Sie sind auf Seite 1von 5

SUMMARY

CLIENT: M/s. MANIPAL UNIVERSITY JAIPUR


CONSULTANT : SOBHA LTD
SECTION : ELECTRICAL
PROJECT : IT Infra @ MUJ Admin Block , JAIPUR
SUBJECT : INTERNAL ELECTRICAL WORKS - SUMMARY

SL.No. SUMMARY AMOUNT REMARKS

1.00 LAB ELECTRICAL WORKS 49,709

2.00 MISCELLANEOUS WORKS 3,117

TOTAL FOR ELECTRICAL WORKS 52,826

VAT @ 85% x 14 .50% on Total value 6,511

ST @ 70% x 15% on Total Value 5,547

Grand Total 64,884

NOTES :
1) If any changes in the Taxes it will be claimed as per actual.

Page -1 / 5
CLIENT: M/s. MANIPAL UNIVERSITY, JAIPUR
CONSULTANT : SOBHA LTD
SECTION : ELECTRICAL
PROJECT : IT Infra @ MUJ Admin Block , JAIPUR
SUBJECT : ELECTRICAL WORKS - SUMMARY

Sl.
PARTICULARS UNIT QUANTITIES RATE AMOUNT REMARKS
Nos.

INTERNAL WIRING
Supply & Installation, Testing and Commissioning
of point wiring using 2 x 1.5 + 1 R x 1.0 sqmm
PVC insulated FRLS multi stranded 1100V grade
copper wires drawn in 20mm dia 2mm thick PVC
FRLS conduit including all conduit accessories
such as bends, Junction boxes etc. The wiring
( A) - shall be done in complete looping in system. The
1.00 switches used shall be moulded on Clipsal
/Approved Make integral GI box with clear
earthing facility. The wiring shall be complete
with ceiling, switches and all consumables,
connectors etc., The lighting circuit number to be
placed in switch plate with sticker and ferrules .
(Colour coding of wiring should be adopted)

One light point controlled by one switch


1.1 considered as primary point. (Single Height -
area) {7 meters}
Supply Nos. 5.00 681.87 3,409.35
Installation Nos. 5.00 166.55 832.75
-
For every additional secondary point. (Single
1.2 -
height) {6meters} (General Lighting)
Supply Nos. 5.00 430.09 2,150.45
Installation Nos. 5.00 138.14 690.70
-
One Fan controlled by One no. of One way
1.4 -
switch with step type electronic regulator.
Supply Nos. 4.00 1,202.09 4,808.36
Installation Nos. 4.00 320.36 1,281.44
-
Supply & Installation of 3 Core 2.5 Sqmm
1100V Flexible Copper cable in white and
1.50 black colour for UPS in existing tray, wireways, -
conduit and furniture. (UPS / RP / LIGHT
circuit)
Supply Mtrs. 111.20 62.70 6,972.24
Installation Mtrs. 111.20 12.74 1,416.69
-
2.10 10 A SP Pole MCB 'C' -
Supply Nos. 4.00 527.00 2,108.00
Installation Nos. 4.00 29.00 116.00
-
-
Supply and installation of 1no. Of 6 amps 3 pin
socket controlled by 1no. Of 6 amps SP switch
2.04 -
with 3module GI box and accessories etc.,
(Raw power points in Utility)
Supply Nos. 220.43 -
Installation Nos. 58.78 -
-
Supply and installation of 1no. Of 6/16 amps
3/5 pin socket controlled by 1no. Of 16 amps
2.01 SP switch with 3module GI box and -
accessories etc., (Raw power points in
corridor and water cooler)
Supply Nos. 269.42 -
Installation Nos. 70.54 -
-
Supply & Installation of 2 NO. of 6A Socket
2.02 controlled by 1 NO. of 6A SP switch on UPS -
with GI box and accessories etc.,
Supply Nos. 14.00 511.40 7,159.60
Installation Nos. 14.00 83.27 1,165.78
-
Supply & Installation GI box for VGA outlet
1.20 -
Projector Points
Supply No's 14.00 79.36 1,111.04
Installation No's 14.00 25.47 356.58
-
Supply & Installation of 25mm dia 2mm thick
PVC FRLS conduit (excluding wiring) with
2.70 -
clamps, bends, collar, suspensions, junction
box etc.
Supply Mtrs. 174.00 42.36 7,370.64
Installation Mtrs. 174.00 20.26 3,525.24

Installation of light fixtures Nos. 10.00 393.00 3,930.00


Installation of Fans Nos. 4.00 326.00 1,304.00

TOTAL PART - B 49,708.86

Page -2 / 5
CLIENT: M/s. MANIPAL UNIVERSITY, JAIPUR
CONSULTANT : SOBHA LTD
SECTION : ELECTRICAL
PROJECT : IT Infra @ MUJ Admin Block , JAIPUR
SUBJECT : MISCELLANEOUS WORKS - SUMMARY

Sl.
PARTICULARS UNIT QUANTITIES RATE AMOUNT REMARKS
Nos.

Wall chasing and refilling with cement mortar for wall


1.1 RMtrs. 31 102 3,117
conduiting ( 2"x2") with wire mesh

TOTAL 3,117

Page -3 / 5
CLIENT: M/s. MANIPAL UNIVERSITY, JAIPUR -
CONSULTANT : SOBHA LTD
SECTION : ELECTRICAL
PROJECT : IT Infra @ MUJ Admin Block , JAIPUR
SUBJECT : MISCELLANEOUS WORKS - SUMMARY

Sl.No Description Manufacturer For Estimation

1 LT Cables/HT Cable KEI/Polycab

2 LT Cable End terminations


a) Metal Glands HMI/SMI
b) PVC Glands Hensel
c) Lugs Dowells/HEX

4 DISTRIBUTION BOARDS MDS- Legrand / Schneider

5 MCCB & MCB MDS- Legrand / Schneider


ELCB/RCCB/RCBO & SURGE PROTECTION
6 MDS- Legrand / Schneider
DEVICES
7 INDUSTRIAL PLUG AND SOCKET MDS- Legrand

Wheather Proof INDUSTRIAL PLUG AND SOCKET


8 Hensel / Eqv
& Enclosures

9 PVC Rigid Conduits & accessories -FRLS grade Atul/Precision

10 PVC - flexible conduits. Finolex/Precision

11 PVC TRUFF Precision/Salzer

12 MS/GI CONDUIT & Accessories AKG/Bharat

Single core multistrand flexible copper wiring


13 KEI/ Cobra
cables up to 6sqmm size - Insulation grade FRLS

Single core/Multi core multistrand flexible


14 KEI/ Cobra
copper grade PVC insulated cables

Switches, sockets, GI Boxes and Accessories


15 Salzer- White Colour
( Common area & Room )

16 Metal ( MS Powder coated/GI) Cable Tray Pushpak

Metal ( MSPowder coated/GI) Race ways/Wire


17 Pushpak
Ways and DRAW BOX

Page -4 / 5
CLIENT: M/s. MANIPAL INTEGRATED SERVICES Date: 22-01-2014
CONSULTANT : SOBHA LTD
SECTION : ELECTRICAL
PROJECT : NEW ACADEMIC BLOCK ( PHASE 1 ) FOR MANIPAL UNIVERSITY, JAIPUR
SUBJECT : DB BREAKER UP (PHASE 1)

SL.
DESCRIPTION GF 1F 2F 3F TF Total
No

3, 4Way, 7 segment DB (Common area General Lighting DB)


Incomers 1No. 25A, 4P, 10kA,MCB 'C' Curve
- - - - - 0
Phase outgoing 3Nos. 25A, 30mA, DP, RCCB
12Nos. Of outgoing 10A SP MCB With 'C' Curve

3, 6Way, 7 segment DB (Common area General Lighting DB)


Incomers 1No. 25A, 4P, 10kA,MCB 'C' Curve
3 2 2 2 - 9
Phase outgoing 3Nos. 25A, 30mA, DP, RCCB
18Nos. Of outgoing 10A SP MCB With 'C' Curve

3, 4Way, 7 segment DB (Common area Emergency Lighting DB)


Incomers 1No. 25A, 4P, MCB 'C' Curve
- - - - - 0
Phase outgoing 3Nos. 25A, 30mA, DP, RCCB
12Nos. Of outgoing 10A SP MCB With 'C' Curve

3, 8Way, SPN DB (Common area Emergency Lighting DB)


Incomers 1No. 25A, 30mA, DP, RCCB 2 1 1 1 - 5
Class 6Nos. Of outgoing 10A SP MCB With 'C' Curve
Room /
I
Common 3, 4Way, 7 segment DB (Common area RPDB)
area Incomers 1No. 40A, 4P, MCB 'C' Curve
- - - - - 0
Phase outgoing 3Nos. 40A, 30mA, DP, RCCB
12Nos. Of outgoing 16A SP MCB With 'C' Curve

3, 6Way, 7 segment DB (Common area RPDB)


Incomers 1No. 40A, 4P, MCB 'C' Curve
2 2 - 1 - 5
Phase outgoing 3Nos. 40A, 30mA, DP, RCCB
18Nos. Of outgoing 16A SP MCB With 'C' Curve

3, 8Way, 7 segment DB (Common area RPDB)


Incomers 1No. 63A, 4P, MCB 'C' Curve
- - 2 2 - 4
Phase outgoing 3Nos. 63A, 30mA, DP, RCCB
24Nos. Of outgoing 16A SP MCB With 'C' Curve

1, 8Way, SPNDB (Dry Snacks / Coffee DB)


Incomers 1No. 32A, DP, MCB 'C' Curve
1 2 - - - 3
6Nos. Of outgoing 16A SP MCB With 'C' Curve

3, 6Way, 7 segment DB (UPS DB)


Incomers 1No. 63A, 4P, MCB 'C' Curve
1 1 1 1 - 4
Phase outgoing 3Nos. 63A, 30mA, DP, RCCB
18Nos. Of outgoing 16A SP MCB With 'C' Curve
UPS
II
DB'S 3, 12Way, 7 segment DB (UPS DB)
Incomers 1No. 63A, 4P, MCB 'C' Curve
- - - 1 - 1
Phase outgoing 3Nos. 63A, 30mA, DP, RCCB
36Nos. Of outgoing 16A SP MCB With 'C' Curve

3, 6Way, 7 segment DB (LAB DB)


Incomers 1No. 63A, 4P, MCB 'D' Curve
III LAB DB'S 2 2 2 - - 6
Phase outgoing 3Nos. 63A, 30mA, DP, RCCB
18Nos. Of outgoing 16A SP MCB With 'D' Curve

Das könnte Ihnen auch gefallen