VENTILATION DESIGN WORK SHEET


Organization: Elevation: 0 Feet
Location: Temperature: 70 Degrees F
Shop: Factor:
Velocity Pressure Calculation Method
1 Duct Segment Identification filter plenum duct
1a Type of Duct (GALV=Galvinzied) (BLK=Black Iron, Al, SS) GALV GALV GALV
2 Volumetric Flowrate: (See Design Criteria) c 4325 4325 4325
3 Minimium Transport Velocity (See Design Criteria) fpm
4 Duct Diameter (Round Duct) inches
5 Duct Area
6 Actual Duct Velocity
7 Duct Velocity Pressure (Vd/4005)^2 = VP "w
8 H Slot Area Sq. Ft.
9 O S Slot Velocity fpm
10 O L Slot Velocity Pressure "
11 D O Slot Loss Factor (ACGIH Vent Manual Chapter 10)
12 T Acceleration Factor 0o
13 S S Plenum Loss per VP
14 U Plenum SP
15 C Duct Entry Loss Factor (See Design Specifications)
16 T Acceleration Factor (if Vd>Vs; 1) 1 or 0
17 I Duct Entry Loss per VP
18 O Duct Entry Loss
19 N Other Loss "wg
20 Hood Static Pressure (SPh) "
21 Straight Duct Length feet
22 Friction Factor (Hf)
23 Friction Loss per VP
24 No. of 90 Degree Elbows
25 Elbow Loss per VP (See Table Below or ACGIH, Fig 5-13)
26 Number of Entries
27 Entry Loss per VP (See Table Below or ACGIH, Fig 5-14)
28 Special Fittings Loss Factors
29 Duct Loss per VP
30 Duct Loss
31 Duct SP Loss
32 Cumulative Static Pressure "wg
33 Governing Static Pressure "wg
34 Corrected Volumetric Flowrate (Balanced) cfm
35 Resultant Velocity Pressure "
36 Corrected Velocity (Based on the Governing SP) fpm

PERTINENT EQUATIONS: 90 Degree Round Elbow


R/D 0.5 0.75
Q corr. = Q Design (SP gov./ SP duct)^1/2 Stamped 0.71 0.33

Page1
VentDesign

5Piece 0.46
VP r = ((Q1 + Q2)/(4005(A1 + A2)))^2 or 4Piece 0.5
= (Q1/Q3)*VP1 + (Q2/Q3)*VP2 3Piece 0.9 0.54
60 elbow = 2/3 loss
Hf = 0.0307(V^0.533)/(Q^0.612) = GALV in Line 1a 45 elbow = 1/2 loss
30 elbow = 1/3 loss
= 0.0425(V^0.465)/(Q^0.602) = BLK in Line 1a
Branch Entry
FSP = SP outlet - SP inlet - VP inlet Loss Factors
Angle Factor
Ce = Coefficient of Entry = (VP / SPh)^1/2 or 15 0.09
1 (for perfect hood - No losses) 30 0.18
SPh = HoodStaticPressure=(V/4005)^2 45 0.28
60 0.44
VP = VelocityPressure=SPhhe 90 1

he = EntryLoss=FhxVP

TP = TotalPressure=SP+VP Fan Specifications


Blade Type:
SP;VP = StaticPressure;VelocityPressure Size:
RPM:
Vd = DuctVelocity HP:

Page2
VentDesign

HEET
Date: 2-Mar-17
Drawing No.
Designer:
Method
FANin FANout Duct
GALV GALV GALV
4325 4325 4325

90 Degree Round Elbow Loss Factors


1 1.5 2 2.5
0.22 0.15 0.13 0.12

Page3
VentDesign

0.33 0.24 0.19 0.17


0.37 0.27 0.24 0.23
0.42 0.34 0.33 0.33

FSP= Fan Static Pressure #VALUE!

TP= FSP+VPout= #VALUE!

ME= Mechanicalefficiency
(Usually.5.65)

ME= 1 Q= 0

BHP= QxTP= #VALUE!


6356xME
DeltainSP: #VALUE!
DeltainSP(1): #VALUE!
Existing Required
Tubeaxial

###

Page4