AHU DETAILS FOR CBCL PROJECT, CAMBODIA

AHU No. Area Name Type Panel Thermal Air qty Air qty Air qty S.P. S.P. Fresh Fresh air Fresh air Fresh air Filter Filter Filter Coil Coil Coil
of Thick. Break in Cfm in Cmh in L/S in mm in Pa Air Qty Qty Qty section section section capacity capacity Section
AHU in Profile of of Damper Cfm Cmh L/S EU-3 F-7 EU-13 TR Kw with
MM TB WC WC Class Class Class coil
OR Rows
Standard Deep

AHU-01 QC LAB DS 43+/-2 TB 7528 12798 3555 50 500 Yes 752 1278 355 Yes 18.0 63.2 4
AHU-02 MICRO LAB DS 43+/-2 TB 2200 3740 1039 100 1000 Yes 2200 3740 1038 Yes Yes Yes 18.0 63.2 6
AHU-03 FINAL SYRUP ROOM DS 43+/-2 TB 27000 45900 12750 50 500 Yes 2700 4590 1274 Yes Yes 39.9 140.4 4
AHU-04 DRYBASE STORAGE DS 43+/-2 STD 3600 6120 1700 40 400 Yes 360 612 170 Yes 8.8 31 4
AHU-05 TREATED FRESH AIR UNIT DS 43+/-2 TB 6584 11192 3109 50 500 Yes 6584 11193 3108 Yes 25.9 91 4
AHU-06 ADMIN CANTEEN DS 43+/-2 TB 3500 5951 1653 50 500 Yes 866 1472 409 Yes 11.0 38.6 4
AHU-07 ADMIN OFFICE DS 43+/-2 TB 13250 22525 6257 50 500 Yes 2250 3825 1062 Yes 33.9 119.3 4

Notes:-
1 All Chilled water coils shall be made of copper tubes with Aluminum fins only. Chilled water inlet 7 deg C / 12 deg C
2 FAD - Fresh Air Damper Opposed Blade Construction Aluminium.
3 RAD - Return Air Damper Opposed Blade Construction Aluminium.
4 DS - Double Skin Air Handling Unit with PUF Injected panels.
5 NA - Not Applicable.
6 All Dampers shall be Opposed Blade Construction & Aluminium.
7 CW - Coil - Chilled Water Coil. Trane AHU with mentioned coil rows are acceptable
8 FM - Floor Mounted Air Handling Units.
9 CS - Ceiling Suspended Air Handling Units.
10 All AHU's are double skin with outer skin made from pre coated sheets & inner skin made of GI sheets and PUF poured in between.
11 FC - Forward Curved Blowers. BC - Backward Curved Blowers.
12 All motors suitable for VFD application
13 AHU-03 Fan rating mentioned is duty point. Fan to be selected for 14186 L/s. Single fan per AHU is acceptable
Coil Coil Coil Coil Fresh air Mixing box Supply Return S.P. Outlet Type
Entering Entering Leaving Leaving % UV Blower Blower in Pa damper Of AHU Starter
DB WB DB WB Germicidal Section Section of & fire Ceiling Panel
Temp Temp Temp Temp system with with WC damper or with
Deg C Deg C Deg C Deg C blower blower Floor VFD
BC or BC or Mount.
FC FC CS/FM
Plug fan Cmh

23.7 17.3 13.4 12.7 Yes Yes BC Yes FM Yes


32.0 29.4 100% FA Yes Yes BC 3740 40 Yes FM Yes
25.3 18.4 13.5 12.8 Yes Yes BC Yes FM Yes
23.7 17.3 13.4 12.7 Yes Yes BC Yes CS Yes
32.0 29.4 100% FA Yes Yes BC Yes FM Yes
29.0 21.4 13.9 13.1 Yes no BC Yes FM Yes
28.3 20.9 13.8 13.1 Yes no BC Yes FM Yes