Beruflich Dokumente
Kultur Dokumente
BD-00
Special current transformers
TYPE A, TYPE B
Technical parameters
Highest voltage for equipment [kV] 0,72
Power frequency test voltage, 1 min. [kV] 3
Rated primary current [A] 50 to 1250
Rated short-thermal current (max) [kA/s] 31,5/3
0,2, 0,2S , 0,5, 0,5S, 1,
Accuracy classes
5P, 10P
Flammability class E
All the transformers meet the specif cations of relevant standards, Outer diameter of ring CT 200 147
i.e. the IEC, GOST. Height of ring CT 100 75
BD-00 TYPE A, TYPE B parameters for secondary current 5 A:
2
BD-00 TYPE A, TYPE B parameters for secondary current 1 A:
3
Dimensions:
BD 00 TYPE A
BD 00 TYPE B
BD-00 TYPE A BD-00 TYPE B
100
147
90 40
123 75
90 40
5
8,
29
4x
129
8,5
59
2x
176
69
147
123
100
200
249
275
15
Figure 1.1: BD-00 TYPE A dimensions Figure 1.2: BD-00 TYPE B dimensions
15
M5
M5
Drawing n.
1VL4600299R0101
Drawing n.
1VL4600298R0101
Figure 1.4: Application examples of BD-00-A and BD-00-B in Unigear 550 (up to 17,5 kV)
4
Medium Voltage Products
BD-00
Special current transformers
TYPE C
Technical parameters
Highest voltage for equipment [kV] 0,72
Power frequency test voltage, 1 min. [kV] 3
Rated primary current [A] 100 to 1250
Rated short-thermal current (max) [kA/s] 31,5/3
0,2, 0,2S , 0,5S, 0,5, 1,
Accuracy classes
5P, 10P
Flammability class E
5
BD-00 TYPE C parameters for secondary current 5 A:
6
BD-00 TYPE C parameters for secondary current 1 A:
1) Every other parameters have to be agreed with the manufactur- 303V0209 600//1 10 0,5FS10 - -
er and will be considered on special basis. 303V0210 600//1 15 0,5FS10 - -
303V0211 600//1 10 5P10 - -
2) Reconnectable variants are also possible, but need to be exam- 303V0212 600//1 15 5P10 - -
ined on special basis (according to customers requirement 303V0213 600//1/1 5 0,5FS10 5 5P10
and the agreement with manufacturer). 303V0214 600//1/1 7,5 0,5FS10 7,5 5P10
303V0215 800//1 10 0,5FS10 - -
303V0216 800//1 15 0,5FS10 - -
303V0217 800//1 10 5P10 - -
303V0218 800//1 15 5P10 - -
303V0219 800//1/1 5 0,5FS10 5 5P10
303V0220 800//1/1 7,5 0,5FS10 7,5 5P10
303V0221 1000//1 10 0,5FS10 - -
303V0222 1000//1 15 0,5FS10 - -
303V0223 1000//1 10 5P10 - -
303V0224 1000//1 15 5P10 - -
303V0225 1000//1/1 5 0,5FS10 5 5P10
303V0226 1000//1/1 7,5 0,5FS10 7,5 5P10
303V0227 1250//1 10 0,5FS10 - -
303V0228 1250//1 15 0,5FS10 - -
303V0229 1250//1 10 5P10 - -
303V0230 1250//1 15 5P10 - -
303V0231 1250//1/1 5 0,5FS10 5 5P10
303V0232 1250//1/1 7,5 0,5FS10 7,5 5P10
7
Dimensions:
100
90 40
129
8,5
85
2x
100
200
249
275
M5
Drawing n.
1VL4600300R0101
Figure 2.2 BD-00 TYPE C with the bushing (CT rod) used in Unigear type ZS1 (24 kV variant)
8
Medium Voltage Products
BD-00
Special current transformers
Technical parameters
Highest voltage for equipment [kV] 0,72
Power frequency test voltage, 1 min. [kV] 3
Rated primary current [A] 100 to 1250
Rated short-thermal current (max) [kA/s] 31,5/3
0,2, 0,2S , 0,5S, 0,5,
Accuracy classes
1, 5P, 10P
Flammability class E
9
Dimensions:
1VLC000516-Rev.3,en 2014.11.18
BD-00 - Application
BD-00 on the bushing with insulation up to 17,5 kV 3 pcs of BD-00 current transformers in AIS Unigear 550
ABB s.r.o. The data and ilustrations in this catalogue are not binding. We
PPMV Brno reserve the right to make changes of the content, in the course
of technical development of the product.
Videnska 117
619 00 Brno, Czech Republic
Tel.: +420 547 152 021
+420 547 152 614
Fax: +420 547 152 626
E-mail: info.ejf@cz.abb.com