75 en
520 Series
LSN improved Fire Detectors (EU)
BDLF.01U.025.877
A1.en / 03.02.2006
Page 0 STFIR/PRM1 / zab
Product Information 520 Series LSN improved Fire Detectors (EU) PI 34.75 en
Table of Contents
1. Product Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.1. System Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
1.2. Configuration of the Detector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
1.3. Functional Description of the Sensor Technology . . . . . . . . . . . . . . . . 8
1.4. LED Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
1.5. Performance Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
2. Planning Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
2.1. General Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
2.2. Network Topologies for LSN Improved . . . . . . . . . . . . . . . . . . . . . . . . . 13
3. Programming . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
4. Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
4.1. Detector and Trim Ring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
4.2. Detector Base . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
4.3. Mounting Boxes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
5. Mounting Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
5.1. Ceiling Mount Back Box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
5.2. Detector Base / Detector Base with Relay . . . . . . . . . . . . . . . . . . . . . . 21
5.3. Address Allocation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
5.4. Detector and Trim Ring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
5.5. Builtin Housing for Concrete Ceilings . . . . . . . . . . . . . . . . . . . . . . . . . 26
5.6. Surface Mount Back Box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
5.7. External Detector Alarm Displays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
BDLF.01U.025.877
Page 3 A1.en / 03.02.2006
STFIR/PRM1 / zab
Product Information 520 Series LSN improved Fire Detectors (EU) PI 34.75 en
6. Order Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
6.1. Detector and Trim Ring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
6.2. Detector Bases / Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
6.3. Mounting Boxes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
6.4. Service / Hardware Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
8. Repair . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
9. Disposal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
11. Abbreviations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
BDLF.01U.025.877
Page 4 A1.en / 03.02.2006
STFIR/PRM1 / zab
Product Information 520 Series LSN improved Fire Detectors (EU) PI 34.75 en
1. Product Description
The 520 series fire detectors combine the advantages of the improved LSN technol-
ogy with the aesthetic benefits of flushmounted installation and the option to choose
the color. The detectors are specially designed for connection to the Modular Fire
panel Series 5000 with the significantly exrtended LSN system parameters. They can
also be connested to all classic LSN fire panels.
The detectors with associated trim ring are available in the versions white and
transparent with color toning inserts. Through the use of the supplied color toning
inserts, optimum adjustment to many different environments becomes possible.
The lack of an optical labyrinth and their easilycleaned smooth surface means the
detectors are also suitable for applications in highdust areas.
The low profile, flushmounted design allows the use the detectors even in areas that
must be free of protrusions.
Thanks to the geometric arrangement of two separate optical sensor systems, the de-
tectors are not sensitive to interference, such as that caused by insects. The scattered
light volume that is evaluated by the sensors is located in the free space a few centime-
ters below the ceiling.
The contamination level is measured constantly. Contamination of the detector sur-
face leads to an active adjustment of the threshold (drift compensation) and a fault indi-
cation at the panel in the case of heavier contamination.
The detector is available as a scattered light fire detector only or as a multisensor de-
tector with an additional gas sensor.
The combination of scattered light detector and gas sensor allows the evaluation of
signals with the help of modern signal processing methods. The result is high immunity
against deceptive alarms and extended application possibilities in environments that
are not suitable for pure scattered light smoke detectors.
The integrated rotary switches allow for an automatic or manual allocation of ad-
dresses.
The FAP520 detectors can be connected directly to the Local SecurityNetwork LSN.
Accessories
The 520 series detectors are generally mounted flush with the ceiling in false ceilings.
The detector and base are installed in a robust ceiling mount back box. In addition, a
housing for mounting within concrete ceilings can be used.
For special applications where recessed ceiling mounting is not possible, a surface
mount back box is available. This is used as an alternative to the ceiling mount back box.
The surface mount back box with damp room seal also allows the detector to be used
in a humid environment.
For special applications, e.g. control of an emergency door in accordance with DIBt,
base variants are available with relay (only in combination with the Modular Fire Panel
FPA5000).
In the GBbase versions, integrated jumper elements are provided that preserve the
loop function if the detector is removed.
BDLF.01U.025.877
Page 5 A1.en / 03.02.2006
STFIR/PRM1 / zab
Product Information 520 Series LSN improved Fire Detectors (EU) PI 34.75 en
All bases have an integrated strain relief for false ceiling cables.
The connection terminals are easily accessible. Cables up to 3.3 mm2 in cross section
can be used.
An innovative concept for locking the detector module utilizing the pushin/pushout prin-
ciple allows very quick and easy insertion and exchange of the click and lock detector.
For the detector test and detector exchange, a special userfriendly service accessory
is available.
BDLF.01U.025.877
Page 6 A1.en / 03.02.2006
STFIR/PRM1 / zab
Product Information 520 Series LSN improved Fire Detectors (EU) PI 34.75 en
5 = Twocolor LED:
1.
red = alarm
green = test mode / trouble 2 3
6 = Pollution sensor
7 = Measuring area
2.
7
BDLF.01U.025.877
Page 7 A1.en / 03.02.2006
STFIR/PRM1 / zab
Product Information 520 Series LSN improved Fire Detectors (EU) PI 34.75 en
Pollution sensor
The contamination level of the detector surface is measured and evaluated continu-
ously by the pollution sensor (Fig. 1., Pos. 6). A threestage contamination display can
be read out at service (see Chapter 7.1.).
BDLF.01U.025.877
Page 8 A1.en / 03.02.2006
STFIR/PRM1 / zab
Product Information 520 Series LSN improved Fire Detectors (EU) PI 34.75 en
LED Operation
Status LED
Standby off
Alarm red, flashes
Trouble green, double flash every 8 to12 second
Test mode green, flashes once every second
BDLF.01U.025.877
Page 9 A1.en / 03.02.2006
STFIR/PRM1 / zab
Product Information 520 Series LSN improved Fire Detectors (EU) PI 34.75 en
BDLF.01U.025.877
Page 10 A1.en / 03.02.2006
STFIR/PRM1 / zab
Product Information 520 Series LSN improved Fire Detectors (EU) PI 34.75 en
D When using the FAA500TTL test adapter, an integrated reed switch automati-
cally switches the detector into the test mode.
D The EMC security fulfills the guidelines according to VdS 2110 (VdS Schaden-
verhtung GmbH) as well as UL 268.
D Can be connected to the LSN fire panels FPA5000, BZ 500 LSN, UEZ 2000 LSN,
UGM 2020 and to other fire panels or their receiver modules with identical connec-
tion conditions.
D VdS Approval
D CE conform according to EN 547
BDLF.01U.025.877
Page 11 A1.en / 03.02.2006
STFIR/PRM1 / zab
Product Information 520 Series LSN improved Fire Detectors (EU) PI 34.75 en
2. Planning Notes
2.1. General Notes
The 520 series detectors are approved for indoor use only!
The detectors must be installed exclusively in the FAA500 series
bases provided. In addition, the detector base must be installed in
an FAA500BB ceiling mount back box or in an FAA500SB sur-
face mount back box.
that no parts of the detector surface be-
come covered. 3. 2
D The detector may only be installed in a position which is out of arms reach.
Minimum installation height recommended by BOSCH: 2.70 m.
D The 520 series detectors may not be installed in rooms with data transmission by
means of highintensity infrared light (e.g. in rooms with IR systems for interpreters).
D The detectors must be mounted so that they are not exposed to any direct sunlight.
D A minimum distance of 50 cm from lamps must be maintained.
The detectors may not be mounted in a cone of light from lamps.
D The standard spring inside the bases allows detector mounting in false ceiling
panels. For concrete and wooden ceiling, replace with the FAA500SPRING with
red marking (ordering information see section 6.2.).
D Maximum permitted air speed: 20 m/s.
D Maximum number of FAP500 detectors connectable to the Local SecurityNetwork
LSN:
BOSCH LSN fire panels: up to 28 detectors per NVU as loop or stub line
Modular Fire Panel FPA5000: up to 85 detectors per LSN 0300 module.
BDLF.01U.025.877
Page 12 A1.en / 03.02.2006
STFIR/PRM1 / zab
Product Information 520 Series LSN improved Fire Detectors (EU) PI 34.75 en
When planning, consider the expected total current consumption and line
resistance to ensure a minimum voltage supply of 15 V for each detector.
R
R R
R
R
R
R R
Stubs (1 or 2) and Ttaps Loops or stubs mixed with Mixed loop topology:
mixed Ttaps If detectors marked by R
are removed, any of the
remaining detectors is still
functioning.
BDLF.01U.025.877
Page 13 A1.en / 03.02.2006
STFIR/PRM1 / zab
Product Information 520 Series LSN improved Fire Detectors (EU) PI 34.75 en
3. Programming
LSN detectors are programmed according to the required operating mode.
Programming is carried out with the programming software using a PC or laptop con-
nected to the fire panel.
The suitable response sensitivity of the multisensor detector is programmed by speci-
fying the operating location (e.g. computer room, office, large kitchen). The selection of
the operation location determines the optimal characteristic diagram for the fire and dis-
turbance variable evaluation.
If, according to the operating location, a low sensitivity is set for the optical sensor, the
alarm goes off only if the detector senses high levels of smoke and of CO at the same
time. This is the case with open or smouldering fire.
Programming the multisensor detector and linking all detectors by algorithms, consider-
ably increases the fire detection reliability and lowers the false alarm rate.
FAPOC 520(P)
o ratinng
Conference room / waiting room / exhibition hall low
lwayys
he opera
Warehouse with vehicle traffic low
of th
Kitchen / casino / restaurant during operation low
th C un
ess o
Garage low
egarrdles
Office (daily operation) medium of the
School / kindergarten medium
nsitivvity o
h, re
BDLF.01U.025.877
Page 14 A1.en / 03.02.2006
STFIR/PRM1 / zab
Product Information 520 Series LSN improved Fire Detectors (EU) PI 34.75 en
In the case of the optical FAPO 520 detector, the sensitivity of the optical sensors can
be set on three levels. Depending on the operating location, the optical sensor of the
detector is thus adjusted to the environmental conditions. For fire detection, also the
time behavior of the fire characteristics is evaluated. This is very different from the time
behavior of the disturbance variables.
FAPO 520(P)
For execution of the function test for the FAPO 520 and FAP
OC 520 detector, the detector must be switched to test mode. This
can be carried out via the fire panel or via the reed switch at the de-
tector with the help of a magnet.
BDLF.01U.025.877
Page 15 A1.en / 03.02.2006
STFIR/PRM1 / zab
Product Information 520 Series LSN improved Fire Detectors (EU) PI 34.75 en
4. Technical Specifications
4.1. Detector and Trim Ring
Detector type FAPOC 520/FAPOC 520P FAPO 520/FAPO 520P
Detection principle Combination of scattered light Scattered light measurement
and combustion gas measure-
ment
Special features Contamination detection Contamination detection
Drift compensation in optical Drift compensation in optical
and in gas measuring unit unit
Adress allocation Manual or automatic address setting via rotary switches
Operating voltage 15 V DC to 33 V DC
Current consumption 3.25 mA
Individual display Twocolor LED: red / green
Alarm output By data word via twowire signal line
Indicator output Open collector, switches 0 V over 1.5 k, max. 15 mA
Response sensitivity
O unit < 0,36 dB/m (EN 547) < 0,18 dB/m (EN 547)
Gas unit In ppm range
Max. monitoring area 120 m2 (Heed local guidelines)
Maximum installation height 16 m (Heed local guidelines)
Minimum installation height Out of arms reach
Minimum distance to lamps 0.5 m
Permitted air speed 20 m/s
Perm. operating temperature 10 C to +50 C 20 C to +65 C
Permitted relative humidity < 95 % (noncondensing)
Protection category accord-
IP 33 IP 53
ing to EN 60 529
Interference immunity According to VdS 2110, DIN EN 501304 and UL 268
Dimensions
Detector without trim ring 113 x 55 mm (without base) / 113 x 70 mm (with base)
Detector with trim ring 150 x 55 mm (without base) / 150 x 70 mm (with base)
Housing material Polycarbonate
Color of detector housing Signal white, RAL 9003
Color of det. front panel
White variant Signal white, matt
Transparent variant (P) Transparent / silver gray, RAL 7001
Weight (without / with pack.)
Detector Approx. 180 g / 370 g Approx. 170 g / 360 g
Trim ring FAA500TR(P) Approx. 30 g / 60 g
VdS Approval number G 205 119 G 205 125
EC Certification of Conform. 0786CPD20202 0786CPD20201
BDLF.01U.025.877
Page 16 A1.en / 03.02.2006
STFIR/PRM1 / zab
Product Information 520 Series LSN improved Fire Detectors (EU) PI 34.75 en
BDLF.01U.025.877
Page 17 A1.en / 03.02.2006
STFIR/PRM1 / zab
Product Information 520 Series LSN improved Fire Detectors (EU) PI 34.75 en
BDLF.01U.025.877
Page 18 A1.en / 03.02.2006
STFIR/PRM1 / zab
Product Information 520 Series LSN improved Fire Detectors (EU) PI 34.75 en
5. Mounting Notes
The 520 series detectors may only be installed with an FAA500
detector base in combination with a FAA500BB ceiling mount
back box or an FAA500SB surface mount back box.
1
104 mm
129 mm
4
5.
Pos. Description
1 Cable duct connection (UL only)
2 Bracket
3 Screws for fastening base
4 Cable bushing
BDLF.01U.025.877
Page 19 A1.en / 03.02.2006
STFIR/PRM1 / zab
Product Information 520 Series LSN improved Fire Detectors (EU) PI 34.75 en
D Pull the cable through one of the cable bushings. A cable tie around the cable
sheath will secure the cable against being pulled out accidentally.
D Insert the ceiling mount back box in the false ceiling from below.
D A triangular marking (see Fig. 6., Pos. M) is impressed into the outer edge of the
ceiling mount back box. Turn the ceiling mount back boxes so that all markings are
in a line. In this way, the long, middle windows of the detectors will later appear in
a line to give a harmonious overall visual effect.
Fig. 6.: Alignment of ceiling mount back box, base and detector
M
LED
FAPO 520(P)
6. FAA500BB FAA500 FAPOC 520(P)
BDLF.01U.025.877
Page 20 A1.en / 03.02.2006
STFIR/PRM1 / zab
Product Information 520 Series LSN improved Fire Detectors (EU) PI 34.75 en
63,5 mm
cure electrical connection through the clamped
contacts when mounting the detector.
The bases are provided with three mounts
for cable ties. 7.
. These can be used for fastening the base during the wiringup.
Pos. Description
1 Connection terminals 1
2 Mount for cable ties
3 Labeling on LSN connec- 2
tions
4 Fastening slot 3
8.
BDLF.01U.025.877
Page 21 A1.en / 03.02.2006
STFIR/PRM1 / zab
Product Information 520 Series LSN improved Fire Detectors (EU) PI 34.75 en
1 Fire panel
2 Next detector
MPA External detector alarm
display (optional), not for 1
relay bases 2
b2
ye
bk
rd
wh MPA wh
LSN a1/a2
LSN b1
ye
gn gn
9.
D The base is fastened into the ceiling mount back box with four screws. It can be
rotated in the long slots through an angle of 20_ so that fine alignment is possible.
BDLF.01U.025.877
Page 22 A1.en / 03.02.2006
STFIR/PRM1 / zab
Product Information 520 Series LSN improved Fire Detectors (EU) PI 34.75 en
Pos. Description
1 Alignment of the marking on the ceil-
ing mount back box
2 Long slot for fastening the base
3 Spring
4 Triple guidegroove
5 Single guidegroove 3 4
10.
D Place the base in the ceiling mount back box so that the marking on the backbox
(see Fig. 10., Pos. 1) coincides with the single guidegroove on the base (Pos. 5).
D Turn the base until the fastening screws are approximately in the middle of the long
slots (Pos. 2).
D Adjust the bases around this position until they appear in a line.
D Tighten the four screws.
BDLF.01U.025.877
Page 23 A1.en / 03.02.2006
STFIR/PRM1 / zab
Product Information 520 Series LSN improved Fire Detectors (EU) PI 34.75 en
When connecting the detectors to the LSN fire panels BZ 500 LSN, UEZ 2000 LSN
oder UGM 2020, all detectors have to be addressed by CL 0 0.
When connecting the detectors to the Modular Fire Panel FPA5000, the address allo-
cation is done automatically or manually.
In case of a manual allocation, all detectors of the same loop, stub or Ttap have to
have an address between 001 and 254. Addresses between 255 and 299 are not allo-
wed and produce a fault message on the fire panel.
If the addresses shall be allocated automatically by the fire panel, all detectors must
have the address 0 0 0.
BDLF.01U.025.877
Page 24 A1.en / 03.02.2006
STFIR/PRM1 / zab
Product Information 520 Series LSN improved Fire Detectors (EU) PI 34.75 en
BDLF.01U.025.877
Page 25 A1.en / 03.02.2006
STFIR/PRM1 / zab
Product Information 520 Series LSN improved Fire Detectors (EU) PI 34.75 en
226 mm
226 mm
75 mm
ca. 150 mm
F
202 mm
15.
The FAA500CB builtin housing is used for the installation of the detector into con-
crete ceilings. It allows for easy connection of conduits.
The FAA500CB builtin housing is placed on the concrete form, fastened and se-
cured against floating.
Pipe or cable inlets at the FAA500CB builtin housing within the wall areas are made
with an universal cutting tool. After removing the formboards, the front part (see
Fig. 15., Pos. F) is opened with a fretsaw or hole saw.
Into the hole of the builtin housing, a FAA500BB ceiling mount back box is then
inserted which takes base and detector.
BDLF.01U.025.877
Page 26 A1.en / 03.02.2006
STFIR/PRM1 / zab
Product Information 520 Series LSN improved Fire Detectors (EU) PI 34.75 en
Z
j max.:
0.61,2 cm
20 mm
Y PG 13,5
8,5 mm
4,1 mm
35 mm 8,5 mm
Y Z Y
25 mm
Mounting occurs
via the elongated slots or
via the four mounting holes to mount directly to 4 inch electrical boxes or single gang
switch boxes (for US).
BDLF.01U.025.877
Page 27 A1.en / 03.02.2006
STFIR/PRM1 / zab
Product Information 520 Series LSN improved Fire Detectors (EU) PI 34.75 en
The base is mounted inside the back box via four fastening points (see Pos. X in
Fig. 17.).
X
FAA500SB / FAA500SBH:
150 mm
X
FAA500SB
80 mm
FAA500SBH
82 mm
X
X
17.
BDLF.01U.025.877
Page 28 A1.en / 03.02.2006
STFIR/PRM1 / zab
Product Information 520 Series LSN improved Fire Detectors (EU) PI 34.75 en
51 79
B B
57
A
79
C _+ C
B B
D 79
FAA420RI
31
X
18. A
D To remove the cover from the base plate (see Fig. 18., left side), press the single
snapfit hook with a flat tool (e.g. screw driver) and carefully lift the cover.
D The FAA420RI is mounted directly on the ceiling or wall. Fasten the base plate
by four (B) or two (C) screws on an even and dry surface.
BDLF.01U.025.877
Page 29 A1.en / 03.02.2006
STFIR/PRM1 / zab
Product Information 520 Series LSN improved Fire Detectors (EU) PI 34.75 en
D If the cable is surfacefeeded, remove the prepunched cable entries (X) of the
housing. Through the entry (D) beneath the connection board, the cable can be
feeded flushmounted.
D To fit the cover on the base plate, place the two slots of the cover on the holding pins.
Slightly press the cover onto the base plate until the snapfit hook locks into place.
Terminal assignment
The FAA420RI remote indicator is connected via two ter-
minals.
Terminal Assignment _ +
Conventional technology / LSN
+ Conventional technology / LSN + 19.
BDLF.01U.025.877
Page 30 A1.en / 03.02.2006
STFIR/PRM1 / zab
Product Information 520 Series LSN improved Fire Detectors (EU) PI 34.75 en
60 85
A
55
85
1234
Y
55
39
MPA X
A
11
20. Y
BDLF.01U.025.877
Page 31 A1.en / 03.02.2006
STFIR/PRM1 / zab
Product Information 520 Series LSN improved Fire Detectors (EU) PI 34.75 en
Terminal assignment
Terminal Assignment
T.1 Ground
T.2 Flashing input (LED flashes)
T.3 Static input (LED lights up)
T.4 Static input (LED lights up) 1234
Only connect to T.4 via a series resistor (integrated in the 21.
case of BOSCH detectors); otherwise, the LED could be
destroyed.
BDLF.01U.025.877
Page 32 A1.en / 03.02.2006
STFIR/PRM1 / zab
Product Information 520 Series LSN improved Fire Detectors (EU) PI 34.75 en
6. Order Overview
6.1. Detector and Trim Ring
Product ID Designation
F.01U.510.149 FAPO 520 Optical fire detector LSN improved, white
F.01U.510.151 FAPOC 520 Multisensor fire detector LSN improved,
optical / chemical, white
F.01U.510.161 FAPO 520P Optical fire detector LSN improved,
transparent with color toning inserts
F.01U.510.162 FAPOC 520P Multisensor fire detector LSN improved,
optical / chemical, transparent with color toning inserts
4.998.151.295 FAA500TRW Trim ring, white,
for the detectors FAPO 520 and FAPOC 520
4.998.151.296 FAA500TRP Trim ring, transparent with color toning inserts
for FAPO 520P and FAPOC 520P detectors
Color toning inserts for FAPO 520P, FAPOC 520P and FAA500TRP
Fig. 22.: Color samples for color toning inserts
Color RAL
6016 5015
beige 1001 6018 5005
6027 4003
sulfur yellow 1016 7004
2007
red orange 2001 7012
fluorescent 2007 2001
orange 8003
1016
erica violet 4003 8011
BDLF.01U.025.877
Page 33 A1.en / 03.02.2006
STFIR/PRM1 / zab
Product Information 520 Series LSN improved Fire Detectors (EU) PI 34.75 en
BDLF.01U.025.877
Page 34 A1.en / 03.02.2006
STFIR/PRM1 / zab
Product Information 520 Series LSN improved Fire Detectors (EU) PI 34.75 en
The 520 series detectors do not require to be removed from their bases
for routine maintenance.
If occasionally a detector requires replacement due to a design change
or damage to the device then this should be carried out by a qualified en-
gineer.
This should only be undertaken when the system is offline and the user
has made alternative arrangements for emergency evacuation.
D Maintenance and inspection work should be carried out regularly and by trained
technical personnel.
D Bosch Sicherheitssysteme GmbH recommends a functional and visual inspection
at least once a year.
Detector type
Test steps
O OC
Check of the LED display x x
Visual check of the mounting x x
Visual inspection for damage and contamination of the
x x
detector surface
Check monitoring area for limitations of function and
x x
interference caused by lamps
Test of the optical sensors (see Chap. 7.4.) x
Combined test with detector test device and CO testing x
gas (see Chap. 7.3.)
BDLF.01U.025.877
Page 35 A1.en / 03.02.2006
STFIR/PRM1 / zab
Product Information 520 Series LSN improved Fire Detectors (EU) PI 34.75 en
D 8digit serial number:The year of manufacture is coded in the first digit of the
serial number (example: serial no. 30068421 year of manufacture 2003).
D Contamination level: The contamination level is given as a percentage:
Contamination level Fire panel display Required action
Light (> 50%) LS contam Clean at next service
Reliability of detection is still guar-
Moderate (> 75%) LS dusty
anteed, clean as soon as possible
Reliability of detection no longer
Heavy (100%) LS malfunction guaranteed, fault indication at the
fire panel
D Operating hours: Display of the operating time in hours since first putting into
operation.
D Current measurement values:
Analog smoke value of the scattered light sensor:
Detector state Value
New detector, as supplied < 300
Light contamination > 500
Heavy contamination > 600
Malfunction will be triggered > 700
Maximum measurement value 1023
CO value: Current measurement value of the CO sensor (only in the case of FAPOC 520).
The maximum measurement value is 1023.
BDLF.01U.025.877
Page 36 A1.en / 03.02.2006
STFIR/PRM1 / zab
Product Information 520 Series LSN improved Fire Detectors (EU) PI 34.75 en
D On the central unit, switch the detector zone to be inspected into test mode. This
automatically sets the detector into revision operation and readies it for the detector
test.
. Only in revision operation the detectors individual sensors will trigger with the
corresponding test device. For an alarm, all sensors must trigger at the same time.
The C sensor is triggered using CO test aerosol, the O sensors by being covered
up. No O testing gas is required.
D Now hold the test device under the detector so that the test beaker is flush with the
trim ring and seals it tightly.
. Make sure that the test beaker does not tilt, which could cause the detector
to be lifted up and consequently become detached from its fastening.
D Spray the CO testing gas for approximately 1 sec.
. The test head must remain over the detector until the detector has been triggered.
Distribution of the COtesting gas in the test head and therefore the sensor trigger
time can take up to 20 sec.
D Both scattered light areas are covered by the test beaker, so that both optical
sensors are also triggered at the same time.
D The detector triggers the alarm and the red alarm LED flashes.
BDLF.01U.025.877
Page 37 A1.en / 03.02.2006
STFIR/PRM1 / zab
Product Information 520 Series LSN improved Fire Detectors (EU) PI 34.75 en
2. Alternative
D The detector can be tested in normal operation if a test device with magnet is used.
D Figure 23. shows the position of the reed switch (Pos. R) in the case of OC
detectors.
. If you imagine the CO sensor (Pos. CO) to be in a 12 oclock position, the reed
switch (Pos. R) is located at approximately 2 oclock.
CO R
LED
23.
BDLF.01U.025.877
Page 38 A1.en / 03.02.2006
STFIR/PRM1 / zab
Product Information 520 Series LSN improved Fire Detectors (EU) PI 34.75 en
D On the fire panel, switch the detector zone to be inspected to test mode. This
automatically sets the detector into revision operation and readies it for the detector
test.
D Hold a sufficiently large object (e.g. the detector test device or the detector
exchanger) in both scattered light areas until an alarm is triggered. No O testing gas
is required.
2. Alternative
D The detector can be tested in normal operation if a test device with magnet is used.
D Figure 24. shows the position of the reed switch (Pos. R) in O detectors.
. If you imagine a line through the detector LED to be at the 12 oclock position,
the reed switch (Pos. R) is located at approximately 2 oclock.
LED
24.
D The LED of the detector flashes green once a second as soon as the reed switch
has been triggered.
. The detector will now remain in test readiness for 60 sec with automatically set test
parameters (e.g. reduction of the delay time to 15 sec). The green LED flashes for
as long as the detector remains in test readiness.
D Now hold the test device under the detector so that the test beaker is flush with the
trim ring. By covering the scattered light areas, both optical sensors are triggered
simultaneously (no O testing gas is required).
D The detector triggers the alarm and the red alarm LED flashes.
. In the case of programmed intermediate alarm storage, longer trigger times occur.
BDLF.01U.025.877
Page 39 A1.en / 03.02.2006
STFIR/PRM1 / zab
Product Information 520 Series LSN improved Fire Detectors (EU) PI 34.75 en
8. Repair
In case of a defect, the detector must be replaced.
9. Disposal
Packaging Film of the Fire Detectors with CSensor
The packaging bag of the multisensor detectors with Csensor consists of tearresist-
ant PEALU laminated film and may be disposed of with the household garbage.
BDLF.01U.025.877
Page 40 A1.en / 03.02.2006
STFIR/PRM1 / zab
Product Information 520 Series LSN improved Fire Detectors (EU) PI 34.75 en
11. Abbreviations
ABS = AcrylonitrileButadieneStyrene
a.P. = auf Putz (surfacemounted)
FACP = Fire Alarm Control Panel
PI = Product information
PP = Polypropylene
UEZ = Universelle Europazentrale (universal European fire panel)
UGM = Universelle Gefahrenmeldezentrale (danger detection system)
UL = Underwriters Laboratories
O = Optical (smoke)
BDLF.01U.025.877
Page 41 A1.en / 03.02.2006
STFIR/PRM1 / zab
Product Information 520 Series LSN improved Fire Detectors (EU) PI 34.75 en
BDLF.01U.025.877
Page 42 A1.en / 03.02.2006
STFIR/PRM1 / zab
Product Information 520 Series LSN improved Fire Detectors (EU) PI 34.75 en
BDLF.01U.025.877
Page 43 A1.en / 03.02.2006
STFIR/PRM1 / zab