Project name : Chest Disease Hospital Entered By :Nouri Industrial Est


Model Ref. : CH-01-04 ( APSa 285-2 ) Qty : 4
Input Data :
Refrigerant : R134a
Power Supply : 380-415/3ph/50Hz
Ambient [ F ] : 110.00
Cooler Water In [ F ] : 54.00
Cooler Water Out [ F ] : 44.00
Fouling Factor [ ft F h/Btu ] : 0.000250
Glycol : Water
Elevation [ ft ] : 0

Output Data :
Cooler W.P.D [ Psi ] : 5.11 Total Power Input : 308.48 k W
Water Flow Rate [ GPM ] : 537.37
Minimum Loop Volume [ Gallon ] : 2686.80 kW/TR : 1.37
Minimum Flow Rate [ GPM ] : 360.10
Calculated capacity [ Btu / hr ] : 2701055.00
Calculated capacity T.R : 225.09
Calculated velocity [ fpm ] : 570.86
Operating Conditions :
Compressor Power Input [ kW ] : 292.48
EER : 8.69
COP : 2.55
IPLV EER : 13.8972
IPLV kW/Ton : 0.86
AHRI Conditions :
@ 100 % @ 75 % @ 50 % @ 25 % @ 10 %
EER 10.64 12.89 14.82 15.12 14.42
kW/Ton 1.128 0.931 0.810 0.794 0.832

Sound Data ( db ) :
Compressor Option
Frequency [ Hz ] 63 125 250 500 1k 2k 4k 8k Total (dBA)
Sound Power [ SWL ] 94 91 94 90 95 92 88 78 98
Sound Pressure [SPL] @ 3 [ ft ] 77 74 77 73 78 75 71 61 81

Condenser Data :
>> Coil :
Material : MICRO-CHANNEL
No. of condensers : 10
Total Air Flow Rate [ CFM ] : 171733
>> Fan :
Condenser Fans : Propeller (Axial)
Type of Drive : Direct driven
No. of fans : 10

Compressor :
No. : 2
Electrical Data
Compressor
No. : 2

Page 1 of 15
2.0 03/09/2016

Project name : Chest Disease Hospital Entered By :Nouri Industrial Est


Condenser Fan Motor
No. : 10
KW : 1.6
FLA : 3.5

MCA : 648.575
MOP : 800
MDS : 800

Model Layout :

Page 2 of 15
2.0 03/09/2016

Project name : Chest Disease Hospital Entered By :Nouri Industrial Est


Model Load Distribution :

Page 3 of 15
2.0 03/09/2016

Project name : Chest Disease Hospital Entered By :Nouri Industrial Est


Model Ref. : CH-01-04 @ 118.4 ( APSa 285-2 ) Qty : 4
Input Data :
Refrigerant : R134a
Power Supply : 380-415/3ph/50Hz
Ambient [ F ] : 118.40
Cooler Water In [ F ] : 54.00
Cooler Water Out [ F ] : 44.00
Fouling Factor [ ft F h/Btu ] : 0.000250
Glycol : Water
Elevation [ ft ] : 0

Output Data :
Cooler W.P.D [ Psi ] : 4.34 Total Power Input : 329.55 k W
Water Flow Rate [ GPM ] : 500.55 kW / TR : 1.57
Minimum Loop Volume [ Gallon ] : 2502.70
Minimum Flow Rate [ GPM ] : 335.50
Calculated capacity [ Btu / hr ] : 2515968.00
Calculated capacity T.R : 209.66
Calculated velocity [ fpm ] : 570.86
Operating Conditions :
Compressor Power Input [ kW ] : 313.55
EER : 7.58
COP : 2.22
IPLV EER : 13.8972
IPLV kW/Ton : 0.86
AHRI Conditions :
@ 100 % @ 75 % @ 50 % @ 25 % @ 10 %
EER 10.64 12.89 14.82 15.12 14.42
kW/Ton 1.128 0.931 0.810 0.794 0.832

Sound Data ( db ) :
Compressor Option
Frequency [ Hz ] 63 125 250 500 1k 2k 4k 8k Total (dBA)
Sound Power [ SWL ] 94 91 94 90 95 92 88 78 98
Sound Pressure [SPL] @ 3 [ ft ] 77 74 77 73 78 75 71 61 81

Condenser Data :
>> Coil :
Material : MICRO-CHANNEL
No. of condensers : 10
Total Air Flow Rate [ CFM ] : 171733
>> Fan :
Condenser Fans : Propeller (Axial)
Type of Drive : Direct driven
No. of fans : 10

Compressor :
No. : 2
Electrical Data
Compressor
No. : 2

Page 4 of 15
2.0 03/09/2016

Project name : Chest Disease Hospital Entered By :Nouri Industrial Est


Condenser Fan Motor
No. : 10
KW : 1.6
FLA : 3.5

MCA : 648.575
MOP : 800
MDS : 800

Model Layout :

Page 5 of 15
2.0 03/09/2016

Project name : Chest Disease Hospital Entered By :Nouri Industrial Est


Model Load Distribution :

Page 6 of 15