Beruflich Dokumente
Kultur Dokumente
1. A transformer has 600 primary turns connected to a 1.5 kV supply. Determine the number of
N1 V1
For a transformer, N 2 V2
V2 240
N 2 N1 (600)
from which, secondary turns, V1 1500 = 96 turns
2. An ideal transformer with a turns ratio 2:9 is fed from a 220 V supply. Determine its output
voltage.
N1 2
N2 9 V1 220 V
and
N1 V1 N 2 9
V2 V1 220
N 2 V2 from which, output voltage, N1 2
= 990 V
3. A transformer has 800 primary turns and 2000 secondary turns. If the primary voltage is 160 V,
N1 800
N 2 2000 V1 160 V
and
N1 V1 N 2 2000
V2 V1 160
N 2 V2 from which, output voltage, N1 800 = 400 V
4. An ideal transformer with a turns ratio 3:8 has an output voltage of 640 V. Determine its input
voltage.
N1 V1 N1 3
V1 V2 640
N 2 V2 from which, input voltage, N 2 8 = 240 V
5. An ideal transformer has a turns ratio of 12:1 and is supplied at 192 V. Calculate the secondary
voltage.
N1 12
N2 1 and V1 192 V
N1 V1 N 2 1
V2 V1 192
N 2 V2 from which, output voltage, N1 12 = 16 V
6. A transformer primary winding connected across a 415 V supply has 750 turns. Determine how
many turns must be wound on the secondary side if an output of 1.66 kV is required.
N1 V1 V2 1660
N 2 N1 750
N 2 V2 from which, secondary turns, V1 415 = 3000 turns
7. An ideal transformer has a turns ratio of 15:1 and is supplied at 180 V when the primary current
N1 12
N 2 1 , V1 220 V and I1 4 A
N1 V1 N 2 1
V2 V1 180
N 2 V2 from which, output voltage, N1 15 = 12 V
N1 I 2 N1 15
I 2 I1 4
N 2 I1 from which, secondary current, N 2 1 = 60 A
8. A step-down transformer having a turns ratio of 20:1 has a primary voltage of 4 kV and a load of
N1 20
N2 1 and V1 4000 V
N1 V1 N 2 1
V2 V1 4000
N 2 V2 from which, output voltage, N1 20 = 200 V
V2 I 2 I2
Secondary power = = 10000 i.e. 200 = 10000
10000
I2
from which, secondary current, 200 = 50 A
9. A transformer has a primary to secondary turns ratio of 1:15. Calculate the primary voltage
necessary to supply a 240 V load. If the load current is 3 A determine the primary current.
N1 V1 I2 1 V 3
1
N 2 V2 I1 i.e. 15 240 I1
1 V 1
1 V1 240
If 15 240 then primary voltage, 15 = 16 V
1 3 15
I1 3
If 15 I1 then primary current, 1 = 45 A
supply. Neglecting losses, determine (a) the full load secondary current, (b) the minimum value
of load resistance which can be connected across the secondary winding without the kVA rating
N1 12
10000 = V1 I1 V2 I 2 , N 2 1 and V1 2400 V
10000
I2
10000 VA = V2 I 2 = 200 I 2 from which, secondary current, 200 = 50 A
V2 200
RL
(b) Load resistance, I2 50 = 4
N1 I 2 N 2 1
I1 I2 50
(c) N 2 I1 from which, primary current, N1 12 = 4.17 A
transformer whose secondary voltage is 150 V. Calculate the primary voltage and the turns ratio
V2 150
I2
Secondary current, R 2 20 = 7.5 A , I1 5 A and V2
= 150 V
N1 V1 N1 I2 7.5
V1 V2 V2 150
N 2 V2 from which, primary voltage, N 2 I1 5 = 225 V
N1 I 2 7.5 3
Turns ratio, N 2 I1 5 = 1.5 or 2 or 3:2
1. A 500 V/100 V, single-phase transformer takes a full load primary current of 4 A. Neglecting
losses, determine (a) the full load secondary current, and (b) the rating of the transformer.
V1 I 2 V 500
I 2 I1 1 (4)
(a) V2 I1 from which, full load secondary current, V2 100 = 20 A
V1 I1 500 4
(b) Transformer rating = = 2000 VA = 2 kVA
2. A 3300 V/440 V, single-phase transformer takes a no-load current of 0.8 A and the iron loss is
500 W. Draw the no-load phasor diagram and determine the values of the magnetizing and core
500
cos O
from which, 3300 0.8 = 0.1894 and O cos 1 0.1894 79.08
3. A transformer takes a current of 1 A when its primary is connected to a 300 V, 50 Hz supply, the
secondary being on open-circuit. If the power absorbed is 120 watts, calculate (a) the iron loss
current, (b) the power factor on no-load, and (c) the magnetizing current.
IO 1A V1 300 V
and
V1 I O cos O
(a) Power absorbed = total core loss = 120 =
IO cos O
i.e. 120 = (300)
120
I I cos O 300
and iron loss current, C O = = 0.40 A
IC 0.4
cos O
(b) Power factor on no-load, IO 1 = 0.40
I M IO 2 IC 2 12 0.402
magnetizing current, = 0.917 A
Calculate (a) the primary and secondary current, (b) the number of primary turns and (c) the
V1 I1 V2 I 2 60000 VA
(a) Transformer rating =
60000 60000
I1
hence, primary current, V1 1600 = 37.5 A
60000 60000
I2
and secondary current, V2 100 = 600 A
V1 N1 V1 1600
N1 N2 50
(b) V2 N2 from which, primary turns, V2 100 = 800 turns
E 2 4.44 f M N 2
(c) from which,
E2 100
M
4.44 f N 2 4.44 50 50
maximum flux, = 9.0 mWb
sectional area of the core is 270 cm2. When the primary winding is connected to a 300 volt supply,
determine (a) the maximum value of flux density in the core, and (b) the voltage induced in the
secondary winding
300
from which, maximum flux density, m = (4.44)(50)(40) Wb = 0.033784 Wb
(see chapter 7)
Hence, Bm 270 10 = 0.033784
-4
0.033784
4
from which, maximum flux density, Bm = 270 10 = 1.25 T
V1 N1 N 2
V N N1
(b) 2 = 2 from which, V2 = V1
520
i.e. voltage induced in the secondary winding, V2 = (300) 40 = 3900 V or 3.90 kV
3. A single-phase 800 V/100 V, 50 Hz transformer has a maximum core flux density of 1.294 T
2
and an effective cross-sectional area of 60 cm . Calculate the number of turns on the primary and
secondary windings.
B
A M BM A 1.294 60 104
Since then = 7.764 mWb
E1 800
N1
E1 4.44 f M N1 4.44 f M 4.44 50 7.764 103
from which, primary turns,
= 464 turns
John Bird Published by Taylor and Francis 273
E2 100
N2
E 2 4.44 f M N 2 4.44 f M 4.44 50 7.764 103
from which, secondary turns,
= 58 turns
4. A 3.3 kV/110 V, 50 Hz, single-phase transformer is to have an approximate e.m.f. per turn of 22 V
and operate with a maximum flux of 1.25 T. Calculate (a) the number of primary and secondary
E1 E2
(a) E.m.f. per turn = N1 = N 2 = 22
E1 3300
Hence primary turns, N1 = 22 = 22 = 150
E 2 110
and secondary turns, N2 = 22 = 22 = 5
E1 3300
from which, m = 4.44 f N1 = (4.44)(50)(150) = 0.0991 Wb
m 0.0991
B
hence area, A = m = 1.25 = 0.07928 m or 792.8 cm
2 2
1. A single-phase transformer has 2400 turns on the primary and 600 turns on the secondary. Its no-
load current is 4 A at a power factor of 0.25 lagging. Assuming the volt drop in the windings is
negligible, calculate the primary current and power factor when the secondary current is 80 A at a
I1 '
Let be the component of the primary current which provides the restoring m.m.f.
I1 ' N1 I 2 N 2
Then
I1 '
80 600
I1 '(2400) (80)(600) 2400
i.e. from which, = 20 A
cos 2 0.8
If the power factor of the secondary is 0.8, then
I2 2 36.87 V2 I1 ' 20 A
In the phasor diagram shown below, = 80 A at an angle to and and is
shown anti-phase to I 2
IO O 75.52 V1
The no load current, = 4 A is shown at an angle to
I1 I1 ' IO
Current is the phasor sum of and and by calculation:
= (4)(0.25) + (20)(0.8) = 1 + 16 = 17 A
I1
= 17 15.87 = 23.26 A
2 2
Hence, magnitude of
15.87 15.87
tan 1 1 tan 1 43.03
and 17 and 17
1. A transformer has 1200 primary turns and 200 secondary turns. The primary and secondary
resistances are 0.2 and 0.02 respectively and the corresponding leakage reactances are 1.2
and 0.05 respectively. Calculate (a) the equivalent resistance, reactance and impedance
referred to the primary winding, and (b) the phase angle of the impedance.
2 2
V 1200
R e R1 R 2 1 0.2 0.02
(a) Equivalent resistance, V2 200 = 0.92
Ze R e 2 X e 2 0.92 2 3.02
Equivalent impedance, = 3.138 or 3.14
John Bird Published by Taylor and Francis 277
Re 0.92 0.92
cos e e cos 1
(b) Ze 3.138 and phase angle of impedance, 3.138 = 72.95
1. A 6 kVA, 100 V/500 V, single-phase transformer has a secondary terminal voltage of 487.5 V
2. A transformer has an open circuit voltage of 110 volts. A tap-changing device operates when the
regulation falls below 3%. Calculate the load voltage at which the tap-changer operates.
110 V2
100%
Hence, 3 = 110
3(110)
110 V2
from which, 100
3(110)
V2 110
and 100 = 106.7 V = voltage at which the tap-changer operates.
1. A single-phase transformer has a voltage ratio of 6:1 and the h.v. winding is supplied at 540 V.
The secondary winding provides a full load current of 30 A at a power factor of 0.8 lagging.
Neglecting losses, find (a) the rating of the transformer, (b) the power supplied to the load, (c) the
primary current.
V1 6 540
V2
V2 1 V1 540 V 6 = 90 V and I2 = 30 A
and hence,
V2 I 2 90 30
(a) Rating of transformer = = 2700 VA or 2.7 kVA
(b) Power supplied to load = V I cos = (2700)(0.8) since power factor = cos = 0.8
V1 I 2 V2 1
I1 I2 30
(c) V2 I1 from which, primary current, V1 6
=5A
2. A single-phase transformer is rated at 40 kVA. The transformer has full-load copper losses of
800 W and iron losses of 500 W. Determine the transformer efficiency at full load and 0.8 power
factor.
1.3
1
Hence, efficiency, 33.3 = 0.961 or 96.10%
3. Determine the efficiency of the transformer in problem 2 at half full-load and 0.8 power factor.
1
40 0.8
Half full load power output = 2 = 16 kW
2
Copper loss (or I R loss) is proportional to current squared
2
1
800
Hence, copper loss at half full load = 2 = 200 W
Input power at half full load = output power at half full load + losses = 16 + 0.7 = 16.7 kW
losses 0.7
1 1
Hence, efficiency, input power 16.7 = 0.9581 or 95.81%
load copper loss of 1600 W. Calculate its efficiency for a load of 60 kW at 0.8 power factor.
Load power = 60 kW
60 3
Hence the transformer is at 80 4 full load
2
3
1600
Hence, copper loss at 3/4 load = 4 = 900 W
1.5
1
Hence, efficiency, 61.5 = 0.9756 or 97.56%
(i) full-load, unity power factor (ii) 0.8 full-load, unity power factor (iii) half full-load, 0.8
power factor. Assume that iron losses are 200 W and the full-load copper loss is 300 W
losses 0.5
1 1
Hence, efficiency, input power 15.5 = 0.9677 or 96.77%
Losses =
0.8 300 200 192 200
2
= 392 W or 0.392 kW
Input power at 0.8 full load = output power at 0.8 full load + losses
= 12 + 0.392 = 12.392 kW
0.392
1
Hence, efficiency, 12.392 = 0.9684 or 96.84%
(iii) At 0.5 full load and 0.8 power factor, output power = 0.5 15 0.8= 6 kW
Input power at 0.5 full load = output power at 0.5 full load + losses
= 6 + 0.275 = 6.275 kW
0.275
1
Hence, efficiency, 6.275 = 0.9562 or 95.62%
6. A 300 kVA transformer has a primary winding resistance of 0.4 and a secondary winding
resistance of 0.0015 . The iron loss is 2 kW and the primary and secondary voltages are 4 kV and
200 V respectively. If the power factor of the load is 0.78, determine the efficiency of the
Total copper loss = I12 R1 + I22 R2, (where R1 = 0.4 and R2 = 0.0015 )
= (75)2(0.4) + (1500)2(0.0015)
= 7625 W = 7.625 kW
losses
1
input power
Efficiency, = 100%
7.625
1
= 241.625 100% = 96.84%
(b) Since the copper loss varies as the square of the current, then total
2
1
copper loss on half load = 5625 2 = 1406.25 W
= 3406.25 W or 3.40625 kW
1
Output power on half full load = 2 (234) = 117 kW
losses
1
input power
= 100%
3.40625
1
= 120.40625 100% = 97.17%
7. A 250 kVA transformer has a full load copper loss of 3 kW and an iron loss of 2 kW. Calculate
(a) the output kVA at which the efficiency of the transformer is a maximum, and (b) the
2 2
x2
Hence, 3x 2
2
from which, 3 and x= 3 = 0.8165
Thus, the output kVA at maximum efficiency = 0.8165 250 = 204.1 kVA
4
1
Hence, maximum efficiency, 167.3 = 0.9761 or 97.61%
1. A transformer having a turns ratio of 8:1 supplies a load of resistance 50 . Determine the
2
N1 8
2
RL
The equivalent input resistance, R1 = N 2 = 1 (50) = 3200 = 3.2 k
resistance of 270
2 2
N N1
R1 1 R L 30
N 2 i.e. 270 = N 2
2
N1 270 N1
9 9 3
from which, N 2 30
and N2
3. Determine the optimum value of load resistance for maximum power transfer if the load is
connected to an amplifier of output resistance 147 through a transformer with a turns ratio of
7:2
The equivalent input resistance R1 of the transformer needs to be 147 for maximum power transfer.
2 2
N1 N 2 2
2
RL
R1 = N 2 from which, RL = R1 N1 = 147 7 = 12
4. A single-phase, 240 V/2880 V ideal transformer is supplied from a 240 V source through a cable
of resistance 3 . If the load across the secondary winding is 720 determine (a) the primary
current flowing and (b) the power dissipated in the load resistance.
N1 V1 240 1
(a) N 2 V2 2880 12
R IN R R1
Total input resistance, =3+5=8
V1 240
I1
Hence, primary current, R IN 8 = 30 A
N1 I 2 N1 1
I 2 I1 30
(b) N 2 I1 from which, N 2 12 = 2.5 A
I 2 2 R L 2.5 720
2
2 2 2
N N1 12 N1
R1 1 R L 768
N 2 hence 12 = N 2 and
768 N 2
N1 12 1
and N2 768 8
transformer. Determine (a) the value of the load resistance and (b) the power dissipated in the
load.
2 2 2
N N 1
R 1 1 R L R L R 1 2 (20000)
N 2 from which, load resistance, N1 16 = 78.13
R IN R1
(b) Total input resistance when source is connected to the matching transformer is ,
i.e. 20 k + 20 k = 40 k
V 20
I1
Primary current, 40000 40000 = 0.5 mA
N1 3 16
0.5 10
N1 I 2
I 2 I1
N 2 I1 from which, N 2 1 = 8 mA
I 2 2 R L 8 103 78.13
2
1. A single-phase auto transformer has a voltage ratio of 480 V:300V and supplies a load of
30 kVA at 300 V. Assuming an ideal transformer, calculate the current in each section of the
winding.
V1 I1 V2 I 2
Rating = 30 kVA =
30 103
I1
Hence, primary current, 480 = 62.5 A
30 103
I2
and secondary current, 300 = 100 A
2. Calculate the saving in the volume of copper used in an auto transformer compared with a
double-wound transformer for (a) a 300 V:240 V transformer, and (b) a 400 V:100 V
transformer.
V2 240
(a) For a 300 V:240 V transformer, x = V1 300 = 0.80
V2 100
(b) For a 400 V:1000 V transformer, x = V1 400 = 0.25
1. A three-phase transformer has 600 primary turns and 150 secondary turns. If the supply voltage
is 1.5 kV determine the secondary line voltage on no-load when the windings are connected
VL VP
(a) For a delta connection,
VP1
hence, primary phase voltage, = 1.5 kV = 1500 V
N 2 150
VP1 (1500)
VP2 N1 600 = 375 V
Secondary phase voltage, =
3 375
hence, secondary line voltage = = 649.5 V
VL
VP
(b) For a star connection, VL 3 VP or 3
VL1 1500
VP1
Primary phase voltage, 3 3 = 866.0 V
VL VP
For a delta connection,
N1 V1 N 2 150
VP2 VP1 (866.0)
N 2 V2 from which, secondary phase voltage, N1 600
1. A current transformer has two turns on the primary winding and a secondary winding of 260
turns. The secondary winding is connected to an ammeter with a resistance of 0.2 , the
resistance of the secondary winding is 0.3 . If the current in the primary winding is 650 A,
determine (a) the reading on the ammeter, (b) the potential difference across the ammeter, and
N1 2
I 2 I1 (650)
(a) Reading on ammeter, N 2 260 = 5 A
I 2 R 2 (5)(0.2)
(b) P.d. across ammeter = =1V