Sie sind auf Seite 1von 8

Settings calculation for Distance protection Relay

Principle line(km)= 24 Rarc= 20 R1=


Longest line(km)= 86 Rft= 5 X1=
Shortest line(km)= 26.37

Calculated values of different zone settings- 220 kv

ZONE1 ZONE2 ZONE3 ZONE4 (REV)


X() 3.100109 4.6501632 17.76104 2.128903
Rph-ph() 4.615475 4.9232128 8.231392 4.422658
Rph-e() 10.61548 10.923213 14.23139 10.42266
0.08014 Primary current= 800 Secondry current= 1
0.40366 Primary voltage= 220,000 Secondry voltage= 110

CTR/PTR= 0.4

Line S C Cond - dear


CTR= 800
PTR= 2000
Settings calculation for Distance protection Relay

Principle line(km)= 15.925 Rarc= 20 R1= 0.08109


Longest line(km)= 37.431 Rft= 5 X1= 0.19306
Shortest line(km)= 15.925

Calculated values of different zone settings- 132 KV Line Conduc

ZONE1 ZONE2 ZONE3 ZONE4 (REV)


X() 0.819861 1.229792 3.433636 0.512413
Rph-ph() 3.677696 3.849877 5.063989 3.54856
Rph-e() 8.677696 8.849877 10.06399 8.54856
Primary current= 400 Secondry c 1 CTR= 400
Primary voltage= 132,000 Secondry v 110 PTR= 1200

CTR/PTR= 0.333333

132 KV Line Conductor = Panther (D.C.)


Settings calculation for Distance protection Relay

Principle line(km)= 112 Rarc= 20 R1= 0.03252


Longest line(km)= 175 Rft= 5 X1= 0.33086
Shortest line(km)= 103
C

alculated values of different zone settings- 400 KV Line Conducto

ZONE1 ZONE2 ZONE3 ZONE4 (REV)


X() 8.1523912.22859 26.11313 4.6858048
Rph-ph() 3.951939 5.829969 3.2105645
Rph-e() 7.676293 8.076939 9.954969 7.3355645
Primary current= 1000 Secondry current= 1 CTR=
Primary voltage= 400,000 Secondry voltage= 110 PTR=

CTR/PTR=
CTR/PTR= 0.275

400 KV Line Conductor = 2* Moose


1000
3636.364

Das könnte Ihnen auch gefallen