Beruflich Dokumente
Kultur Dokumente
Design Condition:
Suction lift 3m
Discharge lift 7m
Pump Capacity, Qp
Di 2
QP A water water
4
QP
0.1023 m 2 m m3 m3
1.68 0.0138 0.828
4 sec sec min
Friction Heads, hf
100
Straight Pipe ------------------------------------------------------------ 3.1 m
_____________________
For 75 mm pipe
_____________________
From Figure 7 6, Pressure drop for water flowing in schedule 40 steel pipes,
Refrigeration and Air-conditioning by Stoecker & Jones, page 138.
For 100 mm pipe @ 260C & 1.68 m/sec water velocity, k = 0.991
Therefore,
220 Pa m of H 2 O
h f 1 3.6 m x x 0.991 784.872 Pa 0.784872 kPa x 0.1017
m kPa
hf1 0.0798 m of H 2 O
101
800 Pa m of H 2 O
h f 2 13.17 m x x 0.993 10,462.248 Pa 10.462248 kPa x 0.1017
m kPa
hf 2 1.064 m of H 2 O
Also,
Velocity Heads, hv
hV 1
VS
2
1.68 m / sec 2 0.1438 m of H O
2 g 2 9.81 m / sec 2
2
hV 2
VD
2
2.62 m / sec 0.3499 m of H O
2
2 g 2 9.81 m / sec 2
2
Therefore,
Whp
QP water H T
0.828 m 3 min 9.81 kN m 3 11.6375 m 1 min 60 sec
2.112 hp
0.746 0.746 kW hp
102
Motor Power, Pm
Whp 2.112 hp
Pm 2.82 hp
p 0.75
From METC for standard motor sizes, use 3 hp electric motor to drive the
water pump.
SPECIFICATIONS
Total lift, hS 10 m
Schedule 40
Schedule 40
H2O
Motor Power, Pm 3 hp
104