HXE34K

HXE34K Three Phase


Four Wire Conventional
Meter
HXE34K is a direct connection meter
applied in two- or three-phase network for
measuring active and reactive energy. It
features compact design, multi TOU
functions and multi communication
protocol.

n Highlights
Optical communication(IEC62056-21)
DLMS/COSEM protocol capable(optional)
RF communication(optional)

n Main Functionalities
Active/reactive energy and tariff measurement l Display content and circle configurable
Demand l LCD Backlights configurable to increase
l Demand Interval configurable readability in low light conditions(optional)
l Block or slide mode configurable 2 LED for metering calibration
l Active and reactive MD with time stamp Bypass detection for tampering-proof(optional)
l Active and reactive MD in tariff with time Event Record
stamp l External magnetic detection and record
Instantaneous values measurement (optional)
Tariff l Meter Cover open detection and record
l Up to 4 tariffs (optional)
l Up to 10 divisions per day, weekend l Terminal Cover open detection and record
configurable (optional)
l Up to 8 daily tables DLMS/COSEM protocol capable(optional)
l Up to 12 seasons, working day and RS485 or RS232 optional alternative(optional)
weekend tariff scheme configurable per Four quadrant reactive energy in tariffs(optional)
season Load profile (optional)
l Week table l Channel quantity customized before leaving
l Up to 120 holidays configurable individually the factory; up to 14channels
per year l Depth of each channel customized before
LCD Display leaving the factory
l 12-Month Billing Data l Flexible record modes
l Large display with 8 digits, easy for reading Auxiliary terminals for energy pulse output
l LCD display with OBIS code
n Specifications
Description Value
Accuracy CT: Class 0.5S or Class 1 (IEC), Class A or Class B (MID),Class
2(Reactive)
Voltage
Reference voltage 3x220/380V-3x240/415V
Operating voltage range 80%-120%Un
Current
Basic current 1.5A,5A(CT) 5A,10A(DC)
Maximum current 6A(CT),40A, 60A, 80A, 100A(DC)
Starting current < 0.4%Ib0.2% CT
Frequency 50Hz or 60Hz
Temperature
Operation range -2555
Limit range for storage and transport -4070
Humidity Up to 95% non-condensing
Power Consumption
Power consumption in voltage circuit (active) 2 W
Power consumption in voltage circuit (apparent) 10 VA
Power consumption in current circuit 1 VA
Insulation Strength
AC voltage test 4kV during 1min
Impulse voltage test 1.2/50s mains connections 6kV

EMC
Electrostatic discharges(Contact discharges) 8kV
Electrostatic discharges(Air discharges) 15kV
Surge immunity test 4kV
Fast transient burst test 4kV
Electromagnetic RF fields (80MHz to 2000MHz) 10V/m(with current), 30V/m(without current)
Connection Terminals 9mm x 9mm
Housing
Protection degree IP54(with long terminal cover)
Meter cover Opaque PC+ glass fiber with a transparent window
Meter base Opaque PC+ glass fiber
Terminal cover Opaque PC + glass fiber
Display
Digit size 10.0mm x 5.0mm
Number of digits 8
Communication Interface
Optical communication IEC62056-21 or DLMS
RS485/RS232 IEC62056-21 or DLMS
RF IEC62056-21, <30m
Weight
Net weight Approx.1.12kgDT
Approx.1.14kgCT
Package Approx.0.1kg

n Standard
Electricity metering equipment (a.c.) General requirements, tests and test conditions Part 11: Metering
IEC62052-11
equipment
Electricity metering equipment (a.c.) Particular requirements Part 21:Static meters for active energy(classes 1
IEC62053-21
and 2)
Electricity metering equipment (a.c.) Particular requirements Part 21:Static meters for active energy(classes 1
IEC62053-22
and 2)
Electricity metering equipment (a.c.) Particular requirements Part 23: Static meters for reactive energy
IEC62056-23
(classes 2 and 3)
"Electricity metering Data exchange for meter reading, tariff and load control Part 21 : Direct local data
IEC62056-21
exchange"
"Electricity metering Data exchange for meter reading, tariff and load control Part 42: Physical layer services
IEC62056-42
and procedures for connection"
Electricity metering Data exchange for meter reading, tariff and load control Part 46: Data link layer using
IEC62056-46
HDLC protocol
Electricity metering Data exchange for meter reading, tariff and load control Part 53:COSEM Application
IEC62056-53
layer
Electricity metering Data exchange for meter reading, tariff and load control Part 61:OBIS Object
IEC62056-61
identification system
Electricity metering equipment (a.c.) Part 1: General requirements, tests and test conditions Metering

EN50470-1 equipment(class indexes A, B and C)

Electricity metering equipment (a.c.) Part 3: Particular requirements Static meters for active energy (class

EN50470-3 indexes A, B and C)


n Dimensions

n Connection Diagram

Direct Connection Type

Transformer Operated Type