Sie sind auf Seite 1von 4

(1)

Calculate the energy input in Btu/day;


Pout
Pin

1000 MW

0.40
Pin 2500 MW

Convert unit MW to BTU/day.


1000 kW 24 hr 3412 Btu
Pin 2500 MW
1MW 1day 1kW.hr

Pin 2.05 1011 Btu/day

Calculate the allowable particulate emissions;


lb
0.015
million Btu
The particulate matter emission as per standard is . (from table 1).
PM allow Pin Standard PM
Btu lb 1million Btu
2.05 1011 0.015
day million Btu 106 Btu
lb
3075 or
day
lb 1ton
3075
day 2000 lb
ton
PM allow 1.5375
day

NO x
Calculate the allowable emissions;
lb
1.0
NO x MW.hr
The emission as per standard is . (From table 1).
NO x allow Pout Standard NO x
lb 24 hr 1ton
1000 MW 1.0
MW.hr 1day 2000 lb
ton
NO x allow 12
day
SO x
Calculate the allowable emissions;
lb
SO x 1.4
MW.hr
The emission as per standard is . (From table 1).
SO x allow Pout Standard NO x
lb 24 hr 1ton
1000 MW 1.4
MW.hr 1day 2000 lb
ton
SO x allow 16.8
day

Hg
Calculate the allowable emissions;
lb
0.020
Hg GW.hr
The emission as per standard is . (From table 1).
Hg allow Pout Standard NO x
lb 1GW 24 hr 1ton
1000 MW 0.020
GW.hr 1000 MW 1day 2000 lb
ton
Hg allow 0.00024
day