SOLUTION :
Considering the thickness of the landfill typically ranging from 5.0 to
8.2 m, the depth of improvement is selected as 8 m. Based on the
composition of the landfill, it can be considered as a Previous Soil.
Since the landfill has a high degree of saturation, the nc value is
selected as 0.5 (refer to the Recommended nc Value Table).
1 | M E T O D E P E R B A I K A N TA N A H
As a result, the required energy per blow can be computed as
follows:
nc = 0,38 ; Di = 8 m
8 m=0, 38 W t H d
21,0526= W t H d
W t H d =443,213 ton. m
443,213
H d =
2 | M E T O D E P E R B A I K A N TA N A H
Based on the applied energy guidelines, the unit applied energy for
landfills ranges from 600 to 1100 kJ/m3
3 | M E T O D E P E R B A I K A N TA N A H
assume crater depth : 1.3 m
Therefore, the required total applied energy for ironing passes is
4 | M E T O D E P E R B A I K A N TA N A H
Ae = s2 = 2,62 = 6,76 m2
AE = AEHEP = 3205 kJ/m2 ;
Wt = 15 t ; Hd = 26,9 m
AEHEP x A e
Nd=
Wt Hd
3205 x 6,76
Nd= 2
=5,36 6
26,9 x 1 5 x 10 m/s
For the number of drops at one location at 6 for each pass, the
crater depth can be estimated as follows:
Based on the FHWA guidelines, the upper bound of SPT N value after
dynamic compaction ranges from 20 to 40 (refer to the Upper Bound
Test Values after Dynamic Compaction Table for Landfills).
5 | M E T O D E P E R B A I K A N TA N A H
The induced settlement for uncontrolled fill ranges from 5 to 20%
(refer to the Approximate Induced Settlement as Percent of
Improvement Depth Table for Uncontrolled Fills). If the average
percentage (i.e., 13%) is considered, the possible induced
settlement is :
S = 0.13 8 m = 1.04 m.
2,6
2,6
6 | M E T O D E P E R B A I K A N TA N A H
2
1,3
3,14 x( )
2
Area Ratioof Improvement= =0,196
2,62
7 | M E T O D E P E R B A I K A N TA N A H
8 | M E T O D E P E R B A I K A N TA N A H
9 | M E T O D E P E R B A I K A N TA N A H