Sie sind auf Seite 1von 6

A.

TECHNICAL SPECIFICATIONS FOR STP and ETP


Expected quantity of waste water ........................ m3/day 21.4
Design Flow up of Combined treatment plant .....m3/day 25
Operation............................................................... hours 24

(a) Industrial effluent treatment plant

Concurrence /
Description Required as per Specifications Variance by
Tenderer

1.Acid Dosing Tank

Quantity 1 no. 1 no.

Capacity 50 litres 50 litres

MOC PVC PVC

Make Sintex

(b) DM & RO Reject Water Treatment Plant

Concurrence /
Description Required as per Specifications Variance by
Tenderer

1.Chemical Dosing tank

Quantity 2 nos. 2 nos.

Capacity 50 litres 50 litres

MOC PVC PVC

Make Sintex
(c) Coolant Treatment Plant

Concurrence/Variance by
Description Required as per Specifications
Tenderer
1.Oil Skimmer for
Collection tank
Quantity 1 no. 1 no.
Capacity 15 LPH 15 LPH
Model Tote-IT Tote-IT
Make Abanaki,USA

2.Oil Skimmer for


Reaction tank
Quantity 1 no. 1 no.
Capacity 3 LPH 3 LPH
Model Mighty Mini Mighty Mini
Make Abanaki , USA

3.Raw waste pump


Quantity 2 Nos. (1 working + 1 standby) 2 Nos. (1 working + 1 S)
Capacity 1 m3/hr 1 m3/hr
Head 10 m 10 m
Motor Submersible suitable for 3 phase, Submersible suitable for 3 phase,
400/440 Volts, AC Supply 400/440 Volts, AC Supply
MOC All SS All SS
Make Dharani/CNP
4.Reaction Tank Mixer
Quantity 1Nos. 1Nos.
Drive Drive unit comprising reduction Drive unit comprising reduction
gear gear
Motor 1 HP TEFC motor suitable for 3 1 HP TEFC motor suitable for 3
phase, 400/440 Volts, AC phase, 400/440 Volts, AC
Shaft and blades of SS Shaft and blades of SS
MOC
construction construction
Make Kankan Engineers
5. Chemical Dosing tanks
Quantity 3 Nos. 3 Nos.
Capacity 100 Litres Each 100 Litres Each
MOC PVC PVC
Make Sintex
6.Chemical Tank
Agitators

Quantity 3 nos. 3 nos.

Capacity For 100 liters capacity tank For 100 liters capacity tank

Drive unit comprising reduction Drive unit comprising reduction


Drive
gear gear

0.5 HP TEFC motor suitable for 0.5 HP TEFC motor suitable for
Motor
400/440 volts, 400/440 volts,

3 Phase, 50 Hz; AC supply, 3 Phase, 50 Hz; AC supply,

Shaft and blades of SS Shaft and blades of SS


MOC
Construction Construction

Make Kankan Engineers

7.Auric Filter

Quantity 1 no. 1 no.

Model 01BM
01BM
Make Auric Techno Services
(d) Combined treatment Plant

Concurrence/Variance by
Description Required as per Specifications
Tenderer
1.Bar Screen
Quantity 1 No. 1 No.
Size 500mm x 500mm 500mm x 500mm
Screen spacing/opening 20-50 mm 20-50 mm
Screen operation Manual Type Manual Type
Make Klean

2.Raw Sewage pumps


Quantity 2 nos. (1 working + 1 standby) 2 nos. (1 working + 1 S)
Capacity 2m3/hr 2m3/hr
Head 10 m 10 m
Motor Submersible suitable for 3 phase, Submersible suitable for 3
400/440 Volts, AC Supply phase, 400/440 Volts, AC
Make Dharani/CNP

3.Blowers
Type Twin lobe type Twin lobe type
Quantity 2 nos. (1 working + 1 standby) 2 nos. (1 working + 1 S)
3
Capacity 50m /hr 50m3/hr
Pressure 0.4 kg/cm2 0.4 kg/cm2
Accessories Inlet filter, inlet silencer, Pressure Inlet filter, inlet silencer,
gauge, Pressure relief valve, Non Pressure gauge, Pressure
return valve, base frame, V belt etc. relief valve, Non return valve,
base frame, V belt etc.
Make
Everest/Usha
4.Air diffusers (self closing)
1 set 1 set
Quantity
2m long 2m long
Length
HDPE pipe grid on bottom of HDPE pipe grid on bottom of
Mounted on aeration tank
aeration tank
Make Southern Cogen
5.Return Sludge Pumps
Quantity 2 nos. (1 working + 1 standby) 2 nos. (1 working + 1 S)
Type Horizontal. Non clogging, Semi Horizontal. Non clogging,
open impeller Semi open impeller
Capacity 2 m3/hr 2 m3/hr
Head 10 m 10 m
MOC All CI All CI
Motor suitable for 3 phase, 400/440 Volts, suitable for 3 phase, 400/440
50 cycles, AC Supply Volts, 50 cycles, AC Supply
Johnson Pumps
Make

6.Filter feed pumps


2 nos. (1 working + 1 standby) 2 nos. (1 working + 1 S)
Quantity
2 m3/hr 2 m3/hr
Capacity
15 m 15 m
Head
Horizontal, mono block Horizontal, mono block
Type
suitable for 3 phase, 50 cycles, AC suitable for 3 phase, 50
Motor
Supply cycles, AC Supply
All CI All CI
MOC
Make Crompton/Kirloskar

7.Pressure Sand filter


1 nos. 1 nos.
Quantity
Capacity 2 m3/hr 2 m3/hr
Type Vertical Cylindrical Vertical Cylindrical
Size 500mm dia x 1800mm ht 500mm dia x 1800mm ht
MOC M.S. M.S.
Make KLEAN
8.Sodium hypochlorite
dosing
Quantity 1 no. 1 no.
Capacity 50 litre 50 litre
MOC PVC PVC
Make Sintex
9.Interconnecting piping
and valves
a. All piping should be of C class a.All piping should be of C
with ISI marked, class with ISI marked,
b. All valves should be C.I. Butterfly b.All valves should be C.I.
type, Butterfly type,
c. PP/HDPE pipes should have c.PP/HDPE pipes should
Make 6kg/cm2. have 6kg/cm2.
Tata/Jindal

10.Electricals for the Plant Motor Control Centre (MCC), Motor Control Centre
Cabling and Earthing system for (MCC), Cabling and Earthing
various motors. system for various motors.
16 Feeders MCC Panel with
IP52 Protection

Das könnte Ihnen auch gefallen