Indoor switch disconnectors

L-TRI 5
up to 36 kV
Selection list

T&D
Power Distribution

Terms of delivery
The General Terms of Delivery, as amended, shall apply.
Illustrations
The illustrations are not binding for delivery.

Contents
Introduction and Product range
General
Switch disconnectors range L-TRI 5
Disconnector range TRI 5
Main application areas for the range L-TRI 5
Special features of the switch disconnector
range L-TRI 5
Type designation
Product range 12/17,5 kV
Product range 24/36 kV
Product range 12/24 kV according to IEC 60420

4
4
4
4
4
4
5
6
7
8

Description
Cable disconnector L-TRI 5...-D
Transformer disconnector L-TRI 5...-UH-KS-A
Switch disconnectors L-TRI 5...-KS-AA
Transformer disconnector L-TRI 5...-UH-D
Transformer disconnector L-TRI 5F...-UH-KS-A
Mounted earthing switch at the cable disconnector
Mounted earthing switch at transformer disconnector

9
9
10
11
11
12
13
14

Accessories
Auxiliary switch HS 3
Standard attachment variants for auxiliary switches
Signalling switch MSKM
Breaking-current shunt release
(operating current release AA)
Capacitor dividers
Clamping lever
Manual Drives
Motor Drives
Plug-in board

15
15
16
17
17
18
18
19
19
19

Fitting position, selection of driving side


and shaft lengthes
Fitting position
Selection of driving side
Selection shaft lengthes

20

Regulations and tests


Regulations
Tests
Transformer disconnectors
according to IEC 60420 Type L-TRI 5F
Transformer disconnectors
according to DIN EN 60265
Climatic conditions
Low maintenance
Quality
Economy

22
22
22

20
21
21

23
23
23
23
23
23

Selection tables
Characteristic values of switch disconnectors
(cable disconnectors)
Characteristic values of switch disconnectors
(transformer disconnectors)
Selection of HH subrange fuses

24
24

Dimensioned drawings and weights


L-TRI 5, 12 kV30
L-TRI 5, 17,5 kV
L-TRI 5, 24 kV37
L-TRI 5, 36 kV41
L-TRI 5F according to IEC 60420, 12kV
L-TRI 5F according to IEC 60420, 24kV

30

Fax-Request for quotation

45

26
28

34
43
44

Introduction

General
Switch disconnectors range
L-TRI 5
The switch disconnectors of the
range L-TRI 5 are proven flat chamber types to perform the various
switching functions in medium-voltage distribution systems. They are the
result of more than 50 years experience in development and manufacture of switch disconnectors by
ALSTOM (former Concordia Sprecher). The simple, low-maintenance
and highly economic indoor switch
disconnectors of the range L-TRI 5
have hundred-thousand-fold proved
to be good in practical system
operation.
The switch diconnectors of the
range L-TRI 5 are in accordance
with the norms DIN EN 60694
(VDE 0670 Part 1000), IEC 60694
and DIN EN 60265 (VDE 0670
Part 301), IEC 60265-1. Additionally, selected variants are in compliance with DIN EN 60420 (VDE
0670 Part 303), IEC 60420 or
CSA Standard CS22.2 No. 0
and 193.

Disconnector range TRI 5

Due to the integrated rapid


ON/OFF switching in the drive, the
disconnector has the same short-circuit making capacity than the switch
disconnector.
Disconnectors of the range TRI 5
are in compliance with the norms
DIN EN 60129 (VDE 0670 Part 2)
IEC 60129.
For technical data and dimensions
see the TRI 5 list.

Main application areas for


the range L-TRI 5
Switch disconnectors of the range
L-TRI 5 are used in indoor mediumvoltage switchgear systems. They
have a making capacity and are
suited to switch:
load currents
currents in ring mains
transformers, cables and
overhead lines.
The switch disconnectors from the
range L-TRI 5 are the reliable and
economic solution for reconstruction
and maintencance measures, extensions, rehabilitation or improvement
of personnel protection according to
BGV A2 (former VBG 4).

Without arc quenching device (flat


explosion chamber and arcing
blade), the above switch disconnectors can be used as disconnectors.
4

Special features of the switch


disconnector range L-TRI 5
high reliability and long service
life
low operating cost due to long
periods between maintenance
procedures
space-saving by narrow and
compact design
high switching capability
low operating torques
use also in harsh climatic
conditions
best choice as substitute for older
switch disconnectors (ECOFIT
measures) or disconnectors
(BGV A2 measures)
switch-disconnector-fuse combination according to IEC 60420/VDE
0670 Part 303 available.

Type designation
The type designation for the switch
disconnector discloses essential
technical data. The example shows
the structure of the type designation.

L-TRI 5/12/400/210-D-EA-VA
Switch disconnector according to IEC 60265
Rated voltage 12 kV
Rated current 400 A
Pole centre spacing 210 mm
Standard drive
Rapid ON/OFF
Mounted earthing switch at moving-contact side
Mechanical interlock for EA
Type designation for switch disconnectors of the range L-TRI 5

Variant

Rated voltage

kV

Rated current

Pole centre spacing

mm

Type designation

Remarks

L-TRI 5/

without/with fuse attachment


according to IEC 60265

L-TRI 5F/

with fuse attachment


according to IEC 60420
12/
17.5/
24/
36/
400/
630/
1000/
1250/
1600/
2500/
125
165
210
250
270
275
300
340
370
400
5

Product range 12/17,5 kV


Type

Rated
voltage

Rated
current

Pole centre
spacing

Fuse
carrier

Spring
action

Breaking current shunt reMounted


lease
earthing switch

-D
400/
630/

125 T
165
210

-D
- UH
- KS - A

250

- KS

12/

1000/

(- AA)**
- AA

2500/

- ET

- VT

- EA

- VA

- ET

- VT

- EU

- VU

- ET
- EU

- VT
- VU

- ET

- VT

- ET

- VT

- EA

- VA

- ET

- VT

- EA

- VA

- ET

- VT

- EA

- VA

- ET

- VT

- EU

- VU

- ET

- VT

- EU

- VU

- ET

- VT

- ET

- VT

- ET

- VT

- EA

- VA

165
210
-D

1250/

Mechanical
interlock

250
210

-D

250

L-TRI 5/
-D
-D

400/
210

- UH
- KS - A

630/

- KS

(- AA)**
- AA

17,5/
1250/

250

-D

2500/

270

-D

Legend:
T
Phase partitions
D
Standard drive, rapid ON/OFF
KS
Stored energy drive; rapid CLOSING breaking energy stored / rapid OPENING
UH
Fuse carrier
A
Fuse trip linkage for all-pole tripping
AA
Breaking-current shunt release
ET
Mounted earthing switch at fixed-contact side
EA
Mounted earthing switch at moving-contact side
EU
Mounted earthing switch at fuse carrier, external
VT
Mechanical interlock for ET
VA
Mechanical interlock for EA
VU
Mechanical interlock for EU
**
Breaking-current shunt release
The type designation may end behind the spring action.
Example: L-TRI 5/12/630/210-UH-KS-A
Switch disconnector with fuse carrier, stored energy drive and all-pole tripping by striking pin operation.
When motor-driven, no mechanic interlock between disconnector and earthing switch is possible!
6

Product range 24/36 kV


Type

Rated
voltage

Rated
current

Pole centre
spacing

Fuse
carrier

Spring
action

Breaking
Mounted
current shunt
earthing switch
release

-D

400/
630/

165 T
250
275

-D
- UH
- KS - A

300

- KS
24/

(- AA)**

- AA

Mechanical
interlock

- ET

- VT

- EA

- VA

- ET
- EUI
- EU

- VT
- VUI
- VU

- ET
- EUI
- EU

- VT
- VUI
- VU

- ET

- VT

- ET

- VT

- EA

- VA

- ET

- VT

- EA

- VA

- ET

- VT

- EA

- VA

- ET

- VT

- EUI

- VUI

- ET

- VT

- EUI

- VUI

- ET

- VT

- EA

- VA

250
1000/

-D

275
300

1250/
-D

300
1600/

L-TRI 5/
-D
340(T)
-D
630/

370

- UH
- KS - A

400

(- AA)**

36/

340(T)
1000/

-D

370
400

Legend:
T
Phase partitions
(T)
Phase partitions as option
D
Standard drive, rapid ON/OFF
KS
Stored energy drive; rapid CLOSING breaking energy stored / rapid OPENING
UH
Fuse carrier
A
Fuse trip linkage for all-pole tripping
AA
Breaking-current shunt release
ET
Mounted earthing switch at fixed-contact side
EA
Mounted earthing switch at moving-contact side
EU
Mounted earthing switch at fuse carrier, external
EUI
Mounted earthing switch at fuse carrier, internal
VT
Mechanical interlock for ET
VA
Mechanical interlock for EA
VU
Mechanical interlock for EU
VUI
Mechanical interlock for EUI
**
Breaking-current shunt release
The type designation may end behind the spring action.
Example: L-TRI 5/24/630/275-UH-KS-A
Switch disconnector with fuse carrier, stored energy drive and all-pole tripping by striking pin operation.
When motor-driven, no mechanic interlock between disconnector and earthing switch is possible !
7

Product range 12/24 kV


according to IEC 60420
Type

Rated
voltage

Rated
current

Pole centre
spacing

Fuse
carrier

Spring
action

Breaking
current shunt
Mounted
release
earthing switch

Mechanical
interlock

125 T
12/

400/*

165
210

- UH

- KS - A

(- AA)**

- UH

- KS - A

(- AA)**

- ET

- VT

- EU

- VU

- ET

- VT

- EUI

- VUI

- EU

- VU

250

L-TRI 5F/

165 T
24/

400/*

250
275
300

Legend:
T
Phase partitions
KS
Stored energy drive; rapid CLOSING breaking energy stored / rapid OPENING
UH
Fuse carrier
A
Fuse trip linkage for all-pole tripping
AA
Breaking-current shunt release
ET
Mounted earthing switch at fixed-contact side
EUI
Mounted earthing switch at fuse carrier, internal
EU
Mounted earthing switch at fuse carrier, external
VT
Mechanical interlock for ET
VUI
Mechanical interlock for EUI
VU
Mechanical interlock for EU
*
Commonly, the rated current of the switch-disconnector-fuse combination is lower (see technical data).
**
Breaking-current shunt release
The type designation may end behind the spring action.
Example: L-TRI 5F/12/400/210-UH-KS-A
Switch disconnector with fuse carrier, stored energy drive and all-pole tripping by striking pin operation.
When motor-driven, no mechanic interlock between disconnector and earthing switch is possible !
8

Description
Cable disconnector
L-TRI 5...-D
Legend
(1)
(2)
(3)
(4)

Base frame
Epoxy resin insulator
Switch shaft (drive)
Main current path with
push rod
(5) Arcing chamber

(5)

(4)

(2)

(1)
(3)

L-TRI 5...-D

Design
The standard disconnector comprises the above 5 main components.
The welded frame from sectional
steel (1) bears the epoxy resin insulators (2), the main current paths (4)
and the arcing chamber (5).
The frame also bears the switch
shaft (3) with latching facility and
the catch springs. The ribbed push
rod with a very high creep resistance connects the switch shaft to
the main current path.

Torsion spring disconnector


(D-disconnector)
Torsion springs are integrated in the
switch shaft. Turning the shaft end
makes that the torsion springs
become pre-loaded so that energy
is stored. At the end of turning, a
cam plate drives the catch and
releases the stored energy. This
makes that the closing and opening
speed is independent of the operator. Thus, closing on a possibly
occurred short-circuit can be ensured. Also breaking of different currents is possible both in normal and
faulty system operation. In the end
position there is a reliable catch
through the stored energy drive. The
drive angle is 90.

Arcing chamber
The switch disconnectors L-TRI 5
employ the proved flat arcing chambers working on the hard-gas principle. The arc quenching facility is
shunted to the main current path
and includes a flat arcing chamber
and an arcing blade for each
phase.
Due to the optimized design and
the use of an improved quenching
medium both the dimensions could
be reduced and also the service life
was increased.
For switch disconnectors with
increased breaking capacity a
modified quenching system with
special arcing blades is available
as option.

Transformer disconnector
L-TRI 5...-UH-KS-A

(5)

(4)

Legend
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)

Base frame
Epoxy resin insulators
Switch shaft (drive)
Main current path with
push rod
Arcing chamber
Fuse carrier
Latch
Fuse tripping device

(6)

(8)
(2)

(3)

(7)

(1)
L-TRI 5...-UH-KS-A

Design

Drive for KS disconnector

Arcing chamber

As for the D-type disconnector, also


this type consists of the main components (1) to (5). Additionally, the
elongated base frame bears epoxy
resin insulators with fuse carriers (6)
to accommodate HH fuses according to DIN 43625 and the functional device for fuse tripping (8).

For the drive type KS..


(rapid CLOSING, stored energy for
OPENING, rapid OPENING) lowmaintenance springs are used. Loading of the breaking springs occurs
automatically during the closing
action. After the rapid closing
action the opening energy remains
stored in the breaking spring. Opening may occur immediately after
closing by actuation of the switch
shaft (drive) or by tripping of a HH
fuse or by an attached breaking-current shunt release. The drive angle
is 90.

The switch disconnectors L-TRI 5


employ the proved flat arcing chambers working on the hard-gas principle. The arc quenching facility is
shunted to the main current path
and includes a flat arcing chamber
and an arcing blade for each
phase.
Due to the optimized design and
the use of an improved quenching
medium both the dimensions could
be reduced and also the service life
was increased

10

Switch disconnectors
L-TRI 5...-KS-AA
General
The switch disconnector L-TRI 5...KS-AA is a device with trip-free
release and rapid closing.
In principle, the drive works like
that of the transformer disconnector
-UH-KS-A (for this see drive of KS
switch). Opening may occur immediately after closing by actuation of
the switch shaft (drive) or by an
attached breaking-current shunt
release. Apart from the short-circuit
making capacity, the technical data
are the same as for the transformer
disconnector type UH-KS- A.
The type L-TRI 5...-KS-AA has a
reduced short-circuit making capacity Ima = 50 kA.
Design
The design of the disconnector type
KS-AA is similar to that of the type
UH-KS-A. However, it does not
include the additional row of 3
epoxy resin insulators with the fuse
carriers and the fuse tripping
device. Consequently, the disconnenctor base frame is correspondingly shorter compared with the
type UH-KS-A.

Switch disconnectors
L-TRI 5...-KS-AA

Transformer disconnector
L-TRI 5...-UH-D
General
In addition to the transformer disconnector L-TRI 5...-UH-KS-A also
the type L-TRI 5...-UH-D is available.
The differences are the following:
no HH fuse tripping
torsion spring actuation
(D-disconnector) (see under cable
disconnector L-TRI 5...-D).
Design
The design and the dimensions of
this variant correspond to those of
the type L-TRI 5...-UH-KS-A, however, without fuse tripping and latch
(see design of the type L-TRI 5...
-UH-KS-A).

Transformer disconnector
L-TRI 5...-UH-D
11

Transformer disconnector
L-TRI 5F...-UH-KS-A
The switch-disconnector-fuse combination type L-TRI 5F with all-pole
mechanical release for the striking
pin release of the HH fuse links
meets the specific test conditions
according to DIN EN 60420 (VDE
0670 Part 303), IEC 60420.
A prerequisite for the fulfilment of
the above norms is an improved
patent-pending arc quenching
system with arcing chamber and
sickle shaped arcing blade. Apart
from that, the type L-TRI 5F...-UHKS-A is equal to the standard transformer disconnector L-TRI 5...-UHKS-A.

L-TRI 5F...-UH-KS-A-EU-VU

12

Mounted earthing switch


at the cable disconnector

A t t a c h m e n t

t o

f i x e d - c o n t a c t
(3)

(5)

s i d e

E T

(1)

Legend
(1)
(2)
(3)
(4)
(5)
(6)

Base frame elongation


Earth shaft
Earth blade
Rapid closing
Earth contact
Mechanical interlock

(2)

(6)

(6)

(2)

(5)

(3)

A t t a c h m e n t

t o

(4)

m o v i n g - c o n t a c t

s i d e

E A

L-TRI 5...-D-ET-VT-EA-VA

General

Design

Drive

Earthing switches mounted to switch


disconnectors improve the safety for
the operating staff and the operational reliability. The mounted earthing
switches have a defined high
making capacity and are equipped
with a rapid closing facility in form
of a rocker spring. The connection
between switch shaft and frame
forms a reliable transition resistance
so that an additional earthing strip
is not necessary. The purpose determines the type of the mounted earthing switch with making capacity at
the fixed- and/or moving-contact
side of the switch disconnector.

The earthing shaft (2) with the earth


blades (3) is born by the frame
elongation (1) and connected to the
disconnector frame. The earthing
contacts (5) are mounted to the
connecting brackets. Between earthing shaft (2) and disconnector
frame, the spring stack for rapid
closing (4) is attached.
Earthing switches may be mounted
on the:
fixed-contact side ET
moving-contact side EA
and also at both sides.

Rapid starting of the earth switch


drive is via the toggle spring action.
When operating the shaft the dead
point is exceeded after approx. 15
and the rapid closing activated. It is
possible to integrate a mechanical
interlock between the shafts of the
switch disconnector and the mounted earthing switch (VT and VA).It
prevents the closing of the opened
earthing switch as long as the
switch disconnector is CLOSED and
the closing of the opened switch disconnector with the earthing switch
closed.This mechanical interlock is
possible both in manual operation
of the switch disconnector and also
for the mounted earthing switch.

13

Mounted earthing switch


at transformer disconnector

Mounted earthing switch ET

There are three options for attachment of the earthing switch to the
transformer disconnector:
type ET at the fixed-contact side
type EU at the side of the outer
fuse contacts, externally mounted
(apart from 36 kV)
type EUI at the side of the outer
fuse contacts, internally mounted
(only possible for 24 and 36 kV).
Attachment combinations are possible between ET and EUI or ET and
EU. It is possible to realize mechanical interlocks between the shafts
of the switch disconnector and the
mounted earthing switch
(VT; VUI; VU).
The mechanical interlock prevents
the
closing of the opened earthing
switch with the switch disconnector in CLOSED position, and
closing of the opened switch
disconnector with the earthing
switch in CLOSED position.

Mounted earthing switch EUI

Mounted earthing switch EU

14

Accessories

Auxiliary switch HS3


Switch disconnectors and mounted
earthing switches can be equipped
with auxiliary switches type HS 3
as 4-pole, 6-pole or 10-pole variants with randomly programmable
contacts (normally closed, normally
opened, change-over). The high
switching capability allows the
direct triggering of releases, locking
magnets and attachments to motor
drives (see technical data).

Auxiliary switch (HS3) for switch disconnectors type L-TRI 5 and L-TRI 5F
Rated
voltage
kV

Rated
current
A

Pole centre
spacing
mm

12

400...2500

17,5
24
36

4-pole

Number of
contacts
6-pole

10-pole

125
165
210, 250

400...2500

210, 250, 270

400...1600

165
250, 275, 300

340, 370, 400

10-pole

630...1000

Auxiliary switch (HS3) at mounted earthing switch


Rated
voltage
kV

Rated
current
A

Pole centre
spacing
mm

4-pole

Number of
contacts
6-pole

12

400...2500

125
165
210, 250

400...2500

210, 250, 270

400...1600

165
250, 275, 300

340, 370, 400

17,5
24
Example of a 4-pole
auxiliary switch
attachment at the
fixed-contact side
(ET)

36

630...1000

Technical data
Auxiliary switch HS3

Switching capability
Short-circuit strength
Time constant T=L/R
15

24 V DC

60 V DC

110 V DC

220 V DC

220 V AC

8A
1 kA
30 ms

3A
1 kA
30 ms

2A
1 kA
30 ms

1A
1 kA
30 ms

10 A
1 kA

Standard attachment variants


for auxiliary switches

Auxiliary switch ET

Mounted earthing switch ET

Normally, the attachment of the


auxiliary switch to the disconnector
is at the moving-contact side between
the phases L1 and L2. For the mounted earthing switch variant EA at
the moving-contact side between the
phases L2 and L3.
In the case of earthing switch variants EA and ET the auxiliary switch
ET is mounted at the fixed-contact
side between the phases L1 and L2.
Other variants of attachment on
request.

Auxiliary switch for


switch disconnector

16

Mounted earthing
switch EA
Auxiliary switch EA

Signalling switch MSKM


The transformer disconnector with
HH fuse release has a signalling
switch MSKM which indicates the
fuse release. This signalling switch
is located at the fuse tripping shaft.

Signalling switch (MSKM), HH fuse released (only possible with all-pole fuse release).
Available options:

1 NO + 1 NC
2 NO
2 NC

Technical data
Signalling switch MSKM

Switching capability
Time constant
T=L/R

24 V DC

60 V DC

110 V DC

220 V DC

220 V AC

10 A
20 ms

6A
21 ms

4A
22 ms

2A
23 ms

6A

Signalling
switch
MSKM
Attachment of breaking-current
shunt release AA at stored breaking energy device.

Breaking-current shunt release


(operating current release AA)
It is possible to attach breaking-current shunt releases to the switch disconnectors L-TRI 5 with stored breaking energy (-KS).
They are used for remote breaking
and are designed for pulsed operation. The associated auxiliary switch
(standard variant) disconnects the
breaking-current shunt release from
the supply voltage after breaking.
The breaking-current shunt releases
are available for the following auxiliary voltages:
220 V AC/DC
110 V AC/DC
60 V DC
(Other values on request)

17

Capacitor dividers
The range L-TRI 5 is available with
capacitor dividers as option. Along
with the recommended separate
system units testing for dead state
and phase coincidence is by integrated and non-integrated voltage
testing systems according to
VDE 0682 Part 415 and
E DIN IEC 78/183/CDV. Condisering the electrical characteristics
and strengthes the capacitor dividers correspond to common post
insulators and are suited for connection to both high-resistive and also
low-resistive systems. Attachment of
the capacitor dividers is possible at
the moving-contact or fixed-contact
side.

Divider attachment at movingcontact side

Clamping lever
With the standard variant, the following clamping levers are available
for the operation of the switch disconnectors and earthing switches:

Clamping
lever type
QW 7

switch disconnector QW 7
earthing switch QW 6
As an option, it is possible to use a
ring lever elongation QV 1 for the
hook-stick operation.
Clamping
lever type
QW 6

Switch disconnectors
L-TRI 5...-D-EA- VA

18

Manual drives
As standard, a linkage-type manual
drive STA 2 and an articulated
drive STAD 2 are available for the
mechanical operation of the switch
disconnectors L-TRI 5. In the most
applications, mounting of these
drives depends on the cubicle variant so that only a short information
on the different options is given
here.
If required, please contact us.

STA 2

STAD 2

Motor drives
Motor drives are available for the
electrical operation of the switch
disconnectors L-TRI 5. The motor
drives are directly attached to the
base frame of the switch disconnector so that a complete switch-drive
unit is established.

Motor drive examples

Plug-in board
If desired, a plug-in board can be
pushed into the opened switch vertically to the switch base frame
below the arcing chamber. It is not
part of the switch disconnector. Lateral deposition of the plug-in board
according to panel variant. Recommended board thickeness:
12 kV = 4 mm
17.5 kV = 6 mm
24 kV = 8 mm
36 kV = 10 mm
19

Fitting position, selection of driving side and shaft lengthes

Fitting position
In the case of cable disconnector
(type L-TRI 5...-D) having a rated
current of up to 630 A and a horizontally located switch shaft any
fitting position is possible (see
sketch). For the cable diconnectors
>= 1000 A and transformer disconnectors (type L-TRI 5...-UH-KS-A)
wall-mounting with the arcing chambers on top is standard. For deviating fitting positions please consult
us.

Ceiling-fitting

180

Standard
wall-fitting

Upside-down
wall-fitting

Floor-fitting

Possible fitting positions

20

Selection of the driving side


The selection of the driving side depends on whether manual or motor drive is used and on the mechanical interlock.
Switch disconnector
Attached
Manual drive
motor drive
left
right
left
right

1)

Mounted earthing switch


Attached
Manual drive
motor drive
left
right
left

Mechanical interlock

1), 2)

1) For a combination of 3 switching devices (1 switch disconnector and 2 mounted earthing switches) only two motor drives
are possible as a maximum. Referred to the device they are located opposite to each other.
2) The motor drive is only possible for the earthing switch at the moving-contact side (EA).

Selection of possible shaft lengthes


The selection of the available shaft lengthes depends on the rated voltage and the pole centre spacing.
Rated voltage
Pole centre spacing (mm)
Shaft length (mm)

566
588
666
766
866
966
1066
1100
1500

125 T

12 kV
165
210

250

210

17.5 kV
250
270

165 T

24 kV
250
275

300

340 T
340

36 kV
370

400

21

Regulations and tests

Regulations
Disconnector type

Regulations
DIN EN

VDE

IEC

Number

Part

L-TRI 5 ...-D, UH-D, UH-KS-A, KS-AA

60694
60265-1

0670

1000,
301

60694
60265-1

L-TRI 5F ...-UH-KS-A

60694,
60420

0670

1000,
303

60694,
60420

L-TRI 5 ...-D, UH-D, UH-KS-A, KS-AA


(CSA)

60694
60265-1

0670

1000,
301

60694
60265-1

CSA

C22.2
(0; 193)

Tests
The switch disconnectors have
proved their outstanding features
during type testing according to the
valid national and international
standards and comprehensive test
series in the development stage and
also in practical use.
The tests were carried out in own
high-performance test floors and by
independent testing institutions such
as FGH, IPH or KEMA for example.

They also include the use in type


tested switchgear. Additionally, the
reliability, operational safety and
mechanical function were tested
during long-time tests.
The technical data given in this
catalogue represent standardized
rated values. They are not the upper
limit values of the switch in any
case. If required, you can request
for them.

22

The switch disconnectors up to


630 A have to be classified as
multipurpose switch disconnectors
of the class E1 according to
IEC 60265-1.

Transformer disconnectors
according to
IEC 60420 type L-TRI 5F
The norm IEC 60420 is a supplementary regulation for "Transformer
disconnectors" and especially
applies to switch-disconnector-fuse
combinations with fuse release (type
L-TRI 5F...-UH-KS-A). The combination from switch disconnector and
fuse is considered to be one unit
and has to be tested correspondingly. As the norm also requires
the breaking of high fault currents
with unfavourable power factors
(cos ) the arc quenching system
was modified and improved without
renunciation of the proven concept
of the flat arcing chamber. The type
L-TRI 5F can be easily recognized
by the curved arcing blades (see
figure, page 12).
The type L-TRI 5F-UH-KS-A can be
used with operating voltages of
10/12kV up to a transformer
power of 1000 kVA, and with
operating voltages 20/24kV up to
a transformer power of 1250 kVA.
A fuse selection table assigns the
tested HH fuse links from different
manufacturers to the different rated
transformer powers and is to be
considered for engineering (see
selection table on pages 28/29).

Transformer disconnectors
according to
DIN EN 60265
Additionally, also switch-disconnector-fuse combinations according to
DIN EN 60265 (VDE 0670 Part
301), IEC 60265-1 are available,
which are suited for breaking
higher transformer powers.
With 12 kV up to a transformer
power of 1250 kVA.
With 24/36 kV up to a transformer power of 1600 kVA.

Climatic conditions
The design, components and tolerances for the switch disconnectors
are selected so that the devices can
be used without any restriction in
indoor conditions according to
IEC 60694 and IEC 60265 (DIN
EN 0670 Part 1000 and Part 301)
with increased values between
25C and +40C.

Low maintenance
In normal operational conditions
(so called EVU use) as specified in
valid regulations the switch disconnectors of the range L-TRI 5 are
virtually maintenance-free, that
means the time between two maintenance procedures is approximately 15 years under normal
climatic conditions.
An inspection is recommended after
1500 switching cycles or after
serious short-circuit stresses.
In practical system operation it is
not needed to replace any parts. In
the case that the allowed number of
breaking operations has been actually reached it is possible to easily
replace the arc quenching facility.

Quality
The achieved steady high quality
standard of our products is ensured
by the quality assurance management according to DIN ISO 9001
introduced in 1993.

Economy
When it comes to procurement cost
we recommend to consider the
advantageous economic effects of
the product range L-TRI 5 including
accessories in terms of quality,
operational and functional
reliability, availability and low
maintenance expenses.

23

Selection tables

Characteristic values of the switch


disconnectors (cable disconnectors)
Type
according to standard
Rated voltage
Rated frequency
Rated lightning impulse withstand voltage
against earth
between the poles
across the isolating gap
Rated withstand alternating voltage
against earth
between the poles
across the isolating gap
Rated current
Rated short-time current

accordi
Ur
fr
Up

1s
3s

Number of operations with rated short-circuit making current

Rated system breaking current with 20 cycles


System breaking current with 3 cycles
System breaking current with 200 cycles
Rated ring mains breaking current
Rated transformer breaking current
Rated cable and overhead line breaking current
Rated earth-fault breaking current
Rated cable and overhead line breaking current
under earth-fault conditions
Mechanical operation cycle numbers

Pole centre spacing


(3-pole switchgear)

Rated peak current


Rated short-circuit making current
1)
2)

12
50/60

kV
kV
kV

75
75
85

kV
kV
kV
A
kA
kA
kA
kA

28
28
32
1000
40
23
63
63
2
630
1000
32
630
10
50
150
86

1000
32
23
80
63
2
630
1000
32
630
10
50
150
86

1250
40
25
100
50
2
630
1250
35
630
10
50
150
86

2500
50
35
125
50
2
630
2500
35
630
10
50
150
86

400
25
18
63
63
2
400

1500

Ud

Rated peak current


Rated short-circuit making current

Mounted earthing switch


Rated short-time current

kV
Hz

1s
3s

Ir
Ik
Ip
Ima
n
I1

I2a
I3
I4a, I4b
I6a
I6b
n
125
165
210
250
270
275
300
340
370
400
Ik
Ip
Ima

A
A
A
A
A
A
A
A

mm
mm
mm
mm
mm
mm
mm
mm
mm
mm
kA
kA
kA
kA

400
25
18
63
63
2
400

630
25
18
63
63
2
630

32
400
10
50
150
86

32
630
10
50
150
86

1500
1)

1500
1)

1500

1500

1000

1000

25
14
63
63

25
14
63
63

252)
142)
63
63

32
23
80
80

32
23
80
80

32
23
80
80

with phase partitions


Higher values on request.
24

32
400
10
50
150
86

25
14
63
63

L-TRI 5
ng to VDE 0670 Part 301 or IEC 60265
17.5
50/60

630
25
18
63
63
2
630

24
50/60

50/60

50/60

95
95
110

125
125
145

170
170
195

145
145
165

38
38
45

50
50
60

70
70
80

70
70
80

2500
50
35
125
45
2
630
1250
35
630
10
50
150
86

400
25
18
63
63
2
400

630
25
18
63
63
2
630

32
630
10
50
150
86

1250
40
25
100
45
2
630
1250
35
630
10
50
150
86

32
400
10
50
285
86

1500

1000

1000

36

1000
32
23
80
63
2
630
1000
32
630
10
50
150
86

1250
40
25
100
37
2
630
1250
35
630
10
50
150
86

1600
40
25
100
37
2
630
1600
35
630
10
50
150
86

630
20
14
50
25
2
630

32
630
10
50
285
86

1000
40
23
63
63
2
630
1000
32
630
10
50
150
86

630
20
14
50
25
2
630

32
630
6,3
25
70
40

1000
20
14
50
25
2
630
1000
32
630
6,3
25
70
40

32
630
6,3
25
70
40

1000
20
14
50
25
2
630
1000
32
630
6,3
25
70
40

1500

1500

1500

1500

1000

1000

1000

1000

1000

1000

1)

1)

1)

1)

20
14
50
50

20
14
50
50

20
14
50
50

20
14
50
50

25
14
63
63

32
23
80
80

32
23
80
80

25
14
63
63

25
14
63
63

252)
142)
63
63

32
23
80
80

32
23
80
80

25

32
23
80
80

Characteristic values of switch disconnectors


(transformer disconnectors)
Type
according to standard
Rated voltage
Rated frequency
Rated lightning impulse withstand voltage
against earth
between the poles
across the isolating gap
Rated withstand alternating voltage
against earth
between the poles
across the isolating gap
Rated current
Rated short-time current

Ur
fr
Up

1s
3s

Number of operations with rated short-circuit making current

Rated short-circuit breaking current


System breaking current with 20 cycles
System breaking current with 200 cycles
Rated transformer breaking current
Rated cable and overhead line breaking current I
Rated current for fuse carrier4)
Rated take-over current
with striking pin release
Mechanical operation cycle numbers

Pole centre spacing


(3-pole switchgear)

Opening times of the switch disconnector


with striking pin operation
Type of the approved fuse striking pin
Fuse gauges

1s
3s

Rated peak current


Rated short-circuit making current
Number of operations with rated short-circuit making current
1)
2)
3)
4)

kV
Hz

12
50/60

36
50/

kV
kV
kV

75
75
85

95
95
110

125
125
145

170
170
195

kV
kV
kV
A
kA
kA
kA
kA

28
28
32

38
38
45

50
50
60

Ud

Rated peak current


Rated short-circuit making current

Mounted earthing switch


Rated short-time current

Fuse switch disconnectors


L-TRI 5
according to VDE 0670 Part 301 or IEC 60265
17.5
24
50/60
50/60

Ir
Ik
Ip
Ima
n

I4

kA
A
A
A
A
A
A

125
165
210
250
275
300
340
370
400
To

mm
mm
mm
mm
mm
mm
mm
mm
mm
ms

mm

Ik

kA
kA
kA
kA

I3
4a, I4b

Ip
Ima
n

400
25
18
63
63
2

630
25
18
63
63
2

400
25
18
63
63
2

630
25
18
63
63
2

400
25
18
63
63
2

630
25
18
63
63
2

70
70
80
630
20
14
50
25
2

400
32
10
50
200

630
32
10
50
200

400
32
10
50
200

630
32
10
50
200

400
32
10
50
200

630
32
10
50
200

630
32
6,3
25
200

1500
1)

1500
1)

1500

1500

1500

1500

1000

1)

1)

1)

medium
292

25
14
63
63
2

medium
367
2923)
25
14
63
63
2

25
14
63
63
2

medium
442

25
14
63
63
2

25
14
63
63
2

medi
53

25
14
63
63
2

with phase partitions


In general, the rated current of a switch-disconnector-fuse combination is lower than the rated current specified by the fuse manufacturer.
With the use of 12kV fuse
Higher values on request

26

20
14
50
50
2

Switch-disconnector-fuse combination
L-TRI 5F
according to VDE 0670 Part 303 or IEC 60420
12
24
50/60
50/60

60
145
145
165

75
75
85

125
125
145

70
70
80
630
20
14
50
25
2

28
28
32
1352)

50
50
60
952)

63
63
2
25
400
32
10
50

63
63
2
25
400
32
10
50

1250

800

1500
1)

1500

80

80

medium
292

medium
442

25
14
63
63
2

25
14
63
63
2

630
32
6,3
25
200

1000

1)

um
7

20
14
50
50
2

27

Selection of HH subrange fuses


Switch disconnector-fuse combination
L-TRI 5F/12 kV (IEC 60420)
Transformer
Run- Operating
ning voltage
No.
kV

Rated
power
kVA

Rated
current
A

Uk
%

Isec
(Ik)
A

250

24

600

315

30

760

400

39

960

500

48

1200

10

250

14

360

10

315

18

455

10

400

23

580

10

500

29

720

10

630

36

910

10

10

800

46

925

11

10

1000

58

1155

Manufacturer

SIBA
Jean Mller
EFEN
Driescher Wegberg
Driescher Moosburg
SIBA
Jean Mller
EFEN
Driescher Wegberg
Driescher Moosburg
SIBA
Jean Mller
EFEN
Driescher Wegberg
Driescher Moosburg
SIBA
Jean Mller
EFEN
Driescher Wegberg
Driescher Moosburg
SIBA
Jean Mller
EFEN
Driescher Wegberg
Driescher Moosburg
SIBA
Jean Mller
EFEN
Driescher Wegberg
Driescher Moosburg
SIBA
Jean Mller
EFEN
Driescher Wegberg
Driescher Moosburg
SIBA
Jean Mller
EFEN
Driescher Wegberg
Driescher Moosburg
SIBA
Jean Mller
EFEN
Driescher Wegberg
Driescher Moosburg
SIBA
Jean Mller
EFEN
Driescher Wegberg
Driescher Moosburg
SIBA
Jean Mller
EFEN
Driescher Wegberg
Driescher Moosburg

HH subrange fuse
with striking pin release, medium type
Type
RatedRatedor Article no.
voltage
current
kV
A
3000413
6/12
50
IKUS 10-50
12
50
67120.0500
6/12
50
DRL6/50S
7.2
50
H220 Sta
12
50
3001213
6/12
63
IKUS 10-63
12
63
67120.0630
6/12
63
DRL6/63S
7.2
63
H221 Sta
12
63
3001213
6/12
80
IKUS 10-80
12
80
67120.0800
6/12
80
DRL6/80S
7.2
80
H221 Sta
12
80
3001213
6/12
100
IKUS 10-100
12
100
67120.1000
6/12
100
DRL6/80S
7.2
80
H221 Sta
12
80
3000413
6/12
31,5
IKUS 10-32
12
32
67120.0320
6/12
31,5
DR10/32S
12
32
H220 Sta
12
32
3000413
6/12
40
IKUS 10-40
12
40
67120.0400
6/12
40
DR10/40S
12
40
H220 Sta
12
40
3000413
6/12
50
IKUS 10-50
12
50
67120.0500
6/12
50
DR10/50S
12
50
H220 Sta
12
50
3001213
6/12
63
IKUS 10-63
12
63
67120.0630
6/12
63
DR10/63S
12
63
H221 Sta
12
63
3001213
6/12
80
IKUS 10-80
12
80
67120.0800
6/12
80
DR10/80S
12
80
H221 Sta
12
80
3001213
6/12
80
IKUS 10-100
12
100
67120.0800
6/12
80
DR10/80S
12
80
H221 Sta
12
80
3001213
6/12
100
IKUS 10-100
12
100
67120.1000
6/12
100

28

Gauge
e
mm
292
292
292
292
292
292
292
292
292
292
292
292
292
292
292
292
292
292
292
292
292
292
292
292
292
292
292
292
292
292
292
292
292
292
292
292
292
292
292
292
292
292
292
292
292
292
292
292
292
292
292
292
292

Take-over current
of the combination

A
450
400
480
500
520
570
500
650
680
680
750
650
800
900
900
1000
750
1050
900
900
250
280
300
280
340
320
330
390
380
430
450
400
480
500
520
570
500
650
680
680
750
650
800
900
900
750
750
800
900
900
1000
750
1050

Selection of HH subrange fuses


Switch disconnector-fuse combination
L-TRI 5F/24 kV (IEC 60420)
Transformator
Run- Operating
ning voltage
No.
kV

Rated
power
kVA

Rated
current
A

Uk
%

Isec
(Ik)
A

20

250

180

20

315

230

20

400

12

290

20

500

14

360

20

630

18

455

20

800

23

460

20

1000

29

580

20

1250

36

725

Manufacturer

SIBA
Jean Mller
EFEN
Driescher Wegberg
Driescher Moosburg
SIBA
Jean Mller
EFEN
Driescher Wegberg
Driescher Moosburg
SIBA
Jean Mller
EFEN
Driescher Wegberg
Driescher Moosburg
SIBA
Jean Mller
EFEN
Driescher Wegberg
Driescher Moosburg
SIBA
Jean Mller
EFEN
Driescher Wegberg
Driescher Moosburg
SIBA
Jean Mller
EFEN
Driescher Wegberg
Driescher Moosburg
SIBA
Jean Mller
EFEN
Driescher Wegberg
Driescher Moosburg
SIBA
Jean Mller
EFEN
Driescher Wegberg
Driescher Moosburg

HH subrange fuse
with striking pin release, medium type
Type
RatedRatedor Article no.
voltage
current
kV
A
3000613
10/24
16
IKUS 20-16
24
16
67140.0160
10/24
16
DR20/16S
24
16
H220 Sta
24
16
3000613
10/24
25
IKUS 20-25
24
25
67140.0250
10/24
25
DR20/25S
24
25
H220 Sta
24
25
3000613
10/24
25
IKUS 20-25
24
25
67140.0250
10/24
25
DR20/25S
24
25
H220 Sta
24
25
3000613
10/24
31.5
IKUS 20-32
24
32
67140.0320
10/24
31.5
DR20/32S
24
32
H220 Sta
24
31.5
3000613
10/24
40
IKUS 20-40
24
40
67140.0400
10/24
40
DR20/40S
24
40
H220 Sta
24
40
3001413
10/24
50
IKUS 20-50
24
50

DR20/40S
24
40
H220 Sta
24
40
3001413
10/24
63
IKUS 20-63
24
63

DR20/50S
24
50
H220 Sta
24
50

IKUS 20-80
24
80

DR20/63S
24
63
H220 Sta
24
63

Example:
Transformer, operating voltage 10 kV, rated power 630 kVA, Uk 4%;
switch-disconnector-fuse combination type Typ L-TRI 5F/12/400/210
Selected fuse: make SIBA, type 30012 13, rated current 80 A, gauge 292 mm

29

Gauge
e
mm
442
442
442
442
442
442
442
442
442
442
442
442
442
442
442
442
442
442
442
442
442
442
442
442
442
442
442

442
442
442
442

442
442

442

442
442

Take-over current
of the combination

A
110
125
130
130
125
210
180
220
210
190
210
180
220
210
190
250
280
280
280
340
320
330
380
380
430
450
400

380
430
570
500

500
520

650

680
680

Dimensioned drawings and weights

Dimensioned drawings and weights for L-TRI 5, 12 kV


L-TRI 5/12/400...1000/...-D

Reference dimension is "C (pole centre spacing)


Define dimension "A (switch shaft length).
Weights in kg
A
966
866
766
966
866
766
730
666
566
588

B
665
665
665
625
625
625
485
485
485
405

C
250
250
250
210
210
210
165
165
165
125T

D
640
640
640
600
600
600
460
460
460
380

Weight for L-TRI 5

26
26
26
23
23
23
20
20
20
19

Weight per mounted earthing switch

10
10
10
9.5
9.5
9.5
8
8
8
7

IR
[A]

400/
630/
1000

400/630

30

L-TRI 5/12/400...630/...-UH-D
L-TRI 5/12/400...630/...-UH-KS-A

Reference dimension is "C (pole centre spacing)


Define dimension "A (switch shaft length).
Weights in kg
A
966
866
766
966
866
766
730
666
566
588

B
665
665
665
625
625
625
485
485
485
405

C
250
250
250
210
210
210
165
165
165
125T

D
640
640
640
600
600
600
460
460
460
380

Weight for L-TRI 5

41
41
41
38
38
38
35
35
35
32

Weight per mounted earthing switch

11
11
11
10.5
10.5
10.5
8
8
8
7

31

L-TRI 5/12/400...630/...-KS-AA

Reference dimension is "C (pole centre spacing)


Define dimension "A (switch shaft length).
Weights in kg
A
966
866
766
966
866
766
730
666
566
588

B
665
665
665
625
625
625
485
485
485
405

C
250
250
250
210
210
210
165
165
165
125T

D
640
640
640
600
600
600
460
460
460
380

Weight for L-TRI 5

30
30
30
26
26
26
23
23
23
22

Weight per mounted earthing switch

10
10
10
9.5
9.5
9.5
8
8
8
7

32

L-TRI 5/12/1250/...-D

Reference dimension is "C (pole centre spacing)


Define dimension "A (switch shaft length).
Weights in kg
A
966
966
766

B
630
630
630

C
250
210
210

D
700
600
600

Weight for L-TRI 5

Weight per mounted earthing switch

57
55
55

13
12.5
12.5

L-TRI 5/12/2500/250-D

Weights in kg
Weight for L-TRI 5

68

Weight per mounted earthing switch

13
33

Dimensioned drawings and weights for L-TRI 5, 17,5 kV


L-TRI 5/17.5/400...630/210-UH-D
L-TRI 5/17.5/400...630/210-UH-KS-A

x for fuse size 12kV

Define dimension "A (switch shaft length).


Weights in kg
A
966
866
766

Weight for L-TRI 5

Weight per mounted earthing switch

48
48
48

10
10
10

34

L-TRI 5/17.5/400...630/210-KS-AA

L-TRI 5/17,5/400...630/210-D

Define dimension "A (switch shaft length).


Weights in kg
A
966
866
766

Weight for L-TRI 5

Weight per mounted earthing switch

28
28
28

10
10
10
35

L-TRI 5/17.5/1250/250-D

Weights in kg
Weight for L-TRI 5

Weight per mounted earthing switch

57

13.5

L-TRI 5/17,5/2500/270-D

Weights in kg
Weight for L-TRI 5

Weight per mounted earthing switch

70

14
36

Dimensioned drawings and weights for L-TRI 5, 24 kV


L-TRI 5/24/400...1000/...-D

Reference dimension is "C (pole centre spacing)


Define dimension "A (switch shaft length).
Weights in kg
A
1066
966
1066
966
966
866
766
766
666
566

B
775
775
775
775
655
655
655
485
485
485

C
300
300
275
275
250
250
250
165T
165T
165T

D
750
750
750
750
630
630
630
460
460
460

Weight for L-TRI 5

32
32
32
32
29
29
29
28
28
28

Weight per mounted earthing switch

11.5
11.5
11.5
11.5
10.5
10.5
10.5
8.5
8.5
8.5

IR
[A]

400/
630/
1000

400/
630

37

L-TRI 5/24/400...630/...-UH-D
L-TRI 5/24/400...630/...-UH-KS-A

Reference dimension is "C (pole centre spacing)


Define dimension "A (switch shaft length).
Weights in kg
A
1066
966
1066
966
966
866
766
766
666
566

B
775
775
775
775
655
655
655
485
485
485

C
300
300
275
275
250
250
250
165T
165T
165T

D
750
750
750
750
630
630
630
460
460
460

Weight for L-TRI 5

57
57
57
57
53
53
53
51
51
51

Weight per mounted earthing switch

11.5
11.5
11.5
11.5
10.5
10.5
10.5
8.5
8.5
8.5

38

L-TRI 5/24/400...630/...-KS-AA

Reference dimension is "C (pole centre spacing)


Define dimension "A (switch shaft length).
Weights in kg
A
1066
966
1066
966
966
866
766
766
666
566

B
775
775
775
775
655
655
655
485
485
485

C
300
300
275
275
250
250
250
165T
165T
165T

D
750
750
750
750
630
630
630
460
460
460

Weight for L-TRI 5

Weight per mounted earthing switch

36
36
36
36
33
33
33
32
32
32

11.5
11.5
11.5
11.5
10.5
10.5
10.5
8.5
8.5
8.5

39

L-TRI 5/24/1250/300-D

Define dimension "A (switch shaft length).


Weights in kg
A
1066
966

Weight for L-TRI 5

60
60

Weight per mounted earthing switch

15
15

40

Dimensioned drawings and weights for L-TRI 5, 36 kV


L-TRI 5/36/630...1000/...-D

Reference dimension is "C (pole centre spacing)


Define dimension "A (switch shaft length).
Weights in kg
A
400
370
340 T
340

41

Weight for L-TRI 5

Weight per mounted earthing switch

59
59
59
57

13
13
13
13

UP

170
170
170
145

L-TRI 5/36/630/...-UH-D
L-TRI 5/36/630/...-UH-KS-A

Reference dimension is "C (pole centre spacing)


Define dimension "A (switch shaft length).
Weights in kg
A
400
370
340 T
340

42

Weight for L-TRI 5

Weight per mounted earthing switch

UP

98
98
98
96

13
13
13
13

170
170
170
145

Dimensioned drawings and weights for L-TRI 5F according to IEC 60420, 12 kV


L-TRI 5F/12/400...630/...-UH-KS-A accordimg to IEC 60420

Reference dimension is "C (pole centre spacing)


Define dimension "A (switch shaft length).
Weights in kg
A
966
866
766
966
866
766
730
666
566
588

B
665
665
665
625
625
625
485
485
485
405

C
250
250
250
210
210
210
165
165
165
125T

D
640
640
640
600
600
600
460
460
460
380

Weight for L-TRI 5

41
41
41
38
38
38
35
35
35
32

Weight per mounted earthing switch

11
11
11
10.5
10.5
10.5
8
8
8
7

43

Dimensioned drawings and weights for L-TRI 5F according to IEC 60420, 24 kV


L-TRI 5F/24/400...630/...-UH-KS-A nach IEC 60420

Reference dimension is "C (pole centre spacing)


Define dimension "A (switch shaft length).
Weights in kg
A
1066
966
1066
966
966
866
766
766
666
566

B
775
775
775
775
655
655
655
485
485
485

C
300
300
275
275
250
250
250
165T
165T
165T

D
750
750
750
750
630
630
630
460
460
460

Weight for L-TRI 5

Weight per mounted earthing switch

57
57
57
57
53
53
53
51
51
51

11.5
11.5
11.5
11.5
10.5
10.5
10.5
8.5
8.5
8.5

44

Das könnte Ihnen auch gefallen