Just start calculate for 3000 l/s fresh air volume and set point temp is 16 C.
We all know that, there are two kinds of heat for fresh air,Sensible and Latent Heat.
Cooling process for Sensible and De-humidification for removing of moisture.
Q = m c T
Q = V c T
Q = V h
V = 3 m3/s
= 1.204 m3/kg
h = Enthalpy Differential of entering and leaving air to the coil (kJ/kg)
h = Enthalpy of entering air (Off coil air) - Enthalpy of leaving air (On coil air)
From Psychrometric Chart,
First Point, h1 , Enthalpy of Entering Air is based on Ambient Air temp
(33 C DB/ 26.1 C WB), h1 = 81 kJ/kg.
Second Point, h2 , Enthalpy of Leaving air is
Based on Supply Air Temp 16C ,Coil ADP & Entering Point.
h2= 44 kJ/kg.
So that, h = h1-h2 = 81-44
h = 37 kJ/kg.
Q = V h
Q = 3 x 1.204 x 37
Q = 133.644 kW.