Sie sind auf Seite 1von 1

g Armature Insulation Resistance / HV Proof Tests

Date 11/5/2016 Generator Serial No. 954x104 Prepared by Hassan Shamim


Manufacture GE Turbine Serial No. 899010
Customer HEI FSR No.
Sketch No.
DC INSULATION RESISTANCE (Megohms)
Voltage: 5000 Volts
10 MINUTE MEGGER
Time(Min) Left Center Right
0.5 1200 1120 1030 14000
1.0 2390 2320 2160
12000
2.0 4080 4060 3750
3.0 5310 5680 4930 M 10000
4.0 6550 6440 5650 E
5.0 7300 7730 6400 G 8000
6.0 8000 8310 7450 O
7.0 8670 8930 8430 H 6000
M
8.0 9180 9800 8900
S 4000
9.0 9740 10400 9720
10.0 10130 12100 10400 2000
PI 4.2 5.2 4.8
0
0.0 2.0 4.0 6.0 8.0 10.0 12.0
TIME (Min.)

Left Center Right

HIGH VOLTAGE PROOF TEST (One minute test on each phase with the other phases grounded.)
Rated Voltage (E): KV
Test At: RECOMMENDED TEST VOLTAGES
60 Hz AC Test Voltage (60 Hz): KV
0.1 Hz AC Test Voltage (0.1 Hz): KV
DC DC Test Voltage: KV DC
Actual Test Voltage: KV

LEFT CENTER RIGHT


Passed test at Winding Temp: 40 C
Failed test at Wet Bulb: F
Dry Bulb: F
AC HIPOT DATA (60 HZ) if applicable: Rel. Humidity: 45 %
Test Set:
Polarization Index
LEFT CENTER RIGHT PI = 10min/1min
Excitation Voltage
Current (Amps)

Comments:

D3162043 Sheet: (a) Rev 0.0 - 05/01/05 GE Energy Proprietary Information

Das könnte Ihnen auch gefallen