Sie sind auf Seite 1von 5

1

Voltage Analysis for Placement of DG in


Multiphase Distribution Networks
Parachai Juanuwattanakul, Student Member, IEEE, Mohammad A.S. Masoum, Senior Member, IEEE,
Chittachai Niyomsak, Student Member, IEEE, and Mansour Mohseni, Member, IEEE

worse. This will eventually require static voltage stability


Abstract--This paper presents an effective method for analysis (based on the power flow calculation) to ensure a
placement of DG units in multiphase distribution networks based proper and reliable operation of the power system with large
on system voltage profile. The approach consists of utilizing the amounts of DG [3]. When the power system becomes stressed
positive sequence voltage ratio Vcollapse/Vno-load to identify the (e.g., as a result of load increasing), voltage instability can
weakest three-phase bus for the installation of DG units. DG easily occur. This type of voltage instability mostly occurs at
ratings are determined by evaluating their impacts on voltage
the weakest bus [4]. Therefore, both the location and the
profile, grid losses and maximum loading factor while
considering the voltage limits at all buses. Detailed simulations penetration level of DG become a challenging task for system
are performed for the placement and sizing of a doubly fed planning and operation. Several methods to place DG units
induction generator (DIFG) in the IEEE multiphase 34 node test have been proposed including voltage sensitivity analysis [5],
feeder using DIgSILENT PowerFactory software. The impacts of continuation power flow for determination of the most
DIFG on voltage profile, active power loss and voltage stability sensitive bus to voltage collapse [7], voltage stability index
margin are highlighted. Finally, simulation results indicate that [8], optimization approaches [8-9], voltage profile and loss
voltage limits should be considered as a constraint for the calculations [6, 11]. References [9-10] show that the sizing
methods of DG placement. and location of DG can significantly influence the voltage
profile and should be well planned to maintain the node
Index Terms-- Multiphase network, weakest bus, DG, DIFG,
voltages within permissible limits.
voltage profile, grid loss, and maximum loading factor.
Detailed analyses of unbalanced/multiphase networks based
on continuation three-phase power flow show that the three
I. INTRODUCTION
PV curves on each phase for the unbalanced networks are
The present integration of Distributed Generation (DG) different [12-13]. Therefore, to determine the voltage stability
units in power systems has many advantages, but also margins, the method of symmetrical components has been
challenges the performance of the old networks. One of these applied to merge the three PV curves to one PV curve based
challenges is to investigate the location and the penetration on positive sequence voltage. In addition, to extend and
level of DG units which can easily be absorbed in the system generalize the conventional definition of bus voltage ranking
without major structural changes while keeping all bus voltage index for multiphase networks, symmetrical components are
levels within permissible limits. Due to the high penetration of also applied to the three-phase voltages resulting from three-
DG, voltage instability problems have become important phase power flow [14].
issues in power systems. Most studies confirm that 10-15 % This paper expands the well-known voltage index V/V0 for
penetration of DG can be absorbed in the electricity network balanced three-phase systems and defines an improved
[1]. It is well-known that high penetration levels of DG may positive sequence voltage index of Vcollapse/Vno-load to identify
have significant impacts on voltage profile, grid loss, and the weakest buses in multiphase distribution networks.
voltage stability margin. These impacts may appear either Simulation results are carried out for the IEEE multiphase 34
positively or negatively, depending on the type of distribution node test feeder to determine the appropriate location and
networks, nature of distributed generations and load penetration level of DG in improving voltage profile, reducing
characteristics. grid losses and increasing the maximum loading factor while
It seems reasonable to expect that the connection of DG to keeping all bus voltage levels within the permissible limits.
the utility grid might improve the voltage profile and will Section II discusses the bus ranking for DG placement.
enhance the voltage stability of a distribution system while Section III shows the impact of DG placement. Section IV
reducing active and reactive losses [2]. Even though DG has a presents the test system. Simulation results and analysis are
variety of benefits, it also imposes some problems and provided in Section V, followed by conclusion.
limitations.
These problems become highly significant as the II. BUS RANKING OF MULTIPHASE DISTRIBUTION NETWORKS
penetration level of DG increases and its impact will become
The approach taken in this study is utilizing the bus voltage
ranking index to identify the weakest buses in multiphase
Parachai Juanuwattanakul, M.A.S. Masoum, Chittachai Niyomsak, and distribution networks. This section starts with the definition
Mansour Mohseni are with the Department of Electrical and Computer and derivation of the conventional voltage ranking index
Engineering, Curtin University, Perth, WA, Australia. (e-mail:
parachai3@hotmail.com; m.masoum@curtin.edu.au; (VRI) V/Vo using the two bus balanced network of Fig. 1 and
c.niyomsak@postgrad.curtin.edu.au; mansour.mohseni@curtin.edu.au).

978-1-4673-2729-9/12/$31.00 2012 IEEE


2

continues to extend its application to multiphase networks ,


using symmetrical components [14]. = (8)
,

To compute the proposed VRI for balanced three-phase


networks, , is computed based on the Newton-
Raphson load flow by forcing (3) to zero.

The Jacobian corresponding to (3) is defined as follows:


2
= (9)
Fig. 1. Equivalent circuit of a two bus balanced network.

At the collapse point, Jacobian matrix is singular, therefore:


The conventional VRI is defined for balanced three-phase
networks [8, 9]: .
( ) = 0 = , = (10)
,
= = (1)
,
Substituting (6) and (10) in (8) results in
where j is the bus number, , and , are the
bus voltages for the base-load and no-load operating , .
= = (11)
conditions, respectively. ,
Balanced three-phase load flow can be used to compute
The angle is computed from (12):
, by setting the complex power at bus j to zero:
= (12)
= ( , )= = =0 (2)

where and are the voltages at buses i and j, To extend and generalize the conventional definition of VRI
respectively. Separating real and imaginary parts of (2): for multiphase networks, symmetrical components are applied
to the three-phase voltages resulting from three-phase power
= 0 flow. The new index is defined as the ratio of the positive

= 0 sequence voltage at the collapse point to the positive sequence
voltage at the no-load:
, = + =
(3)
, = =
=
,
(13)
,
where = . The voltage is computed by squaring
Equation (13) can be used to identify the weakest buses of
and adding the real and imaginary parts of (3):
both balanced and unbalanced networks. The node with the
+2 + 0.5 lowest bus voltage ranking index value is classified as the
(4) weakest bus.
+ + + = 0
There are four solutions to (4), III. IMPACTS OF DG PLACEMENT ON VOLTAGE PROFILE, GRID
LOSS, AND MAXIMUM LOADING FACTOR
= ( 4 ) (5) A. Impact of DG on Voltage Profiles
In balanced three-phase networks, voltage profiles are
where = 2 2 and = +
usually plotted using the average bus voltage values. For
+ . However, ( ) is always positive because the unbalanced networks, system unbalanced voltage variance
term (2 2 ) is small as compared to ( ) and index [15] has been proposed for considering voltage profiles
also (4 ) is small as compared to ( ); therefore, the unique instead of using system average voltage [16-17]. However, for
positive and stable solution of (5) is multiphase networks, voltage magnitudes in some phases are
missing. Therefore, in this paper, the voltage profiles of all
= , =+ + ( 4 ) (6) phases will be plotted in the range of 0.95-1.05 p.u. (see Figs.
5 and 6).
Substituting (6) in (1) results in
B. Impact of DG on Grid Losses
.
= = (7) Grid losses associated with the placement and the
penetration level of a DG unit (e.g., at the weakest bus) are
computed and compared with the losses without any
where A = 0.25 2 2 + + compensation device. Active power loss reduction (ALR) by
The propose index in balanced network is defined as: DG units or compensation devices is calculated from:
3

= 100% (14)

Where and P are the total active power losses with


and without DG units, respectively.
The DG penetration level is defined as

= 100% (15)

where and are the total active powers of the DG


units and system loads, respectively.
Fig. 3. Bus ranking for base-case load.
C. Impact of DG on Maximum Loading Factor
Using a continuation three-phase power flow, PV curves for B. Impacts of DG Units on Voltage Profile, Grid Loss, and
multiphase distribution networks will be plotted. The method Maximum Loading Factor
of symmetrical components will then be applied to merge the A DFIG wind turbine with power factor control is installed
three individual PV curves into a single PV curve based on at the weakest three-phase bus (bus 890) and its size is
positive sequence voltage. Finally, the maximum loading
changed to determine its impacts on loading factor, active
factor (MLF) will be determined using the single PV curve power loss reduction, and voltage profile.
based on positive sequence voltage. MLF is defined as the Simulations results are presented in Fig. 4 indicating that
ratio of the maximum system load (at the voltage collapse
active power loss is lowest (ALR = 62.31%) at a DG
point) to the base load. penetration level 40% while the loading factor escalates as the
DG penetration increases.

Fig. 2. The IEEE multiphase 34 node test feeder [14]. Fig. 4. Loading factor and active power loss with different DG penetration at
bus 890.

IV. SIMULATION RESULTS However, with 40% DG penetration at bus 890, as identify
For the analysis of this paper, the IEEE multiphase 34 node by grid loss calculation, the voltage profile of all phases at bus
test feeder of Fig. 2 [18] is considered. The network has been 890 is higher than the upper voltage limit of 1.05 p.u as shown
simulated using DIgSILENT PowerFactory software [19]. The in Fig.5.
system data is available in [18]. This unbalanced multiphase
feeder consists of three-phase and single-phase sections with 1.085
Line-Ground Voltage, phase-a
unbalanced spot loads (Y-PQ, D-PQ, Y-I, D-I, Y-Z, and D-Z), Line-Ground Voltage, phase-b
Line-Ground Voltage, phase-c

distributed loads (Y-PQ, Y-I, Y-Z, D-I, D-Z, and D-PQ), 1.058

three-phase shunt capacitors (at buses 844 and 848), and an in-
Voltage Profile [p.u.]

line transformer (between buses 632 and 688). There are also 1.031
two automatic voltage regulators.
Bus 800 is treated as a slack bus with a voltage setpoint at
1.05 p.u. At a base-case load condition, the voltage at bus 890 1.004

is lower than the permeable voltage limits because the line


between buses 888 and 890 is relatively long. Other bus 0.977

voltages are in the permeable range of 0.95- 1.05 p.u.


0.950
A. Bus Voltage Ranking Based on the Proposed Index
808
810
812
814
850
816
818
824
820
822
826
858
832
852
830
828
854
856
800
864
888
890
834
842
844
846
848
860
836
840
802
862
838
806

Bus Number

Figure 3 shows the bus voltage ranking for the base-case- Fig. 5. Voltage profile with 40% DG penetration at bus 890.
load with two automatic voltage regulators which regulate the
With 30% DG penetration at bus 890, all the bus voltage
voltage in the range of 0.95-1.05 p.u. According to this figure,
profiles are in the range of 0.95-1.05 p.u. as shown in Fig. 6.
the four lowest VRI values are buses 890, 852, 864, and 822,
Notice that the voltage profile of phase c at bus 890 is 1.0499
respectively. The weakest bus is still at bus 890.Therefore, the
p.u., which is very close to the upper voltage limit of 1.05 p.u.
three-phase weakest bus is bus 890 and this bus will be
Any increase in the DG penetration level at this bus beyond
selected for the installation of DG units.
4

300% will causse an overvo oltage conditio


on at bus 890.
8 [5] H. M M. Ayres, W. F Freitas, M. C. DDe Almeida, andd L. C. P. Da
Thherefore, con nsidering voltage limits, the maxim mum Silvva, "Method ffor determiningg the maximuum allowable
peenetration of DGD units that can be installled at bus 890 0 is pennetration level of distributed generation withouut steady-state
abbout 30% (600 0 kW, 666.66 kVA). Furth hermore, the tootal volttage violationss," IET Genneration, Trannsmission &
Disttribution, , vol. 44, pp. 495-508.
acttive power loss is reduced to 60.13% an nd the maximmum [6] D. Baohua, S. Asggarpoor, and Q Q. Wei, "Voltagge analysis of
loaading factor is increased fromm 2.518 to 3.1
150. These resu
ults distr
tribution systemms with DFIG w wind turbines," inn Proc. IEEE
inddicate that voltage
v limits should be considered ass a Pow wer Electronics and Machines in Wind Appliccations, 2009.
coonstraint for thee methods of DG
D placement. PEM MWA 2009., 20009, pp. 1-5.
[7] H. H Hedayati, S. A. N Nabaviniaki, annd A. Akbarimajd, "A Method
1
1.050
Line-Ground
L Voltage, phase-a for Placement of D DG Units in D Distribution Netwworks," IEEE
Line-Ground
L Voltage, phase-b
Line-Ground
L Voltage, phase-c Trannsactions on Poower Delivery, vool. 23, pp. 1620--1628, 2008.
1
1.030 [8] K. V. Kumar and M. P. Selvan, "Planning and operation of
Disttributed Generaations in distribbution systems for improved
Voltage Profile [p.u.]

volttage profile," iin Proc. Poweer Systems Connference and


1
1.010
Expposition, 2009. P PSCE '09. IEEE/P /PES, 2009, pp. 11-7.
[9] M. Alonso and H H. Amaris, "Volltage stability inn distribution
0
0.990 netwworks with DG,"" in Proc. IEEE Bucharest PowerTech, 2009,
pp. 1-6.
[10] F. M M. Nuroglu andd A. B. Arsoy, "Voltage proffile and short
0
0.970 circcuit analysis in ddistribution systeems with DG," iin Proc. IEEE
Cannada Electric Poower Conferencee, 2008, pp. 1-5.
0
0.950
[11] G. W. Jones andd B. H. Chow wdhury, "Distribbution system
operration and plannning in the preseence of distributted generation
808
810
812
814
850
816
818
824
820
822
826
858
832
852
830
828
854
856
800
864
888
890
834
842
844
846
848
860
836
840
802
862
838
806 Bu
us Number
techhnology," in Prooc. IEEE/PES T Transmission andd Distribution
Figg. 6. Voltage profiile with 30% DG penetration
p at bus 890. Connference and Expposition, 2008, ppp. 1-8.
[12] H. M Mori and K. Seeki, "Non-linear--predictor-basedd continuation
V. CON
NCLUSION powwer flow for uunbalanced distrribution system ms," in Proc.
This paper hass extended the application off the conventio onal Trannsmission & D Distribution Connference & Expposition: Asia
andd Pacific, 2009, ppp. 1-4.
buus voltage rank king index of V/V
V o defined fo or balanced thrree-
[13] X. PP. Zhang, P. Ju, and E. Handschhin, "Continuatioon three-phase
phhase systems to o identify the weakest
w buses for the placem ment powwer flow: A tooll for voltage staability analysis oof unbalanced
off DG units in multi-phase systems.s Furrthermore volttage threee-phase powerr systems," IEE EE Transactionns on Power
proofiles, active power
p loss, maaximum loadin ng factor, and bus Systtems, vol. 20, ppp. 1320-1329. 20005.
vooltage limit haave also been investigated. Main M conclusions [14] P. JJuanuwattanakuul and M.A.S. Masoum, "Volltage stability
aree: enh ancement for unnbalanced multipphase distributioon networks,"
The prop posed bus raaking approach h based on the IEEEE Power and Ennergy Society Geeneral Meeting, 2011, pp.1-6.
positive sequence
s voltaage ratio Vcollaapse/Vno-load can
n be [15] D. Baohua, S. Asggarpoor, and Q Q. Wei, "Voltagge analysis of
utilized to
o locate DG units
u at the weeakest three-ph hase tribution system
distr ms with DFIG w wind turbines," inn Proc. IEEE
Pow wer Electronics and Machines in Wind Appliccations, 2009,
and singlee-phase buses. pp. 1-5.
Analysis of simulatio on results indicates that the [16] H. HHedayati, S. A. N Nabaviniaki, and A. Akbarimajd, "A Method
penetratio
on level of DG D is limited d by considerring for Placement of D DG Units in D Distribution Netwworks," IEEE
voltage liimit rather thaan grid loss caalculation and the Trannsactions on Poower Delivery, vool. 23, pp. 1620--1628, 2008.
maximum m loading facto or. [17] G. W. Jones andd B. H. Chow wdhury, "Distribbution system
For consiidering high peenetration leveels of DG unitss, it operration and plannning in the preseence of distributted generation
is necessaary to take volttage limits in to
o account. techhnology," in Prooc. IEEE/PES T Transmission andd Distribution
Connference and Expposition, 2008, ppp. 1-8.
[18] "Raadial Test Feedders," IEEE Distribution Systtem Analysis
VI. REFFERENCES Subbcommittee.
[1]] J.H.R. Enslin n, "Interconnection of distribu uted power to the [19] "DIIgSILENT PoweerFactory Manual," 14.0 ed, 20009.
distribution network,"
n IEEE
E PES Power Systems
S Confereence
and Expositioon, vol.2, 2004, pp.
p 726- 731. VII. BIOGRAPPHIES
[2]] L. Ramesh, S.P.
S Chowdhury y, S. Chowdhurry, Y.H. Song, and
A.A. Natarajaan, "Voltage staability analysis and
a real power loss Parrachai Juanuwattanakul (S'100) received his
reduction in n distributed distribution sy ystem," IEEE/P PES B.EEng (2nd Class HHons.) and M.Enng degrees in
Transmission and Distributtion Conference and Exposittion, Eleectrical Engineeering from Mahanakorn
2008, pp.1-6. Unniversity of Technology, Bangkkok, Thailand
[3]] M. Hasani an nd M. Parniani, "Method of Co ombined Static and andd Kasetsart Univversity, Bangkokk, Thailand in
Dynamic An nalysis of Voltaage Collapse in n Voltage Stabiility
19994 and 1998, rrespectively. Hee is presently
Assessment," IEEE/PES Transmission and Distribution
woorking towards his PhD deegree at the
Conference and Exhibition: Asia
A and Pacific, 2005, pp.1-6.
Eleectrical and Computer Engineering
[4]] R.M. Henriqu ues, N. Martins, J.C.R.
J Ferraz. H.J.C.P.
H Pinto, A..C.
B. Martins, and
a S. Carneiro Jr., " Impact of Induction Moto ors Departmment, Curtin Uniiversity of Techhnology, Perth, A Australia. His
Loads into Voltage Stabilitty Margins of LargeL Systems,"" in research interests includee voltage stabiliity, distributed ggeneration and
Proc. PSCC, Seville, Spain, 2002.
2 FACTS ddevices.
5

Mohammad A.S. Masou um (S88M91


SM05) receeived his B.S., M.S. and Ph h.D.
degrees in Electrical and Commputer Engineerring
in 1983, 19855, and 1991, resspectively, from the
University of Colorado, Boulder, USA. His
research interrests include optimization, po ower
quality and stability
s of pow
wer systems/elecctric
maachines and distrributed generatio
on. Dr. Masoum m is the co-authoor of
P
Power Quality in Power Sysstems and Eleectrical Machin nes
(Ellsevier, 2008) and Power Conversion
C of Renewable
R Eneergy
Sysstems (Springeer, 2011). Curreently, he is an Associate
A Professsor
andd the disciplinee leader for eleectrical power engineering at the
Eleectrical and Commputer Engineerring Departmentt, Curtin Universsity,
Perrth, Australia an
nd a senior membber of IEEE.

Chittachai Niyomsak
N (S'11) received his B.EEng
degree in Powwer Electrical Engineering
E in 2009
2
from Kings Mongkut
M Univerrsity of Technollogy
North Ban ngkok (KMUT TNB), Bangkkok,
Thailand. Hee is going to graduate his M.E Eng
degree in 20111 in Renewable Energy Electrrical
Power Systeems, Curtin University, Peerth,
Auustralia. His reseearch interests in
nclude wind power generation and
voltage stability.

Mansour Mohseni (S09, M11) M received the


B.Sc. and M.Sc. degrees in n electrical poower
engineering frrom Shahid Ch hamran Universsity,
Ahwaz, Iran, inn 2004 and 2007, respectively, and
the PhD deg gree in electriccal and computer
engineering from
f Curtin University, Peerth,
Australia, in 2011.
2 He is currrently an assocciate
lecturer at thhe Department of Electrical and
Coomputer Engineeering, Curtin Un niversity, Perth, Australia. He is the
autthor or co-autho or of over 30 pub blished technicaal papers in his area
a
of expertise. His research
r interests include wind d power generattion,
griid integration off renewable energ gy systems, and power electronics.

Das könnte Ihnen auch gefallen