Beruflich Dokumente
Kultur Dokumente
MPI/PPIusermanual
(english)
Art.Nr.9350
Art.Nr.9350.05M
Art.Nr.9350.10M
Art.Nr.9350.15M
21.02.2014
PI2014
http://www.tpapartner.de/ftp/pub/handbook/en_Handbuch%20MPIPPI.html 1/63
1/20/2016 Handbuch
indexofcontents
MPI/PPI
1Description
2Systemrequirements
2.1Operatingsystem(s)
2.2Software
2.3Hardware
3Installation
3.1Hardware
4Controlelements
4.1Display
5Implementing
5.1Programmingsoftwaretousewithdirectaccess
5.1.1PG2000frS7(V5.10)
5.1.2PSetPG/PCinterface
5.1.2.1PCAdapter(Auto,MPI,PROFIBUS)
5.1.2.2TCP/IPRFC1006Communication
5.1.2.3MPIsetting
5.1.2.4Profibussetting
5.1.2.5TCP/IPRFC1006setting
5.1.2.6ProTool/ProRunTime(RT)Configuration
5.1.3SIMATICStep7Manager(v5.2+SP1)
http://www.tpapartner.de/ftp/pub/handbook/en_Handbuch%20MPIPPI.html 2/63
1/20/2016 Handbuch
5.1.4WindowsControlCenter(WinCC)(v6.0)
5.1.4.1MPIConfiguration
5.1.4.2TCP/IPConfiguration
5.1.4.3Communicationandfaultdiagnosis
5.1.5WindowsControlCenterflexible2004(WinCCflexible)(v5.2.0.0)
5.1.6ProTool/Prov6.0SP2
5.1.7Microwinv3.2(onlyforS7200)
5.1.8S7forWindowsv5.02
6S7InterfaceConfiguratorHelp
6.1Languageselection:
6.2Userinterface:
6.3Busconfiguration
6.4Networksettings
6.5ParameterizeTELEService
6.5.1Index"Network":
6.5.2Index"Modem":
6.5.3Index"Serialparameter":
6.5.4Index"AccessProtection":
6.5.5Index"GSM/ISDN/SMS":
6.5.6Index"Internet/Mail":
6.6Tuning
6.7Factorydefaults
6.8PPIBootoff
6.9EmergencyLoader
7MPIcablemanager
7.1Description
http://www.tpapartner.de/ftp/pub/handbook/en_Handbuch%20MPIPPI.html 3/63
1/20/2016 Handbuch
7.2Installation
7.3Overview
7.3.1Language
7.3.2Interface
7.3.3Update
7.3.4Teleservice
7.3.4.1Telephonebook
7.3.4.2Connect
7.3.4.3Extra
7.3.4.3.1Setup
7.3.4.3.2TSfunction
7.3.4.3.3configureadapter
7.3.4.3.4Importparameter
7.3.4.3.5Exportparameter
7.3.5Tuning
8Technicaldata
8.1PinningRS232
8.2Pinassignment
http://www.tpapartner.de/ftp/pub/handbook/en_Handbuch%20MPIPPI.html 4/63
1/20/2016 Handbuch
MPI/PPI
1Description
TheMPI/PPIcableconnectstheprogrammingdeviceorthecomputerwiththeMPIinterfaceof
anS7300/400orwiththePPIinterfaceofanS7200overtheserialinterface(COMPort).The
cablerecognizesautomaticallywhileattachonitonthePLC,whichPLCtypeisconnected.Atthe
first access from the PDs on the cable it recognizes the baud rate for communicationwiththe
PLC.WiththeprogrammingdevicePG2000orS7forwindowstheMPI/PPIcableworksupto
115.2kbaudonthecomputerside.
Here it can communicate with each member which is connected to the bus or even with the
backplanebus.ItisthebesttoworkovertheS7project.
The MPI/PPIcable supplies itself from the PLC and didnt need a foreign supply. All power
suppliesaregalvanicseperated.To reach high distance to an PLC with the MPI/PPIcable you
needtheMPINETZadaptertofeedthecablewiththe24VDCsupplyvoltage.
2Systemrequirements
2.1Operatingsystem(s)
Windows98+SE
WindowsME/NT/2000
WindowsXP
WindowsVista
Windows7
2.2Software
PLCprogrammingsoftware(egPG2000,Step7,S7forWindows,Microwin)
2.3Hardware
9pin.or25pins.COMinterface
24Vpowersupply(MPIorPPIinterface)
3Installation
3.1Hardware
MPI/PPIstandardmode:
ThecableispluggedwiththeshortcablesidetotheMPIorPPIportofthePLC.TheMPI/PPI
cablesourcesitselfnormallywiththe24Vofthisportanddonotneedexternelvoltage.Thecable
needseverytimeaPLCofcoursethe24VsupplyoroptionallytheMPINetzAdapter.Thelonger
cablesidehastoconnectintheCOMportofyourPDorPC.
Asthecablehassupplyvoltage,youcanseeinthedisplaytheversionoftheincludedfirmware
and start with an internal test of the included parts. After this test the adaptor checks if he is
connectedtoaPLCandtriestorecognizethebaudrateoftheconnectedbus.Inthedisplayofthe
cableyoucanseeallrelevantinformation.
The cable detects automatically the baudrate parameters to the programming device when the
http://www.tpapartner.de/ftp/pub/handbook/en_Handbuch%20MPIPPI.html 5/63
1/20/2016 Handbuch
communicationstartsandwillusethem.
IfyourPDorPChasonlyaCOMportwith25pin,youcanuseanormal"mouseadapter"orour
articlenumber93599tochangethepinsfrom25to9pin.
IfyouwillusetheplcprogrammingsoftwarePG2000orS7frWindowstheMPI/PPIcablewill
workwith115.2kBaudonthePCside.
MPI/PPIasTSAdapter(TS=TeleService):
TheTSpossibilityallowstheconnectionofamodem,tomakeaconnectionwitha2ndModem
and a PC to a S7300/400. The Cable must be connected between the modem (with a special
adapterpiece,noGenderChanger)andthePLC.
ToworkwiththeMPICableinhisTSfunction,youmustmakethefollowingactions:
1)ThecablemustbeconfiguredasaTSAdapter(insteadofPGorPgtheLCDdisplayshows
TSorTs).Youcanturnon/offthesefunctionwiththefreeprogramMPIcablemanager.
2)TheprograminsideofthecablemusthaveaversiongreaterthanV1.45.Thisversionnumber
will be displayed for a short time behind the plugging to a S7 PLC. You can update the cable
softwarewiththefreeprogramMPIcablemanager.
3) You need the TeleServicesoftware from Siemens in your PC to work with the cable. The
configurationofthecablecanbemadewiththeTeleServicesoftwarefromSiemensorwiththe
MPIcablemanager.
4)TheconnectionofthemodemtotheMPIcablemustmadewithaspecialadapterplug
(noGenderChangerorso)
Orderinformationforthespecialadapter:
AdapterforTSfunction9polArticleno.9350TS
TheadapterfortheTSfunctiononlyworkswiththeMPI/PPICablewiththeorder
number9350!
MPI/PPIasHMIAdapter(HMI=HumanMachineInterface):
TheHMIpossibilityallowstheconnectionofaoperatorpanel(whohasnotaninternalMPIport,
but the HMIprotocol and a RS232interface) with a S7300/400. The cable must be connected
betweentheoperatorpanelandthePLC.TheHMIprotocolmustbeapartoftheoperatorpanel.
Behind the version V1.45 of the software inside the cable, you can use the cable as a HMI
adapter.SomeoperatingpanelsaremadetoworkwithaSiemensHMIAdapter.Thepiningto
our cable is different. You may turn the wires 2 and 3 in a little adapter. Please look into the
handbookoftheoperatorpanelwhatyouneedforthecorrectpinning.
4Controlelements
4.1Display
Displaydescriptionfromlefttoright.
Firstline
#02=>InthisexampletherearetwoactivestationsontheMPIBUS
PD=>letterdefinitionofthePCbaudrate.
Display Descriptions
PD 115,2korbaudrateidentificationisactive.
PU USBconnection
P? Baudraterecognitionandaccesswayactive.
TD 115,2korbaudraterecognitionisactive.(cableisconfiguredasTSadapter)
PG 19,2k
TS 19,2k(cableisconfiguredasTSadapter)
Pg 38,4k
Ts 38,4k(cableisconfiguredasTSadapter)
pG 57,6k
tS 57,6k(cableisconfiguredasTSadapter)
PM PPIMulti(187,5k)
00=>thestationnumberoftheMPIcable.(Defaultis0)
(In the system configuration click on Set PG/PC interface. In the following dialog click
properties.NowyoucanchangeintheregistrycardMPIpartstationrelatedtheadress
ofthecable.)
(InthePG2000softwareyoucanfinditbyclickingonOptions
Interfaces.Closetothebottomofthedialogyoucanchangethelocaladdress
ofthecable.)
=>ifthissignappearsinthetopoftheline,yourcableiscommunicatingwiththePLC.
Ifthissignappearsinthebottomoftheline,yourcableiscommunicatingwiththecomputer.
SecondLine
!=>(Exclamationmark)specifiestheconnectiontypetothePLC.
Display Description
! DirectlyconnectedtothePLC.
? NotdirectlyconnectedtothePLC.
!(inverse) DirectlyconnectedtothePLCwithpassiveunitofthePLC.
?(inverse) NotdirectconnectedtothePLCwithpassiveunitofthePLC.
02=>isthestationnumberofaconnectedandactivePLCintheMPIBUS.
Every750milliseconds(asecond)anotheruserwillbedisplayedifmorethenoneuserhas
beenfound.
AG=>Thetypeoftheprotocolwhichisusedforthecabletorunuptothecomputer.
Display Description
Unknownbecausethereisnoconnectionoranolderprotocolversion(before5.0)is
http://www.tpapartner.de/ftp/pub/handbook/en_Handbuch%20MPIPPI.html 7/63
1/20/2016 Handbuch
AG used.
Ag v5.1Protocol
Ag v5.0Protocol
Configurationspecificmessages:
Withthefollowingbaudratesettings,themenumessagechangesaccordingly:
Description8N1:
8=Databits
N=Parity
1=Stopbit
5Implementing
Connectyourmoduleasdescribedinthechapter"Hardwareinstallation"tothePLCandtothe
programmingdeviceortoyourcomputer.
IfyouwanttorespondtoaPLCviathemoduleyouhavetocomplytherequirements
asdescriptinthechapter"systemrequirements".Inaddition,pleasemakesurethat
themoduleisproperlyconnected
5.1Programmingsoftwaretousewithdirectaccess
AfteryouhaveadjustedandconnectedthePLCVCOMortheprogrammingadaptertotheCOM
portonyourcomputer,youwillbeabletoconnectwithyourprogrammingsoftware
tothePLCandworkwithit.
Howyouhavetoadjustyourprogrammingsoftwareisdescribedinthefollowingpoints:
5.1.1PG2000frS7(V5.10)
1.StartthePG2000softwarebyusingthedesktoplinkorbyusingtheapplicationentryinthe
startmenu.
2.Choosefrom"View"=>"S7300/400"
InthemenuOptionsclickInterfaces..
http://www.tpapartner.de/ftp/pub/handbook/en_Handbuch%20MPIPPI.html 8/63
1/20/2016 Handbuch
3.Adialogappears,inwhichyouareableto
set the AGInterface (COMport) in the
sectionInterfaces.
4.ConfigurethebaudrateinthesectionBus
access to 19,2k. Below change the value
forPCMPIto187,5kBaud.
5.SaveyourconfigurationbypressingOK.
ClickthesymbolOpenandafterwardspress
PLC.
Alternativeyoucanclick:
File=>Open=>PLC
Anewwindowappears.Nowyoucaneditthe
blocksinthePLC.
http://www.tpapartner.de/ftp/pub/handbook/en_Handbuch%20MPIPPI.html 9/63
1/20/2016 Handbuch
5.1.2PSetPG/PCinterface
Thisstepisrequiredforthefollowingsoftware:
=>SIMATICStep7Manager(v5.2+SP1)
=>WindowsControlCenter(WinCC)(v6.0)
=>WindowsControlCenterflexible2004(WinCCflexible)(v5.2.0.0)
=>ProTool/Pro(v6.0+SP2)
=>Microwin3.2
2.ClickonSetPG/PCinterface.
3.ADialogwithalistboxnamedInterface
Parameter Assignment Used: appears.
ThisboxshouldoffersomePCAdapter
entries
Ifthisisthecase,pleasecontinuewiththe
stepMPIsettingsorProfibussettings.
Ifyoucan'tfindtheseentriesgoaheadwith
stepPCAdapterorTCP/IPinstallation.
5.1.2.1PCAdapter(Auto,MPI,PROFIBUS)
4.ClickonChoosetoaddtheseentriestothePG/PCinterfaceconfiguration
5.Inthisdialogyoucandeinstalleveryinstalled
constructionset
ChoosePCAdapterfromtheSelectionbox
ontheleftsideandclickonInstall.
http://www.tpapartner.de/ftp/pub/handbook/en_Handbuch%20MPIPPI.html 10/63
1/20/2016 Handbuch
6.Thechosenconstructionsetwillbeinstalledandaquestionappearswhichasksyoutouse
theMPIaccessforthePLCused.
ClickYesifyouwanttousetheMPIcommunicationtype.
OtherwiseclickNo(e.g.ifyouwanttousethePROFIBUScommunicationtype).
5.1.2.2TCP/IPRFC1006Communication
8.Inthedialog"Select",choose"TCP/IP"and
clickon"Install".
9.Aftersuccessfulinstallation,click"Close".
10.BacktotheSetPG/PCinterfacedialogyouwillnowfindthedesiredentriescalledPC
Adapter(Auto)(notsupported),PCAdapter(MPI)andPCAdapter(PROFIBUS).Now
youareabletoconfigurethebus.
IfyouwanttousetheMPIcommunicationtypegoaheadwithstepMPIsetting.
Thesettingsfor"PROFIBUS"isexplainedinProfibussetting.
5.1.2.3MPIsetting
http://www.tpapartner.de/ftp/pub/handbook/en_Handbuch%20MPIPPI.html 11/63
1/20/2016 Handbuch
12.Openthepropertiesdialog
Choosetheregister"LocalConnection"
13.SetheretheCOMport.
Changethe"HighestStationAddress"(HSA)to
"126".
5.1.2.4Profibussetting
http://www.tpapartner.de/ftp/pub/handbook/en_Handbuch%20MPIPPI.html 12/63
1/20/2016 Handbuch
18.IntheregistrycardLocaleconnection
youhavetosettheCOMPort.
19.Setthe"TransmissionRate"to"19200"
22.SaveyoursettingsbyclickingtheOKbutton
and close the opened Set PG/PC
interfacedialog
5.1.2.5TCP/IPRFC1006setting
23.Forthiskindofcommunicationyouonlyhavetoinstallthecorrespondingsoftware.
5.1.2.6ProTool/ProRunTime(RT)Configuration
24.IfyouwanttouseProTool/ProRunTimeyou
http://www.tpapartner.de/ftp/pub/handbook/en_Handbuch%20MPIPPI.html 13/63
1/20/2016 Handbuch
can set the "PG/PC Interface" by selecting the
entry "DPSONLINE". Therefore you have to
select "Access Point of Application" and
configureitasdescribedabove.Theeasiestway
istousetheS7LAN/MPILAN/MPIUSBdriver
whichsupportsUSBandLANproducts.
Theinterfaceconfigurationfortheseprogramsisfinished.
Continuewiththesoftwarewhichyouwanttouse:
=>SIMATICStep7Manager(v5.2+SP1)
=>WindowsControlCenter(WinCC)(v6.0)
=>WindowsControlCenterflexible2004(WinCCflexible)(v5.2.0.0)
=>ProTool/Pro(v6.0+SP2)
=>Microwin3.2
5.1.3SIMATICStep7Manager(v5.2+SP1)
ConfiguratetheinterfaceasdescribedinSetPD/PCInterface.
3.Inthiswindowyoucanediteachassembly
withhisblocks.
5.1.4WindowsControlCenter(WinCC)(v6.0)
ConfiguratetheinterfaceasdescribedinSetPD/PCInterface.
1.StartWinCCbyusingthedesktoplinkortheprogramentryinthestartmenu.
http://www.tpapartner.de/ftp/pub/handbook/en_Handbuch%20MPIPPI.html 14/63
1/20/2016 Handbuch
2. Choose New in the menu File or click on the white (letter) symbol to start a new
project.
4.OKleadsyoutoanewdialog.TypeintheProject
NameandtheSubfolderoftheprojectpath.
ThechosenconfigurationisconfirmedwithCreate.
To use one of the other options please go ahead and read in the manual of
WinCCsoftware.
5.Pleasewaituntiltheprojectiscreated.Theprojectcontentwillbeshownintheleftpartof
themainwindow.
http://www.tpapartner.de/ftp/pub/handbook/en_Handbuch%20MPIPPI.html 15/63
1/20/2016 Handbuch
Thereforeyouhavetorightclickon
Tag Management it opens the
contextmenu.ChooseNewDriver
Connection.
It is very important that the selected driver fits with the PLC otherwise the
connectioncannotbeestablished..
8. You should see now in the Explorer under the branch Tag Management the branch
SIMATIC S7 PROTOCOL SUITE. Expand the branch and many protocols for various
compoundswillappear.
TheGeneralwayofproceedinganewconnectionisto:
Rightclickonthedesiredconnection(MPI>Picture:MPI,TCP/IP>Picture:TCP/IP).A
contextmenuopens.ClickonNewDriverConnection.
ThismanualdescribestheconnectionconfigurationsforMPIandTCP/IP
MPI
TCP/IP
http://www.tpapartner.de/ftp/pub/handbook/en_Handbuch%20MPIPPI.html 16/63
1/20/2016 Handbuch
5.1.4.1MPIConfiguration
5.1.4.2TCP/IPConfiguration
http://www.tpapartner.de/ftp/pub/handbook/en_Handbuch%20MPIPPI.html 17/63
1/20/2016 Handbuch
Exampleconfiguration:
IPaddress192.168.1.55
RackNumber:0
SlotNr.:2
11.Witharightclickonthenewconnectionyoucanstartthepropertiesdialog.Inthisdialog
pleaseclickonproperties.
12.InthisChannelunitproperties
you are able to see all available
connections.
13.Nowyouareabletosetupthenameofthevariableanddifferentmoreproperties.
Inourexample,weassignthefollowingvalues:
Name:S7LAN_MW0
Datatype:unsigned16Bitvalue
Length:2
Address:MW0
http://www.tpapartner.de/ftp/pub/handbook/en_Handbuch%20MPIPPI.html 18/63
1/20/2016 Handbuch
Formatadaptation:WordToUnsignedWord
ClickonChoosebesidetheAddresstodefinetheaddressfromthevariable.
Exampleconfiguration:ThedataareafromthevariableissettoMarkandtheaddressisset
toWord.TheeditboxMWissetto0.
14.ConfirmallopendialogswithOKuntilyoureachthemainwindow.
15.Theconnectionneedstoknowwhichnetworkinterfacecarditshouldbeusedtosenddata
via the Ethernet. Open the System parametersdialog from the context menu (rightclick on
TCP/IP).
16. Choose from the registry card Unit and set the logical device name to your network
interfacecard(usuallythenameoftheNICbeginswithaTCP/IP>).
17.ConfirmwithOK.
18.Nowyouareabletostart thecommunication.Stopitbyclickingon .
5.1.4.3Communicationandfaultdiagnosis
TocleanuperrorsfastertheWinCCSoftwareoffersatoolnamed"ChannelDiagnosis.This
toolanalysesallconnectionsfromyourWinCCsoftware.Fordemonstrationpurposesplease
stopthelaststartedconnectionfromyourWinCCexplorer.
19.Startthesoftware"ChannelDiagnosisbyusingyourlinkinthestartmenu.
Clickonthelastcreated,notactive
connection (with the red X) and
some informations from the
connection will appear in the right
partofthedialog.
http://www.tpapartner.de/ftp/pub/handbook/en_Handbuch%20MPIPPI.html 19/63
1/20/2016 Handbuch
yellow window appears (tooltip)
withdetailederrordescriptions.
5.1.5WindowsControlCenterflexible2004(WinCCflexible)(v5.2.0.0)
PleasemakesurethattheinterfaceconfigurationiscorrectasdescribedinPD/PC
Setinterface
2.FirstyouneedtoselectCreateanemptyprojectonyourfirstpage.
confirmwith"OK.
http://www.tpapartner.de/ftp/pub/handbook/en_Handbuch%20MPIPPI.html 20/63
1/20/2016 Handbuch
4.Aftertheprojecthasbeencreatedrightclickin
the project window on Connectionsof the sub
menuCommunication.
InthecontextmenuclickonAddConnection.
5. A new configuration window Connections opens in the right part of the main window. This
offersyoudifferentsettingoptions.
Importantfortheconnectionis:
=>thecommunicationdriver(setupwhichPLCyouareusing(example:"SIMATICS7300/400))
=>theBaudrate(Setthison"187500")
=>theaddressoftheterminal(HMI)(inthisexample"1)
=>theProfile("MPIforexample)
=>theHighestStationAddress(HSA)(e.g."126)
=>theaddressofthePLC(e.g."2)
6.Nowyoucanstartwithyourwork.
Ifyouhavefinishedworkyoucantransferthis
projecttothepanelbyreadingthenextsteps.
8.InthenewdialogchangetheModetoMPI/DPandsettheStationaddressoftheoperator
panel(e.g.1). If desired you can switch the Delta transfer to On (in this example we set it
Off).
http://www.tpapartner.de/ftp/pub/handbook/en_Handbuch%20MPIPPI.html 21/63
1/20/2016 Handbuch
9.PressthebuttonTransfertostartcommunicationwiththeterminal.Yourprojectisabouttobe
transferred.
TheWinCCflexiblesoftwareisnowabletocommunicatewithyouroperatorpanel.
5.1.6ProTool/Prov6.0SP2
PleasebesurethattheinterfaceconfigurationiscorrectasdescribedinPD/PCset
interface
1.StartProTool/Probyusingthedesktoplinkorprogramentryinthestartmenu.
2.ChoosefromthemenuFilethesubmenuNeworclickontherightsymbol.
3.Thenextdialogaskesyouwhichoperatorpanel
youareusing.
Marktheusedpanel(e.g.TP170A)
4.Nextleadsyoutoanewdialog.Typeinthe
specfic fields the name of the PLC device and
choosetheusedPLCinthedriverselection(e.g.
SIMATICS7300/400V6.0).
http://www.tpapartner.de/ftp/pub/handbook/en_Handbuch%20MPIPPI.html 22/63
1/20/2016 Handbuch
1)andofthePLC(example2).
6.ThebuttonMore...leadsyoutoasmalldialog
where the Highest Station Address should be
configured to 126. Set up the Number of
masters(e.g.1)
7.confirmwithOKuntilyougotbacktotheControlSelection.GoonwithNext.
ConfirmwithOK.
andstartwithyourwork
Ifyouhavefinishedworkingonthisprojectyoucangoonwiththenextsteps.
Pleasewaitwhiletheprojectistransferred.
Thecommunicationbetweentheoperatorpanelisnowestablished.
5.1.7Microwinv3.2(onlyforS7200)
http://www.tpapartner.de/ftp/pub/handbook/en_Handbuch%20MPIPPI.html 23/63
1/20/2016 Handbuch
PleasebesurethattheinterfaceconfigurationiscorrectasdescribedinPD/PCset
interface
1.StartMicrowinusingthedesktoplinkorprogramentryintheStartmenu.
2.ClickonTypeinthemenuPLC
ConfigurethePLCType(e.g.CPU224)aswellastheCPU
Version(e.g.01.22)tothedialog.
3.ClickonCommunications...tostartthenextdialog.
InthesectorAddresssetuptheRemotelistboxwiththestationaddressofthePLC(e.g.2).
If you skipped the point b ( PD/PCset interface) you can configure the PG/PC
interfacewithaclickonSetPG/PCinterface.
http://www.tpapartner.de/ftp/pub/handbook/en_Handbuch%20MPIPPI.html 24/63
1/20/2016 Handbuch
4.Intherightpartofthedialogdoubleclickonthebluearrow symboltotestthecommunication
withthePLC.
5.ThesectorAddressshouldbeupdatedanddisplaysthePLCType.AlsotheCPUofthePLC
isdisplayedintherightpartofthedialog.
6.ConfirmwithOKuntilyougetbacktothemainwindow.
ThecommunicationwiththePLCistnowestablished.
5.1.8S7forWindowsv5.02
Anewdialogappearswhichprovidestosetup
a lot of configuration data about the
communicationwithyourPLC.
http://www.tpapartner.de/ftp/pub/handbook/en_Handbuch%20MPIPPI.html 25/63
1/20/2016 Handbuch
3.ChoosethefirstregistrycardInterface(standard)andsetuptheconfigurationdata
asdescripedbelow:
=>Area:Preferencesfrom:=>PC
=>Area:PLCType:=>S7
=>Area:Protocol:=>MPIUmsetzer
=> Area: Serial Port: => Choose the virtual COM port which has been created by
PLCVCom(e.g.COM4).
=>Area:BaudRate=>Choosethespeedyouwanttouseatthebus(e.g.115200)
=>Area:MPIConverter:
ActivatethecheckboxOnlyMasterattheBusifyouhaveonlyonePLC
inthebus.
LeavethefieldsS7WMPIAddressandMPIAddressPLCasitis.
The number in the listbox Max MPI Address must be higher than the
PLC with the highest station address in your MPI bus. Otherwise every
PLCwhichishigherthanthisnumberwillnotbeenseen(e.g.if there is
onlyonePLCinyourbus15ismorethanenough).
4. After the software is configured , please click Select PLC in the area MPI
Converter.AnewdialogappearswhereyoucanselectthedesiredPLC
ThecommunicationbetweenthesoftwareandyourPLCisestablished.
6S7InterfaceConfiguratorHelp
Languageselection
Userinterface
Busconfiguration
http://www.tpapartner.de/ftp/pub/handbook/en_Handbuch%20MPIPPI.html 27/63
1/20/2016 Handbuch
Networksettings
ParameterizeTELEService
Index"Network"
Index"Modem"
Index"SerialParameter"
Index"AccessProtection"
Index"GSM/ISDN/SMS"
Index"Internet/Mail"
Tuning
Factorydefaults
PPIBootoff
EmergencyLoader
6.1Languageselection:
SelectthemenuConfigurationtochangethelanguagepermanently:
6.2Userinterface:
SelectnearSearchwhichinterfacesaresearchedpermanentlyfordevices.
Youcouldchoose:
Serial AllexistingCOMPortsarescannedfordevices
USB SearchdeviceswhichareconnectedbyUSB
LAN Searchdevicesonallnetworkcards
ThebuttonSearchstartsaparallelsearchonallselectedinterfaces.
AfterselectingaupdateabledevicethebuttonUpdategetsavailable.
http://www.tpapartner.de/ftp/pub/handbook/en_Handbuch%20MPIPPI.html 28/63
1/20/2016 Handbuch
Below the buttons is a list of the found devices. In each line an image, the type of the device,
name (if existing), interface, serial number (if possible) and the OSversion of the device is
displayed.OntherightmostpositiontheactualOSversionontheharddiskisdisplayed.
Thebackgroundofthelinescouldusethefollowingcolours:
White TheOSofthedeviceisuptodate
Lightblue TheOSofthedeviceisnotuptodate,thedevicecouldbeupdated
Red Anerroroccuredbyaccessingthedevice
Yellow Updateisinprogressforthisdevice
Darkblue Selecteddevice
Double click onto a device which could be updated shows the versiondocumentation of the
device(onlyavailableinGerman):
http://www.tpapartner.de/ftp/pub/handbook/en_Handbuch%20MPIPPI.html 29/63
1/20/2016 Handbuch
ThebuttonUpdatewithFDupdatestheOSofthedeviceandsetsthefactorydefault.
ThebuttonBootstrapsetsthefirmware/configurationtofactorydefault.
ThebuttonFactorydefaultssetstheconfigurationtofactorydefault.
ThebuttonParameterizeactivatesadialogregardingtothedevice:
Overview:
Device Dialog
TELEService
ParameterizeTELEService
MPI/PPIProfibusmodem
MPI/PPI ParameterizeTELEService
Choices:
MPIII
Busconfiguration
MPIUSB
ParameterizeTELEService
S7USB Busconfiguration
Choices:
S7LAN
Busconfiguration
MPILAN
Networksettings
ThebuttonPPIBootoffdisablesthePPIbootoptionofaserialconnecteddevice.
The button EmergencyLoader tries to repair LAN products which are in emergencyloader
mode.
ThebuttonTuningactivatesadialogforspecialparameters.
ThebuttonExitleavestheapplication.
6.3Busconfiguration
Toparameterizetheconnectiontothedevice,selectadeviceandclick"Parameterize".
http://www.tpapartner.de/ftp/pub/handbook/en_Handbuch%20MPIPPI.html 30/63
1/20/2016 Handbuch
Regarding to the device you maybe have to click on the button Bus configuration (see
parameterizetable).
Hereyoucanparameterizethefollowing:
UsebusconfigforPC TooksthebusconfigurationfromthePC
choosestheBautrateforthecabletobus
Baudrate
communication
Thehigheststationaddressinthebus
(thelessyouuse,themoreperformanceontheMPIbus,
Higheststationaddress
mustbecorrespondingwiththeconfigurationinthe
CPUs)
TheTSAdapteristheoneandonlymasterintheMPI
http://www.tpapartner.de/ftp/pub/handbook/en_Handbuch%20MPIPPI.html 31/63
1/20/2016 Handbuch
PD/PCistheonlymasteronthe bus
bus (adapterhasttospeaktoallpassiveclients)
Profile Bustypeoftheconnection
WhichlocalstationaddressisusedfortheTSAdapter.
Pleaseconsiderthataprogrammingdevicehasnormally
thenumber0,
Localclientaddress
operatorpanelhave1,CPUsuse2,FM/CPs3etc.
Please:Neverusethesamestationnumberfor2
differentstations!
Protocoltype Protocoltypeoftheconnection
Bootsettings Bootsettingoftheconnection
6.4Networksettings
Hereyoucansetthenetworkconfigurationoftheselecteddevice:
Factorydefault Thisbuttonsetsalloverthenetworkreachabledevicestofactorydefault.
DHCPclientactive WhensetthedeviceactsasDHCPclient.
HereyoucouldentertheIPAddressoverwhichthedeviceisaccessed
IPaddress
inthenetwork.
Subnetmask HereyoucouldentertheSubnetmaskofyournetwork.
Here you could enter the IP address of your Gateway. Usual a router
Gatewayaddress
address.
Devicename Hereyoucouldchangethedevicename.
Factorydefault:
DHCPclientactive notset
IPAddress 192.168.1.56
Subnetmask 255.255.255.0
Gatewayaddress 0.0.0.0
Devicename empty
6.5ParameterizeTELEService
Toparameterizethedevice,firstclickonthedevice,afterthaton"Parameterize".
http://www.tpapartner.de/ftp/pub/handbook/en_Handbuch%20MPIPPI.html 32/63
1/20/2016 Handbuch
Regardingtothedevice,youmaybehavetoclickontheTELEServicebutton.
Afterclickingon"TELEService"amessagewillshowup:
DependingontheversionofyourTELEServicesoftwarechooseYesorNo.
Theregularparameterscanbechangedmanuallyinthefollowingcategories:
6.5.1Index"Network":
Hereyoucanconfiguratefollowing:
http://www.tpapartner.de/ftp/pub/handbook/en_Handbuch%20MPIPPI.html 33/63
1/20/2016 Handbuch
Stationrelated:
PD/PCistheonlymasteron TheTSAdapteristheonlymasterontheMPIbus
thebus (adaptermustspeaktoallpassiveclients)
WhichlocalstationaddressisusedfortheTSAdapter.
Pleaseconsiderthataprogrammingdevicehasnormally
thenumber0,
Address
operatorpanelhave1,CPUsuse2,FM/CPs3etc.
Remind:Neverusethesamestationnumberfor2
differentstations!
Networkrelated:
Networktype ThenetworktypeMPIorPROFIBUS
Transmissionrate ThetransmissionspeedontheMPIbus
Currenttransferrate Showsthecurrenttransferrateofthedevice
Thehigheststationaddressinthebus
(thelessyouuse,themoreperformanceontheMPIbus,
Higheststationaddress
mustbecorrespondingwiththeconfigurationinthe
PLCs)
6.5.2Index"Modem":
Inthisdialogyoucouldconfigurethemodemrelatedsetup.
http://www.tpapartner.de/ftp/pub/handbook/en_Handbuch%20MPIPPI.html 34/63
1/20/2016 Handbuch
ModemSettings:
AT startcommand
&F usefactorysettings
E0 echooff
L1 volumeofspeakerislow
Initialization M1 speakerisonatconnection
Q0 outputofthereturnvalues
V1 returnvaluesplaintext
&C1 DCDshowsstatusofthecarriersound
S0=1 automaticconnectionafter1ring
+++ Switchtocommandmode
Hangup AT startcommand
H Hangupconnection
Location:
Therearetwopossiblecalltechniques:
MFVtone,thetelephonenumberistransferedbyseveral
Thephonesystem
frequencies
uses
IWVpulse,thetelephonenumberistransferedwiththeamountof
severalpulsesontheline
Toaccessanoutside Ifyouneedaprefixbeforeyournumbertoestablishacalloutside,
line,firstdial youmustentertheprefixheree.g.0.
CallPreferences:
Waitfordialtone Incasethemodemshouldwaitforafreeline,youshouldsetthe
beforedialing correspondingcheckbox.
Numberofredial Atnumberofretriesyoucouldconfigurethenumberofretriesfora
http://www.tpapartner.de/ftp/pub/handbook/en_Handbuch%20MPIPPI.html 35/63
1/20/2016 Handbuch
attempts connectionbeforethecallisstopped.
Usingaretryyoucouldenterthesecondstheapplicationshould
Redialafter
waitbetweencalls.
6.5.3Index"Serialparameter":
InthisdialogthetransferratebetweenmodemandTSAdapterisselected.
ConnectionPreferences:
Thetransferratecouldchoosenbetweenthefollwingvalues:
Transferrate
2400,4800,9600,19.2k,38.4k,57.6kand115.2kBaud
Theparitycouldbechoosen,butthisismodemdependend
becausesomemodemscouldnothandletheparitybit:
Parity None:(Thereisnoparitytesting)
Odd:(Theamountofbitssetto1isodd)
Even:(Theamountofbitssetto1iseven)
6.5.4Index"AccessProtection":
Theaccessoveratelephonelinecouldbeconfiguredinthisdialog.
AccessProtection:
Theadministratorcanchangetheconfigurationoveratelephoneline.
Thetwouseraccountscannotchangetheconfiguration.
Theusernameismaximal8characterslong.
Everyuserandtheadministratorshoulduseapasswordwhichisusedtologininthe
TELEServiceoveratelephoneline.
Afterthreefailedretriestheconnectionishangedup,soyoumustcallagain(notlikethe
originalTSadapter).
Afterchangingthepasswordforauser/administratoryoumustretypeitagaincorrectly.
http://www.tpapartner.de/ftp/pub/handbook/en_Handbuch%20MPIPPI.html 36/63
1/20/2016 Handbuch
YoucanenteracallbacknumberwhichisusedforacallbackfromtheTSadapter.Afteryou
dialedthenumberoftheTSadapter,youareaskedforusernameandpassword.Incasethe
usernameandpasswordisvalid,theconnectionishangupandtheTSadaptercallsbackthe
configuredcallbacknumber.
6.5.5Index"GSM/ISDN/SMS":
Informationaboutthethreedifferentdevices:
AnalogModem::
Type Youcouldchoosethelocationofthemodem.
ISDNModem:
ChoosethetypeoftheISDNnetwork:
AT&T5ESS
NothernTelecomDMS100
Type EuroISDNNET3(Standard)
INS64
USNI1
VN4
Choosethetransferprotocoltype:
http://www.tpapartner.de/ftp/pub/handbook/en_Handbuch%20MPIPPI.html 37/63
1/20/2016 Handbuch
Modemlike
V.120
Protocol X.75(Standard)
MLPPP
SoftBonding
HDLC
CLEAR
MultipleSubscriberNumberisusedforallISDNchannels.
MSN
IfemptynoMSNisused.
GSMModem:
PINnumberoftheSIMcard,uptoeightnumericcharacters(onlyforTELE
PIN
SERVICEGSM).
WiththebuttonProvidertheprovidercouldbechoosen.
Readthelistofproviderscouldbeelapsemorethanaminute.
Intheendthepossibleproviderarelistedforselection.WithAutomaticthe
GSMModemtriestoconnectautomaticallytoaprovider.Ontherightsideofthe
button,theactualusedselectionisdisplayed.
DisplayDescription:
Automatic:TheproviderisautomaticallysearchedandselectedfromtheGSM
Provider modem.
Manual:TheProviderisselectedmanuallyfromtheGSMModem
nonetworkregistered:NoconnectiontotheGSMnetwork,thereceivequality
istoobad
setformat:Theformatoftheproviderisset
Manual/automatic:Themodemtriestoselectmanuallytheprovider,ifthisfails
anautomaticsearchisdone
unknown:UnknownresponsefromGSMModem
ThebuttonRefreshreadsthesignalstrengthfromthemodem,thequalityis
displayed.
DisplayDescription:
Unknown:UnknownstateoftheGSMnetwork
noregistration:ThemodemisnotregisteredintheGSMnetwork,noprovider
found
registrationdenied:RegistrationintheGSMnetworkisdenied
Searchnetwork:InSearchforaGSMProvider
GSM:AttachedtoGSM
GSM(ROAMING):AttachedtoGSM,butwithaRoamingPartner.Thiscould
Refresh leadtohighcosts!
Theradioqualityisdisplayed,togetherwiththebiterrorrate.
ValueDescription:
http://www.tpapartner.de/ftp/pub/handbook/en_Handbuch%20MPIPPI.html 38/63
1/20/2016 Handbuch
99Nonetwork,noreceive
00Very,verybadreceivequality
01Verybadreceivequality
02to09Badreceivequality
10to17Mediumreceivequality
18to25Normalreceivequality
26to30Goodreceivequality
31Bestreceivequality
InformationabouttherestoftheIndexGSM/ISDN/SMS:
SMS:
Switches:
NO
SENDSMS
RECEIVESMS
SEND+RECEIVESMS
DMTFCONFIRMATION
SENDSMS+DTMFCONFIRMATION
RECEIVESMS+DTMFCONFIRMATION
SEND+RECEIVE+DTMFCONFIRMATION
SENDMAIL
SENDMAIL+SENDSMS
http://www.tpapartner.de/ftp/pub/handbook/en_Handbuch%20MPIPPI.html 39/63
1/20/2016 Handbuch
SMS SENDMAIL+RECEIVESMS
SENDMAIL+SEND+RECEIVESMS
SENDMAIL+DTMFCONFIRMATION
SENDMAIL+SENDSMS+DTMFCONFIRMATION
SENDMAIL+RECEIVESMS+DTMFQUITTUNG
SENDMAIL+SEND+RECEIVE+DTMFCONFIRMATION
Attention:beforesettingONcheckconfiguration,afteractivatingthe
device
willgoontheMPIbusandtriestoconnecttothedefinedPLC.
ReceiveofSMSonlywithTELEServiceGSMReceiveofDTMFonly
withTELEServiceGSM
BusaddressTS localstationaddress(shouldnotbeusedtwiceintheMPI/Profibus!)
fromthisstationaddresstheflagwordanddatablockisaccessedfor
BusaddressCPU
communication
Communicationflag communicationflagword(thefirstbyteisthecommand,thesecondis
word thestate).Useevenoperandaddresses.
Communicationdata
AddressoftheCPUintheBus
block
ConfiguretheSMSProvidertouse,includingtype,phonenumber
andcharcode.
Provider0/1/2/3 1. FirstInput:Chooseatypeofthetransmission.
2. SecondInput:Telephonenumberoremailaddress.
3. ThirdInput:Chooseacharacterencoding.
NTPServer InputforanNetworkTimeProtocollServer
Erroranalysis::
Thepossibleerrorconditionsforthemodem,mpibusproblemsorotherproblemsaredisplayedin
thistextfield.
Firstthemodemrelatedinformationisshown:
Message
Modemready
Modemerror
Noanswerfrommodem
Modemdetectsring
Endofconnection
connectedviamodemline
Nodialtonedetected
Phonelineortelephonebusy
Phonenumberisblacklistedinmodem
Phonenumberdelayed.Accessdeniedfor1minute.
Faxcalldetected
Datacalldetected
unknownerror
Theselecteddirectaccessnumbernotconfigured
TheconfiguredPINNumberiswrongfortheinsertedSIMCard
TheSIMCardisnotorwronginsertedortheSIMCardisa5VType
PossibleMPIBuserrormessages
MPI/ProfibusConfigurationerroneous
TimeoutatMPI/Profibusdetachfromdevice.
ThelocalstationaddressisusedtwiceintheMPI/Profibus.
A20/M20/TC35Modemoperation
TheMPI/Profibusisnotcorrectlyconfigured
TheHSAisnotconfiguredoptimal
TheMPI/ProfibusBaudrateisnotdetectable
OverflowintheinternalMPIReadbuffer
OverflowintheinternalLANReadbuffer
http://www.tpapartner.de/ftp/pub/handbook/en_Handbuch%20MPIPPI.html 40/63
1/20/2016 Handbuch
OverflowintheserialBuffer
TheselectedMPI/ProfibusBaudrateiswrong
OverflowininternalLANWritebuffer
LANRecieveError
LANSendError
ThePDNumberriswrong
ThetransferredSAPiswrong/unknown
ErrCode01:TheDestinationaddress(XXX)ofaStateprotocol>127detected.Inthe
MPI/ProfibusBustherearenostationspossiblewhichstationnumberisgreaterthan127.
(FC=YYh)
ErrCode02:AtstateprotocoltheSourceAddressisdetectedas127.ThisistheBroadcast
addresswhichisnotpossible.
ErrCode03:ThereceivedStateprotocolsdestinationaddress(XXXrespectivelyYYY)does
notexistintheMPIBus.(FC=ZZh)
ErrCode04:Thefunctioncode(YYh)ofthereceivedStateprotocolfromXXXisincorrect.
The7thBitisHigh,butaccordingtothespecificationtheBithastobelow.
ErrCode05:AStateprotocolhasbeenreceived.Butthefunctioncode(YYh)meansthatthe
participantisnotreadytoenterthebus.
ErrCode06:ThefunctioncodeintheStateprotocolreceivedfromXXXisunknown
(FC=YYh)
ErrCode11:Thesender(XXX)ofthereceiveddataprotocolisunknown.Tosenddatathe
participantmustgettheToken.(SSAP=YYh,FC=ZZh,length=UUU)
ErrCode12:DataprotocolwithSourceaddress255(Broadcast)isuseless.(CPU=XXX,
SSAP=YYh,FC=ZZh,length=UUU)
ErrCode13:Thesender(XXX)ofthereceiveddataprotocolisunknown.Tosenddatathe
participantmustgettheToken.(SSAP=YYh,FC=ZZh,length=UUU)
ErrCode14:The7thBitofthefunctioncodeisHigh,butaccordingtothespecificationtheBit
hastobelow.(CPU=XXX,SSAP=YYh,FC=ZZh,length=UUU)
ErrCode15:Theupper4BitoftheFunctioncodearewrong/unknown)(CPU=XXX,
SSAP=YYh,FC=ZZh,length=UUU)
ErrCode16:Unknownfunctioncodehasbeentransmittedtothecable.(CPU=XXX,
SSAP=YYh,FC=ZZh,length=UUU)
ErrCode17:DestinationSAParedefinedtill3Fhindataprotocols.(CPU=XXX,SSAP=YYh,
FC=ZZh,length=UUU)
ErrCode18:SourceSAParedefinedtill3Fhindataprotocols.(CPU=XXX,SSAP=YYh,
FC=ZZh,length=UUU)
ErrCode19:ReceivedadataprotocolwithdestinationSAP=0,Connectionrequestfrom
anotherbusparticipantwithourcable.(CPU=XXX,SSAP=YYh,FC=ZZh,DSAP=UUh)
ErrCode1A:ParticipantsaresendingdatatoourcablewithsourceSAP=0,whichmeans
thattheparticipanthasnotmadeaconnectionestablishmentorhaslostthenegotiatedSAP.
(CPU=XXX,SSAP=YYh,FC=ZZh,DSAP=UUh)
ErrCode1B:Dataprotocolwithunknowndatafunctioncodereceived.
(CPU=XXX,SSAP=YYh,FC=ZZh,DFC=UUh)
ErrCode1CDataprotocolwithunknowndatafunctioncodereceived.
(CPU=XXX,SSAP=YYh,FC=ZZh,DFC=UUh)
ErrCode1D:Receivedastateprotocolwitherrorcode.(CPU=XXX,FPGA=YYh,RAM=ZZh)
ErrCode1E:FPGAhascausedaninterruptalthoughnodatapresent.
(SD1=XXh,SD1=YYh,CPU=ZZZ,FC=UUh)
ErrCode20:UnknownprotocolatPPIMultimasterMode.(FC=XXh,Lnge=YYY)
ErrCode21:UnknownbaudrateatPPIMultimasterMode.(Baudrate=XXh)
Afterthatadditionalhintsaredisplayed.
6.5.6Index"Internet/Mail":
http://www.tpapartner.de/ftp/pub/handbook/en_Handbuch%20MPIPPI.html 41/63
1/20/2016 Handbuch
TheinternetconnectionisconfiguredbyPPP,oftenausernameandpasswordisneeded.Define
themin"InternetaccessoverPPP".
Attention:ThisisNOTtheusernameandpasswordofyourEMailaccount!
Inthenextsection"Mail"theEMailaccountisdefined:
InternetaccessoverPPP:
Username UsernamefortheInternetaccess
Password UserpasswordfortheInternetaccess
Mail:
Server NameoftheSMTPEmailServers,whichisusedtosendtheEMail.
SourceEMailAddress
Mailfrom
(shouldbefromthesameFreemailer,insteadadeliveryisoftennotpossible)
NameoftheUseraccount
Username
(oftentheEMailaddressorCustomernumber)
Password PasswordfortheEMailAccount
6.6Tuning
Thismenuisonlyusedinsomespecialcases.
Selectthedeviceandclickthebutton"Tuning"andafterthatthefollowingdialogisdisplayed:
http://www.tpapartner.de/ftp/pub/handbook/en_Handbuch%20MPIPPI.html 42/63
1/20/2016 Handbuch
Thefollowingconfigurationispossible,itwillbetransferredtotheCablebypressingthebutton
OK.
TheconfigurationissavedpermanentlyintheFlashROM:
AtProToolRTthecommunicationcouldbreakdown,becausethe
MPICableistransferringtheanswerprotocoltofast.Inthiscase
Delaybeforesend
youcouldinsertatimein0.1msticks.Insertatfirst300,togreat
valuesarepreventingthecommunication.
SomeTouchpanelshastheproblem,thatwhentheygetawrong
versioninformationtheyneverretrytoconnect(andthenthe
HMICableversion
correctversionistransferred).InthiscasetheHMIversion
informationcouldbetransferredimmediately.
WhenusingtheA20orM20Terminal,thecontrollinesonthe
serialportarenotused.InthatcasetheTELEServicefunctionis
A20Terminal notworking.Withthispropertythecontrollinesarenolonger
usedandthereforetheA20/M20cancommunicateover
TELEservice.
ShowErrCode
Showserrormessagesonthedisplayoftheconnecteddevice
messagesindisplay
Bootsettings:
Normally the MPICable automatically selects the correct bus type, no changes are needed. In
specialcasestheMPIBuscouldbeselectedasPPI.
Forexample:ThisapplicationandthePLCarepoweredonatthesametime.Theapplicationis
communicatingimmediatelywith the cable, the PLC is booting, in this case the MPIBus is not
running. The MPIBus is erroneous, so no communication is starting. If this occurs you could
choose,thatthecableisworkingasMPIAdapteronly.
Language:
Youcouldselectthelanguagewhichisusedonthecable(GermanorEnglish).
S5onMPImodeoff:
Deactivatestemporarythe"S5onMPI"function,thecabledoesn'tpollthebusanymore.
sendresettocable:
http://www.tpapartner.de/ftp/pub/handbook/en_Handbuch%20MPIPPI.html 43/63
1/20/2016 Handbuch
Sendresettocable.
Console:
Showssomeinformationaboutthestatusoftheconnection.
6.7Factorydefaults
Thisbuttonsetstheconfigurationoftheselecteddevicetofactorydefaults.
6.8PPIBootoff
InPPIbootmodeS7IFCcannotcommunicatewiththecable.TodisablethePPIbootmode,click
onthebuttonPPIBootoff.Inthefollowingdialogyoumustselecttheserialportwherethecable
isconnected:
6.9EmergencyLoader
LANproductsrunninginemergencyloaderareautomaticallyfoundbyS7IFC:
AfteraclickonEmergencyLoaderthefollowingdialogappears:
http://www.tpapartner.de/ftp/pub/handbook/en_Handbuch%20MPIPPI.html 44/63
1/20/2016 Handbuch
OnaclickonYestheemergencyloadertriestorunthemainprogramofthefirmware.
OnaclickonNotheemergencyloadertriestorewritethecompletefirmware.
7MPIcablemanager
7.1Description
TheMPIcablemanagerallowsyoutoinstallanupdateinyourcablesandmodulesandconfigure
them.
TheMPIcablemanagercanbeusedforthefollowingproducts:
MPILANcableArt.ID.9352LAN
S7LANmoduleArt.ID.9352LANCon
MPIUSBcableArt.ID.9352USB
S7USBmoduleArt.ID.9352S7USB
MPIIIcable(USBoperation)Art.ID.9352+9352.1
MPI/PPIcableArt.ID.9350
TeleServiceArt.ID.9377(ANALOG/ISDN/GSM)OP
MPI/PPIprofibusmodemArt.ID.9379(G)OP
7.2Installation
1. Download the MPIKabelmanager from the productpage of your MPIproduct and start the
installation.
NextclickontothebuttonNext.
Thenclick"Continue".
http://www.tpapartner.de/ftp/pub/handbook/en_Handbuch%20MPIPPI.html 45/63
1/20/2016 Handbuch
3.Selectinthisdialogtheprogramfolderforthe
MPIcablemanagerstartupitems.
Thenclick"Continue".
4.Waitfortheinstallationofthefiles.
5.Endtheinstallationafterasuccessfulcopyof
datawith"Finish".
7.3Overview
7.3.1Language
AfterstartingtheapplicationthetabLanguageisdisplayedatfirst:
http://www.tpapartner.de/ftp/pub/handbook/en_Handbuch%20MPIPPI.html 46/63
1/20/2016 Handbuch
InthisDialogyoucouldchoosetheusedlanguageintheapplication.
YoucouldchoosebetweenGermanandEnglishandconfirmbyclickingonthedesiredlanguage.
7.3.2Interface
InsetinterfaceyoucanchoosetheCOMportyoudeviceisconnectedat.OnlytheCOMport
whichwasaktiveatstartingtheMPIKabelManagerareshown.
SearchupdatetheCOMportlistedinsetinterfaceandputtheKabelmanagertotherespective
COMport.
ForaccessquerychooseDirectifyourproduct
connects via USBcable or Nullmodemcable.
Modemifyourproductconnectsviatelephone
lineorTELENetworkifyourproductconnects
withaTELENetworkdeviceviatelephoneline.
ThebarsbelowshowsatwhichCOMportsomethingwasfoundornot.
7.3.3Update
http://www.tpapartner.de/ftp/pub/handbook/en_Handbuch%20MPIPPI.html 47/63
1/20/2016 Handbuch
ThedisketteshowthecurrentoperatingsysteminstalledonyourPCforcorrespondingproduct.
Thecabelsymbolontherightshowtheoperatingsystemwhichisinstalledonyourproductatthe
moment.
Withthebuttondefaultsettingsyoucansetyourproductsondefaultsettings.Shouldthedevice
beoutoforderafterconfigurated.Thisbuttonisselectableaftertheversioncheck.
With Update you can install the current operating system. This button also is selectable after
versioncheck.
WithversioncheckyourcablewhichisconnectedtotheCOMPortreviewed.
Thesymbolnexttoversioncheckshowstherunningupdate.
WhileupdatedonotplugoutthecablefromthePLCorturnoffthepowersupply(The
cablewilllostalldata)!
Iftheupdateisbreakingbeforefinished,itcouldbethattheMPICabledisplaysinthefirstlineof
the LCD Load 1.50 and in the second line CheckUpd. Close the MPICableManger and
restartit.Aftercheck version (which could time about 30 seconds) and following Update the
brokenupdateisrestartedandfinished.
7.3.4Teleservice
InthisdialogthespezificconfigurationoftheTeleServiceistaken.Thereare3Tabs,wherethe
lastoneisactivated:
http://www.tpapartner.de/ftp/pub/handbook/en_Handbuch%20MPIPPI.html 48/63
1/20/2016 Handbuch
7.3.4.1Telephonebook
Atthemomentnotimplemented!
In this dialog you could define new elements or edit/erase existing elements in your telephone
book.
Youcouldeditthefollowingdata:
=>Namefortheconnection(thesearedisplayedatconnection)
=>street
=>ZIPcodeandcountry
=>TelephonenumberyoucanreachtheTSadapter
7.3.4.2Connect
Atthemomentnotimplemented!
InthisdialogtheconnectiontoanothermodemwithaMPIcableconnectedisstarted.Chooseon
therightsidethenamedconnection,thenpressconnecttoestablishit.
WithHangUpyoucouldstopanexistingconnection.
WiththebuttonStatethestateoftheconnectionisdisplayedatthelowersideofthedialog.
7.3.4.3Extra
http://www.tpapartner.de/ftp/pub/handbook/en_Handbuch%20MPIPPI.html 49/63
1/20/2016 Handbuch
Inthisdialog,allconfigurationtotheTSadapterisdone.
TheactualstateoftheMPIcableisdisplayedrightofthebuttonTSfunction,wherethefollwing
4possibleMessagescouldapear:
TSAdapterfunctionisNOTactiv.ToactivatepressTSfunction
The MPIcable acts like an PCAdapter. There will no answer for TSspezific protocols, the
attachedmodemwillnotinitializedandthebaudratetothePG/Modemisnotfixed.Thebaudrate
isdetectedautomatically.
TSAdapterfunktionisACTIVE.TodisablepressTSfunction
TheMPIcableactslikeanTSAdapter.TherewillananswertoTSspezificprotocols,theadapter
couldnowconfigured.AnattachedModemwillbeinitiliazedandthebaudratetothemodemis
fixed.
SNDERRorRCVERR
Thereisacommunicationerroratsendingorrecievingdatafromthempicable.Disconnectthe
MPIcablefromthepowersupply(PLC).ChangetothetabConnectandafterthatbacktoExtra.
If the problem remains, check the connection to the MPIcable, especially the COMport in the
dialoginterface.
With the buttons you could define which modem is used, activate or disable the TSfunction or
configuretheTSadapter:
7.3.4.3.1Setup
Inthefollwingdialogyoucouldchoosetheusedmodem.
http://www.tpapartner.de/ftp/pub/handbook/en_Handbuch%20MPIPPI.html 50/63
1/20/2016 Handbuch
7.3.4.3.2TSfunction
With this button you select the function of the MPIcable as TS or PCadapter. Right of this
buttontheactualstateoftheMPIcableisdisplayed.
7.3.4.3.3configureadapter
Inthefollowingdialogyoucould,afteractivatingtheMPIcableasTSadapter,configuretheTS
spezificsetup.
Network
http://www.tpapartner.de/ftp/pub/handbook/en_Handbuch%20MPIPPI.html 51/63
1/20/2016 Handbuch
stationrelated:
Hereyoucanconfiguratefollowing:
TheTSAdapteristheoneandonlymasterintheMPIbus
Which local stationaddress is used for the TSAdapter. Please consider that a programming
devicehasnormallythenumber0,operatorpanelhave1,PLCsuse2,FM/CPs3etc.
Please:Neverusethesamestationnumberfor2differentstations!
networkrelated:
Hereyoucanconfiguratefollowing:
TheNettypeMPIorPROFIBUS
ThetransferspeedontheMPIbus
The highest stationadress in the bus (the less you use, the more performanceon the MPIbus,
mustbecorrespondingwiththeconfigurationinthePLCs)
Modem
http://www.tpapartner.de/ftp/pub/handbook/en_Handbuch%20MPIPPI.html 52/63
1/20/2016 Handbuch
Inthisdialogyoucouldconfigurethemodemrelatedsetup.
TheInitStringiscomposedoutofseveralcommandstothemodem:
AT=>startcommand
&F=>usefactorysettings
E0=>Echooff
L1=>loudnessofspeakerislow
M1=>speakerisonatconnection
Q0=>outputofthereturnvalues
V1=>returnvaluesplaintext
&C1=>DCDshowsstatusofthecarriersound
S0=1=>automaticconnectionafter1ring
TheHangUpStringiscomposedof2elements:
+++=>Changetocommandmode
AT=>startcommand
H=>HandUpconnection
Therare2possiblecallingtechnics:
MFVtone,thetelphonenumberistransferbyseveralfrequencies
IWVpulse,thetelephonenumberistransferedwiththecountofseveralpulsesontheline
When you must a precall to establish a call outside your company, you could define it at
Amtskennzahl.
Whenthemodemshouldwaitforafreeline,soyoushouldsetthecorrespondingcheckbox.
Atnumberofretriesyoucouldconfigurethenumberofretriesforaconnectionbeforethecallis
stopped.
When using a retry you could choose the seconds which the application should wait between
calls.
Serialparameter
http://www.tpapartner.de/ftp/pub/handbook/en_Handbuch%20MPIPPI.html 53/63
1/20/2016 Handbuch
InthisdialogthetransferratebetweenmodemandTSAdapterisselected.
Thetransferratecouldchoosenbetweenthefollwingvalues:
2400,4800,9600,19.2k,38.4k,57.6kand115.2kBaud
The Parity could be choosen, but this is modemdependant because some modems could not
transfertheparitybit:
None:(Thereisnoparitytesting)
Odd:(Thenumberofonebitsareodd)
Even:(Thenumberofonebitsareeven)
Password
TheAccessoveratelephonelineonthePLCcouldbeconfiguredinthisdialog.
http://www.tpapartner.de/ftp/pub/handbook/en_Handbuch%20MPIPPI.html 54/63
1/20/2016 Handbuch
TheAdministratorcouldchangetheconfigurationoveratelephoneline,wherean2Usercould
notchangetheconfiguration.
TheUserNameismaximal8Charslong.Everyuserandtheadministratorcoulduseapassword
whichisusedtologintothePLCoveratelephoneline.Thesehavetoenterforeachnewcall.
After3wrongretriestheconnectionishangedup,soyoumustcallagain(Notsowithanoriginal
TSadapter).
Afterchangingthepasswordforoneuser/administratoryoumustretypeitagaincorrectlybefore
itisused.
IncallbacknumberyoucoulddefineatelephonenumberwhichisusedforcallbackfromtheTS
adapter.AfteryouconnectwiththeTSadapter,youareaskedforyourusernameandpassword.
When the correct password and username is transfered, the connection is hangedup and the
TSadapteriscallingbackthisconfiguredcallbacknumber.
GSM/ISDN/SMS
Analogmodem:
YoucouldchoosetheLocationoftheModem.
ISDNmodem:
http://www.tpapartner.de/ftp/pub/handbook/en_Handbuch%20MPIPPI.html 55/63
1/20/2016 Handbuch
Type:ChoosethetypeoftheISDNnetworkswitch:
AT&T5ESS
NothernTelecomDMS100
EuroISDNNET3(Standard)
INS64
USNI1
VN4
Protocol:Choosethetransferprotocoltype:
Modemlike
V.120
X.75(Standard)
MLPPP
SoftBonding
HDLC
CLEAR
DN/MSN:DirectoryNumberresp.MultipleSubscriberNumberIsusedforbothISDNchannels.
Whenusingthenumber255noDN/MSNisused.
GSMmodem:
http://www.tpapartner.de/ftp/pub/handbook/en_Handbuch%20MPIPPI.html 56/63
1/20/2016 Handbuch
PIN:PINNumberoftheSIMCard,upto8numericchars,(onlyforTELESERVICEGSM).
Provider: With the button Provider the provider could be choosen. Reading of the list of
providers could be elapse more than a minute. At end the possible provider are listed for
selection.WithAutomatictheGSMModemtriestoconnectautomaticallytoaprovider.Onthe
rightsideofthebutton,theactualusedselectionisdisplayed.
DisplayDescription:
Automatic:TheproviderisautomaticallysearchedandselectedfromtheGSMmodem.
Manual:TheProviderisselectedmanuallyfromtheGSMModem
nonetworkregistered:NoconnectiontotheGSMnetwork,thereceivequalityistoobad
setformat:Theformatoftheproviderisset
Manual/automatic: The modem tries to select manually the provider, if this fails an automatic
searchisdone
unknown:UnknownresponsefromGSMModem
Refresh:ThebuttonRefreshreadsfromtheModemthereceivequality,thequalityisdisplayed.
DisplayDescription:
Unknown:UnknownstateoftheGSMnetwork
noregistration:ThemodemisnotregisteredintheGSMnetwork,noproviderfound
registrationdenied:RegistrationintheGSMnetworkisdenied
Searchnetwork:InSearchforaGSMProvider
GSM:AttachedtoGSM
GSM(ROAMING):AttachedtoGSM,butwithaRoamingPartner.Thiscouldleadtohighcosts!
TheReceiveQualityisdisplayed,alsoasvaluetogetherwiththebiterrorrate.
ValueDescription:
99Nonetwork,noreceive
00Very,verybadreceivequality
01Verybadreceivequality
02to09Badreceivequality
10to17Mediumreceivequality
18to25Normalreceivequality
26to30Goodreceivequality
31Bestreceivequality
http://www.tpapartner.de/ftp/pub/handbook/en_Handbuch%20MPIPPI.html 57/63
1/20/2016 Handbuch
Messages:
Thepossibleerrorconditionsforthemodem,mpibusproblemsorotherproblemsaredisplayed
inthistextfield.Firstly,themodemrelatedinformationisshown:
Message
Modemready
Modemerror
Noanswerfrommodem
Modemdetectsring
Endofconnection
connectedviamodemline
Nodialtonedetected
Phonelineortelephonebusy
Phonenumberisblacklistedinmodem
Phonenumberdelayed.Accessdeniedfor1minute.
Faxcalldetected
Datacalldetected
unknownerror
Theselecteddirectaccessnumbernotconfigured
TheconfiguredPINNumberiswrongfortheinsertedSIMCard
TheSIMCardisnotorwronginsertedortheSIMCardisa5VType
FollowingthepossibleMPIBuserrormessages
Message
MPI/ProfibusConfigurationerroneous
TimeoutatMPI/Profibusdetachfromdevice.
ThelocalstationaddressisusedtwiceintheMPI/Profibus.
A20/M20/TC35Modemoperation
TheMPI/Profibusisnotcorrectlyconfigured
TheHSAisnotconfiguredoptimal
TheMPI/ProfibusBaudrateisnotdetectable
OverflowintheinternalMPIReadbuffer
OverflowintheinternalLANReadbuffer
OverflowintheserialBuffer
TheselectedMPI/ProfibusBaudrateiswrong
OverflowininternalLANWritebuffer
LANRecieveError
http://www.tpapartner.de/ftp/pub/handbook/en_Handbuch%20MPIPPI.html 58/63
1/20/2016 Handbuch
LANSendError
ThePDNumberriswrong
ThetransferredSAPiswrong/unknown
ErrCode 01: The Destination address (XXX) of a State protocol > 127 detected. In the
MPI/ProfibusBus there are no stations possible which station number is greater than 127.
(FC=YYh)
ErrCode02:AtstateprotocoltheSourceAddressisdetectedas127.ThisistheBroadcast
addresswhichisnotpossible.
ErrCode03:ThereceivedStateprotocolsdestinationaddress(XXXrespectivelyYYY)does
notexistintheMPIBus.(FC=ZZh)
ErrCode04:Thefunctioncode(YYh)ofthereceivedStateprotocolfromXXXisincorrect.
The7thBitisHigh,butaccordingtothespecificationtheBithastobelow.
ErrCode05:AStateprotocolhasbeenreceived.Butthefunctioncode(YYh)meansthatthe
participantisnotreadytoenterthebus.
ErrCode 06: The functioncode in the Stateprotocol received from XXX is unknown
(FC=YYh)
ErrCode11:Thesender(XXX)ofthereceiveddataprotocolisunknown.Tosenddatathe
participantmustgettheToken.(SSAP=YYh,FC=ZZh,length=UUU)
ErrCode 12: Dataprotocol with Sourceaddress 255 (Broadcast) is useless. (CPU=XXX,
SSAP=YYh,FC=ZZh,length=UUU)
ErrCode13:Thesender(XXX)ofthereceiveddataprotocolisunknown.Tosenddatathe
participantmustgettheToken.(SSAP=YYh,FC=ZZh,length=UUU)
ErrCode14:The7thBitofthefunctioncodeisHigh,butaccordingtothespecificationtheBit
hastobelow.(CPU=XXX,SSAP=YYh,FC=ZZh,length=UUU)
ErrCode15:Theupper4BitoftheFunctioncodearewrong/unknown)
(CPU=XXX,SSAP=YYh,FC=ZZh,length=UUU)
ErrCode 16: Unknown functioncode has been transmitted to the cable. (CPU=XXX,
SSAP=YYh,FC=ZZh,length=UUU)
ErrCode17:DestinationSAParedefinedtill3Fhindataprotocols.(CPU=XXX,SSAP=YYh,
FC=ZZh,length=UUU)
ErrCode 18: SourceSAP are defined till 3Fh in dataprotocols. (CPU=XXX, SSAP=YYh,
FC=ZZh,length=UUU)
ErrCode 19: Received a dataprotocol with destinationSAP=0, Connection request from
anotherbusparticipantwithourcable.(CPU=XXX,SSAP=YYh,FC=ZZh,DSAP=UUh)
ErrCode1A:ParticipantsaresendingdatatoourcablewithsourceSAP=0,whichmeans
thattheparticipanthasnotmadeaconnectionestablishmentorhaslostthenegotiatedSAP.
(CPU=XXX,SSAP=YYh,FC=ZZh,DSAP=UUh)
ErrCode1B:Dataprotocolwithunknowndatafunctioncodereceived.
(CPU=XXX,SSAP=YYh,FC=ZZh,DFC=UUh)
ErrCode1CDataprotocolwithunknowndatafunctioncodereceived.
(CPU=XXX,SSAP=YYh,FC=ZZh,DFC=UUh)
ErrCode1D:Receivedastateprotocolwitherrorcode.
(CPU=XXX,FPGA=YYh,RAM=ZZh)
ErrCode1E:FPGAhascausedaninterruptalthoughnodatapresent.
(SD1=XXh,SD1=YYh,CPU=ZZZ,FC=UUh)
ErrCode20:UnknownprotocolatPPIMultimasterMode.(FC=XXh,Lnge=YYY)
http://www.tpapartner.de/ftp/pub/handbook/en_Handbuch%20MPIPPI.html 59/63
1/20/2016 Handbuch
ErrCode21:UnknownbaudrateatPPIMultimasterMode.(Baudrate=XXh)
Afterthatadditionalhintsaredisplayed.
SMS:
SMS:SwitchesProcessingOFF/OnlyReceive/OnlySend/ReceiveandSend.
Attention:beforesettingONcheckconfiguration,afteractivatingthedevicewillgointotheMPI
BUS and tries to connect to the defined PLC. Receive of SMS only with TELESERVICEGSM
ReceiveofDTMFonlywithwithTELESERVICEGSM
TS:localstationaddress(shouldnotbeusedtwiceintheMPI/Profibus!)
PLC:fromthisstationaddresstheFlagwordandDatablockisaccessedforcommunication
MW:communicationflagword(thefirstbyteisthecommand,thesecondisthestate).Useeven
operandaddresses.
DB:communicationdatablock.
Provider 1/2/3/4: Configure the SMSProvider to use, including type, phonenumber and char
code.
Internet/Mail
7.3.4.3.4Importparameter
WiththisbuttonyoucouldimporttheparameterfromanASCIIfile.Thisfileiscompatibletothe
originalfileformat.
7.3.4.3.5Exportparameter
WiththisbuttonyoucouldexporttheparametertoanASCIIfilewhichhasthesamefileformatas
theoriginal.
7.3.5Tuning
http://www.tpapartner.de/ftp/pub/handbook/en_Handbuch%20MPIPPI.html 60/63
1/20/2016 Handbuch
Thistabisonlyusedinsomespecialcases.IfyoupressthebuttonCheckAdapterthecableis
connectedundafterthatthefollowingdialogisdisplayed:
There are the following configuration possible, they will be transferred to the MPICable by
pressingthebuttonTransfer.TheconfigurationissavedpermanentlyintheFlashROM:
Timetosend:
http://www.tpapartner.de/ftp/pub/handbook/en_Handbuch%20MPIPPI.html 61/63
1/20/2016 Handbuch
AtProToolRTthecommunicationcouldbreakdown,becausetheMPICableistransferringthe
answerprotocoltofast.Inthispropertyyoucouldinsertatimein0.1msticks.Insertatfirst300,to
greatvaluesarepreventingthecommunication.
HMICableVersion:
SomeTouchpanelshavetheproblem,thatwhentheygetawrongversioninformationtheynever
retry to connect (and then the correct version is transferred). In this case the HMIversion
informationcouldbetransferredimmediately.
A20Terminal:
When using the A20 or M20Terminal, the controllines on the serial port are not used. In that
case the teleservicefunction is not working. With this property the controllines are no longer
usedandthereforetheA20/M20cancommunicateoverteleservice.
Bootconfiguration:
Normally the MPICable automatically selects the correct bustype, no changes are needed. In
specialcasestheMPIBuscouldbeselectedasPPI.
Forexample:ThisapplicationandthePLCarepoweredonatthesametime.Theapplicationis
communicating immediately with the cable, the PLC is booting, in this case the MPIBus is not
driven.TheMPIBusiserroneous,sonocommunicationisstarting.
Ifthisoccursyoucouldchoose,thatthecableisworkingasMPIAdapteronly..
Language:
Youcouldselectthelanguagewhichisusedfromthecable(GermanorEnglish).
8Technicaldata
TechnicalSpecifications:
Supplyvoltage: 24V/DC+/20%
Powerconsumption: 2watt
Display: doublelinedLCDdisplay
Handling/Configuration: KabelmanagerSoftware
tothePLC:
PPI/MPIbusinterface:9,6KBd187,5KBd
Interfaces:
tothePD/PC:
RS232:9,6KBd115,2KBd
Galvanicseparation: 1000VPPI/MPIbustothePC
Operatingtemperature: 555C
Case: ABSplasticcase
Dimensions: 146x41x29mm
8.1PinningRS232
Direction (of
PinNr. Notation Signalname
cable)
1 DCD DataCarrierDetect In
2 TXD TransmittedData Out
3 RXD ReceivedData In
4 DSR DataSetReady Out
5 GND SignalGround
6 DTR DataTerminalReady In
7 CTS CleartoSend Out
8 RTS RequesttoSend In
http://www.tpapartner.de/ftp/pub/handbook/en_Handbuch%20MPIPPI.html 62/63
1/20/2016 Handbuch
9 NC NotConnected
ThiscableisdesignedtobeconnecteddirectlyonaCOMinterfaceofaPC.Thecablecanbe
lengthenedbya1:1cabletothePCupto15mmaximum.Thecableshouldhaveagoodquality.
8.2Pinassignment
Direction (of
PinNo. Notation Signalname
cable)
1 NC NotConnected
2 M24V Groundofthe24V In
3 Ltg_B DatalineB BiDir.
4 RTSAS RequesttoSendfromthePLC In
5 M5V Groundofthe5V IN
6 P5V 5Voutput Out
7 P24V 24VSupplyinput IN
8 Ltg_A DatalineA BiDi
9 RTSPG RequesttoSendtothePLC Out
Note
The shield is attached with the MPI/PPI connector via the shield of the adapter casing.Tofind
directlyattendedPLCs,RTSASandM5Vmustbeconnectedinthecable.P5Vmeansaoutput
of the cable and works only as an output for a bustermination with resistors. This 5V output
doesntdriveanyloadandhavea100Rresistorinsidehisdirection.
observe:
Dontlengthentheconnectionbya1:1cabletothePLC,becausethereare24Vand5Vinsideof
thecable.Thequalityofthebussignalwillberisendown!
Tolengthentheconnection,pleaseuseaMPINETZAdapterandconnectonlythesignalsLtg_A
andLtg_B1:1andtheshieldatbothsidesofthemetalcasingattheSUBDconnector
Foranextensionofthecablepleasesupplythecablewithexternalpowerandonly
prolong the signals Ltg_A and Ltg_B 1:1. Connect the shield on the SUBD
connector,possiblyincludeaterminationresistors(onthebusEND).
http://www.tpapartner.de/ftp/pub/handbook/en_Handbuch%20MPIPPI.html 63/63