PROGRAMMABLE INTERFACE AND

CONTROL MODULE

MATRIX
MX7-5 m 7 Selfpowerd digital Inputs programmable as N/O or N/C
m 5 Output programmable as Normally Energize or
R LOCK
PRG
O1
L Ax/I.R.F.

OFF

Deenergize O2

O3

m Adjustable time delayed operation of output O4


ON

X04 -R2
m Totally programmable AND/OR matrix
m Local / Remote control
O5

I1

I2
MODE

m Serial communication with Modbus Protocol I3

m Time tagged event recording I4


RS232
I5

M
I6

I7
LINE RELAY MX7-5

Microprocessor fully programmable 7 inputs / 5 outputs unit on modular draw-out card


(1 module 51mm wide)
RS485 serial port for remote programming and communication (Modbus Protocol)
RS232 serial port for local programming and data acquisition (Modbus Protocol)
Intuitive programming and communication software
On board Real Time Clock.
Recording of the last five events (FIFO). Time stamping with 10ms resolution.
Comprehensive self-diagnostic with positive relay alarm
Multivoltage autoranging power supply
Stand alone flush-mounting enclosure or 19'' rack panel (1 module)

Signal and Controls


On relay's front face: 1 Mode selection button (White) 5 LEDs for outputs' status indication
2 Local control buttons On-Off (Red-Green) 3 LEDs for Mode indication
7 LEDs for inputs' status indication 1 LED for Power Supply / IRF indication
Signals Leds are flashing during timing of associated controls.
All signals and controls are available via the serial ports as well.

Connection Diagram

MX7-5

5A
MAX 30Vdc
250Vac

AUXILIARY
SUPPLY
MS-SCE1472-R3

40
MX7-5 M X04-R2

Inputs
Seven optoisolated selfpowered inputs controlled via cold contacts with antirebound logic:

Vout = 24V Iout = 3.5mA - Max external resistance = 1000Ohm


Outputs
Five output relays, each with one N/O contact (N/C on request), operated by any input in AND / OR mode

Programmable operation time delay : xTO = (0 - 655)s, step 0.01s

Programmable reset time delay : xTR = (0 - 655)s, step 0.01s

Electromechanical contacts : Rating : 5A - 380V


AC resistive switching : 1100W max 380V
Make: 30A (peak) 0,5 sec.
Break: 0,5A 125VDC, L/R = 40ms, 105 ops.

One additional Normally Energized relay monitors Internal Relay Failure.


Local / Remote / Lock-out Control
Operating mode can be changed via the 'mode' front panel push button or the serial communication interface:

LOCAL MODE = Local inputs only.


REMOTE MODE = Front panel push buttons can be disabled.
Local inputs can be forced to the TRUE logic status via the RS485 serial port.
LOCK-OUT MODE = OPERATION OF ALL OUTPUTS BLOCKED.
Programming and self-test enabled.

Programming
The unit can be programmed by a PC application tool (MSCOM) via the front panel communication port. Such tool also
monitors the configuration and the operational status of all Inputs and Outputs.

By forcing the status of the inputs via the serial port (remote mode) the user can either simulate field signals (for testing
purposes) or remotely operate the output relays.

Digital Inputs Buttons Internal Fault


I5 Off On IRF OR Columns
I1 I2 I3 I4 I6 I7
O1 O2 O3 O4 O5
AND
AND
AND
AND
AND
AND
Rows AND
AND
AND
AND
AND
OR OR OR OR OR

Programming
Matrix
Timer Timer Timer Timer Timer
Out 1 Out 2 Out 3 Out 4 Out 5

R1 R2 R3 R4 R5
NE / ND NE / ND NE / ND NE / ND NE / ND
OR OR OR OR OR

TR 1 Relay 1 TR 2 Relay 2 TR 3 Relay 3 TR 4 Relay 4 TR 5 Relay 5