SF6 INSULATED CURRENT TRANSFORMER


type TAG from 123 to 300 kV

WeWeknow
know how.
how.
Current Transformer TAG type main
features are:
n Characteristics:
o outdoor installation
o SF6 and SF6-PPR insulation
o cast aluminium housings
o conformity to the main International Standards for
design, test and construction of pressurised
enclosures
o head type design
o explosion proof
o maintenance free

n Reliable design:
o well proven experience with SF6 insulation
technology
o dimensioned to withstand phase-to-earth voltage
at atmospheric internal gas pressure
o earthquake resistant
o computer technology and finite elements analysis
to study electric field, mechanical stresses and
seismic phenomena
o quality system complying with ISO 9001

n Advantages:
o operation reliability, operation safety
o pressure relief device
o remote supervision of insulation condition by
monitoring internal gas density
o no ageing

sustainable solutions. for a better life.


www.vatech-td.com
SF6 INSULATED CURRENT TRANSFORMER
type TAG from 123 to 300 kV

Standards: IEC, ANSI, and main international Standards

Primary ratio change (up to three) and/or secondary taps


Operating pressure: Rated pressure 0.4 Mpa at 20C

Dimensions and weight: A B weight


mm mm kg
TAGa 123-245 L 2160 745 300
TAGa 123 2200 840 370
TAGb 123 2245 990 420
TAGa 145 2310 840 400
TAGb 145 2385 990 450
TAGa 170 2460 840 440
TAGb 170 2535 990 490
TAGma 245 - 300 3350 1000 550
TAGmb 245 - 300 3430 1000 600

Optional accessories:
- polymeric insulator
- column support
- sealable secondary terminal box
- cable glands
Electrical characteristics: - secondary surge arrester

Test Voltages
Highest
primary thermal metering protection
sistem Power TAGa TAGb
LIWL SIWL current current accuracy accuracy
voltage frequency A kA/s class class
kV (r.m.s.) kV (r.m.s.) kV (peak) n of cores
TAG 123 123 230 550 -
TAG 145 145 275 650 - 5P 10P
TPY
TAG 170 170 325 750 - up to 4000 up to 63/1 1 to 4 1 to 6 0.2 0.5 - 1
TPX
TAG 245 245 460 1050 - TPZ
TAG 300 245 460 1050 850

LIWL = rated lightning impulse withstand voltage


SIWL = rated switching impulse withstand voltage TAGa 145 integrated on the
AIS Compact Module MCI 145

Ordering data:
insulation level
rated frequency
rathed thermal current
dynamic current
continuos thermal current
primary current
secondary current
eTD.25.0500.S/BG.C02

rated burden class limit or safety factor


insulator creepage distance
standard
The tecnical data underlined must be indicated in order.
The others can be omitted if standard data are accepted

VA TECH Transmission & Distribution GmbH & Co KEG Product Management


Penzinger Stras 76, A-1141 Vienna Nuova Magrini Galileo S.p.A.
Strada Curagnata, 37 - 17014 Bragno-Cairo Montenotte (SV) Italy
Tel.: **43/1/89 100, Fax: ++43/1/89 100-196
Tel. +39 019 5161 111 - Fax +39 019 5161 401
E-Mail: contact@vatech-td.at, www.vatech-td.com

Das könnte Ihnen auch gefallen