PowerFactory
Relay model description
Published by
DIgSILENT GmbH, Germany
18 Juli 2011
Table of Contents
Table of Contents
- TOC
- TOC2
- TOC3
- IOC
- TEF
- WEF1
- EF4
- Voltage
The main relay contains the measurement units, the distance trip zones with the relevant timers, the power swing element, the
output logic and all other subrelays.
More in detail the following functionalities are modelled in the main relay.
Two measurement units (Measure and Delta Measure block). Please dont forget to insert the nominal current and
the nominal voltage in both blocks.
One starting unit implementing the phase selection logic (Starting block)
One directional element (Dir-Z block)
Five phase-phase loop polygonal distance zones with the relevant timers (Z1P and Z1TP, Z2P and Z2TP,
Z3P and Z3TP, Z4P and Z4TP, Z5P and Z5TPblock ).
Five phase-ground loop polygonal distance zones with the relevant timers (Z1G and Z1TG, Z2G and Z2TG,
Z3G and Z3TG, Z4G and Z4TG, Z5G and Z5TGblock ).
One phase-phase loop high speed polygonal distance zone (Z1P High speed block)
One phase-ground loop high speed polygonal distance zone (Z1G High speed block)
One element detecting the power swing conditions which can be configured to block the distance zones (Power
Swing block)
Two polarizing blocks (Polarizing and Polarizing20 block). Please note that no user input is usually needed in these
blocks. The ability to maintain the right directionality after a fault along a series compensated line is provided by the
Polarizing20 block.
TOC subrelay:
One inverse characteristic phase overcurrent element (TOC Phase block)
One inverse characteristic residual overcurrent element (TOC Residual block)
One not directional inverse characteristic phase overcurrent element with minimum activation threshold and
additional trip delay (Toc2, Toc2 tLow and Toc2 I>Low block)
One time defined phase overcurrent element (Toc2 I>High block)
Three directional time defined zero sequence overcurrent elements (EF4 Step 1, EF4 Step 2, EF4 Step 3, EF4
Dir block)
One not directional inverse characteristic zero sequence overcurrent element with minimum activation threshold and
additional trip delay (EF4 Step 4, EF4 tLow and EF4 Step 4 Imin block)
The ABB REL 531 model can be configured to support the following additional features:
o POTT (Permissive overreach transfer trip) scheme. It can be enabled setting equal to TRIP the POTTTRIP
variable in the logic tab page of the Logic block dialog.
o Single phase trip. It can be enabled setting equal to TRIP the single_pole_trip variable in the logic tab page of
the Logic block dialog.
o Two phases trip. It can be enabled setting equal to TRIP the two_poles_trip variable in the logic tab page of the
Logic block dialog.
The model implementation has been based on the information available in the Technical reference manual
ProtectIT Line high speed distance protection terminal REL 531*2.3 Document No: 1MRK 506 073-UEN
Issued: June 2004 Revision: A document.