SINAMICS V20 Inverter

Running the inverter in motor staging mode

Running the inverter in motor staging mode


Functionality
Motor staging allows the control of up to 2 additional staged pumps or fans, based on a PID
control system. The complete system consists of one pump controlled by the inverter and up
to 2 further pumps / fans controlled from contactors or motor starters. The contactors or motor
starter are controlled by digital outputs from the inverter.
The diagram below shows a typical pumping system.

This document constitutes a free excerpt compiled by the user himself/herself from the documentation provided by Siemens for this product. Siemens disclaims
all liability for the completeness of this document. It shall only be used for the user's own internal purposes. It shall not be passed on to third parties. The complete
documentation can be found at:
/dokumentation/default.aspx?DocVersionId=76829968523&Language=en-US&TopicId=70506433547
5/21/2015

SINAMICS V20 Inverter


Running the inverter in motor staging mode

This document constitutes a free excerpt compiled by the user himself/herself from the documentation provided by Siemens for this product. Siemens disclaims
all liability for the completeness of this document. It shall only be used for the user's own internal purposes. It shall not be passed on to third parties. The complete
documentation can be found at:
/dokumentation/default.aspx?DocVersionId=76829968523&Language=en-US&TopicId=70506433547
5/21/2015

SINAMICS V20 Inverter


Running the inverter in motor staging mode

Setting parameters
Parameter

Function

Setting

P2370[0...2]

Motor staging stop mode

This parameter selects stop mode for external motors when


motor staging is in use.
= 0: Normal stop (factory default)
= 1: Sequence stop

P2371[0...2]

Motor staging configuration

This parameter selects configuration of external motors (M1,


M2) used for motor staging feature.
= 0: Motor staging disabled
= 1: M1 = 1 x MV, M2 = Not fitted
= 2: M1 = 1 x MV, M2 = 1 x MV
= 3: M1 = 1 x MV, M2 = 2 x MV

P2372[0...2]

Motor staging cycling

This parameter enables motor cycling for the motor staging


feature.
= 0: Disabled (factory default)
= 1: Enabled

P2373[0...2]

Motor staging hysteresis [%]

P2373 as a percentage of PID setpoint that PID error P2273


must be exceeded before staging delay starts.
Range: 0.0 to 200.0 (factory default: 20.0)

P2374[0...2]

Motor staging delay [s]

This parameter defines the time that PID error P2273 must
exceed motor staging hysteresis P2373 before staging occurs.
Range: 0 to 650 (factory default: 30)

P2375[0...2]

Motor destaging delay [s]

This parameter defines the time that PID error P2273 must
exceed motor staging hysteresis P2373 before destaging
occurs.
Range: 0 to 650 (factory default: 30)

P2376[0...2]

Motor staging delay override [%]

P2376 as a percentage of PID setpoint. When the PID error


P2273 exceeds this value, a motor is staged / destaged
irrespective of the delay timers.
Range: 0.0 to 200.0 (factory default: 25.0)
Note: The value of this parameter must always be larger than
staging hysteresis P2373.

P2377[0...2]

Motor staging lockout timer [s]

This parameter defines the time for which delay override is


prevented after a motor has been staged or destaged.
Range: 0 to 650 (factory default: 30)

P2378[0...2]

Motor staging frequency f_st [%]

This parameter sets the frequency at which the digital output is


switched during a (de) staging event, as the inverter ramps from
maximum to minimum frequency (or vice versa).
Range: 0.0 to 120.0 (factory default: 50.0)

This document constitutes a free excerpt compiled by the user himself/herself from the documentation provided by Siemens for this product. Siemens disclaims
all liability for the completeness of this document. It shall only be used for the user's own internal purposes. It shall not be passed on to third parties. The complete
documentation can be found at:
/dokumentation/default.aspx?DocVersionId=76829968523&Language=en-US&TopicId=70506433547
5/21/2015

SINAMICS V20 Inverter


Running the inverter in motor staging mode

Parameter

Function

Setting

r2379.0...1

CO / BO: Motor staging status word

This parameter displays output word from the motor staging


feature that allows external connections to be made.
Bit 00: Start motor 1 (yes for 1, no for 0)
Bit 01: Start motor 2 (yes for 1, no for 0)

P2380[0...2]

Motor staging hours run [h]

This parameter displays hours run for external motors.


Index:
[0]: Motor 1 hrs run
[1]: Motor 2 hrs run
[2]: Not used
Range: 0.0 to 4294967295 (factory default: 0.0)

This document constitutes a free excerpt compiled by the user himself/herself from the documentation provided by Siemens for this product. Siemens disclaims
all liability for the completeness of this document. It shall only be used for the user's own internal purposes. It shall not be passed on to third parties. The complete
documentation can be found at:
/dokumentation/default.aspx?DocVersionId=76829968523&Language=en-US&TopicId=70506433547
5/21/2015

Das könnte Ihnen auch gefallen