Sie sind auf Seite 1von 2

DATE :

SITE TEST REPORT


17-02-2016
CONTRACTOR : PA COST INTL
Contract no:
33/13.8 KV HUDAYB SUBSTATION 4400002607
Description: Sheet:
AUX. RELAY TYPE RXMB 1 1 of 2

1. GENERAL DATA AND INFORMATION:

Panel Name : + M01 INCOMER SPARE FEEDER 1 Rated Voltage Ur : 110-125 V DC

Location : 33 KV SWITCHGEAR No. of contacts :COIL A 1-NO


4-DO

Designation : +D1-75SX Type No. : 1MRK 000 873-AN

Manufacturer : ABB

2. MECHANICAL CHECKS AND VISUAL INSPECTION:

3. ELECTRICAL TESTS:

a) FUNCTION TEST:

b) PICK-UP AND DROP OFF TEST:

Limits:
Pick-up voltage: <80% Ur Drop-off voltages: >10% Ur

Tested by: PACOST Witnessed by: SEC-MDNOD RAD


Name: MOHANKUMAR MUTHUSAMY Name :Mr.THAMER

Signature & Date : Signature & Date :


DATE :
SITE TEST REPORT
17-02-2016
CONTRACTOR : PA COST INTL
Contract no:
33/13.8 KV HUDAYB SUBSTATION 4400002607
Description: Sheet:
AUX. RELAY TYPE RXMB 1 2 of 2

(Table 1 of Buyers Guide 1MRK 000 873)

c) OPERATING AND DROP OFF TIME TEST (AT 125V DC) :

Limits:
Pick-Up Time: 8/6.5ms Drop-Off Time: 3/2.5ms
(Table 1 of Buyers Guide 1MRK 000 873)

d) RELAY BURDEN TEST:

Limits:
WATT: 1.5-2 (At 110v DC)
(Table 1 of Buyers Guide 1MRK 000 873)
BURDEN = V*I

TESTING DEVICE:

SEVERKER 780
SERIAL # 1301356
CALIBRATION DATE VALID UP TO 24-11-2016

Tested by: PACOST Witnessed by: SEC-MDNOD RAD


Name: MOHANKUMAR MUTHUSAMY Name :Mr.THAMER

Signature & Date : Signature & Date :