Beruflich Dokumente
Kultur Dokumente
|FAQs|SchneiderElectricNorway
HowtochangetheloadprofiledatainIONSetuptoP
FileformatforMV90andsetthepulsevalue.
GoalsandSymptoms
TheION8600canbeconfiguredtorecordMV90dataineitherEFileorPFileformat.ToaccessthenewPFiledata
formatfeature,youmustusethelatestversionofIONSetup,andhavethelatestframeworkloadedontoyourmeter.
ThisisastepbystepproceduretochangetheLoadprofiledatatoPfileformatandtoconfigurethepulsevalueto
matchwiththesettinginsideMV90.
CausesandFixes
UsingIONSetup
1.OpenIONSetupandconnectthemeterusingSingleDeviceMode.
2.IntheSetupAssistant,navigatetoLogging.SelectLoadProfile.
3.IntheChannelstab,selectthefirstsourcevalueandclickEdit.
4.AModificationWarningpopupwillappearandsaythatparametermodificationswillresetrecordeddata.ClickOK
tocontinueifallnecessaryinformationonthemeterhasbeenrecorded.
5.TheParameterSelectionwindowappears.
EnergyIntervalparametersareinEFiledataformat.
EnergyPulsesparametersareinPFiledataformat.
6.Clickontheplus[+]signbesidetheparameterheadingtoviewtheindividualparameters.
7.SelectthedesiredparameterandclickOK.
8.Repeatsteps3through7forallyourLoadProfilesources.
9.Thenewchannelstoberecordedinloadprofile(Revenuelog)areshownbelow.TheyareendedbyaletterP
http://www.schneiderelectric.no/sites/norway/no/support/faq/faq_main.page?page=content&country=NO&lang=en&id=FA212240&locale=en_US&redirect=true 1/3
27/5/2016 HowtochangetheloadprofiledatainIONSetuptoPFileformatforMV90andsetthepulsevalue.|FAQs|SchneiderElectricNorway
10.Youmaycheckthepulsesrecordedintherevenuelog.
SelectViewfromtoolbar>DataScreens>doubleclickDataRecordersonrightscreen>doubleclickRevenueLog
toviewdata
11.ChangethepulsevaluetomatchwiththesettinginMV90
Thepulses(kwhintP,KVARhintP,etc)aresendingfromIntegratormoduletotherevenuelog(notsendingfromthe
calibrationpulsermodule).Youcanchangethepulsevaluebyenteringtheadvancesetupmode(holdctrlkeyand
leftmouseclickonthedevicename).Pickthecorrespondingmoduleasselectedinstep9(i.e.Kwhdelint,KVARh
delint,etc)
http://www.schneiderelectric.no/sites/norway/no/support/faq/faq_main.page?page=content&country=NO&lang=en&id=FA212240&locale=en_US&redirect=true 2/3
27/5/2016 HowtochangetheloadprofiledatainIONSetuptoPFileformatforMV90andsetthepulsevalue.|FAQs|SchneiderElectricNorway
12.SelectSetupRegisterstab.TheValu/Pulsedeterminestheenergyvalueforonepulse.Foranexample,ifthe
value/pulseoftheKWhdelintIntegratormoduleissetto0.0018,thenitwillsendoutonepulseforevery0.0018kwh.
ThismustmatchwiththesettinginsideMV90.
Repeatstep11and12forallselectedchannelsin9.
FA212240|04Feb2014|EnergyManagementSolutions
http://www.schneiderelectric.no/sites/norway/no/support/faq/faq_main.page?page=content&country=NO&lang=en&id=FA212240&locale=en_US&redirect=true 3/3