install a suitable treatment system (demineralisation, even
partial).
Note: the problem will not be solved by softening the supply
water.
manual active
blocking
1. Drain part of the water and re-start.
2. Verify that the drain valve is properly working.
3. Check for any leakage of the ll valve when the humidier
is switched off.
Reset
E/0708/13/67
Alarmrelay
warning manual not
Do maintenance and/or replace the cylinder.
active
1. Check that the ll pipe from the mains to the humidier and disabling manual active
the internal pipe are not blocked or bent and that there is
sufcient supply pressure (1-8 bar).
2. Check that the ll valve is properly working.
3. Check whether the counter-pressure onto the steam hose
is higher than the maximum limit, preventing the entry of
supply water into the cylinder by gravity.
4. Check that the steam outlet pipe is not choked and that
there is no condensate inside.
Remedy
Type
Reset
3x long
4x long
5x long
6x long
7x long
warning
8x long
9x long
not
active
warning
display: not
manual active
reset
warning
display: not
manual active
reset
Note:
E/0708/13/68
10.2 Reheat
The reheat is an optional extra for your A/C unit. It is installed complete and integrated in the function and
method of operation of the A/C unit. It is used to heat up the air. The following versions of the heater are
available:
- Electrical reheat
- Low pressure hot water reheat (LPHW)
- Refrigerant reheat (RF)
Description
Electrical reheat
LPHW reheat
RF reheat
Operation
The reheat is controlled and monitored by the controller. No further measures are required for operation.
Maintenance
Clean the reheat annually from contaminations and check it for damage.
E/0708/13/69
Installation
The reheats are installed and connected in the A/C unit. The LPHW reheat is to be connected on site to the
external hot water circuit. The pipelines are to be routed out of the A/C unit. The diameters for the connection
piping of the LPHW reheat are listed in the following table.
Baugre
Cabinet
size
Rohr --
Pipe
mm
16
22
22
22
22
Commissioning
The reheats are controlled and monitored by the controller of your A/C unit. No further measures are required for commissioning.
Malfunction causes
Alarm: Reheat defect
All reheat alarms are received by the controller and can be requested according to the equipment.
C7000-control system:
C7000 advanced terminal:
E/0708/13/70
L2
785
865
L1
Cabinet
Baugre
size
mm
960
1360
1710
2110
2510
L1
mm
795
995
784
L2
mm
1607
Supports
Sttzen
Stk
n
Rectangular
Rechteckprole
proles
7070
x 40
x 40
Stk
n
Mafundstreifen
Mafund strips
Stk
n
Schrauben
Screws M8
M8
x 30
x 30
Stk
n
12
16
E/0708/13/71
Cross Connection
Z
(min. 50)
Z (min. 50)
Z (min. 800)
Raised oor
connection refer to
details below
Continuous seal
Raised oor stand
Raised oor support
Mafund strips
Upper edge of
rough oor
E/0708/13/72
Supporting pipe
Raised oor
1
2
3
4
5
6
7
8
9
10
11
12
13
Sealing detail
when distance Z < 100 mm
Sealing detail
when distance Z > 100 mm
Mounting aid
E/0708/13/73
300
75
450
The unit base is available in the versions: open, with damper, with exible connection or with supply grilles.
The unit base can be installed in two ways, with the opening to the front or with the opening to the rear.
L1
L1
L1
D
865
Cabinet
Baugre
size
mm
960
1360
1710
2110
2510
mm
130/80*
210
182
182
173
mm
993
mm
927
1127
1738
L1
mm 700/815*
1015
615
815
615
L2
mm 700/800*
1000
600
800
600
Caution! Each of the unit base versions must be screwed to the unit by 4x M10 screws!
Unit base with grilles
The standard grilles are equipped with horizontal ns which can be adjusted to conduct the air which is
blown out.
E/0708/13/74
300
150
38
300
120
Caution! Each of the unit base versions must be screwed to the unit by 4x M10 screws!
E/0708/13/75
Filter base
Construction
Baugresize
Gertebreite
unit width
mm
1000
1400
1750
2150
2550
mm
960
1360
1710
2110
2510
mm
270
293
376
376
456
Filteranzahl
N of lters
mm
E/0708/13/76
For the air side connection on top of the unit exist different options, which are delivered in a completely
assembled condition. On the installation site these set-ups must be set upon the unit and must be connected
to it.
10.4.3 Duct
500/800
The duct is available with two different heights (500 or 800 mm) for all downow units.
The duct will be set on top of the unit and be screwed with the unit.
B
884
Cabinet
Baugre
size
mm
1000
1400
1750
2150
2550
C*
mm
100
100
45
100
100
D*
mm
905
1250
1450
L1*
mm
800
1200
2 x 800
2 x 800 2 x 1000
Top view:
frame
Baugre
Cabinet
size
mm
1000
1400
1750
2150
2550
mm
1002
1202
E/0708/13/77
500
400
L1
L1
C
884
400
500
400
L1
L1
C
600
884
E/0708/13/78
500
The bag lter is available for all downow units. The bag lter serves for the pre- ltration of the air which is
sucked in and can be obtained in the qualities F6, F7 and F9 (according to EN779).
The bag lter top will be set on top of the unit and be screwed with the unit.
B
884
Cabinet size 1
F7
F9
F7
F9
Cabinet size 2
pressure loss dependant
on the airow with different lter qualities
E/0708/13/79
Cabinet size 3
F7
F9
F7
F9
F7
F9
Cabinet size 4
pressure loss dependant
on the airow with different lter qualities
Cabinet size 5
pressure loss dependant
on the airow with different lter qualities
E/0708/13/80
500/800
The sound insulation plenum is available for all downow units. The plenum will be set on top of the unit and
be screwed with the unit.
By the insertion of the sound absorbing material, a sound attenuation is caused, which is stated across
the acoustic spectrum in octave divisions in the table below. The stated frequencies represent the middle
frequencies of the octaves, to which the attenuation values relate (e.g. 500Hz for the octave from 375Hz to
750Hz).
B = unit width
884
Height: 500 mm
Baugre
Cab. size
VL
dp
Insertion
Einfgungsdmpfung
loss [dB] at octave
in dB bei
middle
Oktavmittenfrequenz
frequency (according
(nach
toVDI
VDI2567)
2567)
m /h
Pa
63 Hz
125 Hz
250 Hz
500 Hz
1 kHz
2 kHz
4 kHz
8 kHz
7200
22
11
16
18
12
11
10200
10
13
13
13500
29
11
11
14
13
10
20500
80
14
15
18
17
13
11
24000
58
12
13
16
15
11
Height: 800 mm
Baugre
Cab. size
VL
dp
Insertion
Einfgungsdmpfung
loss [dB] at octave
in dB bei
middle
Oktavmittenfrequenz
frequency (according
(nach
toVDI
VDI2567)
2567)
m /h
Pa
63 Hz
125 Hz
250 Hz
500 Hz
1 kHz
2 kHz
4 kHz
8 kHz
7200
24
11
14
22
24
16
13
10200
11
11
17
17
11
13500
30
15
16
20
16
12
10
20500
84
10
19
20
25
22
16
13
24000
61
17
18
22
19
14
11
E/0708/13/81
150
Cabinet
Baugre
size
E/0708/13/82
mm
1000
1400
1750
2150
2550
mm
237
287
237
237
275
mm
650
1000
1400
1800
2000
mm
107
107
107
107
107
mm
650
650
675
675
675
mm
120
120
175
175
175
Unit front
Cabinet
Baugre
size
mm
1000
1400
1750
2150
2550
mm
150
200
149
204
145
mm
700
1000
650
800
650
mm
952
1147
950
mm
1777
120 mm
150 mm
E/0708/13/83
Modell
Type
Ventilgre
Valve size
181 / 211
402 / 452 / 512
3/4"
261/291/311/361/401
552/612/702/802/862
1062
1"
1 1/4"
f(PC1)
condenser
PC1
Modell
Type
Ventilgre
Valve size
Closing
Schliedruck
pressure
[bar]
[bar]
181 / 211
402 / 452 / 512
3/4"
10
261/291/311/361/401
552/612/702/802/862
1062
1"
6,5
1 1/4"
f(PC1)
condenser
PC1
E/0708/13/84
Flashes Error
1x
Overload
2x
Overtemperature
3x
Phase reversal
4x
5x
Phase imbalance
6x
Shorted thyristor
E/0708/13/85
L1
L2
L3
I
1
9 10 11 12 13 14 15 16
Reset/Test-Button
Adjusting the nominal
operating current
Run/Alarm LED
A1 A2 N1 N2 97 98 13 14
2
T1
T2
T3
11 12
11 12
11 12
11 12
Off
Class
10
Class
15
Class
20
Reset:
automatically
Reset:
manually
O
13
13
Dip Switch 3:
I
Soft start
Current limitation
(Factory setting)
Ue
Is
Ie
Us
t1
E/0708/13/86
t1
O
4 5
4 5
150% 250%
4 5
4 5
350% 450%
4 5
4 5
4 5
4 5
15%
25%
35%
65%
The maximum current can be set as percentage to the nominal operating current.
(Factory setting: 350%)
1 2
2s
1 2
5s
10 s
1 2
1 2
15 s
1 2
20 s
25 s
1 2
30 s
9 10
9 10
9 10
9 10
6 7
6 7
6 7
6 7
Off
0,5 s
1,0 s
1,5 s
Off
1x t1
2x t1
3x t1
Normal
O
14
15
15
O
16
16
E/0708/13/87
E
RVIC
SE
LZ -
STU
your partner
for
a safe
climate
AIR-CONDITIONING
For your service address please look at the back cover of this manual.
For propositions to improve our manuals, please write to the following address:
dokumentation@stulz.de .
E/0708/13/88