NOTES:
1. AHU SHALL CONSIST OF A FAN SECTION, DX COIL SECTION, PRE & FINAL FILTER SECTION AND MIXING PLENUM SECTION. REFER TO FLOOR PLANS FOR REQUIRED CONFIGURATION.
19
2. TOTAL FAN STATIC PRESSURE IS 1405 Pa. FAN SIZING INCLUDES A 250 Pa STATIC PRESSURE LOSS FOR DIRTY FILTERS.
3. PROVIDE VARIABLE FREQUENCY DRIVE FOR FAN MOTOR IN ACCORDANCE WITH PROJECT SPECIFICATION G7D-2131-00, REFER TO ELECTRICAL DRAWINGS FOR REQUIREMENTS. THIS SCOPE SHALL BE INCLUDED IN THE S17104-554455 CONTRACT.
6. AIR HANDLING UNIT CAPACITY BASED ON OUTSIDE AMBIENT CONDITIONS: 47C DB / 22C WB
7. COORDINATE UNIT SPLITS WITH 1200mm WIDE BY 2100mm HIGH DOOR. UNIT WILL NEED TO BE INTALLED THRU THIS DOORWAY. BREAKDOWN UNIT AS REQUIRED TO INSTALL AHU IN MECH. ROOM.
17
AIR COOLED CONDENSING UNIT SCHEDULE
CAPACITY COMPRESSORS FANS UNIT DIMENSIONS UNIT
AMBIENT MINIMUM MAXIMUM RIGGING UNIT
AT DESIGN UNIT ELECTRICAL UNIT ELECTRICAL STARTER
TAG NUMBER AHU SERVED MAKE MODEL CONDITIONS AIR REFRIG. CIRCUIT OVER CURR. RLA LRA LENGTH WIDTH HEIGHT WEIGHT DISCONNECT ACCESSORIES / COMMENTS
NUMBER CHARACTERISTICS NUMBER HP CHARACTERISTICS
AMPACITY PROTECTION RESPONSIBILITY RESPONSIBILITY
KW C AMPS AMPS VOLTS PHASE HERTZ VOLTS PHASE HERTZ MM MM MM Kg.
16
ACCU-A2110-01 AHU-A2110-01 ZAMIL CAX024 91.3 51.7 R134A 68.6 90 2 COMP. #1:30.1 COMP. #1:225 460 3 60 2 1.5 EA 460 3 60 2200 1100 1800 821 SEE ELECTRICAL SEE ELECTRICAL COPPER FIN / COPPER TUBE CONDENSING
COMP. #2: 25.0 COMP. #2: 173 FOR REQUIREMENTS FOR REQUIREMENTS COIL
15
NOTES:
2. AIR COOLED CONDENSING UNIT CAPACITY BASED ON OUTSIDE AMBIENT CONDITIONS: 33C DB / 29C WB
14
FAN SCHEDULE
STATIC ELECTRICAL RIGGING UNIT
AIRFLOW MOTOR UNIT STARTER
TAG NUMBER AREA SERVED MAKE MODEL TYPE PRESSURE CHARACTERISTICS WEIGHT DISCONNECT ACCESSORIES / COMMENTS
RESPONSIBLITY RESPONSIBLITY 13
l/s Pa kW (HP) DRIVE VOLTS PHASE HERTZ kg
ARRANGEMENT 10 UPBLAST CONFIGURATION, NEMA 4X HEAVY DUTY DISCONNECT, 24V MOTORIZED OPPOSED BLADE OUTLET DAMPER, HOLD SEE
OP. BLDG. A2110 SEE ELECTRICAL FURNISH WITH
EAF-A2110-01 GREENHECK 9-BISW-41 BISW 510 500 1.1 (1-1/2) BELT 460 3 60 80 HI PRO POLYESTER COATING ON ENTIRE UNIT, WEATHER HOOD, EXTENDED LUBRICATION LINES, BASE RAIL WITH SPRING ISOLATORS NOTE #2
PREP RM HOOD FOR REQUIREMENTS UNIT
DRAIN CONNECTION WITHOUT PLUG, SEALED HOUSING FOR OUTDOOR USE
OP. BLDG. A2110 SEE ELECTRICAL FURNISH WITH NEMA 12 DISCONNECT, 24V MOTORIZED OUTLET DAMPER, PERMATECTOR COATING ON ENTIRE UNIT, MOTOR COVER, EXTENDED LUBRICATION
EAF-A2110-02 GREENHECK BSQ-90-7 IN-LINE 365 315 0.56 (3/4) BELT 460 3 60 60 12
LOCKER/TOIL. AREA FOR REQUIREMENTS UNIT LINES, SPRING HANGING ISOLATORS & BRACKET
ARRANGEMENT 10 TH DISCHARGE POSITION, NEMA 12 DISCONNECT, 24V MOTORIZED OPPOSED BLADE OUTLET DAMPER, HI PRO POLYESTER
OA INTAKE SEE ELECTRICAL FURNISH WITH
EAF-A2110-03 GREENHECK 7-BISW-41 BISW 115 500 0.37 (1/2) BELT 460 3 60 70 COATING ON ENTIRE UNIT, SHAFT AND BELT GUARD, EXTENDED LUBRICATION LINES, BASE RAIL WITH SPRING ISOLATORS DRAIN
BLEED FAN FOR REQUIREMENTS UNIT
CONNECTION WITHOUT PLUG, SEALED HOUSING
OP. BLDG. A2110 SEE ELECTRICAL FURNISH WITH NEMA 12 DISCONNECT, 24V MOTORIZED OUTLET DAMPER, PERMATECTOR COATING ON ENTIRE UNIT, MOTOR COVER, EXTENDED LUBRICATION 11
OAF-A2110-01 GREENHECK BSQ-140-20 IN-LINE 1020 560 1.5 (2) BELT 460 3 60 80
OUTSIDE AIR FOR REQUIREMENTS UNIT LINES, SPRING HANGING ISOLATORS & BRACKET
NOTES:
2. HOLD PURCHASE OF FAN; WAITING FOR INFORMATION REGARDING FUME HOOD FROM OWNER.
10
LOCKER/TOILET DIRTY SH. AERO CROSS SENSOR, DOUBLE WALL, INTEGRAL DOOR
TITUS DESV 10 510 510 40 10 SCR 460 3 60 1483 356 318 LEFT HAND INTERLOCK TYPE DISCONNECT SWITCH, AIRFLOW
CVT-A2110-07 AREA CEILING
SENSOR, THERMAL CUTOUTS, 24 VOLT TRANSFORMER
AERO CROSS SENSOR, DOUBLE WALL, INTEGRAL DOOR
SAMPLE RM. 40
CVT-A2110-08 SAMPLE PREP RM TITUS DESV 10 470 470 SCR 460 3 60 1483 356 318 LEFT HAND INTERLOCK TYPE DISCONNECT SWITCH, AIRFLOW
9 5
CEILING
SENSOR, THERMAL CUTOUTS, 24 VOLT TRANSFORMER
NOTES:
THIS DRAWING IS THE PROPERTY OF THE DOW CHEMICAL COMPANY ("DOW") OR AN AFFILIATED
COMPANY OF DOW, IS CONFIDENTIAL, AND MUST NOT BE MADE PUBLIC OR COPIED, AND IS
SUBJECT TO RETURN ON DEMAND. ALL RIGHTS OF INVENTION OR DESIGN ARE RESERVED.
R. ARCILLA
CHECKED
SEP12
OPERATOR BUILDING A2110
A1
S. FARIABI SEP12
THIS DOCUMENT CONTAINS TECHNICAL INFORMATION THAT MAY BE SUBJECT TO PROJECT NO. SCALE
1 0 S14131 SEP12 PROJ. ENGR.
THE EXPORT CONTROL REGULATIONS OF THE UNITED STATES AND/OR OTHER
I. TARIAH SEP12 JURISDICTIONS. IT MAY NOT BE EXPORTED OR RE-EXPORTED EXCEPT AS
A554 NONE 1
BID FAB CONST REF AUTHORIZED UNDER APPLICABLE U.S. OR OTHER EXPORT CONTROL REGULATIONS.
ISSUE MATERIAL OR PROJ.MGR. DRAWING NO. SHEET NO. REV
REV
NO. JOB SPEC
DATE ISSUED FOR
T. KINNEY SEP12 A554-D-A2110-DWG-A05-501 0