Sie sind auf Seite 1von 1

1 DIMENSION DATA

xg
le
B = 6.00 m , footing width
L = 12.00 m , footing length
H
x zg he = 5.00 m , height of equipment
he B
be = 5.00 m , width of equipment
Q h le = 12.00 m , length of equipment
xg = 0.30 m
d1 z zg = 0.30 m
d2 L d1 = 0.30 m
d2 = 0.30 m
d3 d3 = 0.30 m
h = 2.55 m
Rubble/Lean Concrete
1. DESIGN LOAD 4) SEISMIC CALCULATION
1) EQUIPMENT LOADING DATA Seismic Point = 0.80
Empty Weight (Qe) = 500.0 KN Maximum Seismic Coefficient= 0.25
Operation Weight (Qo) = 800.0 KN Equipment Seismic Force, He
= 200 kN

2) WEIGHT OF STRUCTURAL PROPER 5) WIND CALCULATION


Soil (s) = 18.0 KN/m3 Wind Pressure (Wo) = 380 Pa
Reinforced concrete (rc) = 22.5 KN/m3 Height Factor (K) = 0.50
Plain concrete (pc) = 22.0 KN/m3 Aerodynamic Factor = 2.1
Ground water (w) = 9.8 KN/m3 Height of Scaffolding = 5.3 m
*) assumed ground water level GL-0.0m shall be considered on design Equipment Wind Force (Hw)= 32 kN
Hw < 0.7He, L/C B is neglective
3) LOAD COMBINATION 6) FOUNDATION WEIGHT
For soil bearing capacity & stability check Footing Weight (Wf) = 972 kN
Components A B C D Rubble Concrete (Wrc) = 486 kN
FDN Weight 1.0 1.0 1.0 1.0
Empty 1.0 7) BOUYANT FORCE
Operation 1.0 1.0 1.0 Bouyant Force (Bf) = 424 kN
Wind 1.0 1.0
Earthquake 0.7
*) see to 6464 C200-00100 Engineering Standard for
Civil & Buildings

2. SOIL BEARING CHECK 3. SLIDING CHECK


3.1 ALLOWABLE BEARING CAPACITY
For fixed load : Friction coefficient = 0.5
Qaf = 170.0 kN/m2 F : Actual safety ratio
For combined load N : Wf + Qo - Bf
Qac = 330.0 kN/m2 Due to Load Case C:
N 0.5 x 1048.00
F = = = 16.38 > 1.25 OK
3.2 ACTUAL BEARING PRESSURE Hw 32.0
qmax : P/Af + Mx/Sfx + Mz/Sfz, Maximum soil reaction, kN/m2 Due to Load Case D:
qmin : P/Af - Mx/Sfx - Mz/Sfz, Minimum soil reaction, kN/m 2
N 0.5 x 1348.00
F = = = 4.81 > 1.25 OK
P : Q + Wf + Wrc, Total Vertical Load, kN 0.7*He 140.0
Mx : H * (h + d1 + d2 + d3) + Q * zg , Total Moment about X-Axis, kN-m
Mz : Q * xg , Total Moment about Z-Axis, kN-m 4. OVERTURNING CHECK
Af : 72 m2, B * L, Area of Footing MR : Resisting moment
Sfx : 72 m , (L * B ) / 6, Section Modulus of Footing about X-Axis MO : Overturning moment
3 2

Sfz : 144 m3, (H * L2) / 6, Section Modulus of Footing about Z-Axis N : Wf + Qo - Bf


Due to Load Case C:
CASE P (kN) Mx (kN) Mz (kN) qmax qmin Ratio Judge B 6.00
MR = N = 1048.0 x = 3144.0 kNm
A 2258 0 0 31 31 0.18 OK! 2 2
C 1958 331 240 33 21 0.10 OK!
Mo = 100.8 kNm
D 2258 639 240 42 21 0.13 OK!
6 RE-BAR ARRANGEMENT MR 3144.0
F = = = 31.18 > 1.25 OK
This foundation is a block foundation. Moe 100.8
So, re-bar requirement is only shrinkage requirement.BS 8110-1 3.12.11.2.9Due to Load Case D:
Total reinforcement area is more than 0.25% of the concrete gross area. B 6.00
MR = N = 1348.0 x = 4044.0 kNm
Top Bar D16 @ 250 2 2
Bottom Bar D16 @ 250
Mo = 441.1 kNm
Ast = 804.25 mm2
Asb = 804.25 mm2 MR 4044.0
F = = = 9.17 > 1.25 OK
Ast + Asb 0.0025Ac Moe 441.1
804 + 804 = 1608 1500 OK