Range TeSys
Product name TeSys T
Device short name LTMR
Product or component Motor controller
type
Device application Equipment monitoring and control
Measurement current 0.4...8 A
[Us] rated supply 100...240 V AC 50/60 Hz
voltage
Supply current 8 A...62.8 mA
Supply voltage limits 93.5...264 V AC
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof.
Communication port Modbus TCP/EtherNet/IP
protocol
Bus type Ethernet IEEE 802.3 interface, addressing 0...159,
transmission rate 10...100 Mbit/s, RJ45 with 2 shiel-
ded twisted pairs
Complementary
[Ui] rated insulation voltage 690 V conforming to CSA C22.2 No 14
The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications.
690 V conforming to EN/IEC 60947-1
690 V conforming to UL 508
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.
[Uimp] rated impulse withstand voltage 4 kV for supply, inputs and outputs conforming to EN/IEC 60947-4-1
6 kV for current or voltage measurement circuit conforming to EN/IEC 60947-4-1
0.8 kV for communication circuit conforming to EN/IEC 60947-4-1
Short-circuit withstand 100 kA conforming to EN/IEC 60947-4-1
Associated fuse rating 0.5 A gG for control circuit
4 A gG for output
Protection type Locked rotor
Thermal protection
Earth-leakage protection
Reverse polarity protection
Phase unbalance
Phase failure
Thermal overload protection
Power factor variation
Overload (long time)
Load fluctuation
Overload
Network and machine diagnosis type Phase fault and earth fault trip counters
Running hours counter/operating time
Starting current and time
Remaining operating time before overload tripping
Waiting time after overload tripping
Event recording
Motor control command recording
Fault recording
Trip history information
Trip context information
Logic input number 6
Input current 3.1 mA at 100 V
7.5 mA at 240 V
Input/output type Logic input : 0...40 V and <= 15 mA for 25 ms (at state 0)
Logic input : 79...264 V and >= 2 mA for 25 ms (at state 1)
Maximum output switching frequency 2 Hz
Load current 5 A at 250 V AC for logic output
5 A at 30 V DC for logic output
2
Environment
Standards IEC 60947-4-1
EN 60947-4-1
IACS E10
UL 508
CSA C22.2 No 14
Product certifications ABS
CSA
RINA
UL
RMRoS
ATEX
KERI
C-Tick
BV
NOM
EAC
DNV
CCC
LROS (Lloyds register of shipping)
GL
Protective treatment 12 x 24 hour cycles conforming to EN/IEC 60068-2-30
48 h conforming to EN/IEC 60070-2-11
TH conforming to EN/IEC 60068
Fire resistance 650 C conforming to EN/IEC 60695-2-12
960 C conforming to UL 94
Ambient air temperature for operation -20...60 C
Ambient air temperature for storage -40...80 C
Operating altitude <= 2000 m without derating
Mechanical robustness shocks half sine wave acceleration (15 Gn for 11 ms) conforming to EN/IEC
60068-2-27
vibrations mounted on symmetrical rail (1 Gn, 5...300 Hz) conforming to EN/
IEC 60068-2-6
vibrations plate mounted (4 Gn, 5...300 Hz) conforming to EN/IEC 60068-2-6
Contractual warranty
Warranty period 18 months