Sie sind auf Seite 1von 1

Key Plan

FIRE LEGEND ABBREVIATION FIRE GENERAL NOTES FIRE PROTECTION DESIGN CRITERIA
ABBREVIATION DESIGNATION ABBREVIATION DESIGNATION
1. THE FIRE FIGHTING DRAWINGS SHALL BE READ AS ONE UNIT INCLUDING PLANS AND N
MISCELLANEOUS DETAILS CODES AND STANDARDS
SPRINKLER PIPE PIPE DIAMETER
2. FIRE FIGHTING DRAWINGS SHALL BE READ WITH THE ARCHITECTURAL STRUCTURAL, 1. INTERNATIONAL BUILDING CODE 2006
LANDING VALVE & FIRE HOSE RACK PIPE ACV ALARM CHECK VALVE ELECTRICAL, PLUMBING AND OTHER DRAWINGS FOR COORDINATION, VERIFICATION OF

A
BL
ADEQUATE SPACES AND EARLY PROVISIONS OF THE SPECIFICATION.
2. INTERNATIONAL MECHANICAL CODE 2006

QI
BREECHING INLET PIPE AFC ABOVE FALSE CEILING
3. THE DRAWINGS ARE ISSUED FOR FIRE FIGHTING WORKS ONLY AND SHALL NOT BE USED FOR 3. INTERNATIONAL FIRE CODE 2006 Notes
ARCHITECTURAL, STRUCTURAL OR ANY OTHER WORKS
FIRE HYDRANT PIPE ARV AUTOMATIC RELEASE VALVE
4. NFPA 13 - STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS
4. DRAWINGS SHALL NOT BE SCALED FOR EXECUTING THE WORKS. ALL MEASUREMENTS
TEST & DRAIN PIPE CA CLEAN AGENT SHALL BE MADE FROM ESTABLISHED LINES, LEVELS AND BENCH MARKS
5. NFPA 14 - STANDARD FOR THE INSTALLATION OF STANDPIPE AND HOSE SYSTEMS
5. THE DRAWINGS ARE ONLY DIAGRAMMATIC. THE CONTRACTOR SHALL EXECUTE ALL WORK IN
CONCEALED PENDENT SPRINKLER CD CIVIL DEFENCE ACCORDANCE WITH APPROVED SHOP AND INSTALLATION DRAWINGS PER THE PROVISIONS OF 6. NFPA 16 - STANDARD FOR THE INSTALLATION OF FOAM SPRINKLER AND FOAM WATER
THE SPECIFICATION. SPRAY SYSTEM.
UPRIGHT SPRINKLER CP CONTROL PANEL 7. NFPA 22 - STANDARD FOR WATER TANKS FOR PRIVATE FIRE PROTECTION.
6. FOR EQUIPMENT CAPACITIES, RATINGS, TYPES AND CHARACTERISTICS REFER TO
DRAWING REF. NO. 76-10526-F301.
SIDE WALL SPRINKLER D/D DROP DOWN 8. NFPA 24 - STANDARD FOR THE INSTALLATION OF PRIVATE FIRE SERVICE MAINS AND
7. ALL SIZES SHOWN ON DRAWINGS ARE IN mm UNLESS NOTIFIED OTHERWISE. THEIR APPUTUNANCES.
FM-200 / WATER FOAM NOZZLE DI DUCTILE IRON 9. NFPA 92A - RECOMMENDED PRACTICES FOR SMOKE CONTROL SYSTEMS
8. CONTRACTOR SHALL INSTALL FIRE EXTINGUISHERS IN ELECTRICAL ROOMS AND IN FIRE HOSE
CABINETS AS SHOWN IN DRAWINGS AND MENTIONED IN THE SPECIFICATIONS. THE
FHC COMBINED FIRE HOSE CABINET ESFR EARLY SUPRESSION FAST RESPONSE 10. NFPA 92B - GUIDE FOR SMOKE CONTROL SYSTEMS IN MALLS, ATRIA & LARGE AREAS
INSTALLATION SHALL BE IN ACCORDANCE WITH NFPA-10, AND UAE FIRE AND LIFE SAFETY
CODE.
FIRE EXTINGUISHER CABINET F/B FROM BELOW 11. NFPA 90A - INSTALLATION OF AIR CONDITIONING AND VENTILATION SYSTEMS
FEC
9. CONTRACTOR SHALL INSTALL SPRINKLER SYSTEM BELOW FALSE CEILING AND IN VOID
ABOVE FALSE CEILING AS SHOWN IN DRAWINGS, AND MENTIONED IN THE SPECIFICATIONS. THE
12. NFPA 72 - FIRE ALARM DETECTION SYSTEM
FB FIRE BLANKET FB FIRE BLANKET
INSTALLATION SHALL BE IN ACCORDANCE WITH NFPA 13, AND UAE FIRE AND LIFE SAFETY CODE 13. NFPA 2001 - STANDARD ON CLEAN AGENT FIRE EXTINGUISHING SYSTEM
OF PRACTICE (ED. 2011).
FIRE EXTINGUISHER TROLLEY FC FALSE CEILING 14. UAE FIRE AND LIFE SAFERTY CODE OF PRACTICE (EDITION 2011).
10. DESIGN AND INSTALLATION OF STAND PIPE SYSTEM SHALL BE IN ACCORDANCE WITH NFPA-14
FE1 PORTABLE FIRE EXTINGUISHER (WATER, TYPE 9 LTR.) FCL FALSE CEILING LEVEL AND UAE FIRE AND LIFE SAFETY CODE OF PRACTICE (ED. 2011). 15. UAE DEPARTMENT OF CIVIL DEFENSE REQUIREMENTS

11. DESIGN AND INSTALLATION OF FIRE HYDRANT SYSTEM SHALL BE IN ACCORDANCE WITH
FE2 PORTABLE FIRE EXTINGUISHER (CO2 TYPE, 5 KG) FDP FIRE DIESEL PUMP
NFPA-14, NFPA 24 AND UAE FIRE AND LIFE SAFETY CODE OF PRACTICE
(ED. 2011). HAZARD CLASSIFICATION AND PROTECTION:
FE3 PORTABLE FIRE EXTINGUISHER (DRY POWDER TYPE, 4.5 KG) FEP FIRE ELECTRICAL PUMP
12. ALL MATERIALS AND EQUIPMENTS SUPPLIED FOR THE FIRE AND LIFE SAFETY SYSTEMS SHALL 1. ALL BUILDING SPACES (EXCEPT ELECTRICAL ROOMS AND THE IT & TELEPHONE ROOMS)
AT LEAST BE UNDERWRITERS LABORATORY (UL) LISTED OR FACTORY MUTUAL GLOBAL (FM) WILL BE ORDINARY HAZARD, GROUP 1 CLASSIFICATION AND FULLY COVERED WITH
FE3A PORTABLE FIRE EXTINGUISHER (DRY POWDER TYPE, 6 KG) FJP FIRE JOCKEY PUMP SPRINKLER SYSTEM WITH DENSITY OF 0.15 GPM / FT2 AT MOST REMOTE AREA AND 1500 FT2
APPROVED IN ADDITION TO THE APPROVAL OF CIVIL DEFENSE. ARN BM* AH* 08.03.15
WITH SPRINKLER K-FACTOR 5.60. A ISSUED FOR TENDER
FE4 TROLLEY FIRE EXTINGUISHER (CO2 TYPE, 12 KG) FF FIRE FIGHTING 13. CABLES SHALL BE OF LPCB / VDS APPROVED FOR SPECIFIC APPLICATION. Job Project
No Revision Drawn Manager Director Date
2. THE FIRE HOSE RACK SHALL BE 40 mm AT 4.5 BAR PRESSURE AND
FIRE HYDRANT 14. ALL FIRE FIGHTING PIPING MATERIALS SHALL BE GALVANIZED BLACK STEEL INSIDE THE LANDING VALVE SHALL BE 65 mm AT 7.0 BAR PRESSURE.
FE5 TROLLEY FIRE EXTINGUISHER (DRY POWDER TYPE, 25 KG / TRANSFORMER) FH
BUILDING AND DUCTILE IRON FOR OUTSIDE THE BUILDING AND U/G PIPING.
3. THE FIRE EXTINGUISHER SHALL BE WATER TYPE 9 LTR. AND CO2 TYPE 5KG Note: * indicates signatures on original issue of drawing or last revision of drawing
FE6 TROLLEY FIRE EXTINGUISHER (FFP FOAM TYPE, 20 GAL.) FHC FIRE HOSE CABINET 15. FIRE STOP SHALL BE PROVIDED IN EVERY PENETRATION IN FIRE RATED WALL. AT THE MAXIMUM TRAVEL DISTANCE TO NEAREST EXTINGUISHER SET IS 15m. Conditions of Use. This document may only be used by GHD's client (and any other
person who GHD has agreed can use this document) for the purpose for which it was
BREECHING INLET FHR FIRE HOSE RACK 16. HYDRAULIC CALCULATIONS FOR ALL FIRE FIGHTING SYSTEM SHOWING THE PRESSURE, FLOW 4. DIESEL GEN. ROOM SHALL BE PROTECTED WITH FOAM WATER DELUGE SYSTEM. prepared and must not be used by any other person or for any other purpose.
RATE, AND PRESSURE LOSSES SHALL BE SUBMITTED BY CONTRACTOR FOR APPROVAL.
5. TRANSFORMER ROOM SHALL BE PROTECTED WITH WATER SPRAY SYSTEM.
ZCV ZONE CONTROL VALVE FP FIRE PIPE
17. ALL UNDERGROUND FIRE PIPING RUNNING WITH COVER LESS THAN 0.80M FROM FINISH GRADE
LEVEL OR CROSSING ROAD WITH DEPTH OF COVER LESS THAN 0.90M SHALL BE SURROUNDED 6. ELECTRICAL ROOM, IT ROOM, TELEPHONE ROOM & LV ROOM SHALL BE CLEAN AGENT Master Developper / Owner
DV DELUGE VALVE FPVC FIRE PROTECTION VALVE CHAMBER WITH CONCRETE SLEEVE WITH THICKNESS NOT LESS THAN 150mm. SYSTEM.

18. LOCATION OF DEVICES (DETECTORS, SPRINKLERS AND ETC.) SHOWN IN THE DRAWINGS ARE Abu Dhabi Airports Company PJSC
PV PREACTION VALVE FV FLOAT VALVE Planning & Development
INDICATIVE ONLY AND SHALL BE INSTALLED AS PER THE LATEST RCP LAYOUT AND AS PER THE SPRINKLERS SCHEDULE PO Box 94449, Abu Dhabi, U.A.E
LATEST EDITIONS OF NFPA & UAE FIRE AND LIFE SAFETY CODE OF PRACTICES.
FIRE HYDRANT GPM GALLON PER MINUTE T: +971 (0) 2 505 5000
SPRINKLER TYPE K. FACTOR TEMP. RATING (C) F: +971 (0) 2 575 8300

FSCP FIRE SYSTEM CONTROL PANEL GV GATE VALVE UP-RIGHT SPRINKLER 5.6 57-77
CONCEALED PENDENT SPRINKLER 5.6 57-77
ALARM CHECK VALVE H/L HIGH LEVEL

Lead Consultant
PRESSURE REDUCING VALVE HD HEAT DETECTOR
FOAM WATER DESIGN CRITERIA FOR DIESEL GENERATOR ROOM PRE-ACTION SYSTEM
GATE VALVE SCREWED IN INCHES AS PER ADCD, THE FOLLOWING CRITERIA SHALL BE FOLLOWED:
* DOUBLE INTERLOCK PREACTION SYSTEM SHALL BE PROVIDED. THE SYSTEM SHALL BE 10-26 psi PNEUMATIC
SUPERVISING PRESSURE WITH ELECTRIC / PNEUMATIC ACTUATION.
1. THE REQUIRED FOAM CONCENTRATE : AFFF, FFFA
OS & Y VALVE L/L LOW LEVEL
* TWO EVENTS MUST TAKE PLACE TO ACTIVATE THE DELUGE VALVE
2. WATER DEMAND / DESIGN DENSITY : 0.30 GPM / FT2
LV LANDING VALVE 1.) THE FIVE DETECTION DEVICES OR MANUAL EMERGENCY STATION IS OPERATED ACCORDINGLY THE GHD GLOBAL PTY LTD
GATE VALVE FLANGED SOLENOID VALVE IS OPENED.
3. DISCHARGE DURATION : 10 MINUTES 3rd Floor, Guardian Tower, Danet Community
2.) THE SPRINKLER HEAD IS OPENED AND ACCORDINGLY THE LOW PRESSURE DRY VALVE ACTUATOR PO Box 45921 Abu Dhabi United Arab Emirates
PRESSURE RELIEF VALVE m METER WILL OPEN AND A LOW SYSTEM AIR PRESSURE ALARM SOUND. T 971 2 6968700 F 971 2 4472915
4.MINIMUM FOAM-WATER SOLUTION : 3% (OR MORE AS PER MANUFACTURER SPECIFICATIONS)
E abumail@ghd.com W www.ghd.com
CHECK VALVE mm MILLIMETER * THE PRE-ACTION SYSTEM CONTROL PANEL SHALL BE CONNECTED WITH THE MAIN BUILDING FIRE ALARM
5. THE WATER SUPPLY FLOW RATE SHALL BE AVAILABLE FOR DURATION NOT LESS : 60 MINUTES
PANEL AND WITH THE BUILDING BMS.
NOMINAL DIAMETER 6. MAXIMUM AREA PER SPRINKLER : 9.5 M2 Specialist Consultant
SOLENOID VALVE ND
* THE SIZE OF COMPRESSOR AND THE COMPRESSED AIR PIPING SYSTEM SHALL BE SIZED AND CALCULATED
AS PER UAE REGULATION AND NFPA REQUIREMENTS AND AS PER PRE-ACTION MANUFACTURER STANDARDS
PS PRESSURE SWITCH 7. MAXIMUM DISTANCE BETWEEN SPRINKLER ; 3.70 MTS.
STRAINER AND ALL SHALL BE SUBMITTED BY CONTRACTOR FOR APPROVAL BEFORE COMMENCING THE WORK.
8. MAXIMUM SPRINKLER WORKING TEMPERATURE RATING : (55 TO 77C)
ISV VALVE CHAMBER WITH ISOLATING VALVE PV PRESSURE VESSEL * CLOSED SPRINKLER TYPE WILL BE USED IN THE PRE-ACTION SYSTEM. Fire Life Safety, Planning
and Regulatory Specialist
RN RISER NIPPLE SYSTEM DESCRIPTION:
FS FLOW SWITCH (SHALL BE CONNECTED WITH FIRE CONTROL PANEL)
PRESSURE SWITCH
1. THE FIRE PROTECTION SHALL BE DELUGE FOAM / WATER SYSTEM HIGH EXPANSION WITH OPEN
PS S/S STAINLESS STEEL SPRINKLER FIXED SYSTEM
(SHALL BE CONNECTED WITH FIRE CONTROL PANEL)

H HEAT DETECTOR SD SMOKE DETECTOR 2. THE FOAM SYSTEM SHALL INCLUDE, PROPORTIONING DEVICE, DELUGE VALVE, CONCENTRATE Specialist Consultant
CONTROL VALVE AND FOAM CONCENTRATE BLADDER TANK.
H HEAT DETECTOR (INSTALLED AT LOW LEVEL) SRP SPRINKLER RISER PIPE
D SYSTEM ACTUATION:
THE SYSTEM WILL BE ACTUATED BOTH MANUALLY AND ELECTRICALLY USING HEAT DETECTORS
SD ST STRAINER AND SOLENOID VALVES. WHEN ELECTRICALLY ACTIVATED, THE HEAT DETECTOR WILL SENSE THE
Third Party
IONIZATION SMOKE DETECTOR
HEAT AND SEND A SIGNAL TO RELEASE CONTROL PANEL TO OPEN THE SOLENOID VALVE. ONCE Operational Advisor
SV SOLENOID VALVE THE SOLENOID VALVE IS OPENED THE MIXTURE OF WATER AND FOAM WILL DISCHARGE TO THE
SD IONIZATION SMOKE DETECTOR (INSTALLED AT LOW LEVEL)
D SPRINKLERS THROUGH PROPORTIONAL VALVE AND PIPING SYSTEM HANGED ABOVE THE DIESEL
GENERATOR.
O T/A TO ABOVE
PHOTOELECTRIC SMOKE DETECTOR
SYSTEM SUPERVISION:
SHD T/B TO BELOW 1. THE RELEASE CONTROL PANEL SUPERVISES THE WATER SUPPLY TO ENSURE SYSTEM
SMOKE AND HEAT DETECTOR
RELIABILITY AT ALL TIMES.
Client
ADAC
WATER MOTOR GONG U/G UNDER GROUND
2. AN ALARM PRESSURE SWITCH IS OPERATED THROUGH THE SYSTEM'S WATER ALARM LINE
WHEN THE SYSTEM IS DISCHARGED.
ACV ALARM CHECK VALVE WRP WET RISER PIPE
Project
MIDFIELD TERMINAL FIRE
3 WAY MANIFOLD 3 x 65mm
3. THE MAIN CONTROL VALVE IS SUPERVISED FROM ABNORMAL POSITION BY AN INTEGRATED
SUPERVISORY SWITCH SUPERVISES THE VALVE IN AN OPEN POSITION AND WILL CAUSE THE
STATION
F
CONTROLLER TO GO IN A SUPERVISORY ALARM. Title FIRE PROTECTION SERVICES -
STAND PIPE RISER NO.
NO. SYSTEM CONTROLLER:
THE RELEASE CONTROL PANEL IS ONLY FIRE SUPPRESSION RELEASE CONTROL PANEL USED
GENERAL NOTES, LEGEND &
1 DETAIL NUMBER
F100 DRAWING NUMBER
WITH THE FOAM SYSTEM. DESIGN CRITERIA
TS TAMPER SWITCH (SHALL BE CONNECTED WITH FIRE CONTROL PANEL) Scale 1:1 DO NOT SCALE
Drawn A. NOCEJA Designer P. MOHD.
Drafting Design
Check Check
Approved
(Project Director)
Date
This Drawing must not be used for Construction unless signed as Approved
Original Size
Drawing No:
A1
DETAIL DESIGN 76-10526- F001 Rev: A
Plot Date: 7/03/2015 10:14:36 PM Cad File No: C:\Users\fvillete\Documents\76-10526_Midfield Fire Station MEP-Central_fvillete.rvt