Beruflich Dokumente
Kultur Dokumente
Applied Energy
journal homepage: www.elsevier.com/locate/apenergy
h i g h l i g h t s
a r t i c l e i n f o a b s t r a c t
Article history: Gas-fired tankless water heaters are gaining popularity as a means of producing domestic hot water for
Received 17 February 2016 residential applications. As they become more widespread, these devices are increasingly becoming
Received in revised form 4 May 2016 important to researchers who are seeking models of these devices that can be used to make reasonable
Accepted 21 May 2016
predictions of their energy consumption. This is especially true for the case of condensing tankless water
Available online 6 June 2016
heaters as they have been shown to be the most efficient method of producing domestic hot water.
Current models of these devices do exist, however, the uncertainties of their predictions are unclear
Keywords:
and require data collected from onerous field-trials for calibration.
Gas-fired tankless water heater
Building performance simulation
This article makes a contribution by introducing a new model of a condensing tankless water heater
Domestic hot water whose uncertainties are well described that can be calibrated by a less-onerous experimental program
Housing in a laboratory. The model was calibrated with data spanning a range of conditions: inlet temperatures
between 10 and 23 C, water flow rates between 0.08 and 0.27 L s1 and outlet temperatures between
36 and 48 C.
The model predictions were validated against data emanating from a previous field-trial. Above domes-
tic hot water consumption values of 15 MJ day1, the coefficient of determination (r2 value) was 0.98. The
average error (difference between the average model predictions and the measured values) was 3.0% (in
relative terms) while the root mean square error was 4.2%. The maximum error for a single point was
8.7% at a domestic hot water consumption of approximately 30.2 MJ day1.
2016 Elsevier Ltd. All rights reserved.
http://dx.doi.org/10.1016/j.apenergy.2016.05.130
0306-2619/ 2016 Elsevier Ltd. All rights reserved.
G. Johnson, I. Beausoleil-Morrison / Applied Energy 177 (2016) 740750 741
Nomenclature
intermittent use is common, such as in a DHW application. Second, Glanville et al. [11], Healy et al. [10], Bohac et al. [4] and
Schoenbauer et al. [7] found, of the ten houses they monitored, Burch et al. [12] all described a need in this field to determine a
the average DHW draw was 5.7 L, the average draw duration was simple model form that can be calibrated with an experimental
66 s and, on average, there were 26 draws a day. This is a signifi- program consisting of a small number of tests. Currently, the only
cant reason why TWHs perform differently under different interna- reliable method of calibrating Eq. (1) is with an extensive field-
tional standard test conditions [8] and also why the performance of trial. A more easily calibrated model would allow the performance
a TWH is, in practice, different from its rated efficiency. It was of a TWH to be simulated for any arbitrary DHW profile and facil-
shown by Bohac et al. [4], that the North American Energy Factor itate comparisons between different methods of producing DHW.
overstates the energy efficiency of a TWH in a DHW application. Burch et al. [12] proposed that a model based on a lumped heat
The Energy Factor is determined from a standard DHW draw capacity (Eq. (6)) would be suitable for calibration by such a simple
pattern (6 draws of 40.6 L over a 24 h period) where overall experimental program. However, whether the large uncertainty
consumption (243 L day1) was nearly 70% greater than was found margins they presented on their calibration parameters from their
in practice [7]. experimental program would allow for accurate model predictions
Previously [4,5] it has been observed that there is a strong linear is unclear. Glanville et al. [11] also derived some calibration
relationship between the energy input (Ein kJ) and the energy parameters that could be used with the model developed by Burch
output (Eout kJ) of a TWH in practice. Both Bohac et al. [4] and et al. [12], however, the uncertainty of these parameters was not
Hoeschele and Weitzel [5] performed regression analyses to deter- described. Notwithstanding these limitations, a lumped heat
mine the coefficients ci in Eq. (1) from measured field-trial data. capacity approach to modeling could still be viable for a condens-
ing TWH if the uncertainty margins of the calibration parameters
Ein c1 Eout c2 1
could be shown to allow for reasonably accurate predictions. Such
For modeling, Butcher and Schoenbauer [9] suggested it might be a model should also be validated against a large set of actual DHW
possible to derive the coefficients of this linear relationship for a use data to demonstrate its limitations.
heater in a laboratory environment from several representative This article makes a contribution by demonstrating that a sim-
DHW draws. The advantage of this approach was its simplicity. It pled lumped heat capacity condensing TWH model can be cali-
was noted by Bohac et al. [4] that although c1 clearly represents brated by an experimental program that is far less onerous than
the reciprocal of the steady-state efficiency fss , c2 is related to an extensive field-trial. Throughout, the uncertainties of the model
the heat capacity of a TWH (C TWH kJ C1). Healy et al. [10] found calibration parameters are characterized. These uncertainties are
it difficult to robustly characterize c2 . Scatter in Ein and Eout mea- also propagated through to model predictions.
surements at higher consumption levels in their experimental pro- First, based on the analytical solutions to the governing differ-
gram resulted in large uncertainty margins of the c2 values they ential equation of the TWH modeled as a lumped heat capacity, a
derived from regression. Consequently, Healy et al. [10] questioned new model will be introduced based on the energy inputoutput
the validity of this approach. This also suggests that a detailed response of the TWH to only a step-input of heat. Second, Eq. (1)
accounting of experimental uncertainties is necessary in any newly will be shown to represent the energy inputoutput response of
developed model forms. the governing differential equation to the combination of an
initial-energy-impulse combined with a step-input of heat. Third,
1.1. Contributions another new model will be introduced as the average of the first
two models. Exponential decay will be introduced to account for
From the literature reviewed, it is clear that there are the fol- time between DHW draws. The experimental procedures required
lowing knowledge gaps in this field where there is an opportunity to calibrate these models are demonstrated. The validity of the
to make a contribution. First, although Bohac et al. [4] and simplifying assumptions inherent in the lumped-heat capacity
Hoeschele and Weitzel [5] gathered an extensive amount of data approach along with the assumed form of the heat-input function
from their respective field-trials and presented models in the form are validated against data emanating from an earlier study [4].
of Eq. (1), a thorough analysis of the uncertainties of their models The developed model is also intended to support researchers
predictions was unavailable. A model for a condensing TWH whose studying more innovative systems for producing DHW. As an
predictions uncertainties were well described would be an example, applications where solar thermal collectors are used to
advancement. provide DHW for residential applications is an active area of
742 G. Johnson, I. Beausoleil-Morrison / Applied Energy 177 (2016) 740750
research (e.g. Refs. [1322]). In order to assess the energy savings where ut is the unit-step function given by the following
of this type of system, a well-justified model of a conventional definition.
method for producing DHW is required for comparison. The model
0 t<0
being proposed in this research is suitable for this. In particular, the ut 4
case study described in Section 4 demonstrates how the energy
1 tP0
savings of a solar DHW system change when the reference scenario where Q_ inss is the steady-state rate of heat input given by the follow-
is changed from a traditional boiler to the TWH modeled in this ing equation.
research. The next section derives the analytical solutions that
are the foundation of this article. Q_ inss HHV V_ fuelss 5
where HHV is the higher heating value of the fuel (kJ m ) and V_ fuelss 3
2. TWH first-order models
is the steady-state volumetric flow-rate of the fuel (m3 s1) if both
values are at the same standard temperature and pressure condi-
The inspiration for the model forms investigated in this article
tions. This assumption neglects the initial heat-input overshoot that
was from experimental observations (Section 3.2). A typical heat-
was observed experimentally in Section 3.2. It is a significant depar-
input (Q_ in t kW) and temperature-difference (DT C) response ture from the model introduced by Burch et al. [12] but is necessary
from a TWH during a DHW draw is shown in Fig. 1. The heat input to allow for an analytical solution to the governing differential
is given by the following equation. equation shown in Eq. (6).
Q_ in t V_ fuel t HHV 2 According to Burch et al. [12], the differential equation govern-
ing the TWH system can be reasonably well approximated by the
where V_ fuel t is the fuel flow rate that is also a function of time (t) following equation.
and HHV is the higher heating value of the fuel (discussed in
dT
Section 3). _ w C w T T in C TWH
m UA T T env Q_ in t fc 6
dt
Also shown in Fig. 1 are two lines that were superimposed to
illustrate the inspiration for the model forms investigated in the where m _ w is the mass flow-rate of water (kg s1), fc is the
following sections. First, a horizontal line to represent a step- combustion efficiency, C w is the specific heat capacity of water
input whose magnitude is equal to the steady-state input of heat. (kJ kg1 C1), T is the temperature of the TWH which is assumed
This is the assumed form of the heat-input that is the inspiration equal to the outlet water temperature ( C), T in is the inlet water
for the model developed in Section 2.1. Second, a vertical line with temperature, T env is the air temperature in the ambient environ-
an arrow, at time equal to zero, to represent an initial impulse of ment, UA is the heat-loss coefficient of the TWH (kJ C1) and
energy. The combination of these two lines is the inspiration for C TWH is the heat capacity of the TWH (kJ C1).
the model form investigated in Section 2.2. Heat loss to the ambient environment is orders of magnitude
By inspection, it can be seen that the measured heat-input pro- less than the heat input during the initial firing stage. Therefore,
file resembles a step input, although there is significant overshoot it can be neglected during the step input (Eqs. (3) and (4)) of the
initially while the temperature difference profile resembles a first- initial firing stage, representing the governing equation in terms
order-step response that is delayed by several seconds. of the difference between outlet and inlet temperatures DT (Eq.
DT
(7)). Note that a substitution for the derivative dT
dt
ddt has been
2.1. Step-response model made to simplify the solution procedure.
20 C
s _ TWH 9
Heat input (kW)
30 mw C w
15
Step-input of heat The following integral can be used to find Eout t.
Z t
20 Eout t _ w C w DTt dt
m 10
10 0
Measured heat input
Substituting the step response for DTt from Eq. (8) into this inte-
Measured temperature difference
10 gral yields the following equation.
5
Z t
_ w C w DT ss DT 0 DT ss es dt
t
Eout t m 11
0
0 0
0 100 200 300 400
Evaluating the integral in Eq. (11) yields the following equation.
Time from start of experiment (s)
h it
_ w C w DT ss t DT 0 DT ss s es
t
Fig. 1. A typical temperature-difference response of a TWH and heat input Eout t m 12
0
observed during the calibration experiments of Section 3.2.
G. Johnson, I. Beausoleil-Morrison / Applied Energy 177 (2016) 740750 743
Z 0
Substituting s from Eq. (9) into Eq. (12) and evaluating the expres-
sion inside of the square brackets from Eq. (12) yields the following
dtdt 1 20
0
equation.
Note that dt can be regarded in this case as the derivative of ut
Eout t m_ w C w DT ss t DT 0 DT ss with respect to time so the units on the right hand side of Eq. (18)
_
are consistent. Interested readers may find Ref. [23] to be a good
mw C w t
C TWH 1 e CTWH 13 resource for describing how the Dirac distribution may be used
for modeling physical systems.
The energy input to the TWH can be found easily by integrating Eq. After an analogous development to that performed in
(3) according to the following equation. Section 2.1, the model energy inputoutput relationship is given
Z t by the following equation.
Ein t ut Q_ inss dt Q_ inss t 14
Eout t C TWH
0
Ein t DT ss DT 0 21
fss fss
The steady-state efficiency fss is given according to Eq. (15).
A more detailed derivation is provided as Supplementary informa-
_ w C w DT ss
m
fss 15 tion. Although this result is somewhat obvious, it shows that a sim-
Q_ in ss ple linear energy inputoutput relationship of the form in Eq. (1)
The definition of fss (from Eq. (15)) along with an expression for t in can be thought of as the TWHs response to a step-input of heat
terms of Ein t (from Eq. (14)) can be substituted into Eq. (13) to combined with an initial-impulse of energy. This insight assists in
express the energy input in terms of the energy output according understanding the selection for the third and final model form
to Eq. (16). described in the following section.
Eout t DT ss DT 0 C TWH E tfss
in 2.3. Average model
Ein t 1 e CTWH DT ss 16
fss fss
As has been shown at the beginning of Section 2, the heat input
An interesting observation can be made regarding Eq. (16). By tak-
can have some overshoot followed by a steady period. Essentially,
ing the limit as t approaches infinity, the first-order-step-response
the two models previously described represent extreme cases. The
model in Eq. (16) approaches the form of Eq. (1) as is shown below.
step-response model in Section 2.1 is a situation with no heat-
input overshoot and only a steady period. The step-function and
17 initial-impulse-response model in Section 2.2 represents a situa-
tion with a large, instantaneous overshoot followed by a steady
Eq. (17) is of the form Ein t c1 Eout t c2 . By comparison with period. By recognizing that in reality, the actual heat input poten-
Eq. (1), c1 is the reciprocal of the steady-state efficiency 1=fss tially lies somewhere between the two extremes, the arithmetic
and c2 is equal to the amount of energy input required to raise average of the two models presents itself as an interesting option.
the temperature of the TWH from its initial condition to its It is given by the following equation, formed by averaging Eqs. (16)
steady-state value DT ss DT 0 C TWH =fss . This result is consistent and (21).
with the earlier works of Bohac et al. [4] and Hoeschele and Weitzel
[5] who observed a simple linear energy inputoutput relationship.
Eout t DT ss DT 0 C TWH 1 Ein tfss
Ein t 1 e CTWH DT ss 22
This result also satisfies the desire expressed by Healy et al. [10] for fss fss 2
a model that can account for the temporal distribution of a draw
All three of these defined model forms only account for the periods of
pattern. If the TWH is initially at an elevated temperature due to
time when the TWH is firing. The periods between firings are referred
recent use, the energy input required to raise it to its steady-state
to as environmental decay periods [11]. As all three models are based
value will be less than if the TWH was initially at the inlet temper-
on a lumped heat capacity assumption, environmental decay periods
ature value.
can be modeled using the same method for all three models.
The only difference between the model developed here and the
According to Glanville et al. [11], the differential equation
one in Section 2.1 is the assumption of the functional form of the
governing the behavior of the TWH during environmental decay
heat input. In the preceding section, it was assumed that the func-
periods can be approximated by the following equation.
tional form was a step function whose magnitude was equal to the
steady-state heat input. In this section, the functional form will be dT
C TWH UA T T env 0 23
assumed to be the combination of the earlier step function plus an dt
initial impulse of energy equal to the energy required to instantly The solution of this equation is the well-known exponential-decay
bring the TWH from its initial condition DT 0 to its steady-state equation shown below.
value DT ss . This functional form is shown in the following
UA t
equation. T T 0 T env e CTWH T env 24
Q_ in t Q_ inss ut Ess E0 dt 18 0
where T is the temperature of the TWH at the end of the previous
firing period. It will be shown, in Sections 3.5 and 3.8, that this
where Ess E0 is the energy input required to raise the temperature
equation can be used reasonably well to predict the initial condition
of the TWH to its steady-state value from its initial condition and is
DT 0 required by the models defined by Eqs. (16), (21) and (22).
given according to the following equation.
Note that DT 0 can be determined from Eq. (24) by simply subtract-
Ess E0 C TWH DT ss DT 0 =fss 19 ing T in from both sides as is shown below.
The unit impulse dt, given by the Dirac distribution, used in UA t
DT 0 T 0 T env e CTWH T env T in 25
Eq. (18) has the following property.
744 G. Johnson, I. Beausoleil-Morrison / Applied Energy 177 (2016) 740750
ments. The following section describes the experimental apparatus Primary Sensed quantity Sensor type Bias
that was used to gather these data necessary for this purpose. measurement
T; T in ; T fuel Temperature Thermocouple 0:5 C
DT Temperature Thermopile 0:1 C
3. Experimental methods difference
P fuel Absolute Transducer 0:25% reading
The experiments conducted in this article were performed at pressure
V_ w Volumetric flow Oval-gear flow 1% reading and
Carleton University in the facility originally developed by Boucher rate meter 0:0019 L s1
[24] with some modifications. The TWH that was the subject of the V_ fuel Volumetric flow Diaphragm 1% reading and
experiments in this article had a burner capable of providing rate meter 0:0057 L s1
560 kW. For the experiments described in this article, Fig. 2
illustrates the hydronic configuration of the apparatus that was
used along with the location of the various primary measurements The pressure of the supply gas was measured with a transducer
used to derive the necessary parameters relevant to the models so the flow-rate of gas could be corrected to a consistent tempera-
described in the preceding sections. For each experiment, a fixed- ture and pressure (15 C and 101.325 kPA) for use with the HHV
speed pump was used to circulate water from two 1300 L water provided by the utility (38.15 MJ m3). This value has a bias of
tanks through the TWH. A throttling valve was manually adjusted 0:3 MJ m3 to account for its monthly variation over the period
to control the flow-rate of water in each experiment. that the experiments were conducted. It also accounts for the fact
The large thermal mass of the water tanks would ensure the that the utility determined this value by gas chromatograph, a
TWH inlet temperature would rise slowly (approximately measurement technique known to be accurate to within 0:25%
<0.05 C per minute was achieved in practice). An external chilled [25].
glycol stream (8 C) could be activated on-demand and used to cool The bias on the volumetric water and gas flow-rate measure-
the water stored in the tanks before, after or during experiments ments are presented as a percent reading combined with an abso-
via the heat exchanger at the TWH outlet. lute error in (L s1) to account for the resolution of the pulse output
The TWH was vented into the buildings exhaust system which of both meters for the sample period that was used (5 s). The
necessitated the use of an additional external exhaust fan not pre- impact of the instrumentation bias errors listed in Table 1 on the
sent in a typical residential application. However, the use of this parameters derived from them is explained in the following
external fan did not impact measurements during firings as this section.
fan was manually controlled in the lab to impose typical airflow
conditions as measured by a pressure sensor internal to the
TWH. Although this sensor would ensure normal operation during 3.1. Experimental uncertainty
firing, there were some implications related to its use between fir-
ings that are discussed in Sections 3.4 and 3.5. Experimental uncertainties were characterized with conven-
Table 1 describes the instrumentation of the apparatus. All tem- tional methods [26]. A review of these methods is provided as Sup-
peratures were measured with copperconstantan thermocouples plementary information. A description of how the uncertainty
that were calibrated beforehand in the laboratory. Temperature calculations were performed in practice is described in the follow-
difference was measured across the inlet and outlet of the TWH ing sections.
using a five-junction copperconstantan thermocouple (ther-
mopile) that was also calibrated beforehand in the laboratory. 3.1.1. Steady-state parameters
These sensors had exposed junctions that were submerged in the For any steady-state experiment, each measurement sampled
flow. every 5 s was viewed as a repeated observation. Here the repeated
observation of any parameter is denoted by /. For example, a
steady-state experiment of 120 s in duration was considered to
consist of 24 repeated observations of the same parameter
n 24.
External Exhaust Fan
There were several parameters derived from steady-state peri-
ods of operation that were relevant. First, according to Glanville
.
V T P et al. [11], UA can be derived from a steady-state experiment where
fuel fuel fuel the TWH is disabled and water at an elevated temperature is circu-
lated through it. Under these conditions, an instantaneous mea-
TWH surement of this parameter UAi is given by the following
Water Water equation.
tank 1 tank 2
qw C w V_ w;i DT i
UAi 26
. T env ;i T i
1300 L 1300 L
Pump V T
w in
T T
where qw is the density of water. Note that it was assumed
Valve T env T fuel . The calibration value of UA determined for modeling,
described in more detail in Section 3.4, was the sample mean of this
Chilled parameter / measured over a steady period.
Heat
Glycol Exchanger A summary of other important steady-state derived parameters
and their uncertainties is described in Table 2. The instrumenta-
Fig. 2. Schematic representation of the experimental apparatus used to conduct the tion, in particular the flow meters, had greater accuracy at greater
experiments in this article. flow rates as was shown in Table 1. Also, experiments were more
G. Johnson, I. Beausoleil-Morrison / Applied Energy 177 (2016) 740750 745
Q_ inss 7.244.6 kW 1.43.3 2.213.8 1.65.4 3.2. Calibration of the TWH heat capacity
Q_ outss 5.942.3 kW 1.22.8 0.05.6 1.32.9
fss 84.695.9% 1.94.4 1.813.8 2.06.2 The heat capacity C TWH is assumed to be a characteristic con-
(HHV) stant of each individual TWH system. To derive this value, a series
of calibration experiments, with initial conditions equal to zero,
were conducted. Each experiment was conducted in the following
unsteady at lower heat-input rates. This is where the greater stan-
manner. Before the experiment, in order to ensure the initial con-
dard deviations (S) shown in Table 2 were measured.
dition was zero DT 0 0, water was circulated through the TWH
For experiments, instantaneous measurements of Q_ in;i ; Q_ out;i until DT 0 was observed. This would ensure the time between
and fi were derived according to the following equations. experiments was not a factor. All boundary conditions (T in ; T out
Q_ in;i V_ fuel;i HHV 27 and V_ w ) were held steady for the duration of the experiment.
Between experiments boundary conditions were changed by
Q_ out;i V_ w;i qw C w DT i 28 adjusting the set point of the TWH T out , adjusting the throttling
valve V_ w or heating the tank for an extended period of time
Q_ out;i T in . Data from one such experiment are shown in Figs. 3a and 3b.
fi 29 The measured energy input Ein t and output Eout t are each
Q_ in;i
plotted in Fig. 3a against time. The error bars shown are the bias
The steady-state values for these parameters (Q_ inss ; Q_ outss and fss errors derived according to Eq. (31). For the same experiment,
reported in Table 2) were defined as their respective samples mean Eout is plotted against Ein in Fig. 3b. After the TWH reaches a
measured from steady periods of operation.
/ steady-state period of operation, the linearity of the relationship
between Eout t and Ein t is apparent. For the calibration experi-
3.1.2. Integrated parameters ments, 100 s of operation was observed to be sufficient for the
Aside from the steady-state derived parameters in the preced- steady-state period to be reached. The goal of each calibration
ing discussion, for the experiments conducted in this article, there experiment was to derive C TWH according to the following
were several important parameters that were integrated over the equation.
duration of the steady-state and startup transient periods of c2 fss
C TWH 32
TWH operation. One such parameter was the energy input to the DT ss
TWH Ein which was derived from the following equation.
where c2 is the coefficient from Eq. (1). It was derived by a linear
X
m
least-squares regression fit to the data shown in Fig. 3b during
Ein Q_ in;i Dt 30
i1
the steady-state period. To estimate the bias on c2 for the uncer-
tainty analysis, the bias on Eout and the bias on Ein (both as a % of
where Q_ in;i is the heat input measured during the ith sample inter- value) along with the maximum residual of the least-squares
val of duration Dt. Summing the quantity on the right-hand side of regression fit were combined according to standard methods [26].
Eq. (30) from the first to last sample interval yields the total energy In total, 14 tests similar to the one shown in Figs. 3a and 3b
input over that period. It is important to note that for Ein , and other were conducted to calibrate C TWH . A summary of the boundary con-
integrated parameters, the experimental uncertainty had to be han- ditions and results of these experiments is shown in Table 3. Note
dled differently than the steady-state parameters in the preceding that the V_ w values investigated are at the upper range of what
discussion. would be expected in a DHW application [7].
For example, consider the experiment shown in Fig. 1. This
experiment is composed of a transient startup period followed by
7000
a steady-state period. If, for example, Ein was calculated after
120 s m 24, this Ein could only be considered as a single obser-
6000 TWH Energy Input
vation of /. This experiment would have to be repeated several
times under the same boundary conditions then, for each repeated
5000
experiment, each Ein calculated after 120 s could be considered as a
repeated observation of /.
Energy (kJ)
4000
For the experiments in this article, Eq. (31) was used to estimate
the bias on the energy input as the experiments were predomi-
3000
nantly steady-state. A similar approach was taken to estimate
the bias on the energy output as well. This approach is an approx-
2000
imation for the first several measurements during the initial tran-
sient stage of a firing. However, the most important use of these 1000
uncertainty margins was to estimate the uncertainty of the TWHs TWH Energy Output
heat capacity (Section 3.2) and it will later be shown (Section 3.8) 0
that the uncertainty of the TWHs heat capacity is only a small 0 100 200
component of the overall uncertainty of model predictions so this Time from start of experiment (s)
approach was found to be adequate.
Fig. 3a. Energy input and output of the TWH measured during one of several
BEin U 95%;Q_ in m Dt 31 calibration experiments used to derive C TWH each plotted against time from the start
ss of experiment as a separate series.
746 G. Johnson, I. Beausoleil-Morrison / Applied Energy 177 (2016) 740750
87.994.1% (HHV)
iments. Each series in each graph represents the percent difference
between a models predictions and observed experimental values
C TWH Range Range of B S U 95%
for a single validation experiment. A positive percent difference
1
23.121 kJ C 21.725.3 0.882.17 1.03 2.25 indicates an over-prediction of energy consumption. Model predic-
tions were made using the value of C TWH at the bottom of Table 3.
For clarity, in Fig. 4 the range of model predictions shown is
The average value for the heat capacity observed from the 14
restricted to be between 10% of the measured value, therefore,
experiments C TWH is shown at the bottom of Table 3. The range predictions at the beginning of the DHW draw outside of this range
of specific heat values along with the corresponding range of biases are not shown.
observed are shown to the right of C TWH . The maximum bias It can be seen that the average model (in the center of Fig. 4) is
observed was used to calculate U 95% along with the standard more accurate for shorter DHW draw durations. Within 60 s, this
10
0
Step-Response and Initial-Impulse Model (eq: 21)
-5
-10
5
% error
0
Average Model (eq: 22)
-5
-10
0
Step-Response Model (eq: 16)
-5
-10
0 100 200 300 400
Duration of DHW draw (s)
Fig. 4. Percent error between energy input to the TWH observed during 4 validation experiments and predictions made by model Eqs. (16), (21) and (22).
G. Johnson, I. Beausoleil-Morrison / Applied Energy 177 (2016) 740750 747
1 70
60
Steady-State Efficiency (%HHV)
0.95
40
0.9
30
20
0.85
10
0
0.8 0 10 20 30 40 50 60 70
0 10 20 30 40 50 -1
Measured Ein (MJ day )
Heat Output (kW)
Fig. 6. The steady-state efficiency of the TWH versus its heat output during a series Fig. 7. Comparison of the average model predictions against the measured data
of 31 calibration experiments. provided by Bohac et al. [4].
To demonstrate the validity of the whole average model along over a reasonably wide range. This indicates that a comparison
with the exponential decay equation, measured residential DHW between the performance of different TWHs in different environ-
profiles from TWHs emanating from an earlier study [4] were ments is reasonable even if the model parameters are significantly
made available to the authors of this study and the following anal- different.
ysis was performed. In this analysis, model predictions for Ein were To estimate the uncertainty margin for each of the 43 DHW pro-
made for 43 separate DHW profiles and compared to the values files, model predictions were made for the base case, where the
measured by Bohac et al. [4]. Each profile was 1 week of data model parameters values xi were those determined by calibra-
where sampling was performed every second. The profiles were tion in this paper. Model predictions were then repeated for each
from 4 separate sets of occupants, who used 3 different condensing DHW profile for cases where each model parameter was perturbed
TWHs. Weekly average DHW usage spanned a range of 3.9 by its uncertainty margin. Note that the U 95% value shown for fss is
58.5 MJ day1 for the profiles investigated. For this range of DHW a combination (according to Moffat [26]) of the maximum residual
consumption, a range of 5.969.3 MJ day1 of TWH energy con-
reported in Section 3.6 along with the U 95% values determined
sumption was measured [4]. The comparison of modeled and mea-
experimentally shown on Fig. 6 for Q_ out greater than 15 kW.
sured energy consumption is illustrated in Fig. 7. The measured ss
values from Bohac et al. [4] are plotted against the abscissa while In Table 4, @E
@x
in
DE xi was calculated as the mean percent difference
i in
the average model predictions are plotted against the ordinate. between the base case and a perturbed case, for each parameter xi ,
In this analysis, the temperature of the TWH Tt was modeled over the 43 DHW profiles analyzed. The mean result of this analy-
according to the following equation. sis is summarized at the bottom of Table 4. Note that it was unrea-
sonable to derive uncertainty margins from the data measured by
Ein tfss
C Bohac et al. [4] due to the highly transient nature inherent in field-
DT 0 DT ss e TWH DT ss
Tt DT ss T in 34 trial data.
2
Notwithstanding this limitation, the result of this comparison
This equation is consistent with the average model and is necessary indicates that the average models predictions are commensurate
to determine the temperature of the TWH at the end of a firing per- with what has been measured in practice from other condensing
iod from which the environmental decay period begins (Eq. (25)). TWHs. The solid line in the center of Fig. 7 represents the line of
The model parameters that were used are shown in Table 4 perfect agreement. Above and below this line are two other lines
along with a summary of how the error bars shown in Fig. 7 were that represent a 5% deviation from perfect agreement. For the
derived from a perturbation analysis. The parameters that were entire range of the average models predictions, the coefficient of
used for modeling were those determined by calibration in Sec- determination (r2 value) was 0.990. The average error (difference
tions 3.2, 3.4 and 3.6 in a laboratory environment and are different between the average model predictions and the measured values)
than those that would be determined from the TWHs studied by was 4.1% (in relative terms) while the root-mean-square error was
Bohac et al. [4]. However, as can be seen from the results of the 4.5%. The maximum error for a single point was 16.8% at a DHW
perturbation analysis at the bottom of Table 4, the model predic- consumption of approximately 3.9 MJ day1. Above DHW con-
tions are relatively insensitive to changes in the parameters values sumption values of 15 MJ day1, the coefficient of determination
G. Johnson, I. Beausoleil-Morrison / Applied Energy 177 (2016) 740750 749
Table 5
Case study: primary energy savings of a solar DHW system with glazed collectors [16] compared to a traditional boiler and the condensing TWH modeled in this research.
Solar DHW [16] (MJ day1) Gas energy savings (MJ day1)
Traditional boiler [16] Tankless water heater (average model)
Upper uncertainty margin Average model prediction Lower uncertainty margin
Rome 31.8 45.4 41.7 37.1 34.6
Madrid 29.0 41.4 38.1 33.8 31.6
Munich 23.2 33.2 30.5 27.1 25.3
(r2 value) was 0.981. The average error (difference between the investigating experimental uncertainty. An analysis revealed that
average model predictions and the measured values) was 3.0% the calibration parameters required by this model could be deter-
(in relative terms) while the root-mean-square error was 4.2%. mined from an experimental program in a laboratory that is less
The maximum error for a single point was 8.7% at a DHW con- onerous than an extensive field trial and would not propagate an
sumption of approximately 30.2 MJ day1. unreasonable amount of uncertainty to model predictions.
All aspects of the developed model were validated through a
4. Case study: solar DHW comparison between model predictions and data emanating from
a previous study. From this, it was found that the model predic-
One potential use for this TWH model is as a reference case tions of TWH energy consumption were commensurate with data
against which the performance of a more innovative system for measured in a field trial for most cases. The models major limita-
providing DHW may be compared to. To demonstrate this, the fol- tion is that it can under-predict energy consumption by as much as
lowing case study was conducted that compares the performance 8.7% in a typical region of DHW usage. This model is most suitable
of the solar DHW system simulated by Comodi et al. [16] with for use in applications where it is important to quantify the uncer-
glazed collectors to the TWH modeled in this research. tainty of model predictions such as a well-justified reference sce-
In their research, Comodi et al. [16] estimated the payback per- nario for comparison with a more innovative method of
iod for a solar DHW system in different climatic regions. As part of producing DHW. The results presented in this article could hope-
their analyses, they estimated the gas energy savings of the solar fully inspire other researchers to investigate the validity of using
DHW system by comparison with a traditional boiler (70% effi- simple analytical solutions to the lumped-heat-capacity differen-
cient) as a reference scenario. Table 5 shows the gas energy savings tial equations as models to represent the energy performance of
calculated with their reference scenario along with the energy sav- other TWHs.
ings relative to the TWH modeled in this research.
The solar DHW consumption from several locations is shown on Acknowledgments
the left side of Table 5. Next to this are the gas energy savings of
the solar DHW system relative to the traditional boiler. The final The authors of this study are grateful to Ben Schoenbauer and
three columns show a range of gas energy savings based on the the Center for Energy and Environment for sharing the data col-
TWH modeled in this research. Using boundary conditions lected in their TWH field-trial study.
described by Comodi et al. [16] (T in 11:5 C, Tout = 45 C) and an
assumed ambient temperature (Tamb = 18 C), simulations were
conducted with the energy use profiles provided by Bohac et al. Appendix A. Supplementary material
[4] to estimate the range of efficiencies that are appropriate for
the solar DHW consumption shown in Table 5. In this region of Supplementary data associated with this article can be found, in
usage the efficiency varied between 82% and 89.5% due to the tem- the online version, at http://dx.doi.org/10.1016/j.apenergy.2016.
poral distribution of occupant usage patterns. The average between 05.130.
these two boundaries (85.7%) was selected to estimate the average
model predictions in Table 5.
References
One advantage of using the TWH model developed in this
research is that uncertainty margins may be estimated. The lower [1] EIA. Residential energy consumption survey: Water heating in U.S. homes, by
uncertainty margin was estimated as the combination of the housing unit type - Tables HC8.1 (2009) and HC2.8 (2005). Tech. Rep., U.S.
Energy Information Administration; http://www.eia.gov/consumption/
uncertainty caused by the temporal distribution of occupant usage
residential/ Accessed May 27 2016.
patterns (4.4%), and the uncertainty of the models calibration [2] Lutz J, Grant P, Kloss M. Simulation models for improved water heating
parameters (5.5% from Table 4). The upper uncertainty margin systems. Tech. rep., Lawrence Berkeley National Laboratory; 2013.
also considers these two sources but additionally considers a fur- [3] Grant P. Evaluation of the performance of gas tankless water heaters. Masters
thesis, United States: University of Colorado Boulder; 2010.
ther uncertainty of (8.7%) to account for the maximum under- [4] Bohac D, Schoenbauer B, Hewett M, Lobenstein M, Butcher T. Actual savings
prediction of energy consumption described in Section 3.8. and performance of natural gas tankless water heaters. Tech. rep., Center for
As can be seen from Table 5, the ranges of gas energy savings Energy and Environment; 2010.
[5] Hoeschele M, Weitzel E. Monitored performance of advanced gas water
relative to the TWH modeled in this research are significantly less heaters in California homes. ASHRAE Trans 2013;119:21425.
than the gas energy savings relative to the traditional boiler. [6] Bourke G, Bansal P. New test method for gas boosters with domestic solar
water heaters. Sol Energy 2012;86:7886.
[7] Schoenbauer B, Bohac D, Hewett M. Measured residential hot water end use.
5. Conclusions ASHRAE Trans 2012;118:87289.
[8] Bourke G, Bansal P, Raine R. Performance of gas tankless (instantaneous) water
heaters under various international standards. Appl Energy 2014;131:46878.
In this article, a model to describe the energy inputoutput rela-
[9] Butcher T, Schoenbauer B. Application of a linear input/output model to
tionship based on the analytical solutions to the TWH modeled tankless water heaters. ASHRAE Trans 2011;117:6839.
with a lumped heat capacity was developed. The model inspired [10] Healy W, Ullah T, Roller J. Inputoutput approach to predicting the energy
a new method of measuring the heat capacity from experiments. efficiency of residential water heaters testing of gas tankless and electric
storage water heaters. ASHRAE Trans 2011;117:52132.
This method of measuring the heat capacity was shown to produce [11] Glanville P, Kosar D, Stair J. Short-term performance of gas-fired tankless
repeatable results that were amenable to conventional methods of water heater: laboratory characterization. ASHRAE Trans 2013;119:24869.
750 G. Johnson, I. Beausoleil-Morrison / Applied Energy 177 (2016) 740750
[12] Burch J, Thornton J, Hoeschele M, Springer D, Rudd A. Preliminary modeling, [19] Panaras G, Mathioulakis E, Belessiotis V. A method for the dynamic testing and
testing and analysis of a gas tankless water heater. In: Proc. SOLAR, San Diego, evaluation of the performance of combined solar thermal heat pump hot water
United States, 2008. systems. Appl Energy 2014;114:12434.
[13] Asaee R, Ugursal I, Beausoleil-Morrison I, Ben-Abdallah N. Preliminary study [20] Wei H, Liu J, Yang B. Cost-benefit comparison between domestic solar water
for solar combisystem potential in Canadian houses. Appl Energy heater (DSHW) and building integrated photovoltaic (BIPV) systems for
2014;130:5108. households in urban China. Appl Energy 2014;126:4755.
[14] Chow T, Pei G, Fong K, Lin Z, Chan A, He M. Modelling and application of direct- [21] Rodrguez-Hidalgo M, Rodrguez-Aumente P, Lecuona A, Legrand M, Ventas R.
expansion solar-assisted heat pump for water heating in subtropical Hong Domestic hot water consumption vs. solar thermal energy storage: the
Kong. Appl Energy 2010;87:6439. optimum size of storage tank. Appl Energy 2012;97:897906.
[15] Colclough S, McGrath T. Net energy analysis of a solar combi system with [22] Sterling S, Collins M. Feasibility analysis of an indirect heat pump assisted
seasonal thermal energy store. Appl Energy 2015;147:6116. solar domestic hot water system. Appl Energy 2012;93:117.
[16] Comodi G, Bevilacqua M, Caresana F, Paciarotti C, Pelagalli L, Venella P. Life [23] Kamen E, Heck B. Fundamentals of signals and systems using the Web and
cycle assessment and energy-CO2-economic payback analyses of renewable Matlab. Prentice Hall; 2000 [ISBN No.: 0-13-017293-6].
domestic hot water systems with unglazed and glazed solar thermal panels. [24] Boucher E. The design and commissioning of a micro-cogeneration testing
Appl Energy 2016;164:94455. facility. Masters thesis, Canada: Carleton University Ottawa; 2013.
[17] Haillot D, Franquet E, Gibout S, Bdcarrats J. Optimization of solar DHW [25] LaNasa P. Overall measurement accuracy determination and influence. Tech.
system including PCM media. Appl Energy 2013;109:4705. rep., American School of Gas Measurement Technology; 2003.
[18] Uday Kumar N, Mohan G, Martin A. Performance analysis of solar cogeneration [26] Moffat R. Describing the uncertainties in experimental results. Exp Therm
system with different integration strategies for potable water and domestic Fluid Sci 1988;1:317.
hot water production. Appl Energy 2016;170:46675.