LV Transformer Protection Setting:

Tag No. 80-TRN-0667 & 80-TRN-0668


Rating: 2MVA
Voltage 11/0.433kV
% Impedance 6
CT Ratio 125/1 (HV Side)
CT Ratio 3200/1 (LV Side)
Protection Relay Siemens Make
Model 7SJ62
Protection Function 50, 50N, 51, 51N, 64R
Transformer FLA (Ip) 105.0
Transformer FLA (Is) 2667
Through Fault Current (It) 44450

OC Setting (Primary Side) ANSI 51 1.2 x (Ip/Ict)


1.2 x (105/125)
Selected Setting: 1.0
Curve Selected IEC-Normal Inverse
Selected Time Dial 0.35
Phase Inst. Setting 1.5 x (It/Ict)
20.1237272727
Curve Selected Definte Time
Selected Setting: 21
Time Delay 0.01

EF Setting (Primary Side) ANSI 51N 20% of the Ict


0.2 x 125 = 25
Selected Setting 0.2
Curve Selected IEC-Normal Inverse
Selected Time Dial 0.2
Phase Inst. Setting Disabled
Selected Setting: Disabled
Time Delay Disabled
OC Setting (Secondary Side) ANSI 50 1.2 x (Ip/Ict)
1.2 x (2667 /3200)
Selected Setting: 1.0
Curve Selected IEC-Normal Inverse
Selected Time Dial 0.3
Phase Inst. Setting Disabled
Selected Setting: Disabled
Time Delay Disabled

EF Setting (Primary Side) ANSI 50N 20% of the Ict


0.2 x 3200 = 640
Selected Setting 0.2
Curve Selected IEC-Normal Inverse
Selected Time Dial 0.3
Phase Inst. Setting Disabled
Selected Setting: Disabled
Time Delay Disabled

Restricted Earth Fault (64R) 10% of the Ict


0.1 x 3200 = 320
Selected setting 0.1
Selected Time Delay 0.1s

Undervoltage Relay Setting (27) Trip when bus voltage (ph to ph) remain below for 70% nominal value
(ph to ph) remain below for 70% nominal value for 3.0 sec
LV Transformer Protection Setting:

Tag No.
Rating:
Voltage
% Impedance
CT Ratio
CT Ratio
Protection Relay
Model
Protection Function
Transformer FLA (Ip)
Transformer FLA (Is)
Through Fault Current (It)

OC Setting (Primary Side) ANSI 51

Selected Setting:
Curve Selected
Selected Time Dial
Phase Inst. Setting

Curve Selected
Selected Setting:
Time Delay

EF Setting (Primary Side) ANSI 51N

Selected Setting
Curve Selected
Selected Time Dial
Phase Inst. Setting
Selected Setting:
Time Delay
80-TRN-0661, 80-TRN-0662
80-TRN-0663, 80-TRN-0664 & 80-TRN-0665
25 MVA
33/11.5kV
8.463
600/1(Primary Side)
2000/1 (Secondary Side)
Siemens Make
7SJ62
50, 50N, 51, 51G, 51N, 87T
437.4
1255
14831

1.2 x (Ip/Ict)
1.2 x (438/600)
0.88
IEC-Normal Inverse
0.4
1.5 x (It/Ict)
9.6906991789
Definte Time
13
0.01

20% of the Ict


0.2 x 600 = 120
0.2
IEC-Normal Inverse
0.2
Disabled
Disabled
Disabled
EF Setting (Primary Side) ANSI 50N 20% of the Ict
0.2 x 3200 = 640
Selected Setting 0.2
Curve Selected IEC-Normal Inverse
Selected Time Dial 0.3
Phase Inst. Setting Disabled
Selected Setting: Disabled
Time Delay Disabled

Restricted Earth Fault (64R) 10% of the Ict


0.1 x 3200 = 320
Selected setting 0.1
Selected Time Delay 0.1s

Undervoltage Relay Setting (27) Trip when bus voltage (ph to ph) remain below for 70% nominal value
525.6
0.876

(ph to ph) remain below for 70% nominal value for 3.0 sec