COOLING LOADS CALCULATION

Cooling Load Temperature Difference (CLTD) Method


Organization: MSC Elevation: Feet Date: 6-Mar-17
Location: Temperature: 80 F Document No.
Shop: Factor: Designer:

Lat. 32 N Ave. temp (F) 79


Month May Daily range (F) 22
Solar Time 17:00

Design condition DB (F) WB (F) W(lbw/lba) RH (%)


Outdoor 104 0.0144
Indoor 77 0.0098 50

Calculation CLTD
Conduction Load Direction Color U Area(ft2) Fc RSHG
Table Corr.
Glass W Clear 1.04 830 13 8 0.91 6284.10
E Clear 1.04 42 13 8 0.91 317.99
W Clear 1.04 42 13 8 0.91 317.99

Wall N Dark 0.111 840 11 5 0.91 424.24


E Dark 0.111 1176 26 20 0.91 2375.76
S Dark 0.111 840 17 12 0.91 1018.18
W Dark 0.111 388 17 11 0.91 431.11

Roof/Celing HOR Dark 0.09 5400 53 48 0.91 23328.00


Floor HOR 0.35 5400 12 0.91 20638.80
Door E 0.18 42 27 21 0.91 144.47

Solar Load Direction SHGF SC Area(ft2) CLF Fc

Glass W 220 0.95 830 0.56 0.91 88400.31


E 220 0.95 42 0.23 0.91 1837.24
W 220 0.95 42 0.56 0.91 4473.27

RSHG RLHG
Internal source no. Heat rate/unit Fc CLF
People sensible 162 250 0.91 0.83 30589.65
People latent 162 200 32400.00
equip. sensible 0.00
equip. latent 0.00
no. 3.4 Watts FB CLF Fc
Light 3.4 16200 1.25 0.8 0.91 50122.80

Air sensible heat 1.1 cfm Tout(F) Tin(F)


Ventilation 1.1 1620 90 78 21384.00
Infiltration 1.1 126 90 78 1663.20

Air latent heat 4748 cfm Wout Win


Ventilation 4748 1620 0.0144 0.0098 35382.10
Infiltration 4748 126 0.0144 0.0098 2751.94

253,751 70,534
Cooling load
(Btu/hr) 324,285
Tons 27.02
Project
Location Lat. Month
Design condition
DB (F) WB (F) W(lbw/lba) RH (%) Daily range (F) Ave. temp (F)
Outdoor
Indoor Solar Time

Calculation
CLTD
Conduction Direction Color U Area(ft2) Fc RSHG
Table Corr.

Glass

Wall

Roof/Celing
Floor

Door

Solar Direction SHGF SC Area(ft2) CLF Fc

Glass

RLHG
Internal source no. Heat rate/unit Fc CLF
People sensible
People latent
equip. sensible
equip. latent
no. 3.4 Watts FB CLF Fc
Light

Air sensible heat 1.1 cfm Tout(F) Tin(F)


Ventilation
Infiltration

Air latent heat 4748 cfm Wout Win


Ventilation
Infiltration
Cooling load(Btu/hr)
Total
Tons

CLTD CLTDc
LM 16.00 17.00 18.00 16.00 17.00 18.00
Mar -8 50 53 53 36 39 39 CLTDc= [(CLTD+LM)k+(78-TR)+(To-85)]f
Apr -3 50 53 53 41 44 44
May 1 50 53 53 45 48 48 TR = 78F
Jun 2 50 53 53 46 49 49 To = 79F
Jul 1 50 53 53 45 48 48 k=1 f=1
Aug -3 50 53 53 41 44 44

U A CLTDc q roof
16.00 17.00 18.00 16.00 17.00 18.00
Apr 0.09 5400 41 44 44 19926 21384 21384
May 0.09 5400 45 48 48 21870 23328 23328
Jun 0.09 5400 46 49 49 22356 23814 23814
Jul 0.09 5400 45 48 48 21870 23328 23328

SHGF SC A CLF qglass


16.00 17.00 18.00 16.00 17.00 18.00
Apr 224 0.95 830 0.5 0.56 0.55 88312 98909.44 97143.2
May 220 0.95 830 0.5 0.56 0.55 86735 97143.2 95408.5
Jun 216 0.95 830 0.5 0.56 0.55 85158 95376.96 93673.8
Jul 216 0.95 830 0.5 0.56 0.55 85158 95376.96 93673.8

qtotal
16.00 17.00 18.00
Apr 108238 120293.4 118527.2
May 108605 120471.2 118736.5
Jun 107514 119191 117487.8
Jul 107028 118705 117001.8