HFC-227ea provides superior fire protection in a wide range of applications from sensitive electrical
equipment to industrial applications using flammable liquids. HFC-227ea is ideal for applications where
clean-up of other media presents a problem, where weight versus suppression potential is a factor,
where an electrically non-conductive medium is needed and where people compatibility is an overriding
factor. When environmental impact is a consideration, HFC-227ea is particularly useful. It has zero ozone-
depleting potential, low global warming potential and a short atmospheric lifetime. These characteristics
make it suitable not only for new installations using Fikes total flooding systems, but also for Halon 1301
replacement applications.
HFC-227ea is an odorless, colorless, liquefied compressed gas. (See Physical Properties Table for additional
information). It is stored as a liquid and dispensed into the hazard as a colorless, electrically non-conductive
vapor that is clear and does not obscure vision. It leaves no residue and has acceptable toxicity for use in
occupied spaces at design concentration. HFC-227ea extinguishes a fire by a combination of chemical and
physical mechanisms. HFC-227ea does not displace oxygen and therefore is safe for use in occupied spaces
without fear of oxygen deprivation.
HFC-227ea systems shall NOT be used on fires involving the following materials:
Chemicals or mixtures of chemicals that are capable of rapid oxidation in the
absence of air. (Examples include: Cellulose Nitrate and Gunpowder)
Reactive metals such as Lithium, Sodium, Potassium, Magnesium, Titanium,
Zirconium, Uranium, and Plutonium
Metal hydrides such as Sodium Hydride and Lithium Aluminum Hydride
Chemicals capable of undergoing auto-thermal decomposition.
(Examples: Organic Peroxides and Hydrazine)
704 SW 10th Street P.O. Box 610 Blue Springs, Missouri 64013-0610 U.S.A.
Phone: 8162293405 www.fike.com
EXPOSURE LIMITATIONS
Maximum Human
Hazard Type Design Concentration
Expose Time
Normally Occupied Space 6.25% to 10.5% 5 minutes
Normally Un-Occupied Space 11.0% to 12.0% 30 seconds
Note: Fike does not recommend HFC-227ea systems to be used in any normally occupied spaces where the design concentration rquired is above 10.5%
Warning: The discharge of clean agent systems to extinguish a fire can result in potential hazard to personnel from the natural form of the clean agent or
from the products of combustion that result from exposure of the agent to the fire or hot surfaces. Unnecessary exposure of personnel either to the natural
agent or to the products of decomposition shall be avoided.
PHYSICAL PROPERTIES
Chemical Name/Formula Heptafluoropropane / CF3CHFCF3
ASHRAE Designation HFC-227ea
CAS Number 431-89-0
Molecular Weight 170.03
Vapor Density @ 25C (77F) and atm, kg/m3 (lb/ft3) 7.148 (0.4462)
Boiling Point, 1 atm, C (F) -16.4 (2.5)
Melting Point, C (F) -131 (-204)
Critical Temperature, C (F) 101.6 (214.9)
Critical Pressure, kPa (psia) 2930 (424.7)
Critical Density, kg/m (lb/ft )
3 3
621 (38.77)
Liquid Density @ 25C (77F), kg/m3 (lb/ft3) 1386 (86.53)
Vapor Density @ 25C (77F) and 1 atm, kg/m3 (lb/ft3) 7.148 (0.4462)
Specific Heat, Liquid (Cp) @ 25C (77F), kJ/Kg- C (Btu/lbF) 1.247 (0.2979)
Specific Heat, Vapor (Cp) @ 25C (77F) kJ/Kg- C (Btu/lbF) and 1 ATM 0.8136 (0.1945)
Vapor Pressure, Saturated @ 25C (77F), kPa (psia) 453.3 (65.7)
Heat of Vaporization @ Boiling Point kJ/Kg (Btu/lb) 132.6 (56.7)
Thermal Conductivity, Liquid @ 25C (77F), W/m- C (Btu/hr-ftF) 0.0533 (0.0308)
Thermal Conductivity, Vapor @ 25C (77F), W/m- C (Btu/hr-ftF) 0.0127 (0.0073)
Viscosity, Liquid @ 25C (77F), cP (lb/ft-hr) 0.2442 (0.5907)
Relative Dielectirc Strength @ 1 atm, 25C (N2=1) 2.00
Solubility of Water in HFC-227ea @ 20C (68F), ppm 600
Ozone Depletion Potential 0.0
Global Warming Potential (based on a 100-yr ITH for CO2, GWP = 1) 2900
DESCRIPTION
Fike Clean Agent Containers are used in fire extinguishing systems to store the Clean Agent until a fire
develops and the agent must be released. The Clean Agent is retained in the container by a Impulse Valve
assembly which contains a fast-acting rupture disc. The disc will be ruptured, and the Clean Agent released,
through the operation of an actuator by an electric signal that is automatically, manually or pneumatically
controlled.
Fike Clean Agent Containers have passed extensive testing by Factory Mutual and Underwriters Laboratory
and are used in installations where 3 to 1045 pounds (2.0 to 474 kg) of HFC-227ea agent is required. Clean
Agent containers can be filled in 1 pound (0.5 kg) increments to their maximum capacity.
SPECIFICATIONS
Fill Range: 40 to 70 lbs/ft3 (630 to 1121 kg/m3)
Fill Increments: 1.0 lbs (0.5 kg)
Container Super - Pressurization Level: 360 psig at 70F (24.8 bar at 21C)
after filling with dry nitrogen
Container Storage Temperature Limitation: 32F (0C) - minimum, 130F (54.4C) - maximum APPROVALS:
Note: If container temperatures exceeding 130F (54.4C), valve will open automatically, this also fulfills the pressure relief UL Listed
valve requirements in accordance with DOT regulations. ULC Listed
FM Approved
Container Construction: Carbon Steel Alloys
Paint Options: Baked enamel finish white (default) or red
Container Ratings: DOT 4BW500
TC 4BWM534
Actuation Methods: Electric/Pneumatic/Manual
704 SW 10th Street P.O. Box 610 Blue Springs, Missouri 64013-0610 U.S.A.
Phone: 8162293405 www.fike.com
CONTAINER DATA/SPECIFICATIONS
Dimensions
Container Fill range
Valve Size Tare Weight (approximate)
Mounting
Size Minimum Maximum Diameter Height Position
P/N
Lb. (L) lbs. (kg) lbs. (kg) IN (mm) lbs. (kg) IN (mm) IN (mm)
5 3 5 1 11 4.2 16.2 Upright
70-272
(2) (2.0) (2.5) (25) (5.0) (102) (411.5) (Valve Up)
10 6 10 1 15 4.2 27.24 Upright
70-273
(4) (3.0) (4.5) (25) (6.8) (102) (691.9) (Valve Up)
20 12 21 1 22 7.0 22.50 Upright -
70-263
(8.5) (5.5) (9.5) (25) (10.0) (178) (571.5) Horizontal
35 22 38 1 32.5 7.0 33.75 Upright -
70-264
(15) (10.0) (17.0) (25) (14.7) (178) (857.3) Horizontal
60 39 68 1 52.5 10.75 28.13 Upright -
70-265
(27) (18.0) (30.5) (25) (23.8) (273) (714.4) Horizontal
100 63 108 1 77 10.75 39.63 Upright
70-266
(44) (28.5) (49.0) (25) (34.9) (273) (1006.5) (Valve Up)
150/150i 87 150 3 118/114 20.0 24.25
70-267 Upright/Inverted
(61) (39.5) (68.0) (80) (53.5/51.7) (508) (616.0)
215 124 216 3 146 20.0 30.13 Upright
70-268
(88) (56.5) (98.0) (80) (66.2) (508) (765.2) (Valve Up)
375 217 378 3 213 20.0 43.38 Upright
70-269
(153) (98.5) (171.5) (80) (96.6) (508) (1101.7) (Valve Up)
650 378 660 3 373 24.0 50.50 Upright
70-270
(267) (171.5) (299.0) (80) (169.2) (610) (1282.7) (Valve Up)
1000 598 1045 3 535 24.0 71.88 Upright
70-271
(423) (271.5) (474.0) (80) (242.7) (610) (1825.6) (Valve Up)
2 of 7
ITEMS SUPPLIED WITH CONTAINER ASSEMBLY
Item Number Description Data Sheet
1 Victaulic Coupling & Nipple IV.1.19.01
2 Impulse Valve IV.1.14.01
3 Pressure Gauge IV.1.13.01
4 Liquid Level Indicator (LLi) C.1.40.01
5 LLi Boss (see note 1) n/a
6 Nameplate (see note 2) n/a
7 Siphone Tube (see note 3) n/a
8 Mounting Straps & Brackets IV.1.18.01
Notes:
1) 100 thru 1000 lb. (44 thru 423 L) containers are equipped with a LLi Boss.
2) Fike nameplate provides the information that is specific to each container: Assembly
and serial number of the container, weight information: tare, gross and agent and
installation, operation and safety information. All containers filled either by the factory
or by an Approved Initial Fill Station are provided with a name plate bearing the UL & FM
markings.
3) Fike Clean Agent containers [except the 150i (Inverted)] are equipped with a siphon
tube. The 20, 35 & 60 lb. containers have bent siphon tubes and the 5, 10 and 100
1000 lb. containers have straight siphon tubes. All containers with siphon tubes can be
mounted upright. The 20, 35 & 60 lb containers can also be mounted horizontally. The
150 container can only be mounted upright and the 150i can only be mounted inverted.
3 of 7
OPTIONAL ITEMS FOR CONTAINER
The following container accessory items must be ordered separately.
ACTUATION COMPONENTS
Electric / Manual Actuation Impulse Valve Operator (IVO) (For detailed information, refer to the IVO Data Sheet IV.1.09.01)
Pneumatic Actuation Impulse Valve Pneumatic Operator (IVPO) (For detailed information, refer to the IVPO Data Sheet IV.1.10.01)
ACTUATION METHODS
Clean Agent containers with an Impulse Valve can be actuated by the following methods:
Method 1 Electric Actuation Single Container System w/ IVO & IRM
Method 2 Electric Actuation Multi-Containers System w / IVO & IRM
Method 3 Electric & Pneumatic Actuation Two Container System w/ IVO & IVPO
Method 4 Electric & Pneumatic Actuation Multi Container System w/ IVO & IVPO
For detailed information on actuation methods, refer to the Impulse Valve Operator (IVO) data sheet IV.1.09.01.
These devices provide the force required to extend a pin that will open the rupture disc, allowing the agent to be released from the
container.
4 of 7
LOW PRESSURE SWITCH
The Low Pressure Switch provides a means to continuously monitoring
the container pressure for a low-pressure condition.
If the pressure inside the container drops below 288 psig (1986 kPa),
the switch contacts will transfer and invoke a trouble indication on the
control panel.
The Low Pressure Switch (P/N 02-12533) has a single pole, double-throw
switch that can be wired for normally open or normally closed.
For detailed information, refer to the Low Pressure Switch Data Sheet
IV.1.13.01.
INSTALLATION
The system installation must comply with the requirements of this
manual; NFPA 2001, latest edition; all applicable local codes, regulations,
and standards and the authority having jurisdiction (AHJ).
Warning: DO NOT start system installation until the final design of the total system has been verified using Fikes Engineered Flow
Calculation.
Warning: The Actuator shall always be the last component installed on a Fike Clean Agent Fire Suppression system to avoid accidental
discharge.
5 of 7
Container Floor Area
Container w/ Plate
Total Container w/ Plate
Container Floor Container Floor Floor
Container Size Weight 1/4: x 2 x 2 plate
Area Loading Loading
lb. (L) lbs. (kg) (6.4mm x 0.6m x 0.6m
ft2 (m2) lbs/ft2 (kg/m2) lbs/ft2 (kg/m2)
see note 1 plate)
see note 2
ft2 (m2)
1000 (423) 1386 (628) 3.14 (0.29) 508 (2493) 4.0 (0.36) 404 (2037)
650 (267) 913 (41) 3.14 (0.29) 333 (1636) 4.0 (0.36) 267 (1467)
375 (153) 527 (239) 2.18 (0.20) 277 (1368) 4.0 (0.36) 156 (788)
215 (88) 328 (148) 2.18 (0.20) 170 (840) 4.0 (0.36) 98 (495)
150 (61) 283 (128) 2.18 (0.20) 138 (680) 4.0 (0.36) 81 (406)
100 (44) 164 (74) 0.63 (0.06) 294 (1400) 4.0 (0.36) 52 (262)
60 (27) 106 (48) 0.63 (0.06) 190 (908) 4.0 (0.36) 36 (180)
35 (15) 51 (23) 0.27 (0.03) 256 (115) 4.0 (0.36) 23 (114)
20 (8.5) 37 (17) 0.27 (0.03) 156 (72) 4.0 (0.36) 16 (83)
10 (4) 23 (11) 0.10 (0.009) 250 (1278) 4.0 (0.36) 12 (60)
5 (2) 15 (7) 0.10 (0.009) 160 (833) 4.0 (0.36) 10 (49)
Notes:
1) Total container weight is based on container tare weight + maximum fill weight
2) Total container weight + 22.5 lbs (10.2 kg) added for 1/4 x 2 x 2 (6.4mm x 0.6m x 0.6m) plate used to calculate container with plate floor loading
6 of 7
RECHARGE ITEMS 1 IN (25) & 3 IN (80) VALVE (Must Order Separate)
After a system has been discharged, the following items must be replaced before a container can be recharged. For a detailed procedure
on recharging a Fike container w/ an Impulse Valve refer to Fikes Recharge Manual (p/n 06-290).
Note: 1 IN Recharge Kit is used on 5, 10, 20, 35, 60 & 100 lb. (2, 4, 8, 15, 27 & 44 L) containers
3 IN Recharge Kit is used on 150, 150i, 215, 375, 650 & 1000 lb. (61, 61i, 88, 153, 267 & 423 L) containers
INDUSTRIES SERVED
Automobile Manufacturing
Industrial Plants
Process Plants
Refineries/Chemical Plants
Marine/Off-shore
INTRODUCTION
Flammable liquid storage facilities are in many industrial and chemical plants as well as
production facilities that use flammable liquids in various processes. These facilities store the
flammable liquids used in processes such as painting, lubrication, fuel, and oil in areas called
Flammable Liquid Storage Areas. These areas are segregated due to the special and careful
handling required when using the flammable liquid.
In a fire suppression system, FM-200 is stored as a liquid in FM-200 storage containers. When called upon by an approved control panel,
the FM-200 will flow through the length of piping required and will immediately change from a liquid to a vapor as it is released through
the discharge nozzle.
To provide proper fire protection for a flammable liquid storage facility, it is imperative that a well-designed, fast response, and trouble
free automatic fire detection system be installed. In many cases vapor or flame detection will be used. Advise should be sought when
designing the detection system due to the amount of detectors available and the conditions in which they operate.
The example on the next page walks through a flammable liquid storage facility designed with a Fike FM-200 system.
EXAMPLE SYSTEM
This example walks through the design for a fire detection and suppression system in a Flammable liquid storage facility.This room
contains barrels of diesel fuel, gasoline, and has storage cabinets with various fuels and amounts of flammable liquid. The room being
protected is 20 X 20 in dimension with a 10 foot ceiling. The first step is to determine the quantity of FM-200 required to protect the
hazard. The quantity of FM-200 required is dependent on the fuels being protected. In order to determine the FM-200 concentration
required, an evaluation of the flammable liquids present must be performed. Once all of the fuels have been identified, the required
FM-200 concentration is determined by choosing the fuel with the highest design concentration required. The design concentration for
each fuel is determined by performing a cup burner test as described in NFPA 2001, Appendix B. A 30% safety factor is then added to the
cup burner concentration, which is the design concentration for that fuel. Contact Fike for design concentrations of particular flammable
liquids. For this example, gasoline requires the highest concentration of FM-200 at 7.5% design concentration at the minimum expected
room temperature of 50F.
704 SW 10th Street P.O. Box 610 Blue Springs, Missouri 64013-0610 U.S.A.
Phone: 8162293405 www.fike.com
This hazard will be protected using a pre-engineered FM-200 system approach with two 180 nozzles. I have used the pre-engineered
approach because I am protecting a single hazard with a single cylinder and I wanted to save engineering time doing the system design.
There are benefits of designing the system engineered over pre-engineered and they are described in the FM-200 Design Guide.
The next step in designing the system is to layout the system nozzles in the protected space. As mentioned before the room requires 154
pounds of FM-200 to protect the hazard. I have decided to use two 180 degree nozzles mounted on the same wall to protect this space.
I have used 180 degree nozzles to minimize the amount of piping required and to keep the piping away from air-handling units and other
equipment in the center of the room. A diagram of the container and piping isometric is shown for your reference.
The next step is to lay out the detection and control system for this facility. As mentioned before, Flame detectors will be used for
detection in this facility. The reason for choosing Flame detectors is that they are good at picking up small, flaming fires that develop
rapidly. I am not going to discuss detector spacing of the Flame detectors due to the wide range of products available and protection
objectives of the system. Fike always recommends that UL Listed and/or FM Approved detectors be used. Consult the detector
manufacturer and Fike for detector spacing limitations.
The Fike SHP PRO conventional control system will be used to provide reliable detection. A layout of the control panel with accessories is
shown on the hazard layout. An equipment list for this hazard is shown for your reference on the next page.
EQUIPMENT LIST
Below is an equipment list for the FM-200 system installed in the flammable liquid stroage room on the diagram above.
FM-200
Version 2.1
This SDS adheres to the standards and regulatory requirements of the United States and may not meet the regulatory
requirements in other countries.
Product name : FM-200
Tradename/Synonym : FE-227
2-Hydroperfluoropropane
Propane, 1,1,1,2,3,3,3-Heptafluoro-
HFC-227eaHP
2-Hydroheptafluoropropane
Heptafluoropropane
2-H-heptafluoropropane
1,1,1,2,3,3,3-Heptafluoropropane
R-227
R227
HFC-227ea
Manufacturer : DuPont
1007 Market Street
Wilmington, DE 19898
1/9
Material Safety Data Sheet
FM-200
Version 2.1
Eyes : Contact with liquid or refrigerated gas can cause cold burns and frostbite.
Inhalation : Misuse or intentional inhalation abuse may cause death without warning
symptoms, due to cardiac effects.
Other symptoms potentially related to misuse or inhalation abuse are:
Anaesthetic effects, Light-headedness, dizziness, confusion,
incoordination, drowsiness, or unconsciousness, irregular heartbeat with a
strange sensation in the chest, heart thumping, apprehension, feeling of
fainting, dizziness or weakness.
Vapours are heavier than air and can cause suffocation by reducing oxygen
available for breathing.
Carcinogenicity
None of the components present in this material at concentrations equal to or greater than 0.1% are listed by
IARC, NTP, or OSHA, as a carcinogen.
Eye contact : In case of contact, immediately flush eyes with plenty of water for at least 15
minutes. Consult a physician if necessary.
Inhalation : Remove from exposure, lie down. Move to fresh air. Keep patient warm and
at rest. Artificial respiration and/or oxygen may be necessary. Consult a
physician.
2/9
Material Safety Data Sheet
FM-200
Version 2.1
General advice : Never give anything by mouth to an unconscious person. When symptoms
persist or in all cases of doubt seek medical advice.
Safeguards (Personnel) : Evacuate personnel, thoroughly ventilate area, use self-contained breathing
apparatus. Keep upwind of leak - evacuate until gas has dispersed.
Spill Cleanup : Ventilate area using forced ventilation, especially low or enclosed places
where heavy vapors might collect.
3/9
Material Safety Data Sheet
FM-200
Version 2.1
Storage : Valve protection caps and valve cutlet threaded plugs must remain in place
unless container is secured with valve outlet piped to use point.
Do not drag, slide or roll cylinders. Never attempt to lift cylinder by its cap.
Use a check valve or trap in the discharge line to prevent hazardous back
flow into the cylinder. Cylinders should be stored upright and firmly secured to
prevent falling or being knocked over.
Separate full containers from empty containers. Keep at temperature not
exceeding 52C. Do not store near combustible materials. Keep container
tightly closed in a dry and well-ventilated place. Store in original container.
Protect from contamination. Avoid area where salt or other corrosive
materials are present.
Engineering controls : Use only with adequate ventilation. Keep container tightly closed.
Eye protection : Safety glasses with side-shields Additionally wear a face shield where the
possibility exists for face contact due to splashing, spraying or airborne
contact with this material.
Skin and body protection : Where there is potential for skin contact, have available and wear as
appropriate, impervious gloves, apron, pants, jacket, hood and boots.
Exposure Guidelines
Exposure Limit Values
1,1,1,2,3,3,3-Heptafluoropropane
AEL * (DUPONT) 1,000 ppm 8 & 12 hr. TWA
4/9
Material Safety Data Sheet
FM-200
Version 2.1
* AEL is DuPont's Acceptable Exposure Limit. Where governmentally imposed occupational exposure limits which
are lower than the AEL are in effect, such limits shall take precedence.
Incompatibility : Alkali metals Alkaline earth metals, Powdered metals, Powdered metal salts
Inhalation : dog
Cardiac sensitization
FM-200
Version 2.1
FM-200
Version 2.1
Environmental Fate
FM-200
Biodegradability aerobic : 1 % OECD Test Guideline 301
Not readily biodegradable.
7/9
Material Safety Data Sheet
FM-200
Version 2.1
Class : 2.2
Labelling No. : 2.2
IMDG UN number : 3296
Proper shipping name : Heptafluoropropane
Class : 2.2
Labelling No. : 2.2
SARA 313 Regulated : SARA 313: This material does not contain any chemical components with
Chemical(s) known CAS numbers that exceed the threshold (De Minimis) reporting levels
established by SARA Title III, Section 313.
California Prop. 65 : Chemicals known to the State of California to cause cancer, birth defects or
any other harm: none known
Health : 1
Flammability : 0
Reactivity/Physical hazard : 0
PPE : Personal Protection rating to be
supplied by user depending on use
conditions.
The information provided in this Safety Data Sheet is correct to the best of our knowledge, information and belief at
the date of its publication. The information given is designed only as a guidance for safe handling, use, processing,
8/9
Material Safety Data Sheet
FM-200
Version 2.1
storage, transportation, disposal and release and is not to be considered a warranty or quality specification. The
information relates only to the specific material designated and may not be valid for such material used in combination
with any other materials or in any process, unless specified in the text.
9/9
C L CE L A E N A NA G A E GN E T N TF I FR I E R ES U S P U P P R P E R S E S S I SO I N O N
ON THE MARKET
C L E A N A G E N T F I R E S U P P R E S S I O N
FIRE SUPPRESSION
Simply said, ECARO-25 is the best way to suppress fires and protect your high-value assets and
business continuity.
All clean agents must remain in the protected space for a specified period of time in order to extinguish a
fire. Thanks to the unique physical properties of the ECARO-25 agent, the hold time in a 5000 cubic foot
enclosure is 27 minutes, compared to a 12 minute hold time for an HFC-227ea system and a 10 minute hold
time for a FK-5-1-12 system. ECARO-25 offers a far superior hold time, allowing more time for trained
personnel response and minimal chance for any fire re-ignition.
In addition, ECARO-25 requires 10% less agent per cubic foot/meter than HFC-227ea systems and
37% less clean agent per cubic foot/meter than FK-5-1-12.
HFC-227ea FK-5-1-12
156lb protects 5000 cubic feet 156lb protects 4550 cubic feet 156lb protects 3650 cubic feet
The superior properties of our unique system allow you to utilize small diameter piping over long distances,
making it easier and less expensive to design your clean agent pipe network. With ECARO-25, you
spend less money on the agent, piping and installation making it the most cost-effective clean agent fire
suppression system available today.
Safe for use where people are present, Fikes clean agent system removes heat and breaks up the fire
at the molecular level. And because it discharges as a gas, it leaves no residue and doesnt require
costly clean-up like water or dry chemical systems. Perhaps the most well respected and globally
recognized of all clean agent fire suppressants, HFC-227ea applications range from computer and
electronic rooms to museums and military vehicles.
Gaseous chemical suppression systems (clean agent systems) have been used for more than
50 years to protect electronics and other valuables that are susceptible to the damaging effects of
water-based suppression systems. Clean agent systems such as ECARO-25, HFC-227ea, and
DuPont FM-200, are superior to water and dry chemicals in virtually every way:
Clean agents are not electrically Because they act quickly, clean
conductive, and do not damage agents greatly reduce the amount
electronics water is a great of smoke and soot damage
conductor and ruins electronics! caused by a fire.
The simplicity of the valve means fewer parts to maintain and greater reliability. As a result of Fikes advanced
rupture disc technology, there is less pressure loss. That efficiency translates into a fire protection system with
longer pipe run capability and flexible installation options.
The Impulse Valve can be configured to operate in multiple ways electric, pneumatic or a combination of
both. The Impulse Valve is capable of firing up to 6 cylinders on a single releasing circuit making systems
with this advanced actuation more cost-effective to design and install.
Fike and Fike Corporation, AXIUS, ECARO-25 and Impulse Technology are trademarks
or registered trademarks of Fike Corporation. DuPont, FM-200 and FE-25 are trademarks or
registered trademarks of E.I. DuPont de Nemours and Company.
WWW.FIKE.COM Copyright 2012, Fike Corporation. All rights reserved. Form No. B9125 1212
Printed in the U.S.A.
I N T E L L I G E N T S U P P R E S S I O N C O N T R O L S Y S T E M
UNPRECEDENTED SPEED
ULTIMATE POWER
EXTREME iNTELLIGENCE
I N T E L L I G E N T S U P P R E S S I O N C O N T R O L S Y S T E M
S P L I T - S E C O N D S P E E D
C H E E T A H X i I N T E L L I G E N C E
Doors Elevators
devices
Address / configure
Releasing of Clean Agent Suppression, Security / CCTV / Building devices via C-Linx
Carbon Dioxide Suppression, Management Awareness software
Watermist, Foam, and Sprinkler / Pre-Action
Handheld training
panel for new
FIRE SUPPRESSION technicians
SOLUTIONS THAT FIT
YOUR NEEDS CHEETAH Xi PROTECTS ANY
OCCUPIED SPACE
The Cheetah Xi gives you the freedom to Whether youre protecting a new
design the ideal system for your facility. building or retrofitting an existing
The 1016 system comes standard with two space, Cheetah Xi has the flexibility
Signaling Line Circuits (expandable to four to address all your requirements.
loops) that support 254 devices each. And you
Data Centers
can network up to 128 Cheetah Xis and /or the
Telecommunications
Fike CyberCat fire alarm panels, for up to any
Generator Rooms
combination of 130,048 sensors and modules!
Cheetah Xi 50 Internet Service Providers
Mining
The Cheetah Xi 50 intelligent fire suppression system, brings all that
Museums
power and technology to stand-alone or smaller business applications.
Warehouses
Flexible, fast and efficient, the Cheetah Xi 50 is the economical choice.
Office Buildings
Industrial Facilities
Same Speed. Same Intelligence. Same Great Value.
I N T E L L I G E N T S U P P R E S S I O N C O N T R O L S Y S T E M
C H E E T A H X i F L E X I B I L I T Y
Cheetah Xi gives you the freedom to design the ideal system for your facility. You can easily control just
a few devices or up to 130,048 devices. Plus, you can mix and match sensors and modules in virtually
any combination needed for your specific application. With Cheetah Xi, the possibilities are endless.
CHEETAH Xi 50
1 Signaling Line
Circuits (SLC)
Supports up to
50 devices
Any combination of sensors and modules
Supports up to 31 Remote Annunciators
E X T R E M E S A F E T Y
I N T E L L I G E N T S U P P R E S S I O N C O N T R O L S Y S T E M
C H E E T A H X i F L E X I B I L I T Y
E X T R E M E P E R F O R M A N C E
I N T E L L I G E N T S U P P R E S S I O N C O N T R O L S Y S T E M
Cheetah Xi, C-Linx, ECARO-25, SHP PRO, MicroMist, CyberCat, Fike and Fike
Corporation are trademarks or registered trademarks of Fike Corporation. FAAST Fire
Alarm Aspiration Sensing Technology is a registered trademark of System Sensor.
All other trademarks, trade names or company names referenced herein are the
property of their respective owners.