Sie sind auf Seite 1von 3

Product data sheet LTMR08EFM

Characteristics motor controller LTMR TeSys T - 100..240 V


AC 8 A for Ethernet TCP/IP

Main
Range TeSys
Product name TeSys T
Device short name LTMR
Product or component Motor controller
type
Device application Equipment monitoring and control
Measurement current 0.4...8 A
[Us] rated supply 100...240 V AC 50/60 Hz
voltage
Supply current 8 A...62.8 mA
Supply voltage limits 93.5...264 V AC

It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof.
Communication port Modbus TCP/EtherNet/IP
protocol
Bus type Ethernet IEEE 802.3 interface, addressing 0...159,
transmission rate 10...100 Mbit/s, RJ45 with 2 shiel-
ded twisted pairs

Complementary
[Ui] rated insulation voltage 690 V conforming to CSA C22.2 No 14

The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications.
690 V conforming to EN/IEC 60947-1
690 V conforming to UL 508

Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.
[Uimp] rated impulse withstand voltage 4 kV for supply, inputs and outputs conforming to EN/IEC 60947-4-1
6 kV for current or voltage measurement circuit conforming to EN/IEC 60947-4-1
0.8 kV for communication circuit conforming to EN/IEC 60947-4-1
Short-circuit withstand 100 kA conforming to EN/IEC 60947-4-1
Associated fuse rating 0.5 A gG for control circuit
4 A gG for output
Protection type Locked rotor
Thermal protection
Earth-leakage protection
Reverse polarity protection
Phase unbalance
Phase failure
Thermal overload protection
Power factor variation
Overload (long time)
Load fluctuation
Overload
Network and machine diagnosis type Phase fault and earth fault trip counters
Running hours counter/operating time
Starting current and time
Remaining operating time before overload tripping
Waiting time after overload tripping
Event recording
Motor control command recording
Fault recording
Trip history information
Trip context information
Logic input number 6
Input current 3.1 mA at 100 V
7.5 mA at 240 V
Input/output type Logic input : 0...40 V and <= 15 mA for 25 ms (at state 0)
Logic input : 79...264 V and >= 2 mA for 25 ms (at state 1)
Maximum output switching frequency 2 Hz
Load current 5 A at 250 V AC for logic output
5 A at 30 V DC for logic output

Jan 20, 2017


1
Permissible power 480 VA (AC-15), Ie = 2 A, 500000 cycles (output)
30 W (DC-13), Ie = 1.25 A, 500000 cycles (output)
Operating rate 1800 cyc/h
Contacts type and composition 1 NO + 1 NC fault signal
3 NO
Metering type Average current Iavg
Phase current I1, I2, I3 RMS
Temperature
Imbalance current
Earth-fault current
Measurement accuracy 3 % power factor (cos > 0.6)
+/- 30 min/year internal clock
0,02 temperature
5...15 % earth fault current internal measurement (for current > 0.1 A)
1 % current
1 % voltage (100...830 V)
5 % active and reactive power
5 % earth fault current external measurement (< 5 % or 0.01 A)
Overvoltage category III
Connection pitch 5.08 mm
Connections - terminals Connector, 1 flexible cable with cable end 0.25...2.5 mm /AWG 24...AWG 14 for
control circuit
Connector, 1 flexible cable without cable end 0.2...2.5 mm /AWG 24...AWG 14
for control circuit
Connector, 1 flexible cable without cable end 0.25...2.5 mm /AWG 24...AWG 14
for control circuit
Connector, 1 solid cable without cable end 0.2...2.5 mm /AWG 24...AWG 14 for
control circuit
Connector, 2 flexible cable with cable end 0.2...1 mm /AWG 24...AWG 14 for
control circuit
Connector, 2 flexible cable without cable end 0.2...1.5 mm /AWG 24...AWG 14
for control circuit
Connector, 2 flexible cable without cable end 0.5...1.5 mm /AWG 24...AWG 14
for control circuit
Connector, 2 solid cable without cable end 0.2...1 mm /AWG 24...AWG 14 for
control circuit
Tightening torque 0.5...0.6 N.m, 3 mm flat screwdriver for control circuit
Pollution degree 3
Electromagnetic compatibility electrostatic discharge 3 (8 kV air, 6 kV contact), conforming to EN/IEC
61000-4-2
fast transients immunity test other circuits level 3 (2 kV), conforming to EN/IEC
61000-4-4
fast transients immunity test on supply and relay outputs level 4 (4 kV), con-
forming to EN/IEC 61000-4-4
conducted RF disturbances (10 V), conforming to EN/IEC 61000-4-6
surges serial mode (1 kV) control circuit, conforming to EN/IEC 61000-4-5
surges common mode (2 kV) communication, conforming to EN/IEC 61000-4-5
surges common mode (2 kV) control circuit, conforming to EN/IEC 61000-4-5
radiated RF fields 3 (10 V/m), conforming to EN/IEC 61000-4-3
voltage dips and interruptions immunity test (70 %, 500 ms), conforming to EN/
IEC 61000-4-11
surges serial mode (0.5 kV) temperature sensor, conforming to EN/IEC
61000-4-5
surges common mode (1 kV) temperature sensor, conforming to EN/IEC
61000-4-5
surges serial mode (2 kV) relay outputs and supply, conforming to EN/IEC
61000-4-5
surges common mode (4 kV) relay outputs and supply, conforming to EN/IEC
61000-4-5
Width 91 mm
Height 61 mm
Depth 122.5 mm
Product weight 0.53 kg
Web services Web server
Compatibility code LTMR

2
Environment
Standards IEC 60947-4-1
EN 60947-4-1
IACS E10
UL 508
CSA C22.2 No 14
Product certifications ABS
CSA
RINA
UL
RMRoS
ATEX
KERI
C-Tick
BV
NOM
EAC
DNV
CCC
LROS (Lloyds register of shipping)
GL
Protective treatment 12 x 24 hour cycles conforming to EN/IEC 60068-2-30
48 h conforming to EN/IEC 60070-2-11
TH conforming to EN/IEC 60068
Fire resistance 650 C conforming to EN/IEC 60695-2-12
960 C conforming to UL 94
Ambient air temperature for operation -20...60 C
Ambient air temperature for storage -40...80 C
Operating altitude <= 2000 m without derating
Mechanical robustness shocks half sine wave acceleration (15 Gn for 11 ms) conforming to EN/IEC
60068-2-27
vibrations mounted on symmetrical rail (1 Gn, 5...300 Hz) conforming to EN/
IEC 60068-2-6
vibrations plate mounted (4 Gn, 5...300 Hz) conforming to EN/IEC 60068-2-6

Contractual warranty
Warranty period 18 months

Das könnte Ihnen auch gefallen