Sie sind auf Seite 1von 8

MC-49 Series Digital Indicating

Temperature Controller

Features

1. DIN size 48x96mm (DIN 1/8), easy setting temperature with digital switch, easy
setting temperature with digital switch.
2. Option for heater broken alarm, and multi-alarm function.
3. With manual reset to eliminate "offset".
4. With T.C.B. indicator for thermo-couple open.
5. Dust-resist by acrylic covers on front panel.

Copyright 2010-2011 MAXTHERMO-GITTA GROUP CORPORATION


Panel Function

Copyright 2010-2011 MAXTHERMO-GITTA GROUP CORPORATION


Standard Specification

Common Specification
Operating Principle D.C. Potentiometric
Input CA. IC. Pt100 3 Wires
Setting Mode Digit
Main Control

Setting Accuracy Within 1%


Controlling Mode ON-OFF , PD
Proportional
2.5%FS Fixed(PD)
Band
Sensitivity 0.3FS (ON-OFF)
Cycle Time PD ABT. 20 Sec. SSR ABT. 3 Sec.
Output

Relay SPDT AC220V5A(Resistance load)

SSR Driver DC 24V(Resistance 1.5K)


Supply Voltage AC 110/220V 50/60Hz
Tolerance Of Supply Voltage 15% Rated Voltage
Power Consumption 1.6VA
Weight 305g
Panel Mounting Flush Mounting
Ambient Temp. 0~55
Ambient Humidity 45~85%RH
Case Gary ABS
Indicator Specification
Principle Dual Slope System
Digital Indicator

Sample Rate 0.4 Second


K.J Type: 1
Resolution PT100 -99~199: 0.1
PT100 0~399 UP:1
Accuracy 0.5% F.S.
Display 0.5" Red Segment LED
Principle Analog
Deviation
Indicator

Accuracy 2.5% F.S.


Range 40
Sub Control Specification
Output 1C, AC 220V5A Relay
Setting Analog
Sensitivity 10% Of Setting Range
Control Mode ON-OFF
Multi Alarm: Set by DIP Switch Inside
Alarm Mode Heater Broken Alarm:
5A, 10A, 20A, 40A, Set by DIP Switch Inside

Copyright 2010-2011 MAXTHERMO-GITTA GROUP CORPORATION


Standard Range
Input Range
0-199, 0-399,
CA(K)
0-599, 0-799, 0-999
IC(J) 0-199, 0-399
PT100 99, 0-99.9, 0-199
DIP Switch Function In Heater Broken Alarm
DIP
1 2
Range
5A OFF ON
10A ON ON
20A OFF OFF
40A ON OFF
DIP Switch Function In Multi Alarm
IP
1 2 3 4 Scheme
Mode

Low Alarm OFF ON OFF ON

Hi Alarm ON OFF OFF ON

Hi-Low Alarm ON ON OFF ON

Low Alarm Inhibit OFF ON ON OFF

Low Alarm Inhibit


And Hi Alarm ON ON ON OFF

Copyright 2010-2011 MAXTHERMO-GITTA GROUP CORPORATION


External Dimension

Mounting Instruction:

Panel Plate Thickness: 0.8~6.5mm Panel Plate Thickness: 6.5~12.5mm

CT Dimension(mm):

Dimension
Panel Cut-Out(mm):

Copyright 2010-2011 MAXTHERMO-GITTA GROUP CORPORATION


Wiring Diagram

Terminal Arrangement Circuit Diagram For Heater Broken Alarm

Copyright 2010-2011 MAXTHERMO-GITTA GROUP CORPORATION


Order Information

A. Model:
49 Series
B. Indicating mode:
0-None
1-Deviation indicating
3-LED indicating
C. Setting mode:
2-Digit without SUB control
9-Main control with digit, mult alarm with analog
A-Main control with digit, SUB control for multi alarm and heater for broken alarm with analog
K-SUB control for heater broken alarm with analog
D. Control mode:
1-ON-OFF action
2-PD action
3-Main control:ON-OFF action
SUB: ON-OFF action
8-Main control: PD action
SUB control: ON-OFF action
E.Output Mode:
1-Relay
2-SSR driver
3-4~20mA DC(For LED Indicating only)
5-Main control: Relay
SUB control: Relay
7-Main control: SSR driver
SUB control: Relay
F.Input:
K-CA
J-IC
P-PT100

Copyright 2010-2011 MAXTHERMO-GITTA GROUP CORPORATION


Contact

Add: 3C25, Taipei World Trade Center, No. 5, Sec. 5, Hsin Yi Rd. Taipei Taiwan, R.O.C.
Tel: 886-2-27206601 (Rep.)
Fax: 886-2-23455120
E-mail: gitta@ms9.hinet.net
http://www.maxthermo.com

Add: 11F., No.168, Jiankang Rd., Zhonghe Dist., New Taipei City 235, Taiwan (R.O.C.)
Tel: 886-2-22287950 (Rep.)
Fax: 886-2-22286140

Add: 86/132-133 m.7 Samaedum Bangkoontien Bangkok 10150 Thailand.


Tel: +662-415-8318 , +662-417-2548-49
Fax: +662-415-8798
http://www.thaimaximum.com

Copyright 2010-2011 MAXTHERMO-GITTA GROUP CORPORATION