SEQUENCE OF OPERATION
PROVIDE REQUIRED
DDC POINTS FOR PROPER 1. THE AIR HANDLING UNIT IS A VARIABLE VOLUME AIR HANDLING UNIT. THE AHU OPERATES 24 HOURS
EXHAUST FAN INTERLOCKS DO
CONTROL OF EQUIPMENT PER DAY 365 DAY PER YEAR.
EAF-A2110-02 INTERLOCK THRU CONTROLS WITH AHU-A2110-01
EAF-A2110-03 INTERLOCK THRU CONTROLS WITH AHU-A2110-01
2. UPON ACTIVATION TO START, THE OUTSIDE AIR FAN SHALL OPEN ITS DISCHARGE DAMPER AND THE 22

FAN SHALL START. THE AIR HANDLING UNITS SUPPLY FAN AND BLEED FAN EAF-A2110-03 SHALL
DI
ACCU CONTROL START. UPON ACTIVATION TO SHUT DOWN, THE AHUS SUPPLY FAN, OUTSIDE AIR FAN AND BLEED
PANEL FAN SHALL SHUT DOWN AND ASSOCIATED ISOLATION DAMPERS SHALL FULLY CLOSE. EXHAUST
DO
ACCU-
FANS, EAF-2110-02 AND EAF-A2110-03, SHALL TURN ON/OFF WITH THE AIR HANDLING UNIT. WHEN
DPS A2110-01
RL EXHAUST FANS ARE OFF THE ASSOCIATED DISCHARGE ISOLATION DAMPER SHALL BE FULLY CLOSED. 21
AIR COOLED CONDENSING UNIT, ACCU-A2110-01, SHALL TURN ON/OFF IN ACCORDANCE WITH
THE AIR HANDLING UNIT.
HOA EAF
AIR COOLED CONDENSING
3. DUCT FIRE/SMOKE DAMPERS SHALL BE OPEN WHEN AHUS ARE IN OPERATION AND SHALL BE CLOSED
UNIT ACCU-A2110-01
WHEN AHUS ARE SHUT DOWN. 20

MOTOR OPERATED ISOLATION


4. ALL SPACE TEMPERATURE SENSORS SHALL REPORT BACK TO THE MAIN DDC PANEL. THE DDC
DAMPER FURNISHED WITH FAN
MOD
CONTROLS SHALL STAGE COMPRESSORS ON/OFF TO MEET THE SPACE WITH THE GREATEST
DEMAND FOR COOLING.

19
GENERAL EXHAUST
FAN (EAF-A2110-02) 5. THE DUCT STATIC PRESSURE SENSOR SHALL CONTROL THE SUPPLY FAN SPEED TO MAINTAIN
DI
SETPOINT. DUCT STATIC PRESURE SETPOINT SHALL BE DETERMINED IN FIELD AFTER
SYSTEM TEST AND BALANCE.
DUCT STATIC PRESSURE
SENSOR. REFER TO DPS
FLOOR PLANS FOR RA 6. A SMOKE DETECTOR LOCATED IN SUPPLY DUCT OF THE AHU SHALL SEND ALARM SIGNAL TO FIRE 18

LOCATION ALARM SYSTEM. THE BUILDINGS FIRE ALARM SYSTEM SHALL BE INCLUDED IN THE S18100-554455
CONTRACT. THE FIRE ALARM SYSTEM SHALL SHUT DOWN AIR HANDLING UNIT, OUTSIDE AIR FAN,

RL
TS AND EXHAUST FANS UPON DETECTION OF SMOKE. UPON UNIT SHUT DOWN, THE ASSOCIATED ISOLATION
AI DI
DAMPERS, OUTSIDE AIR DAMPER, AND SMOKE DAMPERS SHALL CLOSE.
OA
17
DPS OUTSIDE 7. DIFFERENTIAL PRESSURE SWITCH ACROSS FILTER SHALL ALARM THE DDC CONTROL PANEL UPON
DI
AIR FAN HIGH LIMIT SETPOINT OF 250 Pa (ADJ.).
RS
OAF-A2110-01
HIGH STATIC
DPS
DSP DISCHARGE 8. DIFFERENTIAL PRESSURE SWITCH ACROSS INERTIA FILTER SECTION SHALL ALARM THE DDC
OA CONTROL PANEL UPON HIGH LIMIT SETPOINT DETERMINIED IN FIELD (ADJ.).
16

M
AI
DI OAF-
9. DIFERENTIAL PRESSURE SWITCH ACROSS FANS SHALL ALARM THE LOCAL CONTROL PANEL UPON
TS
AI A2110-01
FAN FAILURE.
DI INERTIAL
FILTER BLEED AIR FAN MOD
AIR HANDLING HOA

EAF-A2110-03 15
DPS UNIT, 10. ROOM PRESSURE MONITOR IN THE SAMPLE PREP ROOM SHALL MEASURE AND REPORT ACTUAL NEGATIVE
DPS HOA
AHU-A2110-01 ROOM DIFFERENTIAL PRESSURE BETWEEN THE CORRIDOR AND THE SAMPLE PREP ROOM TO THE DDC
DO MOTOR OPERATED ISOLATION SYSTEM. AN ALARM SIGNAL SHALL BE SENT TO THE DDC SYSTEM UPON CONDITION WHERE THE ROOM
DAMPER FURNISHED WITH FAN NEGATIVE PRESSURE IS NOT MAINTAINED FOR MORE THAN A 30 SECOND (ADJ.) PERIOD.
DO

SA AHU- 14
DI A2110
11. SPACE HUMIDITY LEVEL IN THE SAMPLE PREP ROOM SHALL BE MEASURED AND REPORTED TO THE
SD -01 DDC SYSTEM.
M FSD M FSD M FSD M
PROVIDE CONTROL WIRING
AS REQUIRED FOR FSDS TS SUPPLY
PRE- 12. OUTSIDE AIR AND RETURN AIR TEMPERATURES SHALL BE MEASURED AT EACH UNIT FOR
FAN
DUCT FIRE/SMOKE DAMPER (TYPICAL). VFD FILTER NOTE: THE HVAC CONTRACTOR SHALL PROVIDE INFORMATIONAL PURPOSES.
13
REFER TO FLOOR PLANS FOR FINAL 24 V RELAY FOR ELECTRICAL CONNECTION TO
LOCATION AND QUANTITY FILTERS
MOTOR STARTER FOR EACH FAN OR AHU. THE
AI 13. THE HIGH STATIC DISCHARGE SENSOR SHALL SHUTDOWN UNIT UPON ACTIVATION. SENSOR SETPOINT
AO DX COOLING RELAYS SHALL BE LOCATED IN THE DDC PANEL SHALL BE FIELD ADJUSTABLE.
AI OR A SEPARATE SUB-PANEL. ALL CONTROL
COIL
RS WIRING SHALL BE BY THE HVAC CONTRACTOR
TO FIRE ALARM 12
14. A GAS DETECTOR SHALL BE PROVIDED AT THE OUTSIDE AIR INTAKE. THE GAS DETECTOR AND
T SYSTEM BY OTHER UNLESS OTHERWISE NOTED. RELAY SHALL BE
EQUAL TO PHOENIX MODEL PLC-RSC-24DC/21HC. ASSOCIATED SYSTEM SHALL BE INCLUDED IN THE FIRE ALARM CONTRACT S18100-554455. THIS
SPACE HUMIDITY SYSTEM SHALL SHUT DOWN HVAC UNITS UPON ACTIVATION. UPON HVAC UNIT SHUT-DOWN,
SENSOR LOCATED IN THE SUPPLY FAN, OUTSIDE AIR FAN AND ALL EXHAUST FANS SHALL TURN OFF AND THE ASSOCIATED
SAMPLE PREP ROOM ISOLATION AND OUTSIDE AIR DAMPERS SHALL CLOSE.
11

DIGITAL INPUT SIGNAL 15. EMERGENCY AHU SHUT-DOWN PUSH BUTTON, LOCATED IN THE MONITOR ROOM, SHALL SHUT DOWN ALL
DI
FOR ROOM PRESSURE ALARM HVAC AIR SYSTEMS INCLUDING FUME HOOD EXHAUST FAN EAF-A2110-01 UPON ACTIVATION.

ANALOG INPUT SIGNAL


AI
FOR ROOM PRESSURE MEASUREMENT
10

ROOM PRESSURE MONITOR


RPM
LOCATED IN SAMPLE PREP
ROOM. EQUAL TO SIEMENS
MODEL 547-201B
9

DI

AIR HANDLING UNIT AHU-A2110-01, AIR COOLED CONDENSING UNIT, ACCU-A2110-01,


EMERGENCY HVAC OUTSIDE AIR FAN, OAF-A2110-01, AND EXHAUST FAN, EAF-A2110-02S CONTROL DIAGRAM
SHUT-DOWN SWITCH 8
LOCATED IN
MONITOR ROOM
05
(SEE NOTE #2)
NOTES:

1. ALL DDC CONTROL POINTS SHALL BE WIRED BACK TO THE DDC PANEL FOR CONTROLLER FOR EACH PIECE OF EQUIPMENT, EACH PANEL SHALL BE WIRED BACK TO 7
MASTER DDC PANEL LCP-BLG-A2110-01. REFER TO CONTROL DIAGRAM #01 ON DRAWING A554-D-A2110-A05-508 FOR CONTROL PANEL ARRANGEMENT.

2. ONE EMERGENCY HVAC SHUT-DOWN SWITCH SHALL BE USED TO SHUT-DOWN THE HVAC SYSTEM INCLUDING THE AIR HANDLING UNIT, THE OUTSIDE AIR SUPPLY
FAN, GENERAL EXHAUST FAN AND THE SAMPLE PREP. HOOD EXHAUST FAN SWITCH LOCATED IN THE MONITOR ROOM.
6

THE DOW CHEMICAL COMPANY 3


594x841

THIS DRAWING IS THE PROPERTY OF THE DOW CHEMICAL COMPANY ("DOW") OR AN AFFILIATED
COMPANY OF DOW, IS CONFIDENTIAL, AND MUST NOT BE MADE PUBLIC OR COPIED, AND IS
SUBJECT TO RETURN ON DEMAND. ALL RIGHTS OF INVENTION OR DESIGN ARE RESERVED.

DESIGNED DATE TITLE:


NOTES: REV. DRAWING ISSUE RECORD
MARK
REVISION BY CHK APP DATE
R. ARCILLA SEP12
DRAWN
HVAC
0 ISSUE FOR CONSTRUCTION OB AD SF SEP12 2
-

R. ARCILLA
CHECKED
SEP12
OPERATOR BUILDING A2110
A1

A. DOGANIERI SEP12 HVAC CONTROLS


APPROVED
BORDER

S. FARIABI SEP12
THIS DOCUMENT CONTAINS TECHNICAL INFORMATION THAT MAY BE SUBJECT TO PROJECT NO. SCALE
1 0 S14131 SEP12 PROJ. ENGR.
THE EXPORT CONTROL REGULATIONS OF THE UNITED STATES AND/OR OTHER
I. TARIAH SEP12 JURISDICTIONS. IT MAY NOT BE EXPORTED OR RE-EXPORTED EXCEPT AS
A554 NONE 1
BID FAB CONST REF AUTHORIZED UNDER APPLICABLE U.S. OR OTHER EXPORT CONTROL REGULATIONS.
ISSUE MATERIAL OR PROJ.MGR. DRAWING NO. SHEET NO. REV
REV
NO. JOB SPEC
DATE ISSUED FOR
T. KINNEY SEP12 A554-D-A2110-DWG-A05-510 0