REL NO LTR NO REVISION DWN CKD APVD DATE
ECO - 120791 B 1 SEE SHEET TWO NAS NAS T_AJAYI 04NOV11
D
11 SEE SHEET SEVEN NAS NAS T_AJAYI 04NOV11
D
Notes:
1. Fusing requirements for Arc flash protection for TB7 (Bus/Utility Voltage Sense)*: If your potential circuits have available incident energy > 1.2 Cal/cm2 or 5J/cm2 then you need to protect for arc flash in the lines feeding TB7**.
Available Incident energy > 1.2 Cal/cm2 or 5J/cm2 is typically found when any of the the following is true:
B) Paralleled OR
A) Fuse rating: 600Vac, 0.5A, AIC=200kA, fast acting, current limiting, Class CC (e.g. Ferraz Shawmut ATMR or equiv.)
B) Use 600Vac rejection type fuse holder with AIC=200kA rating, e.g. Ferraz Shawmut 30323R or equiv.
**Fusing protecting the circuit feeding TB7 must also meet all local code requirements.
0630-2941
0630-3613
0630-3080
0630-2867
A 0630-2868 A
0630-2873
DIM
DIAGRAM, SCHEMATIC
HOLE
.X ` 10.00-17.49 +0.25/-0.13
17.50-24.99 +0.30/-0.13 DATE 01-04-2011 SITE CODE
.XX` - CONFIDENTIAL - DWG DWG
PGK
FOR INTERPRETATION FIRST USED ON SHEET
SIZE REV
PROPERTY OF CUMMINS
ANG TOL: ` SCALE
:
POWER GENERATION
OF DIMENSIONING AND
TOLERANCING, SEE
ASME Y14.5M-1994 VTA28 D A035J417 1 OF 7 A
6 5 4 3 2 1
3 ADDED WAKE UP CONNECTIONS TO AUX 101 ZONE C3. NAS NAS T_AJAYI 04NOV11
9 ADD WARNING SYMBOL ZONE B3 NAS NAS T_AJAYI 04NOV11
10 ADD TEXT: SEE FUSING REQUIREMENTS ON SHEET 1, ZONE B3 NAS NAS T_AJAYI 04NOV11
Sw B+ K7 SW B+ T26
REMOTE E-STOP 3300 TB1-16 1B P2-12
1A 1B
5 4 S7-B 3B
JUMPER 1 2A 2B J20-11
1 2 3300 TB1-15 2B
3A 3B P2-5 6 1 P-SWB+ P2-13
REMOTE J20-11 Starter Disconnect Input P3-B
JUMPER 2 4A 4B
E-STOP 4 3
REMOVE K10-86
1B
E-STOP B+
PCC3300 J20-13 Relay Coil B+ Supply
J20-16 Oil Priming Pump Relay Driver
Starter K9
5 4
X10 (10A) B1-BAT P3-A
P3-C
HEATER CONTROL (P3)
D D
JUMPERS 2B X20 (20A)
P20-3 B1-BAT
P2-14 ENG SP4
1 AND 2 TO
INSTALL
3B BASEBOARD P20-15 P2-6 6 1 P2-10
K4-S1
SP4 1B
FUSED B+ K9-1 S1
K4
S2
4B P2-15
REMOTE E- P20-14 FSO K8 TB-BAT
2B
STOP K16-A X21 (20A)
P20-9 5 4 3B B1-BAT K4-BAT K4 K4+
USER INTERFACE GND P20-10
P20-20 P2-7 6 1
P21-9 (AUX 105)
HMI-SP1
4B
5B
P20-21 BATTERY Starter 1
LOCAL E-STOP B+ F-FSO 3A SwB+ - 3B
PART NUMBERS P20-5 A B P2-11
FSO (K1) CHARGING
3 4 ALTERNATOR G1-B+
FUSED B+ PCC3300: 0327-1601 P20-17 S7-C B+ 24VDC
E-STOP 2 1 INPUT (WAKE-UP ON OPEN) P25-2 P20-22 S7-B GND
COOLANT
G1-D+
B1-BAT BT1
LEVEL (S7)
P20-2
P20-4
S7-D SIG G KS
RETURN P25-6 HARNESS, INTERFACE SHIELD GROUNDED IN FOUR PLACES
(WORT BOX): HARNESS ENGINE:
A035N938
P20-7
G1-GND
M BT2
A035H282 P20-12
TB15-1 GND A035P061 K10-SP B+ RETURN
P20-1 1B GND-ENG
P29 must be
HMI 320 PC
TOOL
TB15-3 RS485 A
TB15-4 RS485 B
disconnected to
use PC Tools on
P20-6
P20-18 3B
P2-8
B1-GND KS B1-SW1
BARGRAPH
1B BUS L1
2B BUS L2 USE PTs
IF LL
TB7-1
TB7-2 9 6 J4-5
SEE SHEET 5
SEE SHEET 5
SEE SHEET 5
SEE SHEET 5
LEGEND
3B BUS L3 TB7-3 TB15-5 WAKE-UP3
VOLTAGE FUSED B+ - 2B SEE SHEET 5
P1-3 PCC NET A (+) 4B BUS L4 >600VAC TB7-4 A B
PART NUMBERS AUX 101 IS REQUIRED FOR EXHAUST SEE SHEET 5 OPTIONAL
P1-4 PCC NET B(-) P26-2 P1-5 (AUX 101) TEMPERTURE SENSING.
HMI 114: MODBUS
P1-5 SYSTEM WAKE-UP J26-3 AVR PWM- 1B
0300-6366-02 SEE FUSING REQUIREMENTS ON SHEET 1.
J26-5 AVR B+ RETURN FACTORY CONNECTIONS
P6-2 B+ RETURN J26-6 N/A 1
P12-1 3B
P6-1 HMI FUSED B+ J26-7 FIELD CURRENT-
D1 2 4B FAST ON CONNECTOR
P12-4
J26-8 B+ RETURN 3 5B
P12-2
J26-9 AVR B+
P12-5 HARNESS, SET SCREW TERMINAL
HARNESS, J26-14 FIELD CURRENT+
P12-3 INTERFACE
ALTERNATING PCC3300 TO AUX 105: J26-16 AVR PWM+ LOW COOLANT TEMPERATURE (S4)
P12-6 CURRENT: PLUG CONNECTOR
A035G905 J26-17 N/A
A034Y614 OR
J26-18 KEYSWITCH B+ OUT
- GENSET VOLTAGE
P22-1
A041E318
P26-15
RING TERMINAL
DRIVER ALTERNATOR P22-2
P26-1 P1939 SHLD
RATING P26-10 P1939 (-)
B S:
P22-3
P22-4
P26-11 P1939 (+) 120 ohm Opens @ 85F, Closes @ 65F B
P26-12 PCC NET A (+)
4 AMPS P26-13 PCC NET B (-)
PEAK : P26-4 SHLD
6 AMPS
+
AUX 104 FUEL ACTUATOR (6AMP MAX)
ACT (-)
P21-12 GOV POWER STAGE ACT (+)
TERMINAL BLOCK
AUX 105 P21-8
P21-2
Part numbers
J1-1
J1-2
P1 - 1
P1 - 2
N W V U HM ECM & AVR P21-3 120 ohm Aux 104: 0327-1507 J1-5
P1-5 GOV PS POWER
CT-23
POWERSTAGE B+ RETURN - 1B Sockets: 0323-1200 J1-3
P1-3 GOV PS POWER
CT22-1 87 / 14 85 / A1
P21-9 FUSED B+ - 3B OIL PRESSURE (E1)
K10 KEYSWITCH
CT-22 E1-B
CT22-2/3 30 / 11 86 / A2
P21-11 E1-A
CT23-1 PART NUMBERS E1-C
E-STOP B+ - 2B
CT-21 AUX 105: A028T766
CT23-2/3
G FIELD (+)
FIELD (-)
AVR CONTROL
P17-1
P17-2
P11-13 SENSE
P11-14 RETURN
P11-15 SENSE
E4-B
P11-16 RETURN
UNLESS OTHERWISE SPECIFIED, ALL SIM TO DWN
CUMMINS POWER GENERATION
PC TOOL N_SCHOTTLER
TB15-1 GND DIMENSIONS ARE IN MILLIMETERS
J5-1 DO NOT SCALE PRINT CKD
RS485 SHIELD COOLANT TEMP RIGHT BANK (E3) X ` 0.00- 4.99 +0.15/-0.08
N_SCHOTTLER
TB15-3 RS485 A HARNESS, INTERFACE E3-A 5.00- 9.99 +0.20/-0.10 APVD
HOLE
T_AJAYI
DIM
J5-3
J5-4
TB15-4 RS485 B PC TOOL: A040G672 E3-B .X ` 10.00-17.49 +0.25/-0.13
DATE
DIAGRAM, SCHEMATIC
J5-5
TB15-5 WAKE-UP 17.50-24.99 +0.30/-0.13 01-04-2011 SITE CODE
.XX` - CONFIDENTIAL - DWG DWG
PGK
FOR INTERPRETATION FIRST USED ON SHEET
OF DIMENSIONING AND SIZE REV
PROPERTY OF CUMMINS
ANG TOL: ` SCALE
:
POWER GENERATION
TOLERANCING, SEE
ASME Y14.5M-1994 VTA28 D A035J417 2 OF 7 A
6 5 4 3 2 1
COOLANT COOLANT
COOLANT LEVEL (S7)
D TEMP RIGHT
TEMP LEFT D
BANK (E2)
BANK (E3)
LOW COOLANT
TEMPERATURE
(S4)
MAG PICKUP
(P1)
A
C
C C
C
A
B B
OIL
OIL
K4 PRESSURE
TB-BAT TEMPERATURE
(E1)
B (E4) B
T 26 GND ENG
HMI 114
A A
CT-21
CT-23
CT-22
UNLESS OTHERWISE SPECIFIED, ALL SIM TO DWN
CUMMINS POWER GENERATION
N_SCHOTTLER
DIMENSIONS ARE IN MILLIMETERS
LOCAL E-STOP X `
DO NOT SCALE PRINT CKD N_SCHOTTLER
0.00- 4.99 +0.15/-0.08
5.00- 9.99 +0.20/-0.10 APVD T_AJAYI
DIM
DIAGRAM, SCHEMATIC
HOLE
.X ` 10.00-17.49 +0.25/-0.13
VIEW A-A 17.50-24.99 +0.30/-0.13
DATE SITE CODE
VIEW B-B .XX`
01-04-2011
- CONFIDENTIAL - FOR INTERPRETATION DWG DWG
PGK D
FIRST USED ON SHEET
SIZE REV
PROPERTY OF CUMMINS OF DIMENSIONING AND
ANG TOL: ` SCALE
:
POWER GENERATION
TOLERANCING, SEE
ASME Y14.5M-1994 VTA28 A035J417 3 OF 7 A
6 5 4 3 2 1
D D
1 2 3 4 5 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 1 2 3 4
B B B B B B B B B B B B B B B B B B B B B B B B B B B B B B B B B B B B B B B B B
C
B L L L/N L/N G L1 L2 L3 N
C
1B 2B 3B 4B 5B 6B
AUX 104
TB1 TB8
K7 K8 K9 J18
J TB3 TB5 TB10
1
J26 J14
J25
TB
15
J4 DC WIRE
J J17 ENTRANCE
B 10 B
TB
J J3 J20 9
11
J21
J2 J11
TB
15
A A
AUX 101 AUX 105 3300
DIM
T_AJAYI
DIAGRAM, SCHEMATIC
HOLE
VIEW C-C .X ` 10.00-17.49 +0.25/-0.13
DATE SITE CODE
17.50-24.99 +0.30/-0.13 01-04-2011
.XX` - CONFIDENTIAL - FOR INTERPRETATION DWG DWG
PGK D
FIRST USED ON SHEET
SIZE REV
PROPERTY OF CUMMINS OF DIMENSIONING AND
ANG TOL: ` SCALE
:
POWER GENERATION
TOLERANCING, SEE
ASME Y14.5M-1994 VTA28 A035J417 4 OF 7 A
6 5 4 3 2 1
D D
TB7 J22
J12
CT1 CT2 CT3
K16
1A 1B
K7
2A 2B
3A 3B
MODBUS
4A 4B
5A 5B
K8
1A 1B
REMOTE 2A 2B TB
J20
E-STOP 3A 3B 9
4A 4B
SWITCH (WAKE-UP) 4A 4B
1A 1B
TB
2A 2B
E-STOP B+ 3A 3B
15
C 4A 4B J25 C
1B
J26
1A
J14
2A 2B
FUSED B+ 3A 3B
4A 4B TB-10 TB-5 TB-3
5A 5B J
1A 1B 1 TB-1
2A 2B
TB-8
SW B+ 3A 3B
4A 4B
5A 5B
1A 1B
2A 2B
3A 3B J18
B+ RETURN 4A 4B
5A 5B
FFSO J1 J14
K18
ALTERNATOR
K22 K17 TEMPERATURE J2
B B
FAT J17
(2A)
1A 1B
K23 2A 2B J3 J11
BUS CT
3A 3B J10
SHORTING J21
4A 4B
BLOCK
5A 5B J4
6A 6B J11
L 1A 1B
TB
L 2A 2B 15
L/N 3A 3B HEATER
L/N 4A 4B POWER
G 5A 5B
L1 1A 1B
L2 2A 2B BUS
L3 3A 3B
VOLTAGE
N 4A 4B
A A
DIM
DIAGRAM, SCHEMATIC
HOLE
.X ` 10.00-17.49 +0.25/-0.13
DATE SITE CODE
17.50-24.99 +0.30/-0.13 01-04-2011
.XX` - CONFIDENTIAL - FOR INTERPRETATION DWG DWG
PGK D
FIRST USED ON SHEET
PROPERTY OF CUMMINS OF DIMENSIONING AND SIZE REV
ANG TOL: ` SCALE
:
POWER GENERATION
TOLERANCING, SEE
ASME Y14.5M-1994 VTA28 A035J417 5 OF 7 A
6 5 4 3 2 1
PARALLELING CIRCUIT 11 RHI1 NC CONTACT WAS NO, ZONE B6 NAS NAS T_AJAYI 04NOV11
OPTIONAL RELAYS BREAKER RELAY
CONTROL
PCC
3300 TB1 TB10
A1 13 21 43 43 ALARM
A2 14 22 44 44 RELAY K21 RTD CONNECTIONS
ALARM MODULE THERMISTOR RELAY
RESET
A2 14 22 44 44 RELAY K13 ALARM PCC 3300 TB8-7
TB1-8 A1 13 21 43 43 WHITE
TB1-9 MODULE J22-3 (W) FAT (2A)
RED D.E
A2 14 22 44 44
TB1-5 J1+ BEARING
TB1-10 B+ A1 A2 R RED RTD
GND
A1 13 21 43 43
CONFIGURABLE TB10-10 GND CIRCUIT BREAKER TRIPPED K18 16 18 26 28
J2- WHITE
PCC A2 14 22 44 44 RELAY K14 (TEMPERATURE RED
PTC W2
3300 TB8 TB1-8 MONITORING) 15 25
PC3300 TB10 Ta Tb RED RTD
TB1-9 Generator Circuit WHITE
A1 13 21 43 43
K20 TB1-10 TB10-2 Breaker RED
CONFIGURABLE GND V2
A2 14 22 44 44 RELAY K15 A1 13 21 43 43 SDE Contact RED RTD
K17
A2 14 22 44 44 WHITE
(DELAYED MAKE)
RED U2
RED RTD
TB5 PCC 3300 TB8-12 WHITE
CLOSE STATUS OUTPUT
TB8-9 RED W1
TB8-10 RED RTD
TB10-10
OPEN STATUS OUTPUT WHITE
RED
C RED
V1
C
RTD
WHITE
ALT. TEMP
THERMISTORS RED U1
RED RTD
Fuel Level
GROUND FAULT RELAY
PCC
3300 TB8 B+ RETURN - 2B
RHI1 CT1
Fused B+ - 1A
CT3
RHI1 PCC
FUSE1 3300 TB1
4A A1 A2 T1 T2
126
250
252
253
254
255
90
E
E
TEST
Terminal block - WIRING DIAGRAMS SHOWN ON THIS SHEET
1 2 3 4 ARE GENERALIZED, SEE SPECIFIC
A A A A
CONTROL BOX HEATER INSTALLATION DRAWINGS FOR EACH OPTION
FOR MORE INFORMATION.
1 2 3 4
B B B B
OPERATIONAL)
RESET
Low Fuel Shutdown
1A 2A 3A 4A 5A
ON (RELAY
1B 2B 3B 4B 5B
ALTERNATOR HEATER
HP
HA
HOLE
APV T_AJAYI
10.00-17.49 +0.25/-0.13 D DIAGRAM, SCHEMATIC
DI
.X `
M
DAT SITE CODE
17.50-24.99 +0.30/-0.13 E
01-04-2011
.XX` - CONFIDENTIAL - FOR INTERPRETATION DWG DWG
PGK D
FIRST USED ON SHEET
OF DIMENSIONING AND SIZE REV
ANG TOL: ` SCALE
:
PROPERTY OF CUMMINS
POWER GENERATION
TOLERANCING, SEE
ASME Y14.5M-1994 VTA28 A035J417 6 OF 7 A
6 5 4 3 2 1
BASEBOARD
TB1-2 PCC NET B (-) SEE SHEET 2
TB1-3 B+ RETURN SEE SHEET 2
PCC3300
PART NUMBERS TB1-5 CUSTOMER FUSED B+ SEE SHEET 2 BASEBOARD
PCC3300: 0327-
1601
TB1-4 CONFIGURABLE O/P #5 PART NUMBERS
PCC3300: 0327-
AUX 101 D
TB1-6 CONFIGURABLE O/P #1-A J2-1 RELAY 1 NO
TB1-7 CONFIGURABLE O/P #1-B 1601
TB8-1 DISCRETE INPUT RETURN REMOTE I/O J2-2 RELAY 1 COM
TB1-8 CONFIGURABLE O/P #2-A TB8-2 DISCRETE INPUT RETURN J2-3 RELAY 1 NC
TB1-9 CONFIGURABLE O/P #2-B TB8-3 DELAYED OFF RELAY DRIVER J2-4 RELAY 2 NO
TB1-10 REMOTE START RETURN TB8-4 SWITCHED B+ RELAY DRIVER J2-5 RELAY 2 COM
TB1-11 REMOTE START TB8-5 REMOTE FAULT RESET J2-6 RELAY 2 NC
TB1-12 CONFIGURABLE I/P #1 TB8-6 START TYPE J2-7 RELAY 3 NO
TB1-13 RETURN TB8-7 CONFIGURABLE INPUT #13 J2-8 RELAY 3 COM
TB1-14 CONFIGURABLE I/P #2 TB8-8 CONFIGURABLE INPUT #14 J2-9 RELAY 3 NC
TB1-15 REMOTE E-STOP SEE SHEET 2 TB8-9 CONFIGURABLE OUTPUT #4 J2-10 RELAY 4 NO
TB1-16 REMOTE E-STOP SEE SHEET 2 TB8-10 CONFIGURABLE OUTPUT #3 J2-11 RELAY 4 COM
TB8-11 LOAD DUMP RELAY DRIVER J2-12 RELAY 4 NC
TB8-12 DISCRETE INPUT RETURN
TB3-1 RETURN TB8-13 DISCRETE INPUT RETURN
TB3-2 MASTER CAN SHIELD
J3-1 RELAY 5 NO
TB3-3 MASTER CAN L
J3-2 RELAY 5 COM
TB3-4 MASTER CAN H
J3-3 RELAY 5 NC
TB3-5 CONFIGURABLE OUPUT #20 STATUS
TB9-1 KW LOAD SETPOINT J3-4 RELAY 6 NO
TB3-6 CONFIGURABLE OUPUT #21 STATUS
TB9-2 ANALOG RETURN J3-5 RELAY 6 COM
TB3-7 SPARE OUTPUT FOR FURTURE USE
TB9-3 KVAR LOAD SETPOINT J3-6 RELAY 6 NC
TB3-8 CONFIGURABLE OUPUT #22 STATUS
TB9-4 VOLTAGE BIAS OUTPUT / CONFIGURABLE ANALOGY OUTPUT #2 OUTPUT PREDICTOR
C
TB3-9 TRANSFER INHIBIT/CONFIGURABLE INPUT #20 SWITCH
TB9-5 SPEED BIAS OUTPUT / CONFIGURABLE ANALOG OUTPUT #1 OUTPUT PREDICTOR
TB3-10 RETRANSFER INHIBIT/CONFIGURABLE INPUT #21 SWITCH
TB9-6 ANALOGY RETURN J4-1 RELAY 7 NO
TB3-11 MASTER FIRST START STATUS
TB9-7 KW LOAD SHARE LEVEL J4-2 RELAY 7 COM
TB3-12 RETURN
TB9-8 NOT USED J4-3 RELAY 7 NC
TB9-9 LOAD SHARE SHIELD J4-4 RELAY 8 NO
TB5-1 GENSET CB CLOSE STATUS TB9-10 + KVAR LOAD SHARE LEVEL J4-5 RELAY 8 COM
TB5-2 GENSET CB CLOSE STATUS TB9-11 - KVAR LOAD SHARE LEVEL J4-6 RELAY 8 NC
TB5-3 GENSET CB OPEN STATUS
TB5-4 GENSET CB OPEN STATUS
J10-1 CAN H
TB5-5 GENSET CB OPEN STATUS
J10-2 CAN L
TB5-6 UTILITY CB CLOSE STATUS
J10-3 INPUT #3 CURRENT SOURCE (SEE SHEET 2)
TB5-7 UTILITY CB CLOSE STATUS
J10-4 INPUT #4 CURRENT SOURCE (SEE SHEET 2)
TB5-8 UTILITY CB OPEN STATUS TB10-1 RETURN
J10-5 INPUT #5 CURRENT SOURCE
TB5-9 UTILITY CB OPEN STATUS TB10-2 RETURN
J10-6 INPUT #6 CURRENT SOURCE
TB10-3 UTILITY CB POS A SWITCH
J10-7 5VDC SUPPLY #1 (20 mA MAX)
TB10-4 UTILITY CB POS B/CONFIGURABLE INPUT #23 SWITCH
J10-8 5VDC SUPPLY #2 (20 mA MAX)
TB10-5 UTILITY CB TRIPPED SWITCH
J10-9 INPUT #3 CURRENT RETURN (SEE SHEET 2)
TB10-6 UTILITY CB INHIBIT/CONFIGURABLE INPUT #25 SWITCH
J10-10 INPUT #4 CURRENT RETURN (SEE SHEET 2)
TB10-7 GENSET CB POS A SWITCH
J10-11 INPUT #5 CURRENT RETURN
TB10-8 GENSET CB POS B/CONFIGURABLE INPUT #26 SWITCH B
J10-12 INPUT #6 CURRENT RETURN
TB10-9 RETURN
TB10-10 GENSET CB TRIPPED SWITCH
TB10-11 GENSET CB INHIBIT/CONFIGURABLE INPUT #28 SWITCH
J11-1 INPUT #1 RETURN
TB10-12 UTILITY SINGLE MODE VERIFY/CONFIGURABLE INPUT #29 SWITCH
J11-2 INPUT #1 SENSE
TB10-13 SYNC ENABLE/CONFIGURABLE INPUT #28 SWITCH
J11-3 INPUT #2 RETURN
TB10-14 LOAD DEMAND STOP CONFIGURABLE I/P#31 J11-4 INPUT #2 SENSE
TB10-15 RAMP LOAD/UNLOAD CONFIGURABLE I/P#32 J11-5 INPUT #3 SENSE RETURN (SEE SHEET 2)
TB10-16 RETURN
J11-6 INPUT #3 SENSE (SEE SHEET 2)
TB10-17 RETURN
J11-7 INPUT #4 SENSE RETURN (SEE SHEET 2)
J11-8 INPUT #4 SENSE (SEE SHEET 2)
J11-9 INPUT #5 SENSE RETURN
J11-10 INPUT #5 SENSE
J11-11 INPUT #6 SENSE RETURN
J11-12 INPUT #6 SENSE
J11-13 INPUT #7 RETURN
J11-14 INPUT #8 SENSE (ANALOG 0-38VDC)
J11-15 INPUT #8 RETURN
J11-16 INPUT #8 SENSE (ANALOG 0-38VDC)
A A
HOLE
APV T_AJAYI
10.00-17.49 +0.25/-0.13 D DIAGRAM, SCHEMATIC
DI
.X `
M
DAT SITE CODE
17.50-24.99 +0.30/-0.13 E
01-04-2011
.XX` - CONFIDENTIAL - FOR INTERPRETATION DWG DWG
PGK D
FIRST USED ON SHEET
OF DIMENSIONING AND SIZE REV
ANG TOL: ` SCALE
:
PROPERTY OF CUMMINS
POWER GENERATION
TOLERANCING, SEE
ASME Y14.5M-1994 VTA28 A035J417 7 OF 7 A