Sie sind auf Seite 1von 9

International Journal of Energy Engineering 2013, 3(3): 138-146

DOI: 10.5923/j.ijee.20130303.03

Application of Superposition and Fuzzy Logic Methods to


Determine the Contribution of the Utility and Customer in
Creation of Harmonic Distortions in PCC Bus
Majid Moradlou1 , Farzaneh Eshaghian Dorcheh2 , Mehdi Bigdeli1,*

1
Department of Electrical Engineering, Zanjan Branch, Islamic Azad University, Zanjan, Iran
2
Department of Electrical Engineering, Isfahan University of Technologhy, Isfahan, Iran

Abstract This paper presents a new method for determination of the relative contribution of utility and customer in
creation of voltage and current harmonic distortions in PCC (Point of Co mmon Coupling) bus. In proposed method,
accurate information of harmonic impedance of customers is not needed. At first, using superposition method and
definit ion of harmonic contribution, new indices are defined and an algorith m is proposed. Then, an appropriate fuzzy
inference system is designed and combined with the proposed algorithm in order to determine the approximate contribution
of utility and customer in creat ion of harmon ic distortions. In contrast to the other methods, in proposed method the precise
amount of harmonic impedances of customer is not needed in any case and a p retty estimat ion of contribution of t wo sides
is obtained even in cases where their contribution is close to each other. The analysis is verified by simu lating IEEE 13-bus
industrial distribution system in DIGISILENT software.
Keywords Power Quality, Harmon ic Contribution, Fu zzy Logic, Digsilent Software

harmonic source consisting of harmonic current source in


1. Introduction parallel with harmonic impedance. Upstream and
downstream networks seen fro m PCC bus in the form of
Harmonic d istortions are among the most important Thevenin or Norton equivalent circu its have been modeled
issues related to power quality which have been increased in[5] and[7]. Then, the current and voltage harmonic
in past years. The main reason for harmonic pollution is the contributions of each side at the PCC bus have been defined
use of non-linear loads[1-3]. Therefore fro m one aspect using superposition method. This definition requires the
customers are the main source of these distortions. accurate value of harmonic impedances of upstream and
However, due to co mplexity and topology of networks downstream networks that are usually unknown or difficu lt
along with existence of power factor correcting capacitors to obtain. Different methods have been proposed for the
in them, these distortions spread over the whole network. measurement and calculat ion of harmon ic impedance at a
Thus in todays modern networks, by measuring the specific point in a network; however they are usually
harmonics in one point, it cannot be determined whether the expensive and difficu lt to imp lement[8-15].
upstream or downstream network is the main source of Using the proposed definition for harmonic contribution,
distortions. So, the important question is which side is the it is shown that in order to identify the do minant source in
dominant cause of harmon ic pollution in one point. In order the creation of current (voltage) distortion in PCC bus, it is
to answer this question, an accurate defin ition fo r the term sufficient to compare the corresponding voltage (current)
harmonic contribution should be obtained which is the sources in equivalent Norton (Thevenin) models.
focus of the second part of this paper. Accordingly, different methods have been introduced
The most co mmon method for identificat ion of main [16-19]. The most important of which is the Critical
harmonic source is based on harmonic power direction at Impedance method[18-19]. So me studies[20] have been
PCC bus. However, it has been shown and proved that this shown that in cases where the harmon ic contribution of
metho d does not always p rov id e co rrect resu lts[4-5]. customers and utility is close to each other or there is not
Thunberg and Soder[6] have adopted the Norton model of enough information about the harmonic impedance of
* Corresponding author:
customer, the critical impedance method may provide
bigdeli_aznu@yahoo.com (Mehdi Bigdeli) incorrect results. This problem has been solved in[20] by
Published online at http://journal.sapub.org/ijee defining new indices and employ ing appropriate method.
Copyright 2013 Scientific & Academic Publishing. All Rights Reserved However, this method is not able to estimate the relative
International Journal of Energy Engineering 2013, 3(3): 138-146 139

contribution of network and customers in the creat ion of the If u-P CC is the harmon ic current due to u alone and c-P CC
harmonics and it may give uncertain results in some cases. is the harmonic current due to c alone in PCC bus,
To address mentioned shortcomings, using the definition according to Fig. 1 and using superposition method,
of harmonic contribution in[5],[7] and the proposed following equations can be written:
algorith m in[20], and by designing an appropriate fu zzy Eu
inference system, a new method is proposed. So me I u PCC = (1)
advantages of this work are listed in the following:
Zu + Zc
An intelligent method is proposed to determine the Ec
approximate relative contribution of utility and customer in I c PCC = (2)
Zu + Zc
creation of harmonic distortions at PCC bus. For this
purpose, fuzzy logic is used, which is very popular smart I pcc I u - pcc I c - pcc
= (3)
method.
In proposed method, the precise amount of harmonic By depict ing u-P CC and c-P CC on P CC, uf and c f scalar
impedances of customer is not needed. quantities are obtained. These quantities are defined[5] as
This method not provide incorrect results in contrast utility and customer contribution in producing of P CC
to[19]. respectively, where I PCC is the algebraic su m of these
The proposed method does not give uncertain results
in some cases in contrast to[20]. two quantities. It should be noted that uf and c f can be both
In this regard, definitions of harmonic contribution are positive or one positive and the other negative. These
quantities are positive if they are in the same direction as
presented and then the proposed method and fuzzy system
P CC.
are presented. The validity of the proposed method is
Using phasor equations, uf and cf can be obtained by the
verified by simu lating IEEE 13-bus industrial distribution
following equations:
system[21] using Digsilent software. 2 2 2
I pcc + I c - pcc I u - pcc
I cf = (4)
2. Definition of Harmonic Contribution 2 I pcc
Based on Superposition 2 2 2
I pcc + I u - pcc I c - pcc
The definitions of harmonic contribution of voltage and I uf = (5)
current in a specific point are presented here. Then their 2 I pcc
results are used to identify the dominant source of
harmonics. 2.2. Harmonic Contri bution in Creati ng Vol tage
Distortions
2.1. Harmonic Contri bution in Creati ng Current
As shown in Fig. 2, the upstream and downstream
Distortions
networks seen from PCC, are modeled by their equivalent
As shown in Fig. 1, the upstream and downstream Norton circuit for each specific harmonic. Actually, the
networks seen from PCC are modeled by their equivalent circuit in Fig. 2 is dual for the circuit shown in Fig. 1 and the
Thevenin circuit which consists of a voltage source in series
with harmonic impedance for each specific harmon ic. The relationships E c = Z c I c and E u = Z u I u held in it.
subscripts u and c denote upstream (utility) and According to Fig. 2 and using superposition, the equations (6)
downstream (customer) networks seen fro m PCC bus to (10) can be written for determination of voltage harmon ic
contribution.
respectively. I PCC , VPCC , P and Q are equal the phasors
Zu Z c
of harmonic current phasor, harmonic voltage phasor, Vu - pcc = Iu (6)
harmonic active power and harmonic reactive power Zu + Zc
respectively as measured in PCC.
Zu Z c
Vc - pcc = Ic (7)
Zu + Zc
V pcc Vu - pcc + Vc - pcc
= (8)
Zu ZC 2 2 2
V pcc + Vc - pcc Vu - pcc
Vcf = (9)
2 V pcc
2 2 2
V pcc + Vu - pcc Vc - pcc
Figure 1. Harmonic Thevenin equivalent circuit for utility and costumer Vuf = (10)
seen from PCC bus 2 V pcc
140 M ajid M oradlou et al.: Application of Superposition and Fuzzy Logic M ethods to Determine the
Contribution of the Utility and Customer in Creation of Harmonic Distortions in PCC Bus

Where Vuf and Vcf are defined as utility and customer Fuzzy set introduced by Zadeh[22], has no accurate
boundaries as compared to the classic sets. Elements of a
contribution in producing harmonic VPCC , respectively[5].
fuzzy set belong to it by a certain degree of membership
which is a real value in interval[0 1]. In a classic set, On the
contrary, an element either belongs or does not belong to the
set i.e. the degree of membership can be 0 or 1. The
membership of elements in a fuzzy set is described with the
aid of a membership function valued in the real unit
interval[0 1]. For example the classic set A can be defined as:
{
A = x x 5 } (13)
The fuzzy set B is written belo w in which B (x ) is the
membership function (MF) of the variab le x in B:
Figure 2. Harmonic Norton equivalent circuit for utility and costumer {
B = x, B ( x ) x X } (14)
seen from PCC bus Examples of fu zzy and classic membership functions
related to being tall are shown in Fig 3.
2.3. Identifying the Dominant Source in the Creati on of
Harmonic B ased on Definiti ons of Harmonic
Contri bution
According to the equations (1) to (10), it is seen that in
order to accurately determine the harmonic contribution,
along with the measured values in PCC bus, precise values of
harmonic impedances Z u and Z c are needed. Th is is
difficult to obtain due to numerous uncertainties in harmonic
impedances of the loads. Thus, if the precise amounts of
harmonic impedances are not accessible, another criterion
for identification of do minant harmonic sources must be Figure 3. Membership function rated to "being tall" a) Classic b) Fuzzy
presented.
Fuzzy logic is a generalizat ion of the standard Boolean
By d ifferentiating equations (4) and (5) and using (1) and
logic in wh ich, as opposed to the latter, the fuzzy quantities
(2), equation (11) can be derived as follows:
2 2
not only can be correct or incorrect but can have any value
2 2
I u - pcc I c - pcc Eu Ec between 0 and 1. The Boolean logic operators such as And,
I uf I cf
= = 2
(11) Or, Not etc. also exist in fuzzy logic. So, using fuzzy sets
I pcc I pcc Zu + Zc the bivalent logic can be generalized which can have many
In the same way by d ifferentiating equations (9) and (10) applications.
and using (6) and (7), equation (12) is obtained as follows:
2 2 2 2
Vu - pcc Vc - pcc Iu Ic Zu Z c 2
Vuf Vcf
= = ( ) (12)
V pcc V pcc Zu + Zc
It is shown by (11) and (12) that in order to determine the
dominant source in the creation of harmonic current I PCC , a
comparison between E u and E c will suffice. And in
order to determine the dominant source in the creation of
harmonic voltage VPCC , a co mparison between I u and

I c will be sufficient. Based on this, different methods


Figure 4. Description of linguistic variable "age"
have been presented[16-20].
Using fuzzy logic conditional sentences known as
if-then rules[23] can be easily implemented. These rules
3. Fuzzy Set Theory and Fuzzy consist of two parts: 1) the premise or if and 2) the
Inference Systems conclusion or then. For example these rules can be
written as if x is A then y is B in which A and B are
a) Fuzzy set theory linguistic variables and their values are in sentential form in
International Journal of Energy Engineering 2013, 3(3): 138-146 141

natural language. Fig. 4 shows examples of membership 2 2 2 2


E=
c Zc I pcc + V pcc 2 ( Rc P + X c Q ) (18)
functions for the linguistic variable age tit led as very
young, young and old. 2
Eu Ec =I U IC
2
(19)
b) Fuzzy inference system
Fuzzy inference is the process of mapping an input value Where according to the definition, IC and IU are:
2
to a desired output using fuzzy log ic. According to Fig. 5 = Z u [ Z u I pcc + 2 ( P cos u + Q sin u ) ] (20)
IU
each fuzzy in ference system can be described as follo wing:
2
1) Fuzzification: in this stage every crisp (not fuzzy) IC= Z c [ Z c I pcc 2 ( P cos c + Q sin c ) ] (21)
value is transformed to its corresponding linguistic variable
(fuzzy value). This is done using appropriate membership Where u and c are defined as follows:
functions. X X
2) Knowledge base: this part includes definitions of =u tg=
-1
( u ) , c tg -1 ( c )
membership functions and the necessary if-then rules. Ru Rc (22)
3) Inference- engine: Th is part simu lates human decision , 90 < u , c < 90
making process.
Given the equation (19) and since the denominator in (11)
4) Defu zzificat ion: in this step the fuzzy output is is positive in every case, it is seen that if IU is greater than IC,
converted to a crisp value. then the upstream network is the dominant source in the
creation of I PCC and vice versa. Also based on (20) and
(21), IU is only a function of quantities measured in PCC bus
and the phase and amp litude of Z u and IC is only a function
of quantities measured in PCC bus and the phase and
Figure 5. Block Diagram of a Fuzzy Inference System (FIS) amp litude of Z c . Thus according to the assumptions made
for harmonic impedances at the beginning of this section, IU
is appro ximately known while IC is unknown. Meanwh ile,
4. Proposed Method having the range of variation of Z c and its possible states, a
In the proposed method it is assumed that the upstream maximu m and minimu m can be found for IC. These points
network harmonic impedance Z u is known (similar to are the basis for the proposed approach in this paper.
methods presented in[19-20]). Th is is because uncertainty in Using the concept of duality similar expressions can be
equivalent harmonic impedance is mostly due to derived for the identification of the do minant source in the
uncertainties in harmonic impedances of the loads. If there is creation of harmonic voltage VPCC . Duals of (19) to (22) are
no power factor correction capacitor in the upstream network as follows:
in the vicinity of PCC, it can be assumed that Z u is 2 2
I u I c = VU VC (23)
dominated by the impedance of step down transformer[1-3].
Furthermore; it is assumed that the range of variation of 2
VU
= Yu [ Yu V pcc + 2 ( P cos u Q sin u ) ] (24)
downstream network harmonic impedance Z c is
2
known[19-20]. = Yc [ Yc V pcc 2 ( P cos c Q sin c ) ] (25)
VC
To explain the proposed method, it is assumed that the
goal is to identify the do minant source in the creation of -1 bu b
harmonic current I PCC . According to (11), to compare I uf
= u tg= ( ) , c tg -1 ( c )
gu gc (26)
and I cf , a co mparison between Eu and Ec can be made. , 90 < u , c < 90
According to Fig. 1 and circuit laws, fo llo wing per-unit Where
relationships can be expressed:
1 1
Eu = V pcc + ( Ru + j X u ) I pcc Yu = gu + j bu , Yc =
= g c + j bc
= (27)
Zu Zc
P jQ (15)
= V pcc + ( Ru + j X u )( ) As in IU and IC, the value of VU is known while the value
V pcc* of VC is unknown but its maximu m and minimu m can be
found.
Ec = V pcc ( Rc + j X c ) I pcc
In the fo llowing section, the proposed algorithm will be
P jQ (16) explained and afterwards the designed fuzzy system will be
= V pcc ( Rc + j X c ) ( )
V pcc* introduced.
By separating above relat ions into real and imaginary 4.1. Designed Algorithm
parts, one can have:
2 2 2 2 The proposed algorithm for the estimat ion of relat ive
E=
u Zu I pcc + V pcc + 2 ( Ru P + X u Q ) (17) contribution of the utility and customer in the creat ion of
142 M ajid M oradlou et al.: Application of Superposition and Fuzzy Logic M ethods to Determine the
Contribution of the Utility and Customer in Creation of Harmonic Distortions in PCC Bus

-0.5.
I PCC (in case that the amplitude and harmonic phase of Very Small (VS): for values between -0.5 and -0.8.
Z c is unknown) is as follo ws: Very Very Small (VVS): fo r values smaller than -0.8.
Measurement of I PCC , VPCC , P and Q. Therefore the membership functions for each of the inputs
K1 and K2 is as shown in Fig. 6.
Calculation of IU using (20) and with the assumption
After applying the if-then rules to K1 and K2 , the output
that Z u is known.
K3 is obtained. K3 is also described using triangular
Calculat ion of ICmin and ICmax using (21) based on the membership functions and ranges from 0 to 1. It is used for
range of variations and possible states for Z c . comparing IU and IC and thus for comparing the
Entering IU, ICmin and ICmax to designed fuzzy system. contribution of utility and customer. Definition of K3 and its
Deriving the results from the designed fuzzy system and results are shown in Table 1 and its membership functions
calculation of relative contribution of network and customer. are shown in Fig. 7.
As it is seen in the proposed algorithm, in contrast to past
well-known method[19], there is no need for the precise VVS VS MS LS LL ML VL VVL
1
value of Z c .
For calculat ing the relative contribution of the utility and 0.8

Degree of membership
customer in the creation of VPCC the same algorithm can be
emp loyed. However, instead of IU and IC, VU and VC 0.6
should be replaced, respectively.
0.4
4.2. Designed Fuzzy System
Before describing the fuzzy system, it should be noted that 0.2
the definit ion of ind ices, membership functions and if-then
rules has been done according to experimental results in 0
different conditions, practical values of elements used in
power systems and harmonic models. -1.5 -1 -0.5 0 0.5 1 1.5
k1
In this section the fuzzy system which is used for
calculating the relative contribution of the utility and Figure 6. Membership functions of inputs K1 and K2

customer in the creation of I PCC is described. As it was


mentioned earlier, the inputs to these systems are the values 1
UVLC ULC UMLC EU E EC CMLU CLU CVLU

of IU, ICmin and ICmax. Calculation of relat ive contribution


of the utility and customer in the creation of VPCC is carried 0.8
Degree of membership

out in a similar way but in this case the inputs are values of
VU, VCmin and VCmax. 0.6
a) Defi nition of indices
The two indices K1 and K2 as inputs to the fuzzy system
0.4
are defined as follows:
ICmax IU ICmin IU
= K1 = , K2 (28) 0.2
ICmax ICmin
If K1 is negative then IU is surely greater than IC and the 0
contribution of the upstream network is greater. Also if K2 is
0 0.2 0.4 0.6 0.8 1
positive then IU is surely smaller than IC and the a
contribution of upstream network is less. However it is not
Figure 7. Membership functions of output K3
known how much greater or less this contribution exactly is.
b) Fuzzificati on of inputs and outputs c) Fuzzy if-then rules
Triangular membership functions are used for 36 rules are used for obtaining K3 some of which are
fuzzification of K1 and K2 crisp values and 8 linguistic shown in Table 2. These rules are based on different
variables are used for their expression: combinations of K1 and K2 using AND operator.
Very Very Large (VVL): for values greater than 0.8. d) Fuzzy inference mechanism
Very Large (VL): fo r values between 0.5 and 0.8. Mamdani fuzzy in ference is used in imp lementation of
Moderately Large (M L): for values between 0.25 and this fuzzy system.
0.5. e) Defuzzification
Little Large (LL): for values between 0 and 0.25. For d ifu zzificat ion of K3 the centroid of area method is
Little Small (LS): for values between -0.25 and 0. emp loyed and the resulting crisp value is linguistically
Moderately Small (MS): for values between -0.25 and described using intervals in Table 1.
International Journal of Energy Engineering 2013, 3(3): 138-146 143

Table 1. Definition of K3 and Its Results


ASD harmonic spectrum mentioned in[21] and the other half
Value of K3
Linguistic
Result
is modeled as RL load with a power factor equal to that of the
Description RECT load.
Between 0.8 Contribution of customer is much The 39:T3 SEC load is also considered as harmonic load
CVLU
and 1 greater than utility
Between 0.7 Contribution of customer is
and is modeled like RECT load.
CLU The 29:T11 SEC load is also considered as harmonic load.
and 0.8 relatively greater than utility
Between 0.63 Contribution of customer is 25% of it is modeled as a current source with ASD harmon ic
CMLU spectrum and the rest is modeled as RL load with the same
and 0.7 approximately greater than utility
Contribution of two sides is close RECT load power factor.
Between 0.58 The 5th, 7th and 11th voltage harmonics with the
EC with a little dominancy at customer
and 0.63
side amp litudes of 0.015, 0.009 and 0.005 per-unit respectively
Between 0.42 Contribution of two sides is and a phase of zero degree are in jected in 100: UTIL-69 bus
E
and 0.58 approximately equal as background voltage harmonics so that the voltage THD
Between 0.37 Contribution of two sides is close
and 0.42
EU
with a little dominancy at utility side
reaches 3% in the bus.
Between 0.3 Contribution of utility is The simu lation is done in two different cases for upstream
UMLC and downstream networks of PCC bus.
and 0.37 approximately greater than customer
Between 0.2 Contribution of utility is relatively a) First case
ULC
and 0.3 greater than customer In this case, 03 M ILL-1 is selected as PCC bus and the
Between 0 Contribution of utility is much customer side includes the F1 feeder along with its
UVLC
and 0.2 greater than customer
transformers and its downstream loads. The rest of the
Table 2. Some of defined if-then rules system is considered as upstream network. So the current of
F1 is the same as I PCC . The results of current measurement
Rule No. K1 K2 K3
in PCC bus for 5th, 7th and 11th harmonics are p resented in
1 VVL VVL CVLU
Table 3. Using real data and with the aid of software, the
2 VVL VL CLU
percentage of ratio of voltage and current harmonics with
3 VVL ML CMLU
respect to their fundamental co mponent and the real values
4 VVL LL EC
of Zu and Zc are also mentioned in Tab le 3. THD of voltage
7 VVL VS E
and current in PCC is 7.6 and 6.64 percent, respectively.
9 VL VL CLU
Using superposition method and real data, the real values
10 VL ML CMLU
for customer and network contribution in the creation of
11 VL LL EC
harmonic distortions in PCC bus are given in Table 4. The
12 VL LS EC
negative signs in this table are due to harmonic cancellation
14 VL VS E
in two sides.
16 ML ML CMLU
Now lets assume that the values for harmon ic impedances
17 ML LL EC
of the loads have an error of 50% and 45% in their
18 ML LS E
amp litude and phase, provided that their phases will stay in
21 ML VVS EU
the interval between +90 and -90 degrees. The error in data
22 LL LL EC
related to the 05 FRD F loads will result in an error in
23 LL LS E
phase and amplitude of Zu . In a similar way error in
26 LL VVS EU
informat ion of 29 T11 SEC loads will lead to an error in Zu
27 LS LS EU This error, however, can be neglected and Zu can be assumed
33 MS VVS UMLC as fixed and known.
35 VS VVS ULC To determine the relative harmonic contribution of the
36 VVS VVS UVLC utility and customer in the creation of IP CC, quantities IU,
ICmin and ICmax are calcu lated for the 5th, 7th and 11th
harmonics and presented in Table 5 (the values related to
5. Implementation of Proposed Method above quantities in this table have to be mult iplied with 104).
on a Sample Network In the same way, in o rder to estimate the relative contribution
of either sides in the creation o f VP CC, quantities VU, VCmin
To evaluate the proposed method, the IEEE 13-bus and VCmax are calculated for the 5th, 7th and 11th harmonics
industrial distribution system[21] is used. The simulated and presented in Table 6. Using the values of K1 and K2 in
network in Digsilent software is shown in Fig. 8. Table 5 and Table 6 and the proposed fuzzy inference system,
In order to perform better evaluation the following the relative contribution of customer and the network in the
modifications have been made on the network: creation of desired harmonics is estimated and given in Tab le
Half of the RECT load is modeled as current source with 7.
144 M ajid M oradlou et al.: Application of Superposition and Fuzzy Logic M ethods to Determine the
Contribution of the Utility and Customer in Creation of Harmonic Distortions in PCC Bus

Figure 8. IEEE 13 bus industrial distribution network simulated in Power Factory Digsilent software

Co mparing the real contributions in Table 4 and the are 57 and 43 percent. In these cases, fuzzy system resulted
estimated relative contributions using fuzzy system in Tab le in approximately equal which is not far fro m the reality. In
7, it is observed that: other words, in these cases the fuzzy system produced
In cases of 5th and 11th current harmonics and 5th and 7th responses that were close to the real ones (not exactly the
voltage harmonics the results are exactly the same. In other same as them).
words, in these cases one side is the dominant source with
much greater contribution than the other. Similar results Table 5. Calculated quantities to determine the relative harmonic
contribution of the utility and customer in the creation of I PCC in the first case
have been produced by the fuzzy system, too.
Harmonic
Table 3. The results of current measurement in PCC bus in the first case IU ICmin ICmax K1 K2
order
5 -1.8 158 1200 1.001 1.011
Harmonic order 5 7 11
7 108 -94 300 0.64 -2.15

I pcc % 3.42 2.11 2.36


11 -0.18 193 1860 1.00 1.00

Table 6. Calculated quantities to determine the relative harmonic


contribution of the utility and customer in the creation of VPCC in the first
V pcc % 1.95 7.06 0.38 case
Harmonic
VU VCmin VCmax K1 K2
Amplitude of Zc (ohm) 311.5 406.9 606.9 order
5 455 2.1 8.84 -50.47 -215.7
Phase of Zc (degree) 63.3 69.5 76.2 7 47 -6 -2.4 -20.58 -8.83
Amplitude of Zu (ohm) 6.14 112.7 4.98 11 4.77 0.04 4.51 -0.058 -118.25

Phase of Zu (degree) 87.9 70.3 -89.6 Table 7. Estimation of the relative contribution of customer and utility in
creation of desired harmonics in the first case by means of fuzzy inference
system
Table 4. The real harmonic contribution in PCC bus in the first case
The results of fuzzy inference system
Harmonic order (percent) 5 7 11 Contribution of costumer is much greater than
Current (h=5)
utility
Iuf -10.4 62.3 0.76 Contribution of customer and utility are
Current (h=7)
Icf 110.4 37.7 99.24 approximately equal
Contribution of customer is much greater than
Vuf 84.5 113.9 57 Current (h=11)
utility
Contribution of of utility is much more greater
Vcf 15.5 -13.9 43 Voltage (h=5)
than customer.
Contribution of of utility is much more greater
For 7th current harmonic the real values of relat ive Voltage (h=7)
than customer.
contribution of the network and customer are 62 and 38 Contribution of customer and utility are
Voltage (h=11)
percent respectively. For 11th voltage harmonic these values approximately equal.
International Journal of Energy Engineering 2013, 3(3): 138-146 145

b) Second case Table 12. Estimation of the relative contribution of customer and utility in
creation of desired harmonics in the second case by means of fuzzy
The 03 MILL-1 bus is selected as PCC bus in this case inference system
too. However; the T1 transformer and its upstream network The results of fuzzy inference systems
are considered as upstream network of PCC and the rest of Contribution of customer is much greater than
Current (h=5)
the network are considered as the downstream network of utility
this bus. Thus the current in second side of the T1 Current (h=7)
Contribution of customer and utility are
transformer is the IP CC. The real values resulting fro m the approximately equal
Contribution of utility is much more greater than
measurements in PCC bus for 5th, 7th and 11th harmonics Current (h=11)
customer
are given in Tab le 8 and the real values of contribution of t wo Contribution of utility is much greater than
sides in the creation of current and voltage harmonics are Voltage (h=5)
customer
shown in Table 9 THD of PCC current is 21%. Contribution of two sides is close with a little
Voltage (h=7)
In this case the error range for available values of dominancy at utility side
harmonic impedances is the same as the first case. Voltage (h=11)
Contribution of customer and utility are
approximately equal
Furthermore Z u is assumed fixed and known and its value
is equal to harmonic impedance of the T1 step-down Co mparing the real values for contributions in Table 9 and
transformer. Similar to the first case the, results of proposed the estimated relative contributions using fuzzy system in
method are presented in Table 10 to Table 12. Table 12 it is observed that:
In cases of 5th and 11th current harmonics and 5th voltage
Table 8. The results of current measurement in PCC bus in the second case
harmonics, the results are exactly the same. In other words in
Harmonic order 5 7 11 these cases one side has much greater contribution than the
other and the fuzzy system has also shown this.
I pcc % 2 20.6 1.81
For 11th voltage harmon ic, the real values of relat ive
contribution of the utility and customer are 57 and 43 percent.
V pcc % 1.95 7.06 0.38 In these cases fuzzy system resulted in appro ximately equal
which is not far fro m the reality.
Amplitude of Zc (ohm) 186.6 9.28 3.64 In case of 7th current harmonic, it is seen that a harmonic
Phase of Zc (degree) -2.8 -88.5 -89.7 cancellation has taken place and the real contributions of two
Amplitude of Zu (ohm) 6 8.44 13.27 sides are in opposite direction. Considering the fact that the
Phase of Zu (degree) 89.3 89.5 89.7 real value of customer contribution is -44% it can be
concluded that the customer can have a contribution of 44%.
Table 9. The real harmonic contribution in PCC bus in the second case So the contributions of two sides can be assumed to be close
Harmonic order (%) 5 7 11 to each other. The output of the fuzzy system also confirms
Iuf -0.78 144.3 80.8 this result.
In case of 7th voltage harmonic, the real contributions of
Icf 100.78 -44.3 19.2
two sides are in opposite direction and the contribution of
Vuf 77.4 138.4 46.7 customer is -38% so it can be concluded that the customer
can have a contribution of 38%. So the contributions can be
Vcf 22.6 -38.4 53.3
assumed as equal with a little do minance in the utility side.
The fuzzy system shows the same result.
Table 10. Calculated quantities to determine the relative harmonic
contribution of the utility and customer in the creation of I PCC in the second According to the simu lation results it is seen that using the
case proposed method, the approximate relative contribution of
Harmonic the utility and customer in the creation of harmon ic
IU ICmin ICmax K1 K2
order distortions in PCC bus can be determined. It is also seen that
5 -2.85 66.9 910 1.003 1.043 in proposed method there is no need for precise data related
7 -92.3 -93.8 -93.3 -0.0107 -0.016 to the harmonic impedances of customers.
11 0.2 -0.23 -0.22 -1.91 -1.87

Table 11. Calculated quantities to determine the relative harmonic


6. Conclusions
contribution of the utility and customer in the creation of VPCC in the second
case Due to importance of determination of the relat ive
harmonic contribution of the utility and customer in the
Harmoni
VU VCmin VCmax K1 K2 creation of harmonic distortions in PCC bus and lack of
c order reliable method in this field, a new method is proposed by
5 309 -4.96 185.8 -0.663 -63.3 application of superposition method and fuzzy logic
7 -3429 -3500 -3480 -0.0146 -0.0202 technique. The required data for this purpose are the
measurement results in PCC bus and approximate
11 -17.9 -18.2 -12.3 0.455 -0.0165
informat ion about harmonic impedances of customers. The
146 M ajid M oradlou et al.: Application of Superposition and Fuzzy Logic M ethods to Determine the
Contribution of the Utility and Customer in Creation of Harmonic Distortions in PCC Bus

proposed method in co mparison with other well-known [11] S. Das gupta, S. N. M ohan, and S. K. Sahoo, Application of
methods, never results in an incorrect answer and offers four-switch-based three-phase grid-connected inverter to
connect renewable energy source to a generalized unbalanced
approximately correct estimation of relat ive contributions of micro grid system, IEEE Transactions on Industrial
two sides in the creation of the d istortions. The specifications Electronics, vol. 60, no. 3, pp. 1204-1215, 2013.
and validation of this method have been verified by
simu lating the IEEE 13 bus industrial distribution system in [12] P. E. M elin, et. al, Analysis, design and control of a unified
power-quality conditioner based on a current-source
DIGISILENT software. topology, IEEE Transactions on Power Delivery, vol. 27, no.
4, pp. 1727-1736, 2012.

ACKNOWLEDGEMENTS [13] R. A. Fernandes, S. M . Ranzini, I. Silva, and M . Oleskovicz,


Wrapper attribute selector and intelligent systems applied to
This research was undertaken in the framework of a the identification of residential harmonic sources, in Proc.
research project supported by the Islamic A zad Un iversity, Power and Energy Society General M eeting, IEEE, 22-26
July, 2012.
Zanjan Branch. So, the authors gratefully acknowledge
Zanjan Branch of Islamic Azad University for their financial [14] A. M . Ferrero, M . Prioli, and S. Salicone, Fuzzy
and spiritual supports. M etrology-Sound Approach to the Identification of Sources
Injecting Periodic Disturbances in Electric Networks, IEEE
Transactions on Instrumentation and M easurement, vol. 60,
no. 9, pp. 30073017, 2011.

REFERENCES [15] E. Grsoy, and D. Niebur, Harmonic Load Identification


Using Complex Independent Component Analysis, IEEE
[1] J. Arrillaga, Power System Harmonics, 2nd edition., John Transactions on Power Delivery, vol. 24, no. 1, pp. 285292,
Wiley, New York, 2003. 2009.

[2] IEEE 519-1992, IEEE Recommended Practices and [16] R. A. Fernandes, I. Silva, and M . Oleskovicz, Data M ining
Requirements for Harmonic Control in Electrical Power Applied to Identification of Harmonic Sources in Residential
Systems (ANSI), 1992. Consumers, Latin America Transactions, IEEE (Revista
IEEE America Latina), vol. 9, no. 3, pp. 302-310, 2011.
[3] R. C. Dugan, and M . F. Granghan, Electrical power system
quality, 2nd edition, M c Graw-Hill, New York, 2004. [17] R. Pyzalski R. Lukomski, and K. Wilkosz, Utilization of
The Voltage Rate to Localization of Harmonic Source in a
[4] W. Xu, Power Direction M ethod Cannot be Used for Power Systems, in Proc. IEEE M elecon Conference,
Harmonic Source Detection, IEEE Power Engineering 1091-1094, 2004.
Society Summer M eeting, vol. 2, no. 4, pp. 873-876, 2000.
[18] N. Hamzah, A. M ohamed, and A. Hussain, Harmonic
[5] W. Xu, X. Liu, and Y. Liu, An Investigation on The Validity Source Location at The Point of Common Coupling Based on
of Power-Direction M ethod for Harmonic Sources Voltage M agnitude, in Proc. TENCON. IEEE Region 10
Determination, IEEE Transaction on Power Delivery, vol. Conference, 2004.
18, no. 1, pp. 214-219, 2003.
[19] C. Chen, X. Liu, D. Koval, and W. Xu, Critical Impedance
[6] E. Thunberg, and L. Soder, A Norton Approach to M ethod- A New Detecting Harmonic Sources M ethod in
Distribution Network M odeling for Harmonic Studies, IEEE Distributions Systems, IEEE Transaction on Power
Transaction on Power Delivery, vol. 14, no. 1, pp. 272-277, Delivery, vol. 19, pp. 286-297, 2004.
1999.
[20] C. Liu, and W. Xu, A Critical Impedance-Based M ethod for
[7] W. Xu, and Y. Liu, A M ethod for Determining Customer Identifying Harmonic Sources, IEEE Transaction on Power
and Utility Harmonic Contributions at The Point of Common Delivery, vol. 19, pp. 671-678, 2004.
Coupling, IEEE Transaction on Power Delivery, vol. 15, no.
2, pp. 804-811, 2000. [21] M . Moradlou, M . AghaZadeh, and H. R. Karshenas, A New
M ethod for Identification of M ain Harmonic Source Based on
[8] H. Yang, P. Pirotte, E. De Jaeager, and A. Robert, Harmonic the Superposition and Critical Impedance M ethods in Proc.
emission levels of industrial loads statistical assessments, North American Power Symposium, 2008.
in Proc. CIGRE, paper 36-306, 1996.
[22] Transmission & Distribution Committee, IEEE Power
[9] B. Chazottes, T. Deflandre, and F. Gorgette Estimation the Engineering Society, Test System for Harmonic M odeling
true customers contribution to the power system harmonic and Simulation, IEEE Transaction on Power Delivery, vol.
disturbances, in Proc. Conf. Power Quality Applicat., 14, pp. 579-583, 1999.
Sweden, 1997.
[23] L. A. Zadeh, Fuzzy sets, Inf. Control, No. 8, 338353,
[10] O. Gonbeau, L. Berthet, J. Javerzac, and D. Beudou, 1965.
M ethod to Determine Contribution of The Customer and
The Power Systems to The Harmonic Disturbances, in Proc. [24] Y. Jin, Advanced Fuzzy Systems Design and Applications.
17th International Conference on electrically distribution, New York, Physica- Verlag, Heidelberg, 2003.
Session 2, Paper No.32, Barcelona, 2003.

Das könnte Ihnen auch gefallen