Sie sind auf Seite 1von 1

SCHEDULE OF LOAD & COMPUTATION

LIGHT
SWITCHES AMPERE R A T I N G W I R E S
CIRCUIT DESCRIPTION OF HP VOLT V-A RATING
CONDUIT
LOAD
L.O. C.O. RATING RATING RATING
NO. DIAMETER
GROUND
S1 POLE AT AF NO. & SIZE TYPE
WIRE
2.0 mm2
1 LIGHTS 8 8 230 800 3.47 2 15 60 2# 2.0 mm2 THW
THW
CONVENIENCE
2 9 1620 7.04 20 2# 3.5 mm2
OUTLETS
3 REFRIGERATOR 1 400 1.74 20
4 A.C.U. # 1 1 1 HP 1840 8.00 20
5 A.C.U. # 2 1 1 HP 1840 8.00 20
6 SPARE
TOTAL 8 12 8 3.5 HP 6500 28.25

COMPUTATION FOR LOAD PANEL IN EACH DWELLING UNIT:

TOTAL CURRENT: 28.25 + 25% (8) = 30 AMPERES

APPLICATION OF DEMAND FACTOR:


FIRST 3,000 VOLT-AMPERES AT 100 %, 3,000 x 100% = 3,000 VOLT-AMPERES
REMAINING 3,500 VOLT-AMPERES AT 35%, 3,500 x 35% = 1,225 VOLT-AMPERES
TOTAL VOLT-AMPERES = 4,225 VOLT-AMPERES

TOTAL CURRENT, 4,225 VOLT-AMPERES / 230 VOLTS = 18 AMPERES

FOR SUBFEEDER CONDUCTORS IN EACH DWELLING UNIT,


USE: USE 3.5 mm2/ [ 25 18 A] THW WIRES AND 1 NO. 3.5 mm2

MAIN CB FOR EACH LOAD PANEL:


USE ONE 30-AMPERE TRIP, 60 AMPERE-FRAME MOLDED CIRCUIT BREAKER 1-POLE, 250 VAC, 60 HZ

SCHOOL/DEPARTMENT PROJECT TITLE DESIGNER


UL- ELECTRICAL ENGINEERING MULTI-FAMILY DWELLING UNIT CAYABYAB, KELVIN
[40 UNITS WITH 6 BRANCH CIRCUITS EACH UNIT]
SUBJECT ENGINEER SCALE PAGE
EE 514A ENGR. JONAS M. AGULAN 1:100 E-07A