Sie sind auf Seite 1von 1

STANDARD SPECIFICATION STANDARD SPECIFICATION

ofteiftENGINEERS
ogaiEgRegewr INDIA um-rED FOR SURFACE PREPARATION NO. 6-79-0020
114M MK,'"UMR0 IA GS of Undertaiong) AND PROTECTIVE COATING Rev. 0
PAGE 31 OF 59

AGGRESSWE SOLVENTS LIKE HEXANE, HEXENE, BENZENE, XYLENE AND TOLUENE


13.6 All internal surfaces, accessories and roof structures of Cone and Dome roof tanks

13.6. 1 coat of F-9 @ 75p


-14 to 65 SSPC-SP-10 --- 75
1 DFT/ coat

ETHYLENE GLYCOL (EG) TANKS


13.7 Internal shell-full height, bottom plate, underside of roof and all accessories
3 coats of vinyl
chloride co-polymer
13.7. AMERCOAT 23 @ 225 -
All SSPC-SP-10 None
1
75p /Coat;
(3x75=225)
13.8 Inside pontoon and inside of double deck of all floatingroofs
13.8. 1 coat of F-8 @ 100p 1 coat of F-8 @ 100p
- 14 to 80 SSPC-SP-3 200
1 DFT/coat DFT/coat
WET SLOPS, AMINE soluCons, SOUR WATER , WATER DRAW OFF
13.9
All internal surfaces, accessories and roof structures of Cone and Dome roof tanks
1 coat of F-15
intermediate coat @
13.9. 1 coat of F-15 primer @ 80p DFT/coat + 1 coat
-14 to 90 SSPC-SP-]0 240
1 80p DFT/ coat of F-15 finish coat @
80p DFT/ coat;
(80+80=160)
VACUUM RESIDUE, FUEL OIL , DRY SLOP, BITUMEN AND OTHER HIGH TEMPERATURE
HYDROCARBON LIQUIDS
13.10 Underside of floating roof, internal surface of cone roof, bottom plate, inside of bare shell including
wetted and non wetted surfaces, oil side surfaces of deck plates, oil side surfaces of pontoons, roof
structures, structural steel and ladders
1 coat of F-17
intermediate coat @
13.10 1 coat of F-17 primer 125p DFT/coat + 1 coat 375 .. N.. _
Up to 150C SSPC-SP-10 ote:3
.1 @ 125p DFT/ coat of F-17 finish coat
@125p DFT/ coat.
(125+125=250)
ALKALIS UP TO 50 % CONCENTRATION
13.11
All internal surfaces, accessories and roof structures of Cone and Dome roof tanks
2 Coats of F-6 A @
13.11 1 coat of F-15 primer
mer @
Up to 60C SSPC-SP-10 100p DFT/coat; 280-100 -
1 80p DFT/ coat
(2x100=200)

NOTES
I. All paint coating application including primer shall be carried out after erection and completion
of all welding work at site.

F-6A should be suitable and resistant for immersion service for the respective Hydrocarbons.

This system can be used where maximum operating temperature is below 150C and design
temperature is upto 200C. Cases of operating temperature > 150C are not covered in this spec,
such cases shall be covered in the job specifications.

4 F-6 A shall be suitable for drinking water service and should have competent authority
certification.

Format No. 8-00-0001-F1 Rev. 0 Copyright EIL All rights reserved